Addendum 1

Project DKFX 16-1037 Construct Cryogenics Facility

Joint Base Charleston South Carolina 19 March 2019

1. Sketch SK-001 is to supplement Detail 1 of Sheet CS101 of the contract drawings. The only intent of this sketch is to provide details of the concrete work around the building.

2. Sketch SK-002 provides construction joint, control joint, and expansion joint details for pavement around building foundation as shown on SK-001. Detail 4 of SK-002 is to replace Detail 3 of Sheet C-503 of contract drawing.

3. Contractor shall provide and install an exterior mounted communications jack on the south side of the building. Jack shall be rated for outdoors.

4. Exterior mounted jack shall be connected to the patch panel inside.

5. Keynote E1 on Sheet E-101 is revised with SK-003.

16" CEDAR

X

X

X

X

X

F

O

F

O

F

O

X

X

X

X

X

X

X

X

X

CHAIN-LINK FENCE

ASPHALT

ELEC PANEL

CONC PAD

BASKETBALL

GOAL

EXPANSION JOINTS (TYP)

R

R

R

R

R

R

R

R

R

IRREGULAR SECTIONS TO BE REINFORCED

CONTROL JOINTS

JOINT LAYOUT PLAN

Project Name

Project Location

Map Prepared By

Date

Applicant

Map Reference

SCALE:

1"=20'

North Charleston, SC

March 2018

North Charleston, SC, 29406 Charleston CountyJoint Base Charleston

Construct Cryogenics Facility

320-C Midland Parkway, Summerville, South Carolina, 29485 843.875.3637

ENGINEERING | ARCHITECTURE

CONSTRUCTION JOINTS REQUIRED IN

BETWEEN REINFORCED SECTIONS

SK-001

AutoCAD SHX Text N

THE PREFORMED JOINT FILLER SHALL EXTEND TO A DEPTH EQUAL TO THE THINNEST THICKENED

EDGE. JOINT SEALANT SHALL MEET ASTM C 920, TYPE S OR M, GRADE NS, CLASS 25, USE NT. AND

AS REQUIRED BY UFC 3-250-01FA.

T=THICKNESS

OF PAVEMENT

PREFORMED

NON-EXTRUDING

JOINT FILLER

JOINT SEAL

(SEE NOTE)

" R

EXISTING

PAVEMENT

SCALE: NOT TO SCALE

EXPANSION JOINT (NEW TO EXISTING PAVEMENT)

NOTES:

3"

6X6-W2.0XW2.0 WWF

[FOR IRREGULAR SECTIONS

ONLY (SEE JOINT LAYOUT PLAN)]

COMPACTED SUBGRADE

95% ASTM D-1557

CONCRETE PAVEMENT SECTION

SCALE: NOT TO SCALE

CONCRETE PAVEMENT 6"

PORTLAND CEMENT (4,000 PSI)

4" STONE BASE

(SCDOT SPEC 305)

NOTES:

t

SAWCUT & FILL

WITH SEALANT

t

COMPACTED SUBGRADE

SCALE: NOT TO SCALE

CONTROL JOINT DETAIL

1. INSTALL CONTROL JOINTS SUCH THAT NO DIMEMSION

BETWEEN JOINTS EXCEEDS 16' OR 3t MEASURED IN FEET, WHICHEVER IS LESSER (i.e. FOR A 4" THICK SLAB, MAX.

CONTROL JOINT SPACING = 3*4 = 12').

2. INSTALL CONTROL JOINTS SUCH THAT THE RECTANGULAR

SECTIONS CREATED BETWEEN THE JOINTS DO NOT EXCEED

A 1:1.25 MAXIMUM RATIO (i.e. 10'x12' SECTION).

JOINT DETAILS

Project Name

Project Location

Map Prepared By

Date

Applicant

Map Reference

SCALE:

NTS

North Charleston, SC

March 2018

North Charleston, SC, 29406 Charleston CountyJoint Base Charleston

Construct Cryogenics Facility

320-C Midland Parkway, Summerville, South Carolina, 29485 843.875.3637

ENGINEERING | ARCHITECTURE

XXXXX X X X X X X X

1/8"

T

FILL WITH SEALANT

3"

SCALE: NOT TO SCALE

CONSTRUCTION JOINT DETAIL

JOINT SEALANT SHALL MEET ASTM C 920, TYPE S OR M,

GRADE NS, CLASS 25, USE NT. AND AS REQUIRED BY UFC-3-250-01FA

NOTES:

SK-002

X X X X X X X X X

X X X X X X

HAND HOLE 195

Charleston County GIS

0 100 20050 Feet ± Date: 7/30/2018

PROVIDE NEW, DIRECT-BURIED, 2" PVC CONDUIT AND

12-STRAND SM FIBER-OPTIC CABLE FROM NEW

BUILDING TO HAND HOLE 195 BEHIND BUILDING 675 IAW

ES101.

CONTINUE 12-STRAND SM FIBER-OPTIC CABLE IN

EXISTING CONDUIT FROM HAND HOLE 195 TO

BUILIDING 609.

ENSURE MAINTENANCE LOOPS IN EACH HAND HOLE OR

MAN HOLE.

TERMINATE BOTH ENDS WITH SC TYPE CONNECTORS.

COORDINATE PATCH PANEL ACCESS WITH GOV'T.

TOTAL LENGTH OF FIBER RUN IS APPROXIMATELY 2200'

WITH MAINTENANCE LOOPS.

RPatterson Ellipse

RPatterson Ellipse

RPatterson Ellipse

RPatterson Ellipse

RPatterson Ellipse

RPatterson Ellipse

RPatterson Ellipse

RPatterson Text Box

HAND HOLE

EXISTING CONDUIT

NEW CONDUIT

RPatterson Ellipse

RPatterson Line

RPatterson Line

RPatterson Text Box PROVIDE NEW, DIRECT-BURIED, 2" PVC CONDUIT AND 12-STRAND, SM FIBER-OPTIC CABLE FROM NEW BUILDING TO HAND HOLE 195 LOCATED BEHIND BUILDING 675 IAW ES101.

CONTINUE 12-STRAND SM FIBER-OPTIC CABLE, UTILIZING THE EXISTING SYSTEM OF DUCTBANK AND HAND HOLES, FROM HAND HOLE 195 TO EXISTING BUILDING 609 (APPROX. 2200' CABLE LENGTH, INCLUDING MAINTENANCE LOOPS).

PROVIDE A MAINTENANCE LOOP IN EACH HAND HOLE THE CABLE PASSES THROUGH.

TERMINATE BOTH ENDS WITH SC TYPE CONNECTORS AND PROVIDE SLACK CALBE LOOP AT EACH END PER THE SPECIFICATIONS.

COORDINATE PANEL ACCESS WITH GOV'T.

BOND OSP FIBER OPTIC CABLE ARMOR AND METALLIC STRENGTH MEMBER TO THE MAIN BUILDING GROUNDING SYSTEM WITH #6 AWG OR LARGER GROUND WIRE.

RPatterson Ellipse

Addendum 1
SK-001
Sheets and Views
Layout1
SK-002
Sheets and Views
Layout1

SK-003