Number Question Answer
1 Question:
Will GAFB provide the List of Attendees?
Answer:
Yes, Record of Attendance will be provided with Amendment 0001.
Question:
Do you anticipate an extension for Quote due date (Mar. 29)?
Answer:
Yes, an extension is anticipated. Dates changed from 29 March to 5 Apr 2023.
Question:
Sections 52.228-1, 52.228-15 indicate Bid Guarantee, Performance and Payment Bonds Construction, are these items required for this contract?
Answer:
Does not apply, Those clauses are not included in Solicitation FA303023Q0009; please revisit 13B, Section I, and Section L.
Question:
For the Fire Academy location (B3453), can you provide the required window of shut-down time(s), also if this location will require a temporary chiller solution while the repair is conducted?
Answer:
Multiple factors play into this: The Government would prefer B3453 chiller repair be done in the winter to limit the effect on the facility.
Timing would be dependant on the contract award, NTP, Contractor's submitted schedule, and the Contractors' ability to execute the repair. Normal duty hours at B3453 are 0600 to 1630 M- F; weekend work would be considered upon request. The expectation would be to accomplish this repair within a 4 to 5 day window. The contractor could consider the use of the weekend to allow for correct cure time and reassembly of this chiller the following Monday. The Government will not provide a temporary chiller solution.
Question:
Is there refrigerant currently in any of the three chillers?
Answer:
Yes, all three (3) chillers are fully operational and have refrigerant in them.
Question:
Will we be responsible for recovery, pressure test, vacuum or recharge?
Answer:
Yes, An updated Attachment 1 - Statework of Work (Revision 2) was provided with Amendment 0001. Changes are in - Section 3, 3.3.4, and 3.3.5. and also, Section 4.2, c,d, and e.
7 Question Has an eddy current test been conducted? Will one be required?
Answer:
Eddy current was conducted on all three (3) chillers in 2021.
Question:
Is there oil currently in any of the three chillers?
Answer:
Yes, because all three (3) chillers have refrigerant in them, they all have refrigerant oil in them.
Question:
Will we be responsible for oil filter change, oil change or adding oil?
Answer:
No, unless the contractor creates a circumstance where the refrigerant systems are in some way compromised due to the work required in the SOW. Note- there are no know leaks in any of the three (3) chillers at this time.
Question:
Will we be responsible for any water treatment after the job is complete?
Answer:
No water treatment is required in the execution of the SOW for the Contractor.
Question:
Is retubing an option?
Answer:
No, retubing is not the course the Government has prescribed in the SOW. Retube is far outside the scope of this project.
Question:
What will be the procedure if an area of a tube plate or tube is deemed unrepairable without work that is outside the scope of work?
Answer:
At that point, the Contractor shall alert the Contracting Officer, Contract Specialist and the COR as soon as this is verified. The Government will meet, discuss and the Contractor will provide a path forward toward resolution.
FA303023Q0009 - Questions & Answers Chiller Repairs B259/B521/B3453