Hurlburt Field, FL Tank Inspection Report
Tank No. 90808 Project No.:49-060
TANK INSPECTION REPORT
Tank Name: 90808 Tank Type: Elevated Location: Hurlburt AFB Tank Capacity: 250,000 gallons State: FL Type of Construction: Steel Built By: Unknown Location:
Year Built: 1991 Inspected By: Eric Boling Inspection Date: 2/22/19
GENERAL SUMMARY
Overall the tank is in fair condition with corrosion at most sharp edges and scattered throughout the tank surface, particularly on rod connections, ladders and floor of balcony. Coating system is beginning to show signs of failure with cracking and lifting of the multi-layer coatings throughout the tank surface.
RECOMMENDATIONS
Blast and repaint entirety of tank within next two years to prevent steel loss and protect long term integrity of the tank Enclose electrical and control panels in weatherproof enclosureat next repaint Re-install safety cable on primary ladder with correct alignmentand tension after next repaint.
Replace exterior ladder or solid seal weld sections that arecurrently bolted together. Ladder appears to be salvageable at this time, but corrosion at junction of rungs and sides need to be correctedbefore steel loss requires replacement.
Reattach or replace obstruction lighting on top of tank. Lights are currently working but are not properly attached to roof of tank.
Replace heavily corroded ladder brackets of roof ladder prior to repaint.
Tank No. 90808
STANDARDS
The inspection of the tank was performed with the tank nearly full and no cleaning was performed. The inspection consisted of a visual observation of the tank’s interior (as feasible with water present) and exterior components and coating system. Interior and exterior assessment was documented using digital still photography, representative samples of which are included in the Appendix of this report.
CONDITION OBSERVATIONS
Conditions noted in this report are documented in the following pages and supported by color photographs in the Appendix. Condition ratings used to describe field findings are defined as follows:
Excellent No deficiencies noted.
Good Minor deficiencies noted. Structure is functioning as designed.
Fair Major deficiencies noted. Structure is in need of repair (or replacement) to continue functioning as designed.
Poor Repair or replacement required immediately. Item no longer functioning as designed
CONTAMINATION, HEALTH & SAFETY REPORT
Contamination & Health Overall Condition: Excellent
Overflow pipe is equipped with screen, gasket and flapper to prevent access for insects All manways and hatches fit properly and wereclosed Roof vent is properly screened to prevent access for insects
Facility Safety Compliance Overall Condition: Good
Tank is located inside locked, fenced area at secure military site All ladders and safety climb in good condition, but require some repairs and coating replacement within next 1-2 years to avoid replacement Unable to determine if proper safety grid is over riser entrance at base of bowl to
Tank No. 90808 prevent falls due to presence of water Has 2nd hatch on side of bowl for safety/access during paintingprojects
Tank No. 90808
INTERIOR RESERVOIR INSPECTION REPORT
Interior Reservoir Roof Overall Condition: Fair
Most of ceiling coating in fair condition Heavy corrosion forming along thick, rough weld seams inceiling Undetermined if cathodic protection system is working
Interior Reservoir Walls Overall Condition: Fair
Coating on walls in area of water surface showing consistent corrosion and coating failure Coating on walls throughout showing signs of cracking and beginning to release from steel walls Corrosion is evident on areas of walls below the watersurface
Interior Reservoir Floor Overall Condition: Undetermined
Sediment and corrosion can be seen on floor of bowl, but complete inspection not possible without tank drained.
Interior Reservoir Plumbing Components Overall Condition: Good
Overflow pipe assembly is in good condition with corrosion along piping from water line up. Note: corrosion line on walls and overflow pipe indicate that tank is never completely filling, indicating need for adjustment in controls for filling of thetank.
Visible portion of fill pipe is in good condition with minimal corrosion in vicinity of water surface.
EXTERIOR RESERVOIR INSPECTION REPORT
Exterior Reservoir Roof Overall Condition: Fair
Coating on tank roof is in overall fair condition with scattered spots of minor corrosion, particularly along roof seams. Coating is beginning to crack and lift, which will expose steel to the elements if coating is allowed to continue to degrade.
Roof ladder in serviceable condition but brackets and weld connections require cleaning and recoating within next 1-2 years or will need to be replaced due to on-going metal loss.
Safety climb equipment on roof ladder is properly installed, including alignment and tension.
Roof vent is in good condition and is properly screened, but the tank/vent connection seam is showing minor to heavy corrosion around its perimeter.
Cathodic appear sealed but are corroding and staining top of tank
Tank No. 90808
Lip of primary hatch is corroded and should be rehabbed soon.
Tank No. 90808
Exterior Reservoir Walls Overall Condition: Fair
Coating on exterior walls in fair condition with signs of corrosion and/or coating failures Heavier corrosion along seams under tank belly, which is typical
Exterior Balcony Overall Condition: Fair
Coating on top of balcony in fair condition with signs of corrosion and/or coating failures Balcony railing in good condition with no signs of metal loss at time of inspection
Exterior Riser and Leg Structures Overall Condition: Fair
Windage rods and support beams in fair condition with signs of corrosion and coating failures Support beams in good condition with minor rust forming
Exterior Plumbing Structures Overall Condition: Good
Overflow pipe assembly in good condition and properly braced. Coating is starting to fail, as evidenced on remainder of tank, but piping is still salvageable.
Foundation Overall Condition: Good
Foundation of riser and legs in good condition with grout loss between base and foundation Minor corrosion on anchor bolt nuts with some areas of heavier corrosion on base plates around bolts.
GENERAL TANK SECURITY
Security Overall Condition: Excellent
Tank is located inside locked, fenced area at secure military site Exterior ladder is protected by locked ladder guard
Cathodic Protection System
Type, size, material and # of anodes:Overall Condition: N/A Present but condition unknown.
TA
BL
E
- C oa tin gs
S ch ed ul e
Co at in g
Sy st em
Su rfa ce P re p
Pr im e6
(m ils
DF
T)
Pr od uc t4
In te rm ed ia te
#1
(m ils uc t4
In te rm ed ia te
(m ils uc t4
Fi na l (m ils uc t4
To ta l Sy st em
(m ils
M in
- M ax
O
CS
-4
(M ifi ed
SS
PC
-1
Zi nc -R ich P rim er
2.
- 3
.5
Se rie s 9 1-
H2
Hy dr o- Zi nc
Ep ox y 3.
0- 5.
N1
Po ta -P ox P lu s
Po ly ur et ha ne
.0
E nd ur a-
Sh ie ld
Fl uo ro po ly m er U re th an e
2.
s 7
H yd ro
Fl on
9.
- 1
4.
IC
S-
(M od ifi ed
SS
PC
-1
(Im m er sio n)
-R ich
P rim er s 9
1- H2
Hy dr o-
0%
S ol id s E po xy
.0 s F C2
Ep ox ol in e
.5
(4
- 5
2.
5)
Co nc re
SS
PC
-7
Ac ry lic
E la st om er ic
4.
- 6 s 1
En vi ro -C
Ac ry lic E la st om er ic 4.
- 6 s 1
En vi ro
-C
A st rip e co at o f e po xy sh al l b e ap pl ie d by b ru sh to a ll w el d se am s, la dd er s, ed ge s, et c.
, p rio r t o re ce iv in g fir st in te rm ed ia te c oa t o n ex te rio r s ur fa ce s a nd pr io r t o th e fin is h co at o n in te rio r s ur fa ce s.
A ll in te rio r r oo f b ea m s, sh ar p ed ge s a nd o th er d iff ic ul t t o co at a re as sh al l r ec ei ve
5.
.0 m ils o f e po xy li ni ng
To ta l D ry F ilm T hi ck ne ss fo r r oo f b ea m s, sh ar p ed ge s a nd o th er d iff ic ul t t o co at a re as
A ll pr od uc ts a re as m an uf ac tu re d by
T ne m ec
C om pa ny
, I nc
M il th ic kn es se s f or in di vi du al c oa ts sh al l n ot e xc ee d m an uf ac tu re r’ s w rit te n re co m m en da tio n.
A n ad di tio na l c oa t o f z in c-ric h pr im er sh al l b e sh op
-a pp lie d to th e re pl ac em en t l ad de rs a nd o th er re pl ac em en t p ar ts
7 A n ad di tio na l c oa t o f I nt er m ed ia te sh al l b e ap pl ie d to th e ta nk b ow l e xt er io r f ro m th e ba se o f t he b al co ny to th e ris er st em ju nc tio n.
T ot al S ys te m fo r th is a re a sh al l b e
.5 to
7.
(m ils D
FT
H ur lb ur tF ie ld ,F
L T an k
N o.
Ta nk In sp ec tio n
R ep or t
Pr oj ec t
N o.
:4 9-
Pa ge of
Tank No. 90808
Appendix Photos
1- Tank
ID
Tank No. 90808
2 - Data Plate (Built 1991)
Tank No. 90808
3-Riser hatch bolts heavily corroded
Tank No. 90808
4-Sample tap piping properlyinsulated
Tank No. 90808
5-Grout and coating failure at riserbase
Tank No. 90808
6-Sample tap properly insulated
Tank No. 90808
7-Corrosion and coating failure at anchor bolt
Tank No. 90808
8-Overflow cover face and screen corroding
Tank No. 90808
9-Overflow flapper installedproperly
Tank No. 90808
10-Severe coating failure around sample tap penetration
Tank No. 90808
11-Sample spot of coatingcrack
Tank No. 90808
12-Coating failure at base ofriser
Tank No. 90808
13-Widespread cracking of coating with spots of breakthrough corrosion
Tank No. 90808
14-Base of leg and tension rods
Tank No. 90808
15-Coating cracked, lifted and unprotected steel corroding at base plate
Tank No. 90808
Tank No. 90808
16-Coating failure on tension rod brackets and bolts
Tank No. 90808
Tank No. 90808
Tank No. 90808
17-Coating failure on baseplate
Tank No. 90808
18-Electrical conduits properlysealed
Tank No. 90808
19-Ladder gate properly installed and locked upon arrival
Tank No. 90808
20-Electrical and control boxes exposed to weather
Tank No. 90808
21-Tank secured in lockedfence
Tank No. 90808
Tank No. 90808
Tank No. 90808
22-Coating on cross bracing beginning to fail and corrosion forming
Tank No. 90808
23-Coating beginning to fail and separate on sharp edges on tension rod turnbuckles
Tank No. 90808
24- Coating beginning to fail and separate on sharp edges on tension rod turnbuckles
Tank No. 90808
25-Bolts on rods beginning tocorrode
Tank No. 90808
26-Closer view of turnbucklecorrosion
Tank No. 90808
27-Widespread coating system cracking and lifting
Tank No. 90808
28-Detail of cracking, lifting coating system. Bare steel to be exposed as coating begins to flakeoff.
Tank No. 90808
Tank No. 90808
29-Safety climb loose and out ofalignment
Tank No. 90808
30-Coating failures
Tank No. 90808
31-Corroded, bolted ladder connection. Should be replaced or welded during repaint.
Tank No. 90808
32-Bolted ladderconnection
Tank No. 90808
33-Ladder rungs corroding at connection point
Tank No. 90808
34-Coating cracking and failing on ladder and ladder brackets
Tank No. 90808
35-Ladder rung coatingfailure
Tank No. 90808
36-Coating failure on uppermost windage rods and seams on belly of tank
Tank No. 90808
37-Closer view of belly and rods. Rods appear to be salvageable at this time
Tank No. 90808
38-Coating failure and corrosion at rod and beam connections
Tank No. 90808
39-Coating failure on supportrod
Tank No. 90808
40-Corrosion on bolts at rod and beam connections
Tank No. 90808
41-Close up of coating failure and corrosion at bolt connections
Tank No. 90808
42-Corrosion forming on sharp edges on tank exterior
Tank No. 90808
43-Mildew and widespread coatingcracking
Tank No. 90808
44-Ladder brace corroding will require replacement or welding repair
Tank No. 90808
Tank No. 90808
45-Ladder safety equipment mis-aligned but balcony opening is adequate
Tank No. 90808
46-Toe clearance for ladder at balcony is adequate. Ladder is corroding but salvageable.
Tank No. 90808
Tank No. 90808
47-Coating on balcony floor cracking and corrosion forming. No apparent structural damage to date, but should be addressed in a timelyfashion.
Tank No. 90808
48-Balcony floor and railing coating failures. No cross bracings on railing.
Tank No. 90808
49-Abnormally thick weld seam (should have been ground smooth after construction). Edges are beginning to corrode.
Tank No. 90808
50-Corrosion and paint failures at exterior bowl weld seams
Tank No. 90808
51-Thinning top coat of paint system
Tank No. 90808
52-Coating on balcony floor cracking, blistering and failing. Exposing steel to corrosion formation.
Tank No. 90808
53-Conduit brackets corroding and bleeding onto tank wall
Tank No. 90808
Tank No. 90808
54-Corrosion forming at weld seam of balcony toe kick.
Tank No. 90808
55-Widespread coating failure and corrsion on balcony floor
Tank No. 90808
56-Coating cracking and failing on stem of extra hatch on side of tank bowl (and bolts are corroding)
Tank No. 90808
57-Corroded hatch cover, bolts and balcony floor
Tank No. 90808
58-Corroded bolts, roof ladder braces and balcony floor
Tank No. 90808
59-Coating cracking and failing on exterior of bowl
Tank No. 90808
60-Old bracket connection corroding on side of roof ladder. Should be removed duringrepaint.
Tank No. 90808
61-Coating failure and corrosion on bottom roof ladder brackets
Tank No. 90808
Tank No. 90808
62-Close up of coating system cracking down to bare metal. Corrosion forming as steel losesprotection.
Tank No. 90808
Tank No. 90808
63-Heavy cracking around top of roof ladder from systemic coating failure on exterior of bowl. Cathodic protection bolts corrodingalso.
Tank No. 90808
64-Heavy cracking of coating around and on roof ladder brackets.
Tank No. 90808
65-Safety climb installed correctly on bowl ladder. Rungs of ladder exhibiting coatingfailures.
Tank No. 90808
66-Exterior coating cracking and beginning to peel, allowing underlying steel to corrode
Tank No. 90808
Tank No. 90808
67-One obstruction light not secured to top of tank. Support poles for other lighting and roof in the vicinity of lights corroding.
Tank No. 90808
68-Coating cracking and steel corroding on roof of tank
Tank No. 90808
Tank No. 90808
69-Ladder and hatch exhibiting coating failure and corrosion.
Tank No. 90808
70-Coating cracking and peeling at junction of tank roof and vent
Tank No. 90808
71-Corrosion forming at junction of roof and vent.
Tank No. 90808
72-Heavy corrosion of roof ladderbracket.
Tank No. 90808
Tank No. 90808
73-Remnants of old bracket corroding. Should be removed at next repaint.
Tank No. 90808
74-Cathodic protection cover corroding and staining top of tank.
Tank No. 90808
75-Rooftop coating cracking, blistering and peeling
Tank No. 90808
76-Exterior coating cracking andlifting
Tank No. 90808
77-Interior corrosion at water line
Tank No. 90808
78-Interior corrosion at weld seam above water line
Tank No. 90808
79-View of inlet/outlet pipe through water (which is clear). Doesn't appear to be safety grid over pipe entrance, which creates a fall hazard during tank maintenance.
Tank No. 90808
Tank No. 90808
80-Interior of bowl side hatch and ladder descending into bowl. Both are showing signs of corrosion requiring recoating.
Tank No. 90808
81-Corrosion at water level and along tank wall below water line. Dark area at bottom is staining and sediment.
Tank No. 90808
Tank No. 90808
82-Water is remaining several feet below overflow elevation in the tank with corrosion forming on walls and overflow piping at current waterline.
Tank No. 90808
Tank No. 90808
Tank No. 90808
83-Underside of balcony exhibiting coating failure, particularly along sharp edges
Tank No. 90808
84-Underside of balcony at tank leg junction. Coating failing and peelingalong thick, rough weld seams.
Tank No. 90808
85-Corrosion on wind rods and bolted connections under belly of tank
Tank No. 90808
86-Underside of balcony
Tank No. 90808
87-Underside of balcony. Coating failing and peeling around weepholes in balcony floor.
Tank No. 90808
88-Ladder rungs are 16" in width, which meets current OSHA code.
Hurlburt Field, FL Tank No. 90808
File details come from the government source that posted it.