Requirement Update

FA441719Q0188

September 6, 2019

There has been a brand new 480V, three-phase, 400 amp panel installed replacing the old wall power unit. The new panel is currently wired to the old breaker which is 225 amps. A new breaker will need to be installed. The purchase of the washer shall include the associated electrical connection back to the main panel including: disconnect, wire, conduit, and breaker in the new panel.

Old Requirement:

Wall power unit:

Maximum 600V/60AMP. Current unit is a 460V three phase unit.

Installation of new washer:

Required

New Requirement:

Wall power unit:

Maximum 480V/400AMP. Current unit is a 480V three phase unit.

Installation of new washer:

Required to include associated electrical connection back to the main panel including: disconnect, wire, conduit, and breaker in the new panel.