Hurlburt Field, FL Tank Inspection Report
Tank No. 91134 Project No.:49-060
TANK INSPECTION REPORT
Tank Name: 91134 Tank Type: Elevated (Pedestal) Location: Hurlburt AFB Tank Capacity: 250,000 gallons State: FL Type of Construction: Steel Built By: Unknown Location:
Year Built: Unknown (Data plate painted over) Inspected By: Eric Boling Inspection Date: 2/22/19
GENERAL SUMMARY
Overall the tank is in fair condition with corrosion at most sharp edges and scattered throughout the tank surface, particularly on roof fixtures, ladders and floor of platforms. Coating system is beginning to show signs of failure with cracking and lifting of the multi-layer coatings throughout the tank surface.
RECOMMENDATIONS
Blast and repaint entirety of tank within next two years to prevent steel loss and protect long term integrity of thetank Blast and clean anchor bolts and area inside bolt enclosures as thoroughly as possible. Re-coat and cover front of enclosurewith welded steel plate with grease fitting. Fill void around bolts with grease for maximum long-term protection.
Install safety grating over valve pit in floor of tank.
Repair or replace lighting through dry access tube of tank.
Seal open holes on platforms with welded steel plates duringnext repaint to remove trip/fall hazard.
Tank No. 91134
Replace wet area ladder and safety climb equipment during next repaint.
Tank No. 91134
STANDARDS
The inspection of the tank was performed with the tank nearly full and no cleaning was performed. The inspection consisted of a visual observation of the tank’s interior (as feasible with water present) and exterior components and coating system. Interior and exterior assessment was documented using digital still photography, representative samples of which are included in the Appendix of this report.
CONDITION OBSERVATIONS
Conditions noted in this report are documented in the following pages and supported by color photographs in the Appendix. Condition ratings used to describe field findings are defined as follows:
Excellent No deficiencies noted.
Good Minor deficiencies noted. Structure is functioning as designed.
Fair Major deficiencies noted. Structure is in need of repair (or replacement) to continue functioning as designed.
Poor Repair or replacement required immediately. Item nolonger functioning as designed
CONTAMINATION, HEALTH & SAFETY REPORT
Contamination & Health Overall Condition: Excellent
Overflow pipe is equipped with screen, gasket and flapper to prevent access for insects All manways and hatches fit properly and wereclosed Roof vent is properly screened to prevent access for insects
Facility Safety Compliance Overall Condition: Fair
Tank is located inside locked, fenced area at secure military site Dry area ladders and safety climb in good condition but require coating replacement within next 1-2 years to avoid replacement.
Wet area ladder is heavily corroded and safety climb equipment has been painted over and is unusable. Both should be replaced at next repaint.
Valve pit in floor of tank has no safety grid over it, creating a fall/trip hazard Platforms have open holes that are a fall/trip hazard.
Tank No. 91134
INTERIOR RESERVOIR INSPECTION REPORT
Interior Reservoir Roof Overall Condition: Poor
Most of ceiling coating in poor condition Ceiling coating has completely failed and ceiling is corroding throughout the tank Undetermined if cathodic protection system is working
Interior Reservoir Walls Overall Condition: Fair
Coating on walls in area of water surface showing consistent corrosion and coating failure Coating on walls throughout showing signs of cracking and beginning to release from steel walls Corrosion is evident on areas of walls below the watersurface
Interior Reservoir Floor Overall Condition: Undetermined
Sediment and corrosion can be seen on floor of bowl, but complete inspection not possible without tank drained.
Interior Reservoir Plumbing Components Overall Condition: Good
Overflow pipe assembly is in good condition with corrosion along piping from water line up.
Interior Riser Overall Condition: Good
Wet side of access tube is in generally good shape with coating in better condition than that of ceiling and walls.
EXTERIOR RESERVOIR INSPECTION REPORT
Exterior Reservoir Roof Overall Condition: Fair
Coating on tank roof is in overall fair condition with scattered spots of minor corrosion, particularly along roof seams. Coating is beginning to crack and lift over the entirety of the tank roof, which will expose steel to the elements if coating is allowed to continue to degrade.
Roof vent is in good condition and is properly screened, but the tank/vent connection seam is showing minor to heavy corrosion around its perimeter.
Cathodic appear sealed but are corroding and staining top of tank
Tank No. 91134
Lip of primary hatch is corroded and should be rehabbed soon.
Tank No. 91134
Exterior Reservoir Walls Overall Condition: Fair
Coating on exterior walls in fair condition with signs of corrosion and/or coating failures Heavier corrosion along all sharp edges (painter’s ring, hatches), which is typical
Exterior Pedestal Overall Condition: Fair
Pedestal is heavily mildewed and coating is starting to crack through to the base metal over the entirety of the exterior of the tank. The coating system has reached the end of its useful tank and needs to be replaced soon to protect the integrity of the tank.
Exterior Plumbing Structures Overall Condition: Good
Overflow pipe assembly in good condition and properly braced. Coating is starting to fail, as evidenced on remainder of tank, but piping is still salvageable.
Overflow splash pad and riprap are adequate and functioning properly.
Foundation Overall Condition: Good
Foundation of pedestal in good condition with minor grout loss between base and foundation Interior of anchor bolt enclosures and threads of anchor bolts have coating failure and corrosion that needs to be addressed.
GENERAL TANK SECURITY
Security Overall Condition: Excellent
Tank is located inside locked, fenced area at secure military site All ladders are inside tank with locked door.
Cathodic Protection System
Type, size, material and # of anodes: Overall Condition: N/A
Present but condition unknown.
TA
BL
E
R ec om m en de d
C oa tin gs
S ch ed ul e
Co at in g
Su rfa ce P re p
Pr im e6
(m ils
DF
T)
In te rm ed ia
#1
(m ils
Pr od uc t4
In te rm ed ia
#2 ils uc t4
Fi na l (m ils
To ta l Sy st em ils
D
FT
O
CS
-4
(M ifi ed
SS
PC
-1
Zi nc -R ich im er
.5
3.
Se rie s 9 1-
H2
Hy dr o- Z in c
Ep ox y 3.
0- 5.
N1
Po ly ur et ha ne
.0
3.
E nd ur a- Sh ie ld
Fl uo ro po ly m er
Ur et ha ne
.0
3.
Se rie s 7
H yd ro
Fl on
9.
- 1 4.
IC
S-
SS
PC
-1
(Im m er sio n)
SS
PC
-6 (I nt er io r D ry
Ex ce pt b ot to m o f b ow l)
SS
PC
-6 (I nt er io r D ry
Ta nk B ow l)
Zi nc
0% S ol id s
.5
.5
(M ifi e 2.
- 3
.0
(4 2.
- 5
2.
5)
Se rie s 9 1-
H2
Se rie s F C2
Hy dr o-
Zi nc
Ep ox ol in e
IC
S-
(M od ifi e d) er
.5
3.
Se rie s 9
1- H2
Hy dr o-
Z in c
Ep ox y 4.
6.
Se rie s
Ep ox y 6.
8.
Se rie s
.5 er
.5
3.
Se rie s 9
1- H2
Hy dr o-
Z in c
Ac lic
In su la tio n m ils
Se rie s 9
Ae ro lo n
Ep ox y 2.
4.
Se rie s
HS
P t
4.
7.
Co nc re
SS
PC
-7
Ac lic
E la st om er ic
Ac lic
4.
- 6
4.
- 6 s 1 s 1
En vi ro
-C
En vi ro -C
A str ipe co at of ep ox y s ha ll b e a pp lie d b y b ru sh to al l w eld se am s, lad de rs, ed ge s, etc
., p rio r t o r ec eiv ing fir st int er me dia te co at on ex ter ior su rfa ce s a nd pr ior to th e f ini sh co at on in ter ior su rfa ce s.
2 A ll i nte rio r r oo f b ea ms
, s ha rp ed ge s a nd ot he r d iffi cu lt t o c oa t a re as sh all re ce ive
.0 –4
5.0 m ils of ep ox y l ini ng 3 T ota l D ry Fil m Th ick ne ss fo r r oo f b ea ms , s ha rp ed ge s a nd ot he r d iffi cu lt t o c oa t a re as 4 A ll p ro du cts ar e a s m an ufa ctu re d b y T ne me c C om pa ny , In c.
5 M il t hic kn es se s f or in div idu al co ats sh all no t e xc ee d m an ufa ctu re r’s w ritt en re co mm en da tio n.
6 A n a dd itio na l c oa t o f z inc -ri ch pr im er sh all be sh op -a pp lie d t o t he re pla ce me nt lad de rs an d o the r r ep lac em en t p ar ts.
H ur lb ur tF ie ld ,F
L Ta nk N o.
Ta nk
In sp ec tio n R ep or t Pr oj ec t N o.
:4
9-
Pa ge o f 9
Tank No. 91134
Appendix
Tank No. 91134
Photos
Tank No. 91134
1-Base of pedestal covered with heavy mildew
Tank No. 91134
2-Heavy mildew around entirety of base of pedestal
Tank No. 91134
Tank No. 91134
Tank No. 91134
Tank No. 91134
Tank No. 91134
Tank No. 91134
3-Overflow splash pad and riprap runoff area is adequate and performing as designed with no excess washing
Tank No. 91134
4-Interior of mouth of overflow pipe is heavily corroded, screen is intact with debris partially clogging screen from interior
Tank No. 91134
5-Overflow flapper working properly, but coating is failing and peeling
Tank No. 91134
6-Floor drain screen is intact but corroding
Tank No. 91134
7-All sharp edges on interior of door and door frame corroding
Tank No. 91134
8-Coating beginning to fail on painter's rings allowing corrosion to form
Tank No. 91134
9-Mildew widespread nearly to top of tank pedestal
Tank No. 91134
10-Coating failing on anchor bolts and corrosion forming, particularly in area behind bolts. Should be blasted, tool cleaned and front covered with welded seal plate (with grease fitting installed). Then void in box should be filled with grease.
Tank No. 91134
11-Closer view of anchor bolt
Tank No. 91134
12-Tank data plate painted over
Tank No. 91134
13-Interior light at base of pedestal operational
Tank No. 91134
14-Underside of bottom platform
Tank No. 91134
15-Coatings on interior dry areas of tank in generally good condition
Tank No. 91134
16-Safety grating should be installed over valve pit to prevent fall/trip hazard
Tank No. 91134
Tank No. 91134
Tank No. 91134
17-Coating on floor of first platform is failing and cracking.
Discoloration is combination of mildew, dirt and scattered corrosion.
Tank No. 91134
18-Piping through dry tube of tank is properly braced with room for expansion and contraction of piping.
Tank No. 91134
19-Lighting through dry tube not operational
Tank No. 91134
20-Bolts on fill pipe beginning to corrode
Tank No. 91134
21-Fill pipe bolts
Tank No. 91134
22-Ladder and safety climb properly aligned and functional. No lighting in dry tube.
Tank No. 91134
Tank No. 91134
23-Expansion joint in top of fill pipe in good condition
Tank No. 91134
24-Interior coatings in generally good condition
Tank No. 91134
25-Floor of top platform showing coating failure, with heaviest corrosion on weld seams and sharp edges.
Tank No. 91134
26-Open holes in platform floor should be covered with plate during next repaint to alleviate trip hazard.
Tank No. 91134
27-Top coat of paint in good condition, but coating system is beginning to crack and fail from base coat.
Tank No. 91134
28-More cracking of coating in dry interior and corrosion forming along rough weld seams
Tank No. 91134
29-Blisters in coating on dry interiorwall
Tank No. 91134
30-Exterior of tank through painter's hatch at top of pedestal
Tank No. 91134
31-Corrosion of weld seams as viewed from painter's hatch
Tank No. 91134
32-Downward view of exterior from painter's hatch
Tank No. 91134
33-Exterior coating beginning to fail. Small stress cracking throughout exterior. Difficult to photograph.
Tank No. 91134
34-Small cracks throughout coatings as paint is beginning to fail. Difficult to photograph.
Tank No. 91134
35-General paint fatigue evident at top of dry tube into bowl.
Tank No. 91134
36-Coating is rough with bubbles and drips and beginning to crack.
Tank No. 91134
37-Very rough finish on current coatings. Poor workmanship during prior coating installations. Each coat should have been applied smoothly with any drips, runs or irregularities sanded out.
Tank No. 91134
38-Ladder and safety climb through dry tube in good condition.
Tank No. 91134
Tank No. 91134
39-Ladder through dry tube
Tank No. 91134
40-Cracking and blistering of paint more visible at top of dry tube (interior).
Tank No. 91134
41-More blistering and cracking of interior coating at top of dry tube.
Tank No. 91134
42-Clips and other appurtenances on roof of tank are corroding.
Tank No. 91134
43-Widespread cracking and coating failure on top of tank. Most evident at cathodic protectioncaps.
Tank No. 91134
44-Scattered rust spots where coating isfailing
Tank No. 91134
45-Severe cracking and corrosion forming near hatch on top of tank.
Tank No. 91134
46-Coating on top of tank discolored, cracking and blistering. Has reached end of useful life.
Tank No. 91134
47-Widespread cracking with rust forming in areas where coating has completely released from steel.
Tank No. 91134
48-Up close view of cracking. Difficult to photograph.
Tank No. 91134
49-Discoloration and coating failure around base of tank vent.
Tank No. 91134
50-Vent screen is intact but coating failing on tank vent, most severely along flange edges.
Tank No. 91134
51-Broken conduit and heavy corrosion on top of tank.
Tank No. 91134
52-Corrosion at cathodic protectioncover.
Tank No. 91134
53-Interior wet ladder has widespread coating failure and should be blasted and coated soon or will require replacement. Safety climb equipment has been painted and is not usable. Should be replaced.
Tank No. 91134
54-Corrosion on interior walls visible through water.
Tank No. 91134
55-Major coating failure and rust forming at and above customary waterline throughout tank. Rust also visible on tanks walls below waterline.
Tank No. 91134
Tank No. 91134
56-Junction of dry tube and roof inside wet area of tank showing heavy corrosion along seam.
Tank No. 91134
57-Closer view of complete coating failure in area of water line.
Tank No. 91134
58-Complete failure of coating system in large areas of tank ceiling.
Tank No. 91134
59-More tank ceiling with complete coating failure.
Tank No. 91134
60-Widespread coating failure on tank wall above water line.
Tank No. 91134
61-Stain, minor sediment and corrosion in floor of tank visible through the water.
Tank No. 91134
62-Another view of tank roof and dry tube junction with heavy corrosion at seam.
Tank No. 91134
63-Underside of vent inside tank is corroding. Also clips and seams inside wet area exhibiting coating failure.
Tank No. 91134
64-Ceiling of tank and dry tube seam, corroding at seam and staining adjoining areas.
Tank No. 91134
65-Complet coating failure at top of flanged dry riser on exterior top of tank.
Tank No. 91134
66-Vent in adequate condition but widespread paint fatigue and failure on top of tank.
Tank No. 91134
67-Widespread scattered coating failure with spots of corrosion forming where paint has completely separated from the steel top oftank.
Tank No. 91134
68-Heavy runs in existing coating is sign of poor workmanship. Should have been sanded smooth.
Tank No. 91134
69-Floor of platform is corroding most heavily at thick, rough weld seams.
Tank No. 91134
70-Underside of belly of tank (view from interior platform). Final coat is rough and uneven with cracks beginning to form.
Tank No. 91134
71-Platforms are skip welded, which is acceptable, but welds are very thick and rough, difficult to coat properly.
Tank No. 91134
Tank No. 91134
72-Fill pipe through landing. Properly braced with allowance for expansion and contraction.
Tank No. 91134
73-Widespread "alligator" cracking is visible on underside of hatch to top of tank. Coating system in this condition has reached end of usable life. Not a candidate for overcoating.
Tank No. 91134
74-Close up view of fatigued coating cracking.
Tank No. 91134
75-Uneven thicknesses with heavy runs and drips in existing coating. Poor workmanship in prior paintings.
Tank No. 91134
76-Appears to be a plate welded to cover a hole in side of tank. Very rough weld and coating is cracking at seams and in general area.
Tank No. 91134
77-Close up of blistering, failingpaint.
Tank No. 91134
78-Interior view of underside of tankbelly.
Tank No. 91134
79-Blistering and rusting on fillpipe.