This document is an Addendum to a federal contract for replacing Air Handling Units (AHUs) at Azalea Dining Hall B6960 located at Keesler Air Force Base in Mississippi. The addendum modifies the original Statement of Work (SOW) and Drawings, adding several key requirements: contractors must protect KEF-KSF units from lightning by installing #6 bonding wire to existing grounding conduits, ensure the Superintendent and QA/QC roles are performed by separate individuals, provide 24-hour contact information for at least two contractor representatives, maintain on-site safety protocols, and comply with labor safety standards. Additionally, the electrical drawing (Sheet E-101) was modified by removing the word "Adjacent" to allow disconnect switches to be directly attached to the KEF/KSF units.
View the file
Other files for this federal contract opportunity
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM 1 Date: August 22, 2025
CONTRACT NUMBER: FA301025R0025
PROJECT NAME: Replace AHU’s Azalea Dining Hall B6960
LOCATION: B6960 - Keesler AFB, Mississippi
PROJECT NUMBER: MAHG241052
WORK ORDER: N/A
This Addendum is hereby part of the Contract Documents. The following conditions take precedence over conflict conditions in the Specifications, on the Drawings, and in any other Contract Document. When a change is called for on a Drawing, this change shall carry through all applicable drawings, including all related architectural, civil, structural, mechanical, plumbing and electrical drawings. The Contract Documents are hereby amended in the following particulars:
I. Relating to the Statement of Work:
A. Added to SOW
1. Reference 3.2.4.4.2.2: Properly protect all KEF – KSF units from lightning by providing and installing #6 bonding wire to existing grounding conduits.
B. Added to SOW
1. 3.6.3 The roles of Superintendent and QA/QC must be performed by two separate individuals.
2. 3.6.4 The Contractor shall provide a written notification to the CO of the names and contact information (phone number, and email) of a minimum of two Contractor Representatives that will be responsible for this project and have 24-hour contact availability to answer any questions or address any issues that may arise related to this project.
3. 3.11.2 Safeguard the public and Government personnel, property, materials, supplies, and equipment exposed to Contractor operations and activities; avoid interruptions of Government operations and delays in project completion dates; and control costs in the performance of this contract.
4. 3.11.1 At all times during performance of this contract and until the work is completed and accepted, the Contractor shall have on the worksite a competent safety officer who is satisfactory to the Contracting Officer and has authority to act for the Contractor. Circumstantially, this role may be filled by a qualified Superintendent or a Qualified QA/QC upon approval by the CO.
5. 3.11.3 For these purposes on contracts for construction or dismantling, demolition, or removal of improvements, the Contractor shall:
6. 3.11.3.1 Provide appropriate safety barricades, signs, and signal lights;
7. 3.11.3.2 Comply with the standards issued by the Secretary of Labor at 29
CFR Part 1926 and 29 CFR Part 1910;
8. 3.11.3.3 Ensure that any additional measures the Contracting Officer determines to be reasonably necessary for the purposes are taken.
II. Relating to the Drawings:
A. Drawing Sheet E-101
1. Deleted the word “Adjacent” from Electrical General Note 3. This enables the disconnect switches to be attached to the KEF / KSF.
END OF ADDENDUM 1