FA4418-13-R-0012
Section J, Attachment 2 17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
E001
E001-02 40' CLASS 3, Southern Yellow Pine (S.Y.P.) Treated EA 25
Machine dig and set in average earth. Includes #4 Pole-butt ground system, material handling and spotting.
E001-03 45' CLASS 3, Southern Yellow Pine (S.Y.P.) Treated EA 25
Machine dig and set in average earth. Includes #4 Pole-butt ground system, material handling and spotting.
E001-04 50' CLASS 3, Southern Yellow Pine (S.Y.P.) Treated EA 25
Machine dig and set in average earth. Includes #4 Pole-butt ground system, material handling and spotting.
E001-05 60' CLASS 3, Southern Yellow Pine (S.Y.P.) Treated EA 25
Machine dig and set in average earth. Includes #4 Pole-butt ground system, material handling and spotting.
E001-06 70' CLASS 3, Southern Yellow Pine (S.Y.P.) Treated EA 25
Machine dig and set in average earth. Includes #4 Pole-butt ground system, material handling and spotting.
E002
E002-02 Single Arm Construction Wood Cross Arm - 3-1/2" x 4-1/2" x 8'-0" EA 40
Includes installation up to 45' pole. Complete with all hardware and 1-1/4" x 1/4" flat steel braces.
E002-04 Single Arm Construction Fiberglass Cross Arm - 3-1/2" x 4-1/2" x 8'-0" EA 10
Includes installation up to 45' pole. Complete with all hardware and steel angled 1-piece V-braces.
E002-06 Double Arm Construction Wood Cross Arm - 3-1/2" x 4-1/2" x 8'-0" EA 20
Includes installation up to 45' pole. Complete with all hardware and 1-1/4" x 1/4" flat steel braces.
E002-07 Double Arm Construction Wood Cross Arm - 3-3/4" x 4-3/4" x 10'-0" EA 10
Includes installation up to 45' pole. Complete with all hardware and steel angled 1-piece V-braces.
E003
E003-01 Down Guy (complete) - 3/8" Guy Wire - Up to 45' Pole EA 20
Zinc coated, Class A strand 1x7, minimum breaking strength of 10,800 lbs for 3/8", ASTM A- 363, A-475, A-925, A-855, A-640. Includes 8' diameter screw anchor, rod assembly, guy marker, and all equipment and labor for installation.
E0030-01- 01 For 10" Screw Anchor, Add EA 5 1
E003-02 Down Guy (complete) - 5/8" Guy Wire - Up to 45' Pole EA 10
Zinc coated, Class A strand 1x7, 15,400 breaking strength, ASTM A-363, A-475, A-925, A- 855, A-640. Includes 10' diameter screw anchor, rod assembly, guy marker, and all equipment and labor for installation.
E003-02- 01 For 10" Screw Anchor, Add EA 5 1
E003-03 Guy Guard Plastic EA 72 Includes material and installation. 6
E003-04 3/8" Guy Wire LF 1500 Zinc coated, Class A strand 1x7, min 10,800 breaking strength, ASTM A-363, A-475, A-925, A- 855, A-640. Includes installation.
E003-05 5/8" Guy Wire LF 500 Zinc coated, Class A strand 1x7, min 15,400 breaking strength, ASTM A-363, A-475, A-925, A- 855, A-640. Includes installation.
E003-06 8" Diameter Screw Anchor EA 24 1" x 66" anchor rod, thimble or twin-eye.
Includes installation. 3
E003-07 10" Diameter Screw Anchor EA 12 1-1/4" x 66" anchor rod, thimble or twin-eye.
Includes installation. 2
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
UTILITY POLES
CROSS ARMS
GUYING
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E003-09 Guy Strain Insulators EA 20 Includes installation to down guy or head guy. 4
E004
E004-01 Pin Insulator with pin - 15 kV Class EA 36 Includes installation, wire jumpers, cable splices, termination and connection to overhead conductor.
E004-02 Suspension Insulator with Clevis and Strain Clamp - 15 kV Class EA 36
Includes installation, wire jumpers and connection means from insulator to pole-mounted transformer, overhead conductor, and/or lightning arrestor.
E004-03 Spool Insulator with Clevis - 15 kV Class EA 24
Includes installation, wire jumpers and connection means from insulator to pole-mounted transformer, overhead conductor, and/or lightning arrestor.
E004-04 1 Spool Secondary Rack EA 12 Includes mounting and complete installation, including wire jumpers, connectors, and splicing connection to overhead conductors.
E004-05 2 Spool Secondary Rack EA 12 Includes mounting and complete installation, including wire jumpers, connectors, and splicing connection to overhead conductors.
E004-06 3 Spool Secondary Rack EA 12 Includes mounting and complete installation, including wire jumpers, connectors, and splicing connection to overhead conductors.
E004-07 4 Spool Secondary Rack EA 12 Includes mounting and complete installation, including wire jumpers, connectors, and splicing connection to overhead conductors.
E005
Outdoor load break switch 3-phase, group operated, 3-insulator, vertical break, high strength pin insulators worm gear operating mechanism operating rods, mechanisms, and switch bases are galvanized steel. Includes all brackets and mounting hardware.
E005-01 600A, 14.4 kV, Outdoor Load Break Switch, 3-Phase Vertical Break EA 10
3-Phase Vertical Break, 3 Insulator. Includes mounting, cable jumpers, clamps, and connection to overhead conductors.
E005-02 1200A, 14.4 kV, Outdoor Load Break Switch, 3-Phase Vertical Break EA 2
3-Phase Vertical Break, 3 Insulator. Includes mounting, cable jumpers, clamps, and connection to overhead conductors.
E005-03 1600A, 14.4 kV, Outdoor Load Break Switch, 3-Phase Vertical Break EA 2
3-Phase Vertical Break, 3 Insulator. Includes mounting, cable jumpers, clamps, and connection to overhead conductors.
E005-04 2000A, 14.4 kV, Outdoor Load Break Switch, 3-Phase Vertical Break EA 2
3-Phase Vertical Break, 3 Insulator. Includes mounting, cable jumpers, clamps, and connection to overhead conductors.
E006
110 kV BIL, 15 kV max design voltage, 14.4 kV nominal, polymer or porcelin design insulators.
Includes fusetube, fuselink as specifed by CO, hardware, mounting, NEMA heavy duty bracket(s) for crossarm or direct pole mounting, cable jumpers, parallel-groove terminal clamps, and connections to overhead conductor, lightning arrestor, and/or pole-mounted transformer or riser termination. Does not include lightning arrestor
E006-07 Wildlife Guard EA 20 Polypropylene wildlife protector guard 2
INSULATORS
OUTDOOR LOAD BREAK SWITCH
PRIMARY FUSE CUTOUT - STANDARD CUTOUT
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E007
110 kV BIL, 15 kV max design voltage, 14.4 kV nominal, loadbreak class, polymer or porcelin design insulators, and arc chute interrupter.
Includes fusetube, fuselink as specified by CO, hardware, mounting, NEMA heavy duty bracket(s) for crossarm or direct pole mounting, cable jumpers, parallel-groove terminal clamps, and connections to overhead conductor, lightning arrestor, and/or pole-mounted transformer or riser terminations. Does not include lightning arrestor
E007-01 100-amp EA 24 110KV BIL, 10kAIC ASYM. 5
E007-02 200-amp EA 24 110KV BIL, 12kAIC ASYM. 5
E007-03 300-amp, Blade Only EA 24
110KV BIL. Includes 300-amp blade, hardware, mounting, bracket(s), cable jumpers, parallel-groove terminal clamps, and connections to overhead conductor, lightning arrestor, and/or pole-mounted transformer or riser terminations.
Does not include lightning arrestor.
E007-04 Wildlife Guard EA 20 Polypropylene wildlife protector guard 4
E008
10kV distribution class heavy duty surge arrestor, 8.4 kVrms MCOV, polymer or porcelain housed metal-oxide design. Includes mounting hardware, bracket, mounting, cable jumpers, clamps, and connections to overhead conductor, ground wire, fuse cutout, and/or pole-mounted transformer or riser terminations.
E008-01 Lightning Arrestor EA 36 6
E008-02 Riser Pole Arrestor EA 24 4
E008-02 15 kV Fuse Cutout/ Surge Arrestor/Combination EA 10
110 kV BIL, 15 kV max design voltage, 14.4 kV nominal, loadbreak class, polymer or porcelin design insulators, and arc chute interrupter.
Includes fusetube, hardware, mounting, NEMA heavy duty bracket(s) for crossarm or direct pole mounting, cable jumpers, parallel-groove terminal clamps, and connections to overhead conductor, lightning arrestor, and/or pole-mounted transformer. Includes fuselink as specified by the CO. 10kV distribution class surge arrestor, 8.4 kVrms MCOV, polymer or porcelain housed metal-oxide design.
E009
E009-01 Hot Line Clamp/Connector EA 40 Copper,aluminum, or copper/aluminum. Includes installation up to a 45' pole. 6
E009-02 Stirrup EA 48 Copper,aluminum, or copper/aluminum. Includes installation up to a 45' pole. 8
E010
PRIMARY FUSE CUTOUT - LOADBREAK WITH ARC CHUTE INTERRUPTER
LIGHTING ARRESTORS
ACCESSORIES
RECLOSER
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E010-01 Recloser EA 12
Three phase. Maximum design voltage 15.5 kV, nominal operating voltage 12.47 kV, Basic Impulse Level 110 kV, maximum continuous curret 600A, symmetric interrupting current 10 kA, vacuum arc interruption. Includes installation, complete with hardware and connection to overhead line connectors.
E011
7200V-12470V - 95 kV BIL, Insulation Class 15.0 13200V-14400V - 125 kV BIL, Insulation Class 18.0 65 Degrees C temperature rise ANSI C57.2.20 compliant Pressure relief valve Single or two bushing primary for single-phase or three phase connecton. Primary voltage to 13,200V, secondary service voltages combinations 120V, 208V, 240V, 277V, 347V, 480, or 600V. Price includes installation on wood pole or transformer rack, all hardware, jumpers, clamps, and connection to overhead line, lightning arrestors, fuse cutouts, or riser terminations
E011-01 10 KVA EA 5 1
E011-02 15 KVA EA 5 1
E011-03 25 KVA EA 18 4
E011-04 37.5 KVA EA 9 2
E011-05 50 KVA EA 6 1
E011-06 75 KVA EA 3 1
E011-07 100 KVA EA 3 1
E011-09 One piece tripple transfomer Rack, 3kVA through 50kVA EA 5
Min 6000 lb load capacity for all three positions thru 50kVA. Hot dip galvanized. Includes mounting, all hardware, clamps, and connection to pole ground system.
E011-10 One piece tripple transfomer Rack, 75kVA through 333kVA EA 5
Min 15,000 lb load capacity for all three positions thru 50kVA. Hot dip galvanized. Includes mounting, all hardware, clamps, and connection to pole ground system.
E011-12 Wildlife Guard (bushing) EA 12 Polypropylene wildlife protector guard 2
E012
Installation on poles, including securing to insulators, clevises, or other pole-mounted cable connections. Also, includes jumpers and their connection as needed across insulators.
E012-01 #2 Stranded, bare Copper, medium hard drawn LF 3000 600
E012-02 #1/0 Stranded, bare Copper, medium hard drawn LF 3000 600
E012-03 #2 Stranded, bare Aluminum LF 1500 300
MEDIUM VOLTAGE STATIC/NEUTRAL CONDUCTORS (Overhead Linework)
POLE-MOUNTED TRANSFORMERS (Overhead Linework)
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E013
Installation on poles, including securing to insulators, clevises, or other pole-mounted cable connections. Also, includes jumpers and their connection as needed across insulators.
E013-01 #2 Stranded, bare Copper, medium hard drawn LF 3000 600
E013-02 #2/0 Stranded, bare Copper, medium hard drawn LF 3000 600
E013-03 #4/0 Stranded, bare Copper, medium hard drawn LF 3000 600
E013-04 #2/0 Stranded, bare Aluminum, medium hard drawn LF 3000 600
E013-05 #4/0 Stranded, bare Aluminum, medium hard drawn LF 3000 600
E013-06 336 kcmil ACSR Cable (Merlin) LF 3000 600
E014 Includes equipment, installation, connection from pole-mounted transformer to service entrance, and terminations.
E014-01 #4 Stranded Al. LF 1200 200
E014-02 #2 Stranded Al. LF 1200 200
E014-03 #1/0 Stranded Al. LF 1200 200
E014-04 #2/0 Stranded Al. LF 1200 200
E014-05 #3/0 Stranded Al. LF 1200 200
E015
Includes mobilization, augering, receiving pits, dewatering, cleanup to grade, pulling up to two HPDE conduits per bore, compliance with Air Force ETL 07-01 and UFC 3-555-01. DOES
NOT INCLUDE HDPE CONDUIT (SEE LINE
E016).
E015-01 1-2" Diameter HDPE Conduit LF 600
E015-02 1-2-1/2" Diameter HDPE Conduit LF 600
E015-03 1-3" Diameter HDPE Conduit LF 600
E015-04 1-4" Diameter HDPE Conduit LF 600
E015-05 1-5" Diamter HDPE Conduit LF 300
E015-06 1-6" Diameter HDPE Conduit LF 300
E015-07 2-2" Diameter HDPE Conduits LF 600
E015-08 2-3" Diameter HDPE Conduits LF 600
E015-09 2-4" Diameter HDPE Conduits LF 600
E015-10 2-5" Diameter HDPE Conduits LF 300
E015-11 2-6" Diameter HDPE Conduits LF 300
MEDIUM VOLTAGE PHASE CONDUCTORS
(Overhead Linework)
ALUMINUM TRIPLEX SERVICE DROP
DIRECTIONAL BORING
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E016
Pulled in place by boring machine. Includes pipe welding. Compliance with Air Force ETL 07-01 and UFC 3-555-01, which includes transition to grade Schedule 80 conduit, Schedule 80 elbows, conduit bells, conduit seals, heavy duty polyester composite double braid pull rope, and ETL 07-01 and UFC 3-550-01 compliant concrete encasement to grade. Includes pipe welding as specified in AF guidance. DOES
NOT INCLUDE HORIZONTAL DIRECTIONAL
BORE OR CONCRETE EQUIPMENT PAD.
SEE LINE ITEM E015, DIRECTIONAL BORING.
E016-01 2" HDPE LF 600
E016-02 2-1/2" HDPE LF 600
E016-03 3" HDPE LF 600
E016-04 4" HDPE LF 600
E016-05 5" HDPE LF 300
E016-06 6" HDPE LF 300
E017 Shielded, XLP Insulated, 15 kV, 133 Percent Insulation
E017-01 (In-Duct) #1 Aluminum, EPR. 15 KV LF 1000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-02 (In-Duct) #1/0 Aluminum, EPR. 15 KV LF 1000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-03 (In-Duct) #2/0 Aluminum, EPR. 15 KV LF 2000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-04 (In-Duct) #4/0 Aluminum, EPR. 15 KV LF 2000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-05 (In-Duct) 250 kcmil Aluminum, EPR.
15 KV LF 1000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-06 (In-Duct) 350 kcmil Aluminum, EPR.
15 KV LF 1000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-07 (In-Duct) 500 kcmil Aluminum, EPR.
15 KV LF 1000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-08 (In-Duct) #2 Copper, EPR, 15KV LF 2000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-09 (In-Duct) #1 Copper, EPR, 15KV LF 1000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-10 (In-Duct) #1/0 Copper, EPR, 15KV LF 2000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-11 (In-Duct) #2/0 Copper, EPR, 15KV LF 2000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
High Density Polyethylene Pipe (HDPE) - Directional Bore Installation only.
MEDIUM VOLTAGE CABLES (Underground Linework)
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E017-12 (In-Duct) #4/0 Copper, EPR, 15KV LF 2000 Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-13 (In-Duct) 250 kcmil Copper, EPR, 15KV LF 1000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-14 (In-Duct) 350 kcmil Copper, EPR, 15KV LF 1000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-15 (In-Duct) 500 kcmil Copper, EPR, 15KV LF 3000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-16 (In-Duct) 750 kcmil Copper, EPR, 15
KV LF 1000
Includes cable pulling tension calculations, installation in conduit to not exceed maximum values, jam ratios, or conduit fill.
E017-17 (Direct Bury) #1 Aluminum, EPR. 15 KV LF 1000
Includes survey to clear area and installation of cable in trench. Does not include trenching, backfill, and final grading. Underground splicing is prohibited.
E017-18 (Direct Bury) #1/0 Aluminum, EPR. 15 K LF 1000
Includes survey to clear area and installation of cable in trench. Does not include trenching, backfill, and final grading. Underground splicing is prohibited.
E017-19 (Direct Burial) #2 Copper, EPR, 15KV LF 1000
Includes survey to clear area and installation of cable in trench. Does not include trenching, backfill, and final grading. Underground splicing is prohibited.
E017-20 (Direct Burial) #1/0 Copper, EPR, 15KV LF 3000
Includes survey to clear area and installation of cable in trench. Does not include trenching, backfill, and final grading. Underground splicing is prohibited.
E017-21 Utility Trench (Chain Trencher) LF 2000 Includes exavation, compaction, backfill and final grading. 8" wide, 36" deep trench, medium soil.
E017-22 Utility Trench (Backhoe) LF 2000 Includes exavation, compaction, backfill and final grading. 8" wide, 36" deep trench, medium soil.
E018 Includes installation and mounting on concrete equipment pad. Does not include cable terminations.
E018-01 Pad Mounted - Metal Enclosed Oil Filled 15KV - 95 KV BIL (2-Switches - 2-VFI)
EA 2 1
E018-02 Pad Mounted - Metal Enclosed Air Switches 15 KV- 95 BIL (2-Switches - 2-Fused)
EA 2 1
E019
E019-01 4-Point Connection, 200A EA 6 Includes installation and mounting on concrete equipment pad. Does not include cable terminations.
E019-02 4-Point Connection, 600A EA 12 Includes installation and mounting on concrete equipment pad. Does not include cable terminations.
E019-03 3-Point Connection x 4, 200A EA 12 Includes installation and mounting on concrete equipment pad. Does not include cable terminations.
JUNCTION ENCLOSURES (Underground Linework)
SECTIONALIZING SWITCH (Underground Linework)
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E020
E020-01 CABLE SPLICE #4 STRANDED EA 6 1
E020-02 CABLE SPLICE #2 STRANDED EA 6 1
E020-03 CABLE SPLICE #1/0 STRANDED EA 24 5
E021 15 kV voltage class meeting IEEE Standard 386.
Up to 500 kcmil.
E021-01 600A Loadbreak Elbow EA 12 1
E021-01 200A Loadbreak Elbow EA 12 1
E022
E022-01 CABLE TERMINATION #4
STRANDED EA 6 1
E022-02 INSTALL CABLE TERMINATION #2
STRANDED EA 6 1
E022-03 INSTALL CABLE TERMINATION
#1/0 STRANDED EA 24 5
E023
12470Y/7200V, 13,200Y/7620V, 13800Y/7920V Dead Front Taps: Split +/- 2-1/2% 65 Degrees C temperature rise Liquid Type: Mineral oil Connection: Loop Feed HV Bushings: Wells and Inserts LV Bushiings: Spade-6 hole Fusing: Bay-O-Net Arrester(s): Installed Primary voltage to 13,200V, secondary service voltages combinations 240V/120V, 480V/240V.
Price includes installation on concrete pad.
Without Meters
E023-01 25KVA PAD MOUNTED
TRANSFORMERS (1 PHASE) EA 1 1
E023-01 37.5KVA PAD MOUNTED
TRANSFORMERS (1 PHASE) EA 4 1
E023-01 50KVA PAD MOUNTED
TRANSFORMERS (1 PHASE) EA 20 4
E023-02 75KVA PAD MOUNTED
TRANSFORMERS (1 PHASE) EA 4 1
E023-03 100KVA PAD MOUNTED
TRANSFORMERS (1 PHASE) EA 2 1
E023-04 167KVA PAD MOUNTED
TRANSFORMERS (1 PHASE) EA 1 1
MEDIUM VOLTAGE CABLE SPLICE (Underground Linework)
MEDIUM VOLTAGE CABLE ELBOWS (Underground Linework)
CABLE TERMINATION (Underground Linework)
PAD MOUNTED TRANSFORMERS (1 PHASE)
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E024
Primary: 12470Y/7200V, 13,200Y/7620V, 13800Y/7920V Secondary: 480Y/277, 208Y/120 BIL- 95kV Copper Windings Dead Front Taps: Split +/- 2-1/2% 65 Degrees C temperature rise Liquid Type: Mineral oil Connection: Loop Feed with ON-OFF Radial Switch HV Bushings: Wells and Inserts LV Bushiings: Spade-6 hole Fusing: Bay-O-Net with current limiting fusing with one spare set of fuses Arresters: Installed Price includes installation on concrete pad and secondary cable terminations. Does not include MV terminations
E024-01 75KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 4 1
E024-02 112.5KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 2 1
E024-03 150KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 2 1
E024-04 225KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 1 1
E024-05 300KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 1 1
E024-06 500KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 1 1
E024-06 750KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 1 1
E024-06 1000KVA PAD MOUNT
TRANSFORMERS (3 PHASE) EA 1 1
E025
Includes equipment mobilization, excavation, forms, rebar, 3000 psi concrete, smooth finish, form removal and disposal, finish grading, and installation of ground loop system IAW UFC 3- 530-01.
E025-01 6’ x 6’ x 8” = 0.89CY Reinforced concrete transformer pad EA 15 3
E025-02 7’ x 7’ x 8” = 1.21CY Reinforced concrete transformer pad EA 15 3
E025-03 8’ x 8’ x 8” = 1.58CY Reinforced concrete transformer pad EA 15 3
E026
E026-01 Manhole EA 2 Manholes shall be compliant with AF ETL 10-17, Electrical Manhole Design. Includes excavation, installation, and final grading.
E027 Includes hardware, brackets, installation, fabrication (if necessary), equipment modification, wiring, and all terminations.
PAD MOUNTED TRANSFORMERS (3 PHASE)
REINFORCED CONCRETE TRANSFORMER PAD
MANHOLES
LOW VOLTAGE METERS
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E027-01
LOW VOLT INSTR. METER
INSTALLED ON EXISITNG POLE
INCLUDES METER, SOCKET, CTs, CT MOUNTING BRACKET, INSTRUMENT WIRING AND MISC
CONDUIT FITTINGS.
EA 6 1
E027-02
LOW VOLT INSTR. METER
INSTALLED ON PADMOUNT
INCLUDES METER, SOCKET, CTs, INSTRUMENT WIRING AND MISC
CONDUIT FITTINGS.
EA 6 1
E027-03
LOW VOLT SELF CONT. MTR. UP
TO 200 AMP INCLUDES 2"
CONDUIT RISER & 3/0
CONDUCTORS, METERBASE,
MISC CONDUIT FITTINGS, 10' 2"
RIGID STEEL, BUSHINGS 2 PER
STRAP & STRUT, AND WEATHER
HEAD. (GOVT. OWNED)
EA 6 1
E027-04
15KV. PRIMARY METER ON
EXISTING POLE INCLUDES
SOCKET, METER, WIRING, CTs, PTs
AND MOUNTING BRACKET ON
CROSSARMS.
EA 4 1
E027-05 TRANSFER TYPE "A" METER
(GOVT. OWNED) EA 6 1
E027-06 TRANSFER TYPE "B" METER
(GOVT. OWNED) EA 4 1
E027-07 TRANSFER TYPE "C" METER
(GOVT. OWNED) EA 4 1
E026-08 TRANSFER TYPE "D" METER
(GOVT. OWNED) EA 2 1
E028
Includes all equipment, personnel, and means to conduct high voltage DC tests on medium voltage cable. Price is per cable between termination points.
E028-01 High Voltage DC EA 40
E029
E029-01
Load Center, NEMA 3R, 120/240 volt, 100 ampere main breaker, single phase, 3 wire, service entrance rated, 12 pole, breakers not included.
EA 18 4
E029-02
Load Center, NEMA 3R, 120/240 volt, 200 ampere main breaker, single phase, 3 wire, service entrance rated, 40 pole, breakers not included.
EA 4 1
E0289-03
Panelboard, 120/208 volt, 100 ampere main breaker, three phase, 4 wire, service entrance rated, 24 pole, breakers not included.
EA 4 1
ELECTRICAL PANELS
CABLE TESTING
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E029-04
Panelboard, 120/208 volt, 225 ampere main breaker, three phase, 4 wire, service entrance rated, 42 pole, breakers not included.
EA 2 1
E030 600V, Stranded Type THHN, XHHW, or THWN Copper
E030-01 #12 CLF 10 2
E030-02 #10 CLF 10 2
E030-03 #8 CLF 10 2
E030-04 #6 CLF 10 2
E030-05 #4 CLF 10 2
E050-06 #2 CLF 8 2
E030-07 #1 CLF 8 2
E030-08 #1/0 CLF 4 1
E030-09 #2/0 CLF 4 1
E030-10 #3/0 CLF 4 1
E030-11 #4/0 CLF 4 1
E030-12 250 kcmil CLF 4 1
E030-13 350 kcmil CLF 4 1
E030-14 #500 kcmil CLF 4 1
E031 E031-01 1/2" conduit LF 1000 200
E031-02 3/4" conduit LF 1000 200
E031-03 1" conduit LF 1000 200
E031-04 1-1/4" conduit LF 1000 200
E031-05 1-1/2" conduit LF 1000 200
E031-06 2"conduit LF 1000 200
E031-07 2-1/2" conduit LF 1000 200 E032 E032-1 1" Diameter LF 1000 200
E032-2 2" Diameter LF 1000 200
E032-3 3" Diameter LF 1000 200
E032-4 4" Diameter LF 1000 200
E032-5 5" Diameter LF 1000 200
E032-6 6" Diameter LF 1000 200
E033 Includes couplings, rubber conduit seal, strapping to pole or structure, and conduit elbows
E033-01 RISER CONDUIT (UP TO 4" PVC) LF 500 100
WIRE
CONDUIT, RIGID GALVANIZED STEEL (including couplings)
PVC Conduit - Schedule 40
RISER CONDUIT
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E033-02 RISER CONDUIT (UP TO 4" GALV.
STEEL) LF 200 40
E034 E034-01 Install Buried Cable Tape CLF 2000 E035
E035-01 Bore Under Pavement LF 1000 12" diameter maximum bore, medium soil.
Includes mobilization, setup, cleanup, and excavation. Does not include conduit.
E036 E036-01 Replace Photocell EA 200 E037
E037-01 250 WATT EA 200 40
E037-02 400 WATT EA 50 10
E037-03 1000 WATT EA 50 10
E038 Includes installation, hardware, and connection of fixture wiring power.
E038-01 250 WATT (High Pressure Sodium) EA 10 2 E038-02 400 WATT (High Pressure Sodium) EA 20 4 E038-03 1000 WATT (High Pressure Sodium) EA 10 2 E039
E039-01 175 WATT EA 10 2
E039-02 250 WATT EA 10 2
E039-03 400 WATT EA 20 4
E040
E040-01 #12 COPPER THWN/THHN OR UF LF 1000
E040-02 #10 COPPER THWN/THHN OR UF LF 1000
E040-03 #8 COPPER THWN/THHN OR UF LF 1000
E040-04 #6 COPPER THWN/THHN OR UF LF 1000
E041 Material and installation shall be IAW UFGS-26 41 01.00 10.
E041-01 75' Telescoping Masts EA 10 Includes concrete base and grounding system. 2
E041-02 #2/0 Bare Copper Overhead Conductor (Shield Wires) LF 1000 200
E041-03 #2/0 Stranded Copper Down Conductor LF 100 20
E041-04 Overhead Conductor Connection Hardware EA 100
Includes all hardware for connecting one overhad wire to mast, e.g. bolts, nuts, washers, anchor rod clamp, clamps, pole bands, connectors, and jumpers.
E041-05 Air Terminals - 1/2", Copper, Rounded Tip (not pointed), 12" threaded without Support Brackets
EA 25 To 75' high. Includes base and attachment to facility. 5
E041-06 Air Terminals - 1/2", Copper, Rounded Tip (not pointed), 24" threaded with Support Brackets
EA 20 4
E041-07 Air Terminals - 1/2", Copper, Rounded Tip (not pointed), 36" threaded with Support Brackets
EA 100 20
E041-08 Grounding Access Well - 12" diameter, 18" long, Schedule 80 PVC, galvanized steel lid.
EA 20 4
STREETLIGHT FIXTURE (Includes lamp and photocell)
UNDERGROUND STREETLIGHT CABLE (DIRECT BURIED)
LIGHTNING PROTECTION SYSTEMS
BURIED CABLE TAPE
BORING UNDER PAVEMENT
PHOTOCELL
RELAMP FLOODLIGHT/STREETLIGHT
FLOOD LIGHT FIXTURES (Includes lamp and photocell)
Demo - N/A
Demo - N/A
Demo - N/A Demo - N/A Demo - N/A
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E041-09
Mounting Base for 5/8" Air Terminals.
Vertical, horizontal, ridge,or sloping roof mounting configuration. Adhesive or bolted.
EA 100 20
E041-10 Bonds to metallic structures EA 100 Includes hardware and copper bonding straps 3/4" x 9.5" 20
E041-11 Ground rods - 3/4" x 10' Copper Clad EA 25 5
E041-12 Copper Bonding Conductors, tinned, braided ribbon type with connection lugs-#6 Copper solid - 12"
EA 25 5
E041-13 Copper Bonding Conductors, tinned, braided ribbon type with connection lugs-#6 Copper solid - 18"
EA 25 5
E041-14 Copper Bonding Conductors, tinned, braided ribbon type with connection lugs-#6 Copper solid - 24"
EA 25 5
E041-15 Exothermic Connections (to #2/0) EA 50 10
E041-16 High Compression Connectors (Copper) EA 100 20
E041-17 Conductor anchors/supports EA 100 20 E041-18 Connector- cable to bar (Copper) EA 100 20 E041-19 Grounding Conductors (#2/0 Copper) LF 1000 200 E041-20 Electrical panel surge arrestors EA 10 2 E042 E042-1 Lump sum $100 EA 30
E042-2 Lump sum $200 EA 30
E042-3 Lump sum $300 EA 30 E043
E043-01 Superintendent - Regular Hours HOUR 75
E043-02 Superintendent - Overtime Hours HOUR 25
E043-03 Superintendent - Emergency Response HOUR 75
E043-10 Foreman - Regular Hours HOUR 75
E043-11 Foreman - Overtime Hours HOUR 25
E043-12 Foreman - Emergency Response HOUR 150
E043-20 Electrician/Lineman - Regular Hours HOUR 75
E043-21 Electrician/Lineman - Overtime Hours HOUR 25
E043-22 Electrician/Lineman - Emergency Response HOUR 150
MISCELLANEOUS MINOR MATERIALS
LABOR HOURS
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E043-30 Apprentice - Regular Hours HOUR 75
E043-31 Apprentice - Overtime Hours HOUR 25
E043-32 Apprentice - Emergency Response HOUR 75
E043-40 Laborer - Regular Hours HOUR 75
E043-41 Laborer - Overtime Hours HOUR 75
E043-42 Laborer - Emergency Response HOUR 75
E043-50 Professional Registered Testing Engineer HOUR 800
E044
E044-01 BUCKET TRUCK - EMERGENCY
RESPONSE EQUPMENT HOUR 150
E044-02 BUCKET TRUCK - REGULAR
HOURS HOUR 75
E044-03 LINE TRUCK (DIGGER) -
EMERGENCY RESPONSE HOUR 150
E044-04 LINE TRUCK (DIGGER) - REGULAR
HOURS HOUR 75
E044-05 TRENCHER - REGULAR OR
EMERGENCY RESPONSE HOUR 40
E044-06 HI-POT-UNIT - REGULAR OR
EMERGENCY RESPONSE HOUR 40
E045
E045 Tree Trimming labor & equipment HOUR 300
E046
E046 Asphalt Cutting Removal & Replacement SQ FT 200
E047
E047 Concrete Cutting Removal & Replacement SQ FT 100
E048 Drilling of reinforced concrete slab up to 6" thick, includes bit, layout and setup, and cleanup.
E048-01 1" Diameter Core EA 6
E048-01-01 Each added inch thickness in same hole, add EA 2
E048-02 2" Diameter Core EA 6
E048-02-10 Each added inch thickness in same hole, add EA 2
E048-03 3" Diameter Core EA 6
E048-03-01 Each added inch thickness in same hole, add EA 2
E048-04 4" Diameter Core EA 6
Demo - N/A
Equipment
TREE TRIMMING
ASPHALT REMOVAL & REPLACEMENT
CONCRETE REMOVAL & REPLACEMENT
CONCRETE DRILLING
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
17 June 2013
Repair and Maintain Electrical Distribution System IDIQ Price Schedule
INSTALLATION
QUANTITY
UNIT
INSTALLATION
COST
TOTAL
PRICE COMMENTS DEMOLITION
QUANTITY
UNIT
DEMOLITION
COST
TOTAL
PRICE COMMENTS
I. D. # LINE ITEM DESCRIPTION UNIT
INSTALLATION OF LINE ITEMS DEMOLITION OF LINE ITEMS
E048-04-01 Each added inch thickness in same hole, add EA 2
E048-05 5" Diameter Core EA 6
E048-05-01 Each added inch thickness in same hole, add EA 2
E049 Non-metallic piping.
E049-01 4" Conduit EA 2
E049-02 5" Conduit EA 2 E050
E050-01 Installation and Maintenance of Ventalation System (per manhole) EA 4 Includes ventilation setup and compliance with
UFC 3-560-01, Electrical Safety O&M.
E051
E051-01 Performance Bond (Rate per Thousand) Unit 1
E051-02 Payment Bond (Rate Per Thousand) Unit 1
SubTotals
Demo - N/A
SubTotals
Total
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
Demo - N/A
PENTRATION FIRESTOPPING (MANHOLE)
CONFINED SPACE ENTRY SUPPORT SERVICES
BONDS
Rate Escalation Rate
Option Total with Escalation Rate Option Year 1
Option Year 2
Option Year 3
Option Year 4
Price Schedule