These are clarifying questions to the previous update that was posted

View the file

Other files for this federal contract opportunity

Other files attached to Parts Washer, newest first.
File Type Posted
Parts_Washer_Electrical_Requirement_Update.docx DOCX document
Parts_Washer_Questions_and_Answers_3_September.docx DOCX document
Minimum_Requirements_For_Aqueous_Parts_Washer.docx DOCX document
RFQ_Parts_Washer_FA441719Q0188.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Requirement Update

FA441719Q0188

September 10, 2019

There has been a brand new 480V, three-phase, 400 amp panel installed replacing the old wall power unit. The new panel is currently wired to the old breaker which is 225 amps. A new breaker will need to be installed. The purchase of the washer shall include the associated electrical connection back to the main panel including: disconnect, wire, conduit, and breaker in the new panel.

Old Requirement:

Wall power unit:

Maximum 600V/60AMP. Current unit is a 460V three phase unit.

Installation of new washer:

Required

New Requirement:

Wall power unit:

Maximum 480V/400AMP. Current unit is a 480V three phase unit.

Installation of new washer:

Required to include associated electrical connection back to the main panel including: disconnect, wire, conduit, and breaker in the new panel.

Questions Received from above update

1) Are you asking the vendors to install a breaker in your panel?

A: Yes, a breaker will be installed in a new breaker panel. Please see picture attached.

2) How far away is this machine?

A: The breaker panel is approximately 60 feet from the parts washer.

3) How long does the run need to be?

A: The run is 60 feet from the breaker panel to the parts washer.

4) Does it need to go through any floors/walls?

A: The wiring will feed through a conduit in the drop ceiling and be mounted to a bracket. Please see photo.

5) Does it matter how it’s run?

A: The wiring will be run through the ceiling please see photo from question 4.

The new parts washer will be delivered through a roll up door, and its measurement is slightly larger than 9’ tall x 8’ wide. The current parts washer that needs to be removed is approximately 9’ tall x 7’7” wide.

This is a photo of the newly installed electrical panel for the parts washer.

This is shot of the main breaker.

This is a shot showing that there is nothing installed.

This is a shot of the existing parts washer.

1179107313C Line

1179107313C Text Box Power IN

This is a shot of the inside of the parts washer.

This is a shot of the venting system from the front of the parts washer.

This is a shot of the venting system from the back of the parts washer.

The parts washer will be installed in a pit that is approx 9” deep.

This is a shot of the old breaker that supplies power to the parts washer.

This is a shot of the power conduit that supply’s power to the parts washer via the old breaker. NOTE: This conduit is running above the drop ceiling. The new power conduit will be installed above the drop ceiling to the new power panel shown in photo 1, for estimating purposes, the distance is approx 60’.

This is a shot of the rollup access door.

1179107313C Line

1179107313C Line

1179107313C Text Box 8ft across

1179107313C Text Box 9ft tall

File details come from the government source that posted it.