Attach_7_-_WT_7_Inspection_Report.pdf

PDF 2 MB Posted

Attached to
Cleaning/Repairing of Water Tower #7 Bldg 91134 & Water Tower #808 Bldg 90808
Solicitation number
FA441719RA014
Issued by

About this file

Attachment 7 - Water Tower (WT) 7 Inspection Report

View the file

Other files

File Type Posted
Solicitation_Amendment_-_FA441719RA0140004.pdf PDF
Solicitation_Amendment_FA441719RA0140004_SF_30.pdf PDF
Attach_10_-_Bid_Schedule_Rev_2_14_Aug_19.pdf PDF
Solicitation_Amendment_-_FA441719RA0140003.pdf PDF
Attach_2_-_SOW_14_Aug_19.pdf PDF
Attach_1_-_Specifications_FTEV_10-26976_14_Aug_19.pdf PDF
Solicitation_Amendment_FA441719RA0140003_SF_30.pdf PDF
Attach_10_-_Bid_Schedule_Rev_1_7_Aug_19.pdf PDF
Solicitation_Amendment_-_FA441719RA0140002.pdf PDF
Solicitation_Amendment_FA441719RA0140002_SF_30.pdf PDF
Attach_2_-_SOW_7_Aug_19.pdf PDF
Attach_2_-_SOW_31_Jul_19.pdf PDF
Attach_1_-_Specifications_FTEV_10-26976_1_Aug_19.pdf PDF
Solicitation_Amendment_FA441719RA0140001_SF_30.pdf PDF
Solicitation_Amendment_-_FA441719RA0140001.pdf PDF
Attach_9_-_Tower_Location_Maps.pdf PDF
Attach_8_-_WT_808_Inspection_Report.pdf PDF
Attach_10_-_Bid_Schedule.pdf PDF
Questions_and_Answers_FA441719RA014.pdf PDF
Pre-Proposal_Site_Visit_Sign-In_Roster_18_JUL_19.pdf PDF
Pre-Proposal_Site_Visit_Memo_WT_18_JUL_19.pdf PDF
Attach_2_-_SOW_1_May_19.pdf PDF
Attach_6_-_Additional_Contractor_Information.pdf PDF
Solicitation_-_FA441719RA014.pdf PDF
Attach_3_-_Wage_Determination_4_Jan_19.pdf PDF
Attach_1_-_Specifications_FTEV_10-26976.pdf PDF
Attach_5_-_Financial_Reference_Sheet.pdf PDF
Attach_4_-_Past_Present_Performance_Questionnaire.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Hurlburt Field, FL Tank Inspection Report

Tank No. 91134 Project No.:49-060

TANK INSPECTION REPORT

Tank Name: 91134 Tank Type: Elevated (Pedestal) Location: Hurlburt AFB Tank Capacity: 250,000 gallons State: FL Type of Construction: Steel Built By: Unknown Location:

Year Built: Unknown (Data plate painted over) Inspected By: Eric Boling Inspection Date: 2/22/19

GENERAL SUMMARY

Overall the tank is in fair condition with corrosion at most sharp edges and scattered throughout the tank surface, particularly on roof fixtures, ladders and floor of platforms. Coating system is beginning to show signs of failure with cracking and lifting of the multi-layer coatings throughout the tank surface.

RECOMMENDATIONS

Blast and repaint entirety of tank within next two years to prevent steel loss and protect long term integrity of thetank Blast and clean anchor bolts and area inside bolt enclosures as thoroughly as possible. Re-coat and cover front of enclosurewith welded steel plate with grease fitting. Fill void around bolts with grease for maximum long-term protection.

Install safety grating over valve pit in floor of tank.

Repair or replace lighting through dry access tube of tank.

Seal open holes on platforms with welded steel plates duringnext repaint to remove trip/fall hazard.

Tank No. 91134

Replace wet area ladder and safety climb equipment during next repaint.

Tank No. 91134

STANDARDS

The inspection of the tank was performed with the tank nearly full and no cleaning was performed. The inspection consisted of a visual observation of the tank’s interior (as feasible with water present) and exterior components and coating system. Interior and exterior assessment was documented using digital still photography, representative samples of which are included in the Appendix of this report.

CONDITION OBSERVATIONS

Conditions noted in this report are documented in the following pages and supported by color photographs in the Appendix. Condition ratings used to describe field findings are defined as follows:

Excellent No deficiencies noted.

Good Minor deficiencies noted. Structure is functioning as designed.

Fair Major deficiencies noted. Structure is in need of repair (or replacement) to continue functioning as designed.

Poor Repair or replacement required immediately. Item nolonger functioning as designed

CONTAMINATION, HEALTH & SAFETY REPORT

Contamination & Health Overall Condition: Excellent

Overflow pipe is equipped with screen, gasket and flapper to prevent access for insects All manways and hatches fit properly and wereclosed Roof vent is properly screened to prevent access for insects

Facility Safety Compliance Overall Condition: Fair

Tank is located inside locked, fenced area at secure military site Dry area ladders and safety climb in good condition but require coating replacement within next 1-2 years to avoid replacement.

Wet area ladder is heavily corroded and safety climb equipment has been painted over and is unusable. Both should be replaced at next repaint.

Valve pit in floor of tank has no safety grid over it, creating a fall/trip hazard Platforms have open holes that are a fall/trip hazard.

Tank No. 91134

INTERIOR RESERVOIR INSPECTION REPORT

Interior Reservoir Roof Overall Condition: Poor

Most of ceiling coating in poor condition Ceiling coating has completely failed and ceiling is corroding throughout the tank Undetermined if cathodic protection system is working

Interior Reservoir Walls Overall Condition: Fair

Coating on walls in area of water surface showing consistent corrosion and coating failure Coating on walls throughout showing signs of cracking and beginning to release from steel walls Corrosion is evident on areas of walls below the watersurface

Interior Reservoir Floor Overall Condition: Undetermined

Sediment and corrosion can be seen on floor of bowl, but complete inspection not possible without tank drained.

Interior Reservoir Plumbing Components Overall Condition: Good

Overflow pipe assembly is in good condition with corrosion along piping from water line up.

Interior Riser Overall Condition: Good

Wet side of access tube is in generally good shape with coating in better condition than that of ceiling and walls.

EXTERIOR RESERVOIR INSPECTION REPORT

Exterior Reservoir Roof Overall Condition: Fair

Coating on tank roof is in overall fair condition with scattered spots of minor corrosion, particularly along roof seams. Coating is beginning to crack and lift over the entirety of the tank roof, which will expose steel to the elements if coating is allowed to continue to degrade.

Roof vent is in good condition and is properly screened, but the tank/vent connection seam is showing minor to heavy corrosion around its perimeter.

Cathodic appear sealed but are corroding and staining top of tank

Tank No. 91134

Lip of primary hatch is corroded and should be rehabbed soon.

Tank No. 91134

Exterior Reservoir Walls Overall Condition: Fair

Coating on exterior walls in fair condition with signs of corrosion and/or coating failures Heavier corrosion along all sharp edges (painter’s ring, hatches), which is typical

Exterior Pedestal Overall Condition: Fair

Pedestal is heavily mildewed and coating is starting to crack through to the base metal over the entirety of the exterior of the tank. The coating system has reached the end of its useful tank and needs to be replaced soon to protect the integrity of the tank.

Exterior Plumbing Structures Overall Condition: Good

Overflow pipe assembly in good condition and properly braced. Coating is starting to fail, as evidenced on remainder of tank, but piping is still salvageable.

Overflow splash pad and riprap are adequate and functioning properly.

Foundation Overall Condition: Good

Foundation of pedestal in good condition with minor grout loss between base and foundation Interior of anchor bolt enclosures and threads of anchor bolts have coating failure and corrosion that needs to be addressed.

GENERAL TANK SECURITY

Security Overall Condition: Excellent

Tank is located inside locked, fenced area at secure military site All ladders are inside tank with locked door.

Cathodic Protection System

Type, size, material and # of anodes: Overall Condition: N/A

Present but condition unknown.

TA

BL

E

R ec om m en de d

C oa tin gs

S ch ed ul e

Co at in g

Su rfa ce P re p

Pr im e6

(m ils

DF

T)

In te rm ed ia

#1

(m ils

Pr od uc t4

In te rm ed ia

#2 ils uc t4

Fi na l (m ils

To ta l Sy st em ils

D

FT

O

CS

-4

(M ifi ed

SS

PC

-1

Zi nc -R ich im er

.5

3.

Se rie s 9 1-

H2

Hy dr o- Z in c

Ep ox y 3.

0- 5.

N1

Po ly ur et ha ne

.0

3.

E nd ur a- Sh ie ld

Fl uo ro po ly m er

Ur et ha ne

.0

3.

Se rie s 7

H yd ro

Fl on

9.

- 1 4.

IC

S-

SS

PC

-1

(Im m er sio n)

SS

PC

-6 (I nt er io r D ry

Ex ce pt b ot to m o f b ow l)

SS

PC

-6 (I nt er io r D ry

Ta nk B ow l)

Zi nc

0% S ol id s

.5

.5

(M ifi e 2.

- 3

.0

(4 2.

- 5

2.

5)

Se rie s 9 1-

H2

Se rie s F C2

Hy dr o-

Zi nc

Ep ox ol in e

IC

S-

(M od ifi e d) er

.5

3.

Se rie s 9

1- H2

Hy dr o-

Z in c

Ep ox y 4.

6.

Se rie s

Ep ox y 6.

8.

Se rie s

.5 er

.5

3.

Se rie s 9

1- H2

Hy dr o-

Z in c

Ac lic

In su la tio n m ils

Se rie s 9

Ae ro lo n

Ep ox y 2.

4.

Se rie s

HS

P t

4.

7.

Co nc re

SS

PC

-7

Ac lic

E la st om er ic

Ac lic

4.

- 6

4.

- 6 s 1 s 1

En vi ro

-C

En vi ro -C

A str ipe co at of ep ox y s ha ll b e a pp lie d b y b ru sh to al l w eld se am s, lad de rs, ed ge s, etc

., p rio r t o r ec eiv ing fir st int er me dia te co at on ex ter ior su rfa ce s a nd pr ior to th e f ini sh co at on in ter ior su rfa ce s.

2 A ll i nte rio r r oo f b ea ms

, s ha rp ed ge s a nd ot he r d iffi cu lt t o c oa t a re as sh all re ce ive

.0 –4

5.0 m ils of ep ox y l ini ng 3 T ota l D ry Fil m Th ick ne ss fo r r oo f b ea ms , s ha rp ed ge s a nd ot he r d iffi cu lt t o c oa t a re as 4 A ll p ro du cts ar e a s m an ufa ctu re d b y T ne me c C om pa ny , In c.

5 M il t hic kn es se s f or in div idu al co ats sh all no t e xc ee d m an ufa ctu re r’s w ritt en re co mm en da tio n.

6 A n a dd itio na l c oa t o f z inc -ri ch pr im er sh all be sh op -a pp lie d t o t he re pla ce me nt lad de rs an d o the r r ep lac em en t p ar ts.

H ur lb ur tF ie ld ,F

L Ta nk N o.

Ta nk

In sp ec tio n R ep or t Pr oj ec t N o.

:4

9-

Pa ge o f 9

Tank No. 91134

Appendix

Tank No. 91134

Photos

Tank No. 91134

1-Base of pedestal covered with heavy mildew

Tank No. 91134

2-Heavy mildew around entirety of base of pedestal

Tank No. 91134

Tank No. 91134

Tank No. 91134

Tank No. 91134

Tank No. 91134

Tank No. 91134

3-Overflow splash pad and riprap runoff area is adequate and performing as designed with no excess washing

Tank No. 91134

4-Interior of mouth of overflow pipe is heavily corroded, screen is intact with debris partially clogging screen from interior

Tank No. 91134

5-Overflow flapper working properly, but coating is failing and peeling

Tank No. 91134

6-Floor drain screen is intact but corroding

Tank No. 91134

7-All sharp edges on interior of door and door frame corroding

Tank No. 91134

8-Coating beginning to fail on painter's rings allowing corrosion to form

Tank No. 91134

9-Mildew widespread nearly to top of tank pedestal

Tank No. 91134

10-Coating failing on anchor bolts and corrosion forming, particularly in area behind bolts. Should be blasted, tool cleaned and front covered with welded seal plate (with grease fitting installed). Then void in box should be filled with grease.

Tank No. 91134

11-Closer view of anchor bolt

Tank No. 91134

12-Tank data plate painted over

Tank No. 91134

13-Interior light at base of pedestal operational

Tank No. 91134

14-Underside of bottom platform

Tank No. 91134

15-Coatings on interior dry areas of tank in generally good condition

Tank No. 91134

16-Safety grating should be installed over valve pit to prevent fall/trip hazard

Tank No. 91134

Tank No. 91134

Tank No. 91134

17-Coating on floor of first platform is failing and cracking.

Discoloration is combination of mildew, dirt and scattered corrosion.

Tank No. 91134

18-Piping through dry tube of tank is properly braced with room for expansion and contraction of piping.

Tank No. 91134

19-Lighting through dry tube not operational

Tank No. 91134

20-Bolts on fill pipe beginning to corrode

Tank No. 91134

21-Fill pipe bolts

Tank No. 91134

22-Ladder and safety climb properly aligned and functional. No lighting in dry tube.

Tank No. 91134

Tank No. 91134

23-Expansion joint in top of fill pipe in good condition

Tank No. 91134

24-Interior coatings in generally good condition

Tank No. 91134

25-Floor of top platform showing coating failure, with heaviest corrosion on weld seams and sharp edges.

Tank No. 91134

26-Open holes in platform floor should be covered with plate during next repaint to alleviate trip hazard.

Tank No. 91134

27-Top coat of paint in good condition, but coating system is beginning to crack and fail from base coat.

Tank No. 91134

28-More cracking of coating in dry interior and corrosion forming along rough weld seams

Tank No. 91134

29-Blisters in coating on dry interiorwall

Tank No. 91134

30-Exterior of tank through painter's hatch at top of pedestal

Tank No. 91134

31-Corrosion of weld seams as viewed from painter's hatch

Tank No. 91134

32-Downward view of exterior from painter's hatch

Tank No. 91134

33-Exterior coating beginning to fail. Small stress cracking throughout exterior. Difficult to photograph.

Tank No. 91134

34-Small cracks throughout coatings as paint is beginning to fail. Difficult to photograph.

Tank No. 91134

35-General paint fatigue evident at top of dry tube into bowl.

Tank No. 91134

36-Coating is rough with bubbles and drips and beginning to crack.

Tank No. 91134

37-Very rough finish on current coatings. Poor workmanship during prior coating installations. Each coat should have been applied smoothly with any drips, runs or irregularities sanded out.

Tank No. 91134

38-Ladder and safety climb through dry tube in good condition.

Tank No. 91134

Tank No. 91134

39-Ladder through dry tube

Tank No. 91134

40-Cracking and blistering of paint more visible at top of dry tube (interior).

Tank No. 91134

41-More blistering and cracking of interior coating at top of dry tube.

Tank No. 91134

42-Clips and other appurtenances on roof of tank are corroding.

Tank No. 91134

43-Widespread cracking and coating failure on top of tank. Most evident at cathodic protectioncaps.

Tank No. 91134

44-Scattered rust spots where coating isfailing

Tank No. 91134

45-Severe cracking and corrosion forming near hatch on top of tank.

Tank No. 91134

46-Coating on top of tank discolored, cracking and blistering. Has reached end of useful life.

Tank No. 91134

47-Widespread cracking with rust forming in areas where coating has completely released from steel.

Tank No. 91134

48-Up close view of cracking. Difficult to photograph.

Tank No. 91134

49-Discoloration and coating failure around base of tank vent.

Tank No. 91134

50-Vent screen is intact but coating failing on tank vent, most severely along flange edges.

Tank No. 91134

51-Broken conduit and heavy corrosion on top of tank.

Tank No. 91134

52-Corrosion at cathodic protectioncover.

Tank No. 91134

53-Interior wet ladder has widespread coating failure and should be blasted and coated soon or will require replacement. Safety climb equipment has been painted and is not usable. Should be replaced.

Tank No. 91134

54-Corrosion on interior walls visible through water.

Tank No. 91134

55-Major coating failure and rust forming at and above customary waterline throughout tank. Rust also visible on tanks walls below waterline.

Tank No. 91134

Tank No. 91134

56-Junction of dry tube and roof inside wet area of tank showing heavy corrosion along seam.

Tank No. 91134

57-Closer view of complete coating failure in area of water line.

Tank No. 91134

58-Complete failure of coating system in large areas of tank ceiling.

Tank No. 91134

59-More tank ceiling with complete coating failure.

Tank No. 91134

60-Widespread coating failure on tank wall above water line.

Tank No. 91134

61-Stain, minor sediment and corrosion in floor of tank visible through the water.

Tank No. 91134

62-Another view of tank roof and dry tube junction with heavy corrosion at seam.

Tank No. 91134

63-Underside of vent inside tank is corroding. Also clips and seams inside wet area exhibiting coating failure.

Tank No. 91134

64-Ceiling of tank and dry tube seam, corroding at seam and staining adjoining areas.

Tank No. 91134

65-Complet coating failure at top of flanged dry riser on exterior top of tank.

Tank No. 91134

66-Vent in adequate condition but widespread paint fatigue and failure on top of tank.

Tank No. 91134

67-Widespread scattered coating failure with spots of corrosion forming where paint has completely separated from the steel top oftank.

Tank No. 91134

68-Heavy runs in existing coating is sign of poor workmanship. Should have been sanded smooth.

Tank No. 91134

69-Floor of platform is corroding most heavily at thick, rough weld seams.

Tank No. 91134

70-Underside of belly of tank (view from interior platform). Final coat is rough and uneven with cracks beginning to form.

Tank No. 91134

71-Platforms are skip welded, which is acceptable, but welds are very thick and rough, difficult to coat properly.

Tank No. 91134

Tank No. 91134

72-Fill pipe through landing. Properly braced with allowance for expansion and contraction.

Tank No. 91134

73-Widespread "alligator" cracking is visible on underside of hatch to top of tank. Coating system in this condition has reached end of usable life. Not a candidate for overcoating.

Tank No. 91134

74-Close up view of fatigued coating cracking.

Tank No. 91134

75-Uneven thicknesses with heavy runs and drips in existing coating. Poor workmanship in prior paintings.

Tank No. 91134

76-Appears to be a plate welded to cover a hole in side of tank. Very rough weld and coating is cracking at seams and in general area.

Tank No. 91134

77-Close up of blistering, failingpaint.

Tank No. 91134

78-Interior view of underside of tankbelly.

Tank No. 91134

79-Blistering and rusting on fillpipe.

File details come from the government source that posted it.