Att 4_FTFA 20-RC03 Drawings.pdf
PDF 6 MB Posted
- Attached to
- Replace and Improve HVAC System in Bldg 12722 Federal contract opportunity
- Solicitation number
- FA282322R0007
About this file
This solicitation requests proposals for a replacement and improvement of the HVAC system in Building 12722 at Eglin Air Force Base. Offerors must provide pricing using the 50 Division Cost Estimate worksheet and submit past performance questionnaires from references. Proposals are due within 14 days and the period of performance is estimated at 426 days. The acquisition is set aside for small businesses. The source selection will use tradeoff procedures and proposals shall follow instructions for electronic submission, formatting, and required contract documentation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Answers .pdf | ||
| Section_L_21 April 2022.pdf | ||
| Att 4_FTFA 20-RC03_Drawings_Final_Updated.pdf | ||
| FA282322R00070002.pdf | ||
| FA282322R00070001.pdf | ||
| Section_M.pdf | ||
| Solicitation - FA282322R0007.pdf | ||
| Att 3_Specifications.pdf | ||
| Attachment L2-FRQ.pdf | ||
| Attachment L1-50DC.xls | XLS spreadsheet | |
| Attachment L5-Past Performance Question (PPQ).pdf | ||
| Att 1_SOW-12722.pdf | ||
| Att 2_WD.pdf | ||
| Attachment L6 Cover Letter.pdf | ||
| Attachment L4 Consent Form.pdf | ||
| Attachment L3 Past Performance Information (PPI).pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text
ACC-1
AutoCAD SHX Text
ACC-2
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AHU-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLD
AutoCAD SHX Text
FLD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLD
AutoCAD SHX Text
FLD
AutoCAD SHX Text
AHU-7
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text
AHU-9
AutoCAD SHX Text
AHU-8
AutoCAD SHX Text
AHU-6
AutoCAD SHX Text
AHU-11
AutoCAD SHX Text
AHU-10
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PHASING NOTES
AutoCAD SHX Text CONTRACTOR TO HAVE ALL MAJOR COMPONENTS (INCLUDING CHILLERS, AHUS, PUMPS, AND SWITCH GEAR ECT.) ON SITE BEFORE SHUTTING DOWN ANY SYSTEMS. INSTALL NEW CHILLED WATER PIPING SYSTEM AND DDC CONTROL SYSTEMS WHILE EXISTING SYSTEM REMAINS OPERATIONAL INSTALL NEW CHILLED WATER PUMPS (CWP-1,2) IN NEW CHILLED WATER PIPING SYSTEM INSTALL BYPASS AT FUTURE AHU TIE IN POINTS, RUN NEW CHILLED WATER LOOP. BEFORE DEMOLISHING EXISTING SYSTEM CONTRACTOR TO SCHEDULE A POWER OUTAGE WITH THE USER DURING WHICH THE TRANSITION TO THE NEW SWITCH GEAR SHALL TAKE PLACE. CONTRACTOR TO PRE WIRE NEW WORK AS MUCH AS POSSIBLE TO MINIMIZE SYSTEM DOWNTIME. DEMO AND INSTALL NEW CHILLER (ACC-1) AND CONNECT TO NEW CW PIPING. START UP NEW CHILLER (ACC-1). THE AIR HANDLERS SHALL BE REMOVED AND REPLACED ONE AT A TIME AND SHALL BE CONNECTED TO THE NEW CHILLED WATER SYSTEM. THE ORDER OF THE AIR HANDLER REPLACEMENT SHALL BE BASED ON MISSION REQUIREMENTS. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE OPERATION OF BOTH CHILLED WATER SYSTEMS UNTIL ALL AIR HANDLING UNITS ARE TIED INTO THE NEW CHILLED WATER SYSTEM. DEMO AND INSTALL NEW ACC-2 CONNECTING TO NEW CW SYSTEM. DEMO EXISTING CHILLED WATER PUMPS. THE CONTRACTOR SHALL DEMO AND REMOVE THE EXISTING CHILLED WATER SYSTEM AND PUMPS ONCE THE NEW SYSTEM IS FUNCTIONING. PERFORM FLOW TEST ON FLOOR DRAINS TO VERIFY ANY CLOGS. CONTRACTOR SHALL COORDINATE WITH CUSTOMER THE NEW AHU-5 AND AHU-6 LOCATIONS RELATIVE TO EXISTING EQUIPMENT. AHU-10 AND AHU-11 SHALL BE REMOVED AND NEW AHU-10 INSTALLED BEFORE THE NEW AHU-11 IS INSTALLED THROUGH ACCESS PANEL LOCATED AS INDICATED IN SHEET NOTE. AHU-7 SHALL BE DEMOLISHED AND INSTALLED BEFORE AHU-5 AND AHU-6 IN ORDER TO PROVIDE ENOUGH ROOM TO REMOVE AND INSTALL AHU-7 NOTE: THE BUILDING SHALL BE OCCUPIED AND REMAIN OPERATIONAL DURING CONSTRUCTION. SCHEDULING NOTES: CONTRACTOR TO ALLOW FOR A POSSIBILITY OF TWELVE CLASSIFIED MISSION DAYS IN A SIX MONTH TIME PERIOD DURING WHICH THE PROJECT WILL BE INACCESSIBLE TO THE CONTRACTOR. THE BUILDING AND ITS MISSIONS CHANGE WITH VERY SHORT NOTICE DUE TO THIS THE CONTRACTOR WILL BE REQUIRED AT MINIMUM TO HAVE A SCHEDULING AND COORDINATION MEETING ONCE A WEEK WITH A USER REPRESENTATIVE AND/OR CONTRACTING OFFICERS REPRESENTATIVE. THE CONTRACTOR IS ALSO REQUIRED TO PROVIDE THE USER WITH AN PHYSICAL COPY OF AN OVERALL SCHEDULE THAT IS UPDATED AFTER ANY MAJOR SCHEDULING CHANGE. TYPICAL USER OPERATION HOURS 0600 - 1500 CST. THE BUILDING SHALL BE OCCUPIED AND REMAIN OPERATIONAL DURING CONSTRUCTION. FA NOTE: : THE ENTIRE BUILDING HAS MULTIPLE ACTIVE VESDA SMOKE DETECTION SYSTEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING THE EXISTING VESDA SYSTEMS FROM DAMAGE. SEE FA-001
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G-002
AutoCAD SHX Text
LBT
AutoCAD SHX Text
MECHANICAL PHASING PLAN
AutoCAD SHX Text
AutoCAD SHX Text
GDP
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 1ST FLOOR MECHANICAL PHASING PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 2ND FLOOR MECHANICAL PHASING PLAN
AutoCAD SHX Text
96 CEG, OFFICE FORM 002, FY2013
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
BY
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
EGLIN AIR FORCE BASE, FLORIDA
AutoCAD SHX Text
CENM
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
FTFA 20-RC03
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BLDG 12722 HVAC REPLACEMENT
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
22 JULY 2021
AutoCAD SHX Text
PETERSON ENGINEERING INC.
AutoCAD SHX Text
75 SOUTH "F" STREET
AutoCAD SHX Text
PENSACOLA, FLORIDA 32502
AutoCAD SHX Text
(850) 434-0513
AutoCAD SHX Text
(PROF. ENG. #: 3600)
AutoCAD SHX Text
PEI 2020100
AutoCAD SHX Text
AutoCAD SHX Text
21AC
AutoCAD SHX Text
21AC
AutoCAD SHX Text
AS-BUILT
AutoCAD SHX Text No. 34088
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text Y
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 1/8"= 1'- 0"
AutoCAD SHX Text 5'
AutoCAD SHX Text
AutoCAD SHX Text 5'
15'
SHEET NOTES
AutoCAD SHX Text EXISTING CEILING GRID AND TILES TO BE REMOVED AND REPLACED. EXISTING CEILING ACCESSORIES TO REMAIN, PROTECT DURING CONSTRUCTION. PROVIDE AND INSTALL NEW CEILING GRID IN CEILING ABOVE STAIRS. PLYWOOD CEILING IN ROOM OPEN CEILING AREA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
SUPPLY AIR DIFFUSER
AutoCAD SHX Text
CAN LIGHT
AutoCAD SHX Text
EMERGENCY EXIT LIGHT
AutoCAD SHX Text 2x4 FLORESCENT LIGHT FLUSH MOUNT
AutoCAD SHX Text
4' FLORESCENT LIGHT SUSPENDED
AutoCAD SHX Text
SMOKE DETECTOR
AutoCAD SHX Text
RETURN AIR GRILLE
AutoCAD SHX Text
%%ULEGEND
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
EM
AutoCAD SHX Text
EM
AutoCAD SHX Text
AutoCAD SHX Text 208A
AutoCAD SHX Text 208B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 208C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 210A
AutoCAD SHX Text 203A
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
EM
AutoCAD SHX Text
EM
AutoCAD SHX Text
EM
AutoCAD SHX Text
EMERGENCY STROBE LIGHT
AutoCAD SHX Text
BLUE STROBE LIGHT
AutoCAD SHX Text B
AutoCAD SHX Text
EXISTING ROUND DIFFUSERS
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 106A
AutoCAD SHX Text 110A
AutoCAD SHX Text B
AutoCAD SHX Text
EM
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
EM
AutoCAD SHX Text
EM
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A-100
AutoCAD SHX Text
LBT
AutoCAD SHX Text
REFLECTED CEILING PLANS
AutoCAD SHX Text
AutoCAD SHX Text
GDP
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 1ST FLOOR REFLECTED CEILING PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 2ND FLOOR REFLECTED CEILING PLAN
AutoCAD SHX Text
96 CEG, OFFICE FORM 002, FY2013
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
BY
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
EGLIN AIR FORCE BASE, FLORIDA
AutoCAD SHX Text
CENM
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
FTFA 20-RC03
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BLDG 12722 HVAC REPLACEMENT
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
22 JULY 2021
AutoCAD SHX Text
PETERSON ENGINEERING INC.
AutoCAD SHX Text
75 SOUTH "F" STREET
AutoCAD SHX Text
PENSACOLA, FLORIDA 32502
AutoCAD SHX Text
(850) 434-0513
AutoCAD SHX Text
(PROF. ENG. #: 3600)
AutoCAD SHX Text
PEI 2020100
AutoCAD SHX Text
AutoCAD SHX Text
21AC
AutoCAD SHX Text
21AC
AutoCAD SHX Text
AS-BUILT
AutoCAD SHX Text No. 34088
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text Y
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text 1/8"= 1'- 0"
AutoCAD SHX Text 5'
AutoCAD SHX Text
AutoCAD SHX Text 5'
AutoCAD SHX Text
BLACK&YELLOW
AutoCAD SHX Text
RED&WHITE
AutoCAD SHX Text
YELLOW
AutoCAD SHX Text
YELLOW
AutoCAD SHX Text
BLACK&YELLOW
AutoCAD SHX Text
BLACK&YELLOW
AutoCAD SHX Text
BLACK&YELLOW
AutoCAD SHX Text
BLACK&YELLOW
AutoCAD SHX Text
TYP
AutoCAD SHX Text
NEW WORK NOTES
AutoCAD SHX Text PROVIDE AND INSTALL FLOOR MARKING TAPE AS INDICATED ON SHEET. REFERENCE SPECIFICATION FOR OSHA BASED COLOR GUIDE.
AutoCAD SHX Text
AutoCAD SHX Text A-101
AutoCAD SHX Text
LBT
AutoCAD SHX Text
OSHA FLOOR MARKING LOCATIONS
AutoCAD SHX Text
AutoCAD SHX Text
GDP
AutoCAD SHX Text
96 CEG, OFFICE FORM 002, FY2013
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
BY
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
EGLIN AIR FORCE BASE, FLORIDA
AutoCAD SHX Text
CENM
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
FTFA 20-RC03
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BLDG 12722 HVAC REPLACEMENT
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
22 JULY 2021
AutoCAD SHX Text
PETERSON ENGINEERING INC.
AutoCAD SHX Text
75 SOUTH "F" STREET
AutoCAD SHX Text
PENSACOLA, FLORIDA 32502
AutoCAD SHX Text
(850) 434-0513
AutoCAD SHX Text
(PROF. ENG. #: 3600)
AutoCAD SHX Text
PEI 2020100
AutoCAD SHX Text
AutoCAD SHX Text
21AC
AutoCAD SHX Text
21AC
AutoCAD SHX Text
AS-BUILT
AutoCAD SHX Text No. 34088
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text Y
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 3/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 ENLARGED OSHA FLOOR MARKING PLAN
AutoCAD SHX Text 3/8"= 1'- 0"
AutoCAD SHX Text 7'
AutoCAD SHX Text 2'
AutoCAD SHX Text 12"
AutoCAD SHX Text 1'
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 3'
AutoCAD SHX Text 5'
AutoCAD SHX Text 6'
AutoCAD SHX Text N
AutoCAD SHX Text
%%UFIRST FLOOR KEY PLAN
NO SCALE
D P
R O
J E C
T
B l d g
H
V A
C
R e p l a c e m e n t D
W G
M e c h
F A d w g
A
M
AutoCAD SHX Text
FA-001
AutoCAD SHX Text
LBT
AutoCAD SHX Text
FIRE ALARM GENERAL NOTES
AutoCAD SHX Text
AutoCAD SHX Text
EK
AutoCAD SHX Text
FIRE ALARM GENERAL NOTES
AutoCAD SHX Text
1. THE FIRE ALARM CONTRACTOR SHALL MODIFY THE EXISTING FIRE ALARM SYSTEM AS REQUIRED TO SUPPORT THE NEW HVAC SYSTEM. THE FIRE THE FIRE ALARM CONTRACTOR SHALL MODIFY THE EXISTING FIRE ALARM SYSTEM AS REQUIRED TO SUPPORT THE NEW HVAC SYSTEM. THE FIRE ALARM WORK INCLUDES BUT IS NOT LIMITED TO PROVIDING AND INSTALLING NEW MONITORING MODULES, DUCT SMOKE DETECTORS, AND ALL REQUIRED CONDUIT AND WIRING. ALL WORK SHALL BE IN ACCORDANCE WITH NFPA 72, UFC 3-600-1, THE SPECIFICATIONS, EGLIN CRITERIA, AND THE AUTHORITY HAVING JURISDICTION. 2. THE CONTRACTOR SHALL RETAIN A REGISTERED FIRE PROTECTION ENGINEER (AS DEFINED BY UFC 3-600-01) TO BE THE QFPE FOR THE CONSTRUCTION THE CONTRACTOR SHALL RETAIN A REGISTERED FIRE PROTECTION ENGINEER (AS DEFINED BY UFC 3-600-01) TO BE THE QFPE FOR THE CONSTRUCTION CONTRACTOR SHALL RETAIN A REGISTERED FIRE PROTECTION ENGINEER (AS DEFINED BY UFC 3-600-01) TO BE THE QFPE FOR THE CONSTRUCTION PROJECT. THE QFPE SHALL BE INVOLVED WITH PRODUCTION OF FIRE ALARM SHOP DRAWINGS AND CALCULATIONS. THE QFPE MUST REVIEW AND SIGN AND SEAL THE SHOP DRAWINGS, CUTSHEETS, AND CALCULATIONS PRIOR TO SUBMITTING TO THE GOVERNMENT FOR REVIEW. THE QFPE MAY MAKE ADJUSTMENTS TO THE DEVICE LAYOUTS AS REQUIRED TO MAKE A COMPLETE AND OPERATIONAL SYSTEM. THE INSTALLATION MUST COMPLY WITH SPECIFICATION 28 31 76, UFC 3-600-01, AND NFPA 72. THE QFPE SHALL PROVIDE ALL INSPECTIONS AND INTERFACE WITH THE AHJ AS REQUIRED FOR A COMPLETE INSTALLATION. 3. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 4. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENT IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENT IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 5. A SET OF APPROVED FIRE ALARM SHOP DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. A SET OF APPROVED FIRE ALARM SHOP DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. 6. THE FIRE ALARM INSTALLER SHALL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT THE FIRE ALARM INSTALLER SHALL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. 7. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FMCP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC. 8. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). 9. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE. 10. FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. 11. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 12. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 13. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 14. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 15. ALL WIRING TO BE IN CONDUIT WITH FACTORY APPLIED RED FINISH. ALL WIRING TO BE IN CONDUIT WITH FACTORY APPLIED RED FINISH. 16. PROVIDE DUCT DETECTORS IN SUPPLY AIR SYSTEMS. PROVIDE DUCT DETECTORS IN SUPPLY AIR SYSTEMS. 17. PRE-FINAL & FINAL FIRE ALARM TESTING SHALL BE COORDINATED WITH EGLIN AFB PERSONNEL. PRE-FINAL & FINAL FIRE ALARM TESTING SHALL BE COORDINATED WITH EGLIN AFB PERSONNEL. 18. ALL WIRING TO BE SOLID COPPER. ALL WIRING TO BE SOLID COPPER. 19. MONITORING MODULES FOR SINGLE SERVICE. DUAL INPUT NOT PERMITTED. MONITORING MODULES FOR SINGLE SERVICE. DUAL INPUT NOT PERMITTED. . 20. ALL CONDUIT TO BE NEW AND PROVIDED WITH A FACTORY APPLIED RED FINISH. ALL CONDUIT TO BE NEW AND PROVIDED WITH A FACTORY APPLIED RED FINISH. 21. THE EXISTING FIRE ALARM COMPONENTS ASSOCIATED WITH THE REMOVAL OF THE HVAC SYSTEM AND THE ASSOCIATED CONDUITS SHALL BE REMOVED. THESE THE EXISTING FIRE ALARM COMPONENTS ASSOCIATED WITH THE REMOVAL OF THE HVAC SYSTEM AND THE ASSOCIATED CONDUITS SHALL BE REMOVED. THESE COMPONENTS INCLUDE SMOKE DETECTORS, MONITORING MODULES, AND SHUTDOWN RELAYS. 22. ALL FIRE ALARM CIRCUITS SHALL BE TERMINATED ON TERMINAL STRIPS. WIRE NUTS ARE PROHIBITED. ALL SIGNALLING LINE CIRCUITS (SLC) AND NOTIFICATION ALL FIRE ALARM CIRCUITS SHALL BE TERMINATED ON TERMINAL STRIPS. WIRE NUTS ARE PROHIBITED. ALL SIGNALLING LINE CIRCUITS (SLC) AND NOTIFICATION APPLIANCE CIRCUITS (NAC) ENTERING THE BUILDING AND AT THE FIRE ALARM UNIT SHALL BE PROVIDED WITH SUITABLE SURGE SUPPRESSORS (SEE SPECIFICATIONS) 23. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE PRELIMINARY AND ACCEPTANCE FIRE ALARM TESTS ARE TO BE CONDUCTED. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE PRELIMINARY AND ACCEPTANCE FIRE ALARM TESTS ARE TO BE CONDUCTED. THE TESTS SHALL BE IN ACCORDANCE WITH THE APPROVED TESTS PROCEDURES IN THE PRESENCE OF THE CONTRACTING OFFICER. THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERSONNEL REQUIRED FOR THE TESTS. 24. ALL WORK SHALL COMPLY WITH EGLIN FIRE ALARM/MASS NOTIFICATION REQUIREMENTS. REFER TO SPECIFICATIONS. ALL WORK SHALL COMPLY WITH EGLIN FIRE ALARM/MASS NOTIFICATION REQUIREMENTS. REFER TO SPECIFICATIONS. 25. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL DURING THE EXTENT OF THE PROJECT EXCEPT AS NOTED IN THE VESDA SYSTEM THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL DURING THE EXTENT OF THE PROJECT EXCEPT AS NOTED IN THE VESDA SYSTEM NOTES. 26. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND DEMOLITION OF EXISTING FIRE ALARM DEVICES, CONDUIT, AND THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND DEMOLITION OF EXISTING FIRE ALARM DEVICES, CONDUIT, AND WIRING AS REQUIRED FOR THE DEMOLITION OF THE EXISTING HVAC UNITS. THIS INCLUDES DUCT SMOKE DETECTORS AND RELAY WITH TEST STATION AT AIR HANDLING UNITS BEING DEMOLISHED. FIRE ALARM CONTRACTOR SHALL COORDINATE DEMOLITION OF FIRE ALARM DEVICES WITH MECHANICAL CONTRACTOR. 27. THE EXISTING SYSTEM AND NEW PORTIONS OF THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 72 FOR "RE-ACCEPTANCE TESTING." AT THE EXISTING SYSTEM AND NEW PORTIONS OF THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 72 FOR "RE-ACCEPTANCE TESTING." AT THE FINAL ACCEPTANCE INSPECTION, THIS WILL INCLUDE TESTING 100% OF THE NEW PORTIONS OF THE SYSTEM AND TESTING OF THE EXISTING SYSTEM (10% MINIMUM) AS REQUIRED BY NFPA 72 TO ENSURE THE EXISTING PROGRAM REMAINED INTACT. 28. THE ENTIRE FIRE ALARM SYSTEM AND ALL FUNCTIONS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM THE ENTIRE FIRE ALARM SYSTEM AND ALL FUNCTIONS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM CONTRACTOR SHALL PROVIDE A WRITTEN REPORT OF THE TEST TO EGLIN AFB THAT INDICATES ALL EXISTING FIRE ALARM DEFICIENCIES. ALL EXISTING FIRE ALARM DEFICIENCIES SHALL BE REPAIRED BY EGLIN AFB.
AutoCAD SHX Text 2,650
AutoCAD SHX Text 2,150
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text 2,200
AutoCAD SHX Text
AHU-3
AutoCAD SHX Text 2,820
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
MARK
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
TOTAL AIR (CFM)
AutoCAD SHX Text
AHU-8
AutoCAD SHX Text 8,200
AutoCAD SHX Text
AHU-7
AutoCAD SHX Text 6,000
AutoCAD SHX Text
AHU-6
AutoCAD SHX Text 5,800
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text DUCT SMOKE DETECTOR NOTES: - PROVIDE SUPPLY SIDE (PER NFPA 90A) DUCT SMOKE PROVIDE SUPPLY SIDE (PER NFPA 90A) DUCT SMOKE DETECTOR, AHU INTERFACE (RELAY MODULE), AND REMOTE TEST STATION, AS REQUIRED FOR EACH AHU LISTED IN THE DUCT DETECTOR LOCATION TABLE. - REWORK/EXTEND/INSTALL FIRE ALARM CONDUCTORS AND REWORK/EXTEND/INSTALL FIRE ALARM CONDUCTORS AND CONDUIT TO NEW DEVICES. INTEGRATE NEW DEVICES INTO THE EXISTING SYSTEM AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM. IF EXISTING CIRCUITS CANNOT BE UTILIZED, THEN INSTALL NEW CIRCUITS BACK TO THE EXISTING FIRE ALARM PANEL AS REQUIRED. - THE DUCT SMOKE DETECTOR ASSEMBLY SHALL BE THE DUCT SMOKE DETECTOR ASSEMBLY SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. - PER UFC 3-600-01, DUCT SMOKE DETECTORS ARE NOT PER UFC 3-600-01, DUCT SMOKE DETECTORS ARE NOT REQUIRED WHERE AIR DISTRIBUTION SYSTEMS ARE INCAPABLE OF SPREADING SMOKE BEYOND THE ENCLOSING WALLS, FLOORS AND CEILINGS OF THE ROOM OR SPACE IN WHICH THE SMOKE IS GENERATED. - SEE SHEET FA-100 FOR LOCATIONS OF AHU'S.SEE SHEET FA-100 FOR LOCATIONS OF AHU'S.
AutoCAD SHX Text
MECH. ROOM 209
AutoCAD SHX Text
MECH. ROOM 209
AutoCAD SHX Text
MECH. ROOM 114
AutoCAD SHX Text
MECH. ROOM 111
AutoCAD SHX Text
DUCT SMOKE DETECTOR LOCATION
AutoCAD SHX Text
MECH. ROOM 111
AutoCAD SHX Text
MECH. ROOM 111
AutoCAD SHX Text
MECH. ROOM 209
AutoCAD SHX Text
MECH. ROOM 201
AutoCAD SHX Text 8,200
AutoCAD SHX Text
AHU-9
AutoCAD SHX Text
MECH. ROOM 201
AutoCAD SHX Text 8,200
AutoCAD SHX Text
AHU-10
AutoCAD SHX Text
MECH. ROOM 205
AutoCAD SHX Text 8,200
AutoCAD SHX Text
AHU-11
AutoCAD SHX Text
MECH. ROOM 205
AutoCAD SHX Text 8,200
AutoCAD SHX Text
VESDA SYSTEM GENERAL NOTES
AutoCAD SHX Text THE ENTIRE BUILDING HAS MULTIPLE ACTIVE VESDA SMOKE DETECTION SYSTEMS. THE FOLLOWING PROCEDURES SHALL BE FOLLOWED TO PROTECT THE EXISTING VESDA SYSTEMS DURING THE HVAC REPLACEMENT. 1. THE EXISTING VESDA SYSTEM SHALL BE PROTECTED FROM DAMAGE DURING THE EXTENT OF THE PROJECT. THE GENERAL CONTRACTOR SHALL BE THE EXISTING VESDA SYSTEM SHALL BE PROTECTED FROM DAMAGE DURING THE EXTENT OF THE PROJECT. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH ALL DISCIPLINES TO PROTECT THE EXISTING VESDA SYSTEMS FROM DAMAGE. 2. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR SHUTTING DOWN ALL VESDA SYSTEMS AND COVERING ALL SAMPLING POINTS TO THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR SHUTTING DOWN ALL VESDA SYSTEMS AND COVERING ALL SAMPLING POINTS TO PREVENT DEBRIS AND WELDING/SOLDERING SMOKE FROM ENTERING THE SAMPLING TUBING. THE FIRE ALARM CONTRACTOR SHALL NOTIFY THE THE FIRE ALARM CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER AND THE BUILDING FACILITY MANAGER 30 DAYS BEFORE SHUTTING DOWN THE VESDA SYSTEMS. 3. THE IMPAIRMENT PROCEDURES FOR FIRE ALARM SYSTEMS OUTLINED IN NFPA 72 CHAPTER 10.21 SHALL BE FOLLOWED. THE IMPAIRMENT PROCEDURES FOR FIRE ALARM SYSTEMS OUTLINED IN NFPA 72 CHAPTER 10.21 SHALL BE FOLLOWED. 4. THE GENERAL CONTRACTOR SHALL PROVIDE A FIRE WATCH DURING WORKING HOURS WHEN WORKERS ARE PRESENT AND THE VESDA SYSTEMS ARE THE GENERAL CONTRACTOR SHALL PROVIDE A FIRE WATCH DURING WORKING HOURS WHEN WORKERS ARE PRESENT AND THE VESDA SYSTEMS ARE DISABLED. 5. DURING OTHER PERIODS WHEN THE BUILDING IS UNOCCUPIED AND THE VESDA SYSTEM IS DISABLED, THE GOVERNMENT SHALL BE RESPONSIBLE DURING OTHER PERIODS WHEN THE BUILDING IS UNOCCUPIED AND THE VESDA SYSTEM IS DISABLED, THE GOVERNMENT SHALL BE RESPONSIBLE FOR PROVIDING A FIRE WATCH OR OTHER MITIGATING MEASURES APPROVED BY THE AHJ. 6. UPON COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETELY CLEANING THE VESDA SYSTEMS PER UPON COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETELY CLEANING THE VESDA SYSTEMS PER MANUFACTURER'S INSTRUCTIONS INCLUDING SAMPLING POINTS, PIPING/TUBING, FILTERS, ETC.. THE REPLACEMENT OF THE FILTERS IN THE VESDA SYSTEMS SHALL BE WITNESSED BY THE FIRE ALARM SHOPS AT THE FINAL INSPECTION. 7. AFTER CLEANING THE VESDA SYSTEMS, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING REACCEPTANCE TESTING IN AFTER CLEANING THE VESDA SYSTEMS, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING REACCEPTANCE TESTING IN ACCORDANCE WITH NFPA 72. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE TESTS ARE TO BE CONDUCTED. THE THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE TESTS ARE TO BE CONDUCTED. THE TESTS SHALL BE IN ACCORDANCE WITH THE APPROVED TESTS PROCEDURES IN THE PRESENCE OF THE CONTRACTING OFFICER. THE FIRE ALARM CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERSONNEL REQUIRED FOR THE TESTS. 8. THE FIRE ALARM CONTRACTOR PERSONNEL PERFORMING THE WORK ASSOCIATED WITH THE VESDA SYSTEMS SHALL HAVE A MINIMUM OF FOURS THE FIRE ALARM CONTRACTOR PERSONNEL PERFORMING THE WORK ASSOCIATED WITH THE VESDA SYSTEMS SHALL HAVE A MINIMUM OF FOURS YEARS EXPERIENCE AND BE FACTORY TRAINED IN THE INSTALLATION, ADJUSTMENT, TESTING, AND OPERATION OF THE EXISTING VESDA SYSTEMS. 9. THE FIRE ALARM PERSONNEL TESTING THE VESDA SYSTEMS SHALL MEET THE REQUIREMENTS OF "TEST TECHNICIAN" AS DETAILED IN SPECIFICATION THE FIRE ALARM PERSONNEL TESTING THE VESDA SYSTEMS SHALL MEET THE REQUIREMENTS OF "TEST TECHNICIAN" AS DETAILED IN SPECIFICATION 28 31 76. 10. ALL VESDA SYSTEMS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM CONTRACTOR SHALL PROVIDE A WRITTEN ALL VESDA SYSTEMS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM CONTRACTOR SHALL PROVIDE A WRITTEN REPORT OF THE TEST TO EGLIN AFB THAT INDICATES ALL EXISTING VESDA SYSTEM DEFICIENCIES. ALL EXISTING VESDA SYSTEM DEFICIENCIES SHALL BE REPAIRED BY EGLIN AFB.
AutoCAD SHX Text
96 CEG, OFFICE FORM 002, FY2013
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
BY
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
EGLIN AIR FORCE BASE, FLORIDA
AutoCAD SHX Text
CENM
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
FTFA 20-RC03
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BLDG 12722 HVAC REPLACEMENT
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
22 JULY 2021
AutoCAD SHX Text
PETERSON ENGINEERING INC.
AutoCAD SHX Text
75 SOUTH "F" STREET
AutoCAD SHX Text
PENSACOLA, FLORIDA 32502
AutoCAD SHX Text
(850) 434-0513
AutoCAD SHX Text
(PROF. ENG. #: 3600)
AutoCAD SHX Text
PEI 2020100
AutoCAD SHX Text
AutoCAD SHX Text
21AC
AutoCAD SHX Text
21AC
AutoCAD SHX Text
AS-BUILT
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text J
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text No. 90730 9073090730
STATE OF
D P
R O
J E C
T
B l d g
H
V A
C
R e p l a c e m e n t D
W G
M e c h
F A d w g
A
M
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 110A
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AHU-3
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
AHU-7
AutoCAD SHX Text
AHU-9
AutoCAD SHX Text
AHU-8
AutoCAD SHX Text
AHU-11
AutoCAD SHX Text
AHU-10
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text
AHU-6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
AutoCAD SHX Text
TYP. OF 3
AutoCAD SHX Text
AutoCAD SHX Text
TYP. OF 2
AutoCAD SHX Text
AutoCAD SHX Text
TYP. OF 2
AutoCAD SHX Text PROVIDE SUPPLY SIDE (PER NFPA 90A) DUCT SMOKE DETECTOR, AHU INTERFACE (RELAY MODULE), AND REMOTE TEST STATION, AS REQUIRED. REWORK/EXTEND/INSTALL FIRE ALARM CONDUCTORS AND CONDUIT TO NEW DEVICES. INTEGRATE NEW DEVICES INTO THE EXISTING SYSTEM AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM. IF EXISTING CIRCUITS CANNOT BE UTILIZED, THEN INSTALL NEW CIRCUITS BACK TO THE EXISTING FIRE ALARM PANEL AS REQUIRED.
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text DUCT DETECTOR-DEMO SHUT-DOWN RELAY MODULE-DEMO DUCT DETECTOR-NEW SHUT-DOWN RELAY MODULE-NEW FIRE ALARM CONTROL PANEL-EXISTING
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
FACP
AutoCAD SHX Text
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 110A
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
AHU-3
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
FACP
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
AutoCAD SHX Text
TYP. OF 3
AutoCAD SHX Text
AutoCAD SHX Text
AHU-7
AutoCAD SHX Text
AHU-9
AutoCAD SHX Text
AHU-8
AutoCAD SHX Text
AHU-11
AutoCAD SHX Text
AHU-10
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text
AHU-6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text
THE DUCT SMOKE DETECTOR ASSEMBLY SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72.
AutoCAD SHX Text
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT
AutoCAD SHX Text
LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
AutoCAD SHX Text
OBSTRUCTION
AutoCAD SHX Text
BEND OR OTHER
AutoCAD SHX Text
AIR DUCT
AutoCAD SHX Text
ANY DUCT OVER 3' WIDE, SAMPLE TUBE
AutoCAD SHX Text
MUST GO THRU THE DUCT AND BE CAPPED.
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
6~10 DUCT
AutoCAD SHX Text
WIDTH
AutoCAD SHX Text
TYPICAL DUCT DETECTOR INSTALLATION
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
AUX
AutoCAD SHX Text
FUNC
AutoCAD SHX Text
FMCP
AutoCAD SHX Text
DISPLAY
AutoCAD SHX Text
MONACO TRANSMISSION
AutoCAD SHX Text
SUPERVISING STATION
AutoCAD SHX Text
EVAC
AutoCAD SHX Text
MASS NOTIFICATION SYSTEM
AutoCAD SHX Text
AUDIO/VISUAL
AutoCAD SHX Text
SUPERVISORY BY DEVICE
AutoCAD SHX Text
AUDIO/VISUAL TROUBLE
AutoCAD SHX Text
INDICATION BY DEVICE
AutoCAD SHX Text
XMIT ALARM SIGNAL - PULL
AutoCAD SHX Text
STATION TO SS
AutoCAD SHX Text
XMIT TROUBLE SIGNAL TO SS
AutoCAD SHX Text
XMIT SUPERVISORY SIGNAL
AutoCAD SHX Text
TO SS
AutoCAD SHX Text
FIRE ALARM STROBES
AutoCAD SHX Text
THROUGHOUT
AutoCAD SHX Text
GEN. EVAC MESSAGE
AutoCAD SHX Text
THROUGHOUT
AutoCAD SHX Text
ENERGIZE STROBES
AutoCAD SHX Text
FOR MNS
AutoCAD SHX Text
DE-ENERGIZE FIRE ALARM
AutoCAD SHX Text
STROBES
AutoCAD SHX Text
SILENCE LOC
AutoCAD SHX Text
MICROPHONES
AutoCAD SHX Text
SILENCE FIRE ALARM
AutoCAD SHX Text
EVACUATION MESSAGE
AutoCAD SHX Text
PRE-REC MESSAGE
AutoCAD SHX Text
THROUGHOUT
AutoCAD SHX Text
LIVE VOICE THROUGHOUT
AutoCAD SHX Text
ALARM SIGNALS
AutoCAD SHX Text
AUDIO/VISUAL ALARM
AutoCAD SHX Text
INDICATION BY DEVICE
AutoCAD SHX Text
SUPERVISORY SIGNAL IF
AutoCAD SHX Text
OVERIDING FIRE ALARM
AutoCAD SHX Text
XMIT ALARM SIGNAL - BUILDING
AutoCAD SHX Text
FLOW SWITCH TO SS
AutoCAD SHX Text
XMIT ALARM SIGNAL -SMOKE
AutoCAD SHX Text
DETECTOR TO SS
AutoCAD SHX Text
SHUTDOWN AFFECTED AIR
AutoCAD SHX Text
HANDLER
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
DUCT DETECTOR
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
XMIT ALARM SIGNAL -
AutoCAD SHX Text
ULTA-SENSITVE TO SS
AutoCAD SHX Text
XMIT ALARM SIGNAL - CARBON
AutoCAD SHX Text
MONOXIDE DETECTOR TO SS
AutoCAD SHX Text
XMIT ALARM SIGNAL - CLEAN
AutoCAD SHX Text
AGENT
AutoCAD SHX Text
XMIT ALARM SIGNAL -ROOM FLOW
AutoCAD SHX Text
SWITCH TO SS
AutoCAD SHX Text NOTES: THE EXISTING FIRE ALARM SYSTEM SHALL OPERATE THE SAME EXCEPT THE FIRE ALARM CONTRACTOR SHALL REPROGRAM THE FA CONTROL PANEL TO PERFORM THE FUNCTIONS LISTED IN THE ABOVE MATRIX WHEN THE NEW DUCT SMOKE DETECTORS ARE ACTIVATED.
AutoCAD SHX Text
FA-100
AutoCAD SHX Text
LBT
AutoCAD SHX Text
FIRE ALARM PLANS AND DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
EK
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%U1ST FLOOR FIRE ALARM PLAN - DEMO
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 2ND FLOOR FIRE ALARM PLAN-DEMO
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%U1ST FLOOR FIRE ALARM PLAN - NEW WORK
AutoCAD SHX Text N
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
%%UBLDG 12722 2ND FLOOR FIRE ALARM PLAN-NEW WORK
AutoCAD SHX Text
96 CEG, OFFICE FORM 002, FY2013
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
BY
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
EGLIN AIR FORCE BASE, FLORIDA
AutoCAD SHX Text
CENM
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
FTFA 20-RC03
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BLDG 12722 HVAC REPLACEMENT
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
22 JULY 2021
AutoCAD SHX Text
PETERSON ENGINEERING INC.
AutoCAD SHX Text
75 SOUTH "F" STREET
AutoCAD SHX Text
PENSACOLA, FLORIDA 32502
AutoCAD SHX Text
(850) 434-0513
AutoCAD SHX Text
(PROF. ENG. #: 3600)
AutoCAD SHX Text
PEI 2020100
AutoCAD SHX Text
AutoCAD SHX Text
21AC
AutoCAD SHX Text
21AC
AutoCAD SHX Text
AS-BUILT
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text J
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text K
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text No. 90730 9073090730
STATE OF
Φ
AutoCAD SHX Text M-001
AutoCAD SHX Text
GENERAL MECHANICAL NOTES, LEGEND AND ABBREVIATIONS
AutoCAD SHX Text
AutoCAD SHX Text
96 CEG, OFFICE FORM 002, FY2013
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
APPR'D
AutoCAD SHX Text
BY
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
EGLIN AIR FORCE BASE, FLORIDA
AutoCAD SHX Text
CENM
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
FTFA 20-RC03
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BLDG 12722 HVAC REPLACEMENT
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
22 JULY 2021
AutoCAD SHX Text
PETERSON ENGINEERING INC.
AutoCAD SHX Text
75 SOUTH "F" STREET
AutoCAD SHX Text
PENSACOLA, FLORIDA 32502
AutoCAD SHX Text
(850) 434-0513
AutoCAD SHX Text
(PROF. ENG. #: 3600)
AutoCAD SHX Text
PEI 2020100
AutoCAD SHX Text
AutoCAD SHX Text
21AC
AutoCAD SHX Text
21AC
AutoCAD SHX Text
AS-BUILT
AutoCAD SHX Text No. 34088
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text Y
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
HVAC GENERAL NOTES
AutoCAD SHX Text
1. INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE. 2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. 3. INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. 4. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. 5. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT LOCATIONS AND FITMENT CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT LOCATIONS AND FITMENT 6. COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE INSTALLATION. 7. COORDINATE AND PROVIDE ALL DUCTS AND PIPING TRANSITION REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO COORDINATE AND PROVIDE ALL DUCTS AND PIPING TRANSITION REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT, VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION. 8. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH THE LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH THE STRAIGHT SECTION OF PIPE OR DUCT UPSTREAM AND DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER. 9. ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO PROVIDE A VIBRATION-FREE INSTALLATION. 10. LOCATIONS AND SIZES OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER LOCATIONS AND SIZES OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES INVOLVED. 11. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION. 12. THERMOSTATS INDICATED ADJACENT TO DOORWAYS SHALL BE LOCATED WITHIN 18” OF JAMB AT LOCATIONS WITH THERMOSTATS INDICATED ADJACENT TO DOORWAYS SHALL BE LOCATED WITHIN 18” OF JAMB AT LOCATIONS WITH OF JAMB AT LOCATIONS WITH LIGHT SWITCHES AND MOUNT THERMOSTAT 48" AFF. LOCATE THERMOSTAT SUCH THAT LIGHT SWITCH IS BETWEEN THERMOSTAT AND JAMB. VERIFY THERMOSTAT LOCATION WITH SYSTEM FURNITURE LAYOUT PRIOR TO INSTALLING THERMOSTATS. 13. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING THICKNESS. 14. AVOID ROUTING DUCTWORK AND MECHANICAL EQUIPMENT OVER LIGHTS WHEREVER POSSIBLE. MAINTAIN MINIMUM 6” AVOID ROUTING DUCTWORK AND MECHANICAL EQUIPMENT OVER LIGHTS WHEREVER POSSIBLE. MAINTAIN MINIMUM 6” CLEARANCE BETWEEN MECHANICAL EQUIPMENT AND DUCT INSULATION TO TOP OF LIGHTS. PROVIDE CLEARANCE AND ACCESS ALL AROUND AND BELOW MECHANICAL EQUIPMENT AS REQUIRED FOR ROUTINE MAINTENANCE. 15. SEAL ALL DUCT PENETRATIONS OF WALLS AIRTIGHT, REGARDLESS OF WHETHER WALLS ARE FIRE RATED OR NOT. SEAL ALL DUCT PENETRATIONS OF WALLS AIRTIGHT, REGARDLESS OF WHETHER WALLS ARE FIRE RATED OR NOT. 16. MOUNT DUCTWORK AS HIGH AS POSSIBLE WHERE EXPOSED, UNLESS OTHER WISE NOTED. MOUNT DUCTWORK AS HIGH AS POSSIBLE WHERE EXPOSED, UNLESS OTHER WISE NOTED. 17. ALL SUPPLY AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE ALL SUPPLY AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 2"W.G., SEAL CLASS A, EXTERNALLY INSULATED. METAL DUCT INSULATION RATING PER ASHRE 90.1. METAL DUCT INSULATION RATING PER ASHRE 90.1. METAL DUCT INSULATION RATING PER ASHRE 90.1. 18. ALL RETURN AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE ALL RETURN AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 1” W.G., SEAL CLASS A, EXTERNALLY INSULATED. METAL DUCT INSULATION RATING PER ASHRE 90.1. W.G., SEAL CLASS A, EXTERNALLY INSULATED. METAL DUCT INSULATION RATING PER ASHRE 90.1. 19. ALL CONDENSATE DRAIN LINES SHALL BE INSULATED. ALL CONDENSATE DRAIN LINES SHALL BE INSULATED. 20. ALL FLEXIBLE DUCT TO BE A MAXIMUM OF 6' LONG. ALL FLEX DUCT CONNECTIONS TO BE SEALED WITH MASTIC ALL FLEXIBLE DUCT TO BE A MAXIMUM OF 6' LONG. ALL FLEX DUCT CONNECTIONS TO BE SEALED WITH MASTIC RECOMMENDED BY MANUFACTURER. 21. ALL METAL DUCT INSULATION RATING PER ASHRE 90.1. ALL METAL DUCT INSULATION RATING PER ASHRE 90.1. 22. ALL ELECTRICAL PANELS TO BE RELABELED WITH NEW CIRCUIT INFORMATION. ALL ELECTRICAL PANELS TO BE RELABELED WITH NEW CIRCUIT INFORMATION. 23. ALL CONDENSING UNIT COILS TO BE COATED FOR SALT WATER, MARINE ENVIRONMENT. ALL CONDENSING UNIT COILS TO BE COATED FOR SALT WATER, MARINE ENVIRONMENT. 24. ALL DRAIN PANS TO HAVE DUAL CUTOFF SWITCHES. ALL DRAIN PANS TO HAVE DUAL CUTOFF SWITCHES. 25. PROVIDE ACCESS DOORS IN DUCTWORK FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME PROVIDE ACCESS DOORS IN DUCTWORK FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN DUCTWORK THAT REQUIRE SERVICE/INSPECTION. 26. ALL EQUIPMENT REQUIRING CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, ALL EQUIPMENT REQUIRING CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND PIPED TO THE NEAREST DRAIN AS INDICATED 27. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH REELECTED CEILING PLANS, LIGHTING, AND OTHER COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH REELECTED CEILING PLANS, LIGHTING, AND OTHER CEILING MOUNTED EQUIPMENT AND MODIFY DUCTWORK TO SUIT. 28. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY LOUVER DIMENSIONS INDICATED DOES NOT INCLUDE EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY LOUVER DIMENSIONS INDICATED DOES NOT INCLUDE FRAME OR FLANGES 29. EXPOSED DUCTWORK IN OCCUPIED SPACES SHALL BE DOUBLE-WALL WITH SOLID LINER. PROVIDE GALVANIZED EXPOSED DUCTWORK IN OCCUPIED SPACES SHALL BE DOUBLE-WALL WITH SOLID LINER. PROVIDE GALVANIZED FINISHED SUITABLE FOR PAINTING. 30. ALL OUTSIDE AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR,SMACNA STATIC PRESSURE CLASS 1 ALL OUTSIDE AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR,SMACNA STATIC PRESSURE CLASS 1 W.G.,SEAL CLASS A 31. PROVIDE ALL 90-DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES AND PROVIDE ACCESS DOORS PROVIDE ALL 90-DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES AND PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH TURNING VANES. 32. CONCRETE HOUSE KEEPING PADS TO SUIT MECHANICAL EQUIPMENT, MINIMUM CONCRETE PAD THICKNESS SHALL BE CONCRETE HOUSE KEEPING PADS TO SUIT MECHANICAL EQUIPMENT, MINIMUM CONCRETE PAD THICKNESS SHALL BE 6 INCHES PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 INCHS ON ALL SIDES. 33. CONTRACTOR TO PROTECT SITE INSTRUMENTATION FROM DUST AND DEBRIS DURING ALL PHASES OF CONSTRUCTION CONTRACTOR TO PROTECT SITE INSTRUMENTATION FROM DUST AND DEBRIS DURING ALL PHASES OF CONSTRUCTION
AutoCAD SHX Text WxH
AutoCAD SHX Text 8"%%c
AutoCAD SHX Text HVAC LEGEND RECTANGULAR DUCTWORK, SIZES SHOWN ARE INTERNAL CLEAR DIMENSIONS. (WIDTH x HEIGHT) FIRST FIGURE IS SIDE SHOWN. DUCT SECTION, POSITIVE PRESSURE, FIRST FIGURE IS TOP DIMENSION DUCT SECTION, NEGATIVE PRESSURE, FIRST FIGURE IS TOP DIMENSION ROUND BRANCH DUCT TAKEOFF FROM RECTANGULAR DUCT MAIN.