Att 4_FTFA 20-RC03 Drawings.pdf

PDF 6 MB Posted

Attached to
Replace and Improve HVAC System in Bldg 12722 Federal contract opportunity
Solicitation number
FA282322R0007
Issued by
Department of the Air Force Materiel Command Test Center

About this file

This solicitation requests proposals for a replacement and improvement of the HVAC system in Building 12722 at Eglin Air Force Base. Offerors must provide pricing using the 50 Division Cost Estimate worksheet and submit past performance questionnaires from references. Proposals are due within 14 days and the period of performance is estimated at 426 days. The acquisition is set aside for small businesses. The source selection will use tradeoff procedures and proposals shall follow instructions for electronic submission, formatting, and required contract documentation.

View the file

Other files for this federal contract opportunity

Other files attached to Replace and Improve HVAC System in Bldg 12722, newest first.
File Type Posted
Questions and Answers .pdf PDF
Section_L_21 April 2022.pdf PDF
Att 4_FTFA 20-RC03_Drawings_Final_Updated.pdf PDF
FA282322R00070002.pdf PDF
FA282322R00070001.pdf PDF
Section_M.pdf PDF
Solicitation - FA282322R0007.pdf PDF
Att 3_Specifications.pdf PDF
Attachment L2-FRQ.pdf PDF
Attachment L1-50DC.xls XLS spreadsheet
Attachment L5-Past Performance Question (PPQ).pdf PDF
Att 1_SOW-12722.pdf PDF
Att 2_WD.pdf PDF
Attachment L6 Cover Letter.pdf PDF
Attachment L4 Consent Form.pdf PDF
Attachment L3 Past Performance Information (PPI).pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AutoCAD SHX Text H

AutoCAD SHX Text T

AutoCAD SHX Text

ACC-1

AutoCAD SHX Text

ACC-2

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FLD

AutoCAD SHX Text

FLD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FLD

AutoCAD SHX Text

FLD

AutoCAD SHX Text

AHU-7

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text

AHU-9

AutoCAD SHX Text

AHU-8

AutoCAD SHX Text

AHU-6

AutoCAD SHX Text

AHU-11

AutoCAD SHX Text

AHU-10

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PHASING NOTES

AutoCAD SHX Text CONTRACTOR TO HAVE ALL MAJOR COMPONENTS (INCLUDING CHILLERS, AHUS, PUMPS, AND SWITCH GEAR ECT.) ON SITE BEFORE SHUTTING DOWN ANY SYSTEMS. INSTALL NEW CHILLED WATER PIPING SYSTEM AND DDC CONTROL SYSTEMS WHILE EXISTING SYSTEM REMAINS OPERATIONAL INSTALL NEW CHILLED WATER PUMPS (CWP-1,2) IN NEW CHILLED WATER PIPING SYSTEM INSTALL BYPASS AT FUTURE AHU TIE IN POINTS, RUN NEW CHILLED WATER LOOP. BEFORE DEMOLISHING EXISTING SYSTEM CONTRACTOR TO SCHEDULE A POWER OUTAGE WITH THE USER DURING WHICH THE TRANSITION TO THE NEW SWITCH GEAR SHALL TAKE PLACE. CONTRACTOR TO PRE WIRE NEW WORK AS MUCH AS POSSIBLE TO MINIMIZE SYSTEM DOWNTIME. DEMO AND INSTALL NEW CHILLER (ACC-1) AND CONNECT TO NEW CW PIPING. START UP NEW CHILLER (ACC-1). THE AIR HANDLERS SHALL BE REMOVED AND REPLACED ONE AT A TIME AND SHALL BE CONNECTED TO THE NEW CHILLED WATER SYSTEM. THE ORDER OF THE AIR HANDLER REPLACEMENT SHALL BE BASED ON MISSION REQUIREMENTS. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE OPERATION OF BOTH CHILLED WATER SYSTEMS UNTIL ALL AIR HANDLING UNITS ARE TIED INTO THE NEW CHILLED WATER SYSTEM. DEMO AND INSTALL NEW ACC-2 CONNECTING TO NEW CW SYSTEM. DEMO EXISTING CHILLED WATER PUMPS. THE CONTRACTOR SHALL DEMO AND REMOVE THE EXISTING CHILLED WATER SYSTEM AND PUMPS ONCE THE NEW SYSTEM IS FUNCTIONING. PERFORM FLOW TEST ON FLOOR DRAINS TO VERIFY ANY CLOGS. CONTRACTOR SHALL COORDINATE WITH CUSTOMER THE NEW AHU-5 AND AHU-6 LOCATIONS RELATIVE TO EXISTING EQUIPMENT. AHU-10 AND AHU-11 SHALL BE REMOVED AND NEW AHU-10 INSTALLED BEFORE THE NEW AHU-11 IS INSTALLED THROUGH ACCESS PANEL LOCATED AS INDICATED IN SHEET NOTE. AHU-7 SHALL BE DEMOLISHED AND INSTALLED BEFORE AHU-5 AND AHU-6 IN ORDER TO PROVIDE ENOUGH ROOM TO REMOVE AND INSTALL AHU-7 NOTE: THE BUILDING SHALL BE OCCUPIED AND REMAIN OPERATIONAL DURING CONSTRUCTION. SCHEDULING NOTES: CONTRACTOR TO ALLOW FOR A POSSIBILITY OF TWELVE CLASSIFIED MISSION DAYS IN A SIX MONTH TIME PERIOD DURING WHICH THE PROJECT WILL BE INACCESSIBLE TO THE CONTRACTOR. THE BUILDING AND ITS MISSIONS CHANGE WITH VERY SHORT NOTICE DUE TO THIS THE CONTRACTOR WILL BE REQUIRED AT MINIMUM TO HAVE A SCHEDULING AND COORDINATION MEETING ONCE A WEEK WITH A USER REPRESENTATIVE AND/OR CONTRACTING OFFICERS REPRESENTATIVE. THE CONTRACTOR IS ALSO REQUIRED TO PROVIDE THE USER WITH AN PHYSICAL COPY OF AN OVERALL SCHEDULE THAT IS UPDATED AFTER ANY MAJOR SCHEDULING CHANGE. TYPICAL USER OPERATION HOURS 0600 - 1500 CST. THE BUILDING SHALL BE OCCUPIED AND REMAIN OPERATIONAL DURING CONSTRUCTION. FA NOTE: : THE ENTIRE BUILDING HAS MULTIPLE ACTIVE VESDA SMOKE DETECTION SYSTEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING THE EXISTING VESDA SYSTEMS FROM DAMAGE. SEE FA-001

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G-002

AutoCAD SHX Text

LBT

AutoCAD SHX Text

MECHANICAL PHASING PLAN

AutoCAD SHX Text

AutoCAD SHX Text

GDP

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 1ST FLOOR MECHANICAL PHASING PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 2ND FLOOR MECHANICAL PHASING PLAN

AutoCAD SHX Text

96 CEG, OFFICE FORM 002, FY2013

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

BY

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

EGLIN AIR FORCE BASE, FLORIDA

AutoCAD SHX Text

CENM

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJ. ENGR.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

INDEX NO.

AutoCAD SHX Text

SPEC. NO.

AutoCAD SHX Text

PROJ. NO.

AutoCAD SHX Text

FTFA 20-RC03

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

FILE NO.

AutoCAD SHX Text

96 CEG/CEN

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

CONTENTS

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BLDG 12722 HVAC REPLACEMENT

AutoCAD SHX Text

AS SHOWN

AutoCAD SHX Text

22 JULY 2021

AutoCAD SHX Text

PETERSON ENGINEERING INC.

AutoCAD SHX Text

75 SOUTH "F" STREET

AutoCAD SHX Text

PENSACOLA, FLORIDA 32502

AutoCAD SHX Text

(850) 434-0513

AutoCAD SHX Text

(PROF. ENG. #: 3600)

AutoCAD SHX Text

PEI 2020100

AutoCAD SHX Text

AutoCAD SHX Text

21AC

AutoCAD SHX Text

21AC

AutoCAD SHX Text

AS-BUILT

AutoCAD SHX Text No. 34088

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text Y

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 1/8"= 1'- 0"

AutoCAD SHX Text 5'

AutoCAD SHX Text

AutoCAD SHX Text 5'

15'

SHEET NOTES

AutoCAD SHX Text EXISTING CEILING GRID AND TILES TO BE REMOVED AND REPLACED. EXISTING CEILING ACCESSORIES TO REMAIN, PROTECT DURING CONSTRUCTION. PROVIDE AND INSTALL NEW CEILING GRID IN CEILING ABOVE STAIRS. PLYWOOD CEILING IN ROOM OPEN CEILING AREA

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

SUPPLY AIR DIFFUSER

AutoCAD SHX Text

CAN LIGHT

AutoCAD SHX Text

EMERGENCY EXIT LIGHT

AutoCAD SHX Text 2x4 FLORESCENT LIGHT FLUSH MOUNT

AutoCAD SHX Text

4' FLORESCENT LIGHT SUSPENDED

AutoCAD SHX Text

SMOKE DETECTOR

AutoCAD SHX Text

RETURN AIR GRILLE

AutoCAD SHX Text

%%ULEGEND

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

EM

AutoCAD SHX Text

EM

AutoCAD SHX Text

AutoCAD SHX Text 208A

AutoCAD SHX Text 208B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 210A

AutoCAD SHX Text 203A

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

EM

AutoCAD SHX Text

EM

AutoCAD SHX Text

EM

AutoCAD SHX Text

EMERGENCY STROBE LIGHT

AutoCAD SHX Text

BLUE STROBE LIGHT

AutoCAD SHX Text B

AutoCAD SHX Text

EXISTING ROUND DIFFUSERS

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 106A

AutoCAD SHX Text 110A

AutoCAD SHX Text B

AutoCAD SHX Text

EM

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

EM

AutoCAD SHX Text

EM

AutoCAD SHX Text

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A-100

AutoCAD SHX Text

LBT

AutoCAD SHX Text

REFLECTED CEILING PLANS

AutoCAD SHX Text

AutoCAD SHX Text

GDP

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 1ST FLOOR REFLECTED CEILING PLAN

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 2ND FLOOR REFLECTED CEILING PLAN

AutoCAD SHX Text

96 CEG, OFFICE FORM 002, FY2013

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

BY

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

EGLIN AIR FORCE BASE, FLORIDA

AutoCAD SHX Text

CENM

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJ. ENGR.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

INDEX NO.

AutoCAD SHX Text

SPEC. NO.

AutoCAD SHX Text

PROJ. NO.

AutoCAD SHX Text

FTFA 20-RC03

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

FILE NO.

AutoCAD SHX Text

96 CEG/CEN

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

CONTENTS

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BLDG 12722 HVAC REPLACEMENT

AutoCAD SHX Text

AS SHOWN

AutoCAD SHX Text

22 JULY 2021

AutoCAD SHX Text

PETERSON ENGINEERING INC.

AutoCAD SHX Text

75 SOUTH "F" STREET

AutoCAD SHX Text

PENSACOLA, FLORIDA 32502

AutoCAD SHX Text

(850) 434-0513

AutoCAD SHX Text

(PROF. ENG. #: 3600)

AutoCAD SHX Text

PEI 2020100

AutoCAD SHX Text

AutoCAD SHX Text

21AC

AutoCAD SHX Text

21AC

AutoCAD SHX Text

AS-BUILT

AutoCAD SHX Text No. 34088

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text Y

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text 1/8"= 1'- 0"

AutoCAD SHX Text 5'

AutoCAD SHX Text

AutoCAD SHX Text 5'

AutoCAD SHX Text

BLACK&YELLOW

AutoCAD SHX Text

RED&WHITE

AutoCAD SHX Text

YELLOW

AutoCAD SHX Text

YELLOW

AutoCAD SHX Text

BLACK&YELLOW

AutoCAD SHX Text

BLACK&YELLOW

AutoCAD SHX Text

BLACK&YELLOW

AutoCAD SHX Text

BLACK&YELLOW

AutoCAD SHX Text

TYP

AutoCAD SHX Text

NEW WORK NOTES

AutoCAD SHX Text PROVIDE AND INSTALL FLOOR MARKING TAPE AS INDICATED ON SHEET. REFERENCE SPECIFICATION FOR OSHA BASED COLOR GUIDE.

AutoCAD SHX Text

AutoCAD SHX Text A-101

AutoCAD SHX Text

LBT

AutoCAD SHX Text

OSHA FLOOR MARKING LOCATIONS

AutoCAD SHX Text

AutoCAD SHX Text

GDP

AutoCAD SHX Text

96 CEG, OFFICE FORM 002, FY2013

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

BY

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

EGLIN AIR FORCE BASE, FLORIDA

AutoCAD SHX Text

CENM

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJ. ENGR.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

INDEX NO.

AutoCAD SHX Text

SPEC. NO.

AutoCAD SHX Text

PROJ. NO.

AutoCAD SHX Text

FTFA 20-RC03

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

FILE NO.

AutoCAD SHX Text

96 CEG/CEN

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

CONTENTS

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BLDG 12722 HVAC REPLACEMENT

AutoCAD SHX Text

AS SHOWN

AutoCAD SHX Text

22 JULY 2021

AutoCAD SHX Text

PETERSON ENGINEERING INC.

AutoCAD SHX Text

75 SOUTH "F" STREET

AutoCAD SHX Text

PENSACOLA, FLORIDA 32502

AutoCAD SHX Text

(850) 434-0513

AutoCAD SHX Text

(PROF. ENG. #: 3600)

AutoCAD SHX Text

PEI 2020100

AutoCAD SHX Text

AutoCAD SHX Text

21AC

AutoCAD SHX Text

21AC

AutoCAD SHX Text

AS-BUILT

AutoCAD SHX Text No. 34088

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text Y

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 3/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 ENLARGED OSHA FLOOR MARKING PLAN

AutoCAD SHX Text 3/8"= 1'- 0"

AutoCAD SHX Text 7'

AutoCAD SHX Text 2'

AutoCAD SHX Text 12"

AutoCAD SHX Text 1'

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 3'

AutoCAD SHX Text 5'

AutoCAD SHX Text 6'

AutoCAD SHX Text N

AutoCAD SHX Text

%%UFIRST FLOOR KEY PLAN

NO SCALE

D P

R O

J E C

T

B l d g

H

V A

C

R e p l a c e m e n t D

W G

M e c h

F A d w g

A

M

AutoCAD SHX Text

FA-001

AutoCAD SHX Text

LBT

AutoCAD SHX Text

FIRE ALARM GENERAL NOTES

AutoCAD SHX Text

AutoCAD SHX Text

EK

AutoCAD SHX Text

FIRE ALARM GENERAL NOTES

AutoCAD SHX Text

1. THE FIRE ALARM CONTRACTOR SHALL MODIFY THE EXISTING FIRE ALARM SYSTEM AS REQUIRED TO SUPPORT THE NEW HVAC SYSTEM. THE FIRE THE FIRE ALARM CONTRACTOR SHALL MODIFY THE EXISTING FIRE ALARM SYSTEM AS REQUIRED TO SUPPORT THE NEW HVAC SYSTEM. THE FIRE ALARM WORK INCLUDES BUT IS NOT LIMITED TO PROVIDING AND INSTALLING NEW MONITORING MODULES, DUCT SMOKE DETECTORS, AND ALL REQUIRED CONDUIT AND WIRING. ALL WORK SHALL BE IN ACCORDANCE WITH NFPA 72, UFC 3-600-1, THE SPECIFICATIONS, EGLIN CRITERIA, AND THE AUTHORITY HAVING JURISDICTION. 2. THE CONTRACTOR SHALL RETAIN A REGISTERED FIRE PROTECTION ENGINEER (AS DEFINED BY UFC 3-600-01) TO BE THE QFPE FOR THE CONSTRUCTION THE CONTRACTOR SHALL RETAIN A REGISTERED FIRE PROTECTION ENGINEER (AS DEFINED BY UFC 3-600-01) TO BE THE QFPE FOR THE CONSTRUCTION CONTRACTOR SHALL RETAIN A REGISTERED FIRE PROTECTION ENGINEER (AS DEFINED BY UFC 3-600-01) TO BE THE QFPE FOR THE CONSTRUCTION PROJECT. THE QFPE SHALL BE INVOLVED WITH PRODUCTION OF FIRE ALARM SHOP DRAWINGS AND CALCULATIONS. THE QFPE MUST REVIEW AND SIGN AND SEAL THE SHOP DRAWINGS, CUTSHEETS, AND CALCULATIONS PRIOR TO SUBMITTING TO THE GOVERNMENT FOR REVIEW. THE QFPE MAY MAKE ADJUSTMENTS TO THE DEVICE LAYOUTS AS REQUIRED TO MAKE A COMPLETE AND OPERATIONAL SYSTEM. THE INSTALLATION MUST COMPLY WITH SPECIFICATION 28 31 76, UFC 3-600-01, AND NFPA 72. THE QFPE SHALL PROVIDE ALL INSPECTIONS AND INTERFACE WITH THE AHJ AS REQUIRED FOR A COMPLETE INSTALLATION. 3. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 4. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENT IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENT IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 5. A SET OF APPROVED FIRE ALARM SHOP DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. A SET OF APPROVED FIRE ALARM SHOP DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. 6. THE FIRE ALARM INSTALLER SHALL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT THE FIRE ALARM INSTALLER SHALL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. 7. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FMCP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC. 8. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). 9. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE. 10. FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. 11. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 12. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 13. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 14. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 15. ALL WIRING TO BE IN CONDUIT WITH FACTORY APPLIED RED FINISH. ALL WIRING TO BE IN CONDUIT WITH FACTORY APPLIED RED FINISH. 16. PROVIDE DUCT DETECTORS IN SUPPLY AIR SYSTEMS. PROVIDE DUCT DETECTORS IN SUPPLY AIR SYSTEMS. 17. PRE-FINAL & FINAL FIRE ALARM TESTING SHALL BE COORDINATED WITH EGLIN AFB PERSONNEL. PRE-FINAL & FINAL FIRE ALARM TESTING SHALL BE COORDINATED WITH EGLIN AFB PERSONNEL. 18. ALL WIRING TO BE SOLID COPPER. ALL WIRING TO BE SOLID COPPER. 19. MONITORING MODULES FOR SINGLE SERVICE. DUAL INPUT NOT PERMITTED. MONITORING MODULES FOR SINGLE SERVICE. DUAL INPUT NOT PERMITTED. . 20. ALL CONDUIT TO BE NEW AND PROVIDED WITH A FACTORY APPLIED RED FINISH. ALL CONDUIT TO BE NEW AND PROVIDED WITH A FACTORY APPLIED RED FINISH. 21. THE EXISTING FIRE ALARM COMPONENTS ASSOCIATED WITH THE REMOVAL OF THE HVAC SYSTEM AND THE ASSOCIATED CONDUITS SHALL BE REMOVED. THESE THE EXISTING FIRE ALARM COMPONENTS ASSOCIATED WITH THE REMOVAL OF THE HVAC SYSTEM AND THE ASSOCIATED CONDUITS SHALL BE REMOVED. THESE COMPONENTS INCLUDE SMOKE DETECTORS, MONITORING MODULES, AND SHUTDOWN RELAYS. 22. ALL FIRE ALARM CIRCUITS SHALL BE TERMINATED ON TERMINAL STRIPS. WIRE NUTS ARE PROHIBITED. ALL SIGNALLING LINE CIRCUITS (SLC) AND NOTIFICATION ALL FIRE ALARM CIRCUITS SHALL BE TERMINATED ON TERMINAL STRIPS. WIRE NUTS ARE PROHIBITED. ALL SIGNALLING LINE CIRCUITS (SLC) AND NOTIFICATION APPLIANCE CIRCUITS (NAC) ENTERING THE BUILDING AND AT THE FIRE ALARM UNIT SHALL BE PROVIDED WITH SUITABLE SURGE SUPPRESSORS (SEE SPECIFICATIONS) 23. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE PRELIMINARY AND ACCEPTANCE FIRE ALARM TESTS ARE TO BE CONDUCTED. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE PRELIMINARY AND ACCEPTANCE FIRE ALARM TESTS ARE TO BE CONDUCTED. THE TESTS SHALL BE IN ACCORDANCE WITH THE APPROVED TESTS PROCEDURES IN THE PRESENCE OF THE CONTRACTING OFFICER. THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERSONNEL REQUIRED FOR THE TESTS. 24. ALL WORK SHALL COMPLY WITH EGLIN FIRE ALARM/MASS NOTIFICATION REQUIREMENTS. REFER TO SPECIFICATIONS. ALL WORK SHALL COMPLY WITH EGLIN FIRE ALARM/MASS NOTIFICATION REQUIREMENTS. REFER TO SPECIFICATIONS. 25. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL DURING THE EXTENT OF THE PROJECT EXCEPT AS NOTED IN THE VESDA SYSTEM THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL DURING THE EXTENT OF THE PROJECT EXCEPT AS NOTED IN THE VESDA SYSTEM NOTES. 26. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND DEMOLITION OF EXISTING FIRE ALARM DEVICES, CONDUIT, AND THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND DEMOLITION OF EXISTING FIRE ALARM DEVICES, CONDUIT, AND WIRING AS REQUIRED FOR THE DEMOLITION OF THE EXISTING HVAC UNITS. THIS INCLUDES DUCT SMOKE DETECTORS AND RELAY WITH TEST STATION AT AIR HANDLING UNITS BEING DEMOLISHED. FIRE ALARM CONTRACTOR SHALL COORDINATE DEMOLITION OF FIRE ALARM DEVICES WITH MECHANICAL CONTRACTOR. 27. THE EXISTING SYSTEM AND NEW PORTIONS OF THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 72 FOR "RE-ACCEPTANCE TESTING." AT THE EXISTING SYSTEM AND NEW PORTIONS OF THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 72 FOR "RE-ACCEPTANCE TESTING." AT THE FINAL ACCEPTANCE INSPECTION, THIS WILL INCLUDE TESTING 100% OF THE NEW PORTIONS OF THE SYSTEM AND TESTING OF THE EXISTING SYSTEM (10% MINIMUM) AS REQUIRED BY NFPA 72 TO ENSURE THE EXISTING PROGRAM REMAINED INTACT. 28. THE ENTIRE FIRE ALARM SYSTEM AND ALL FUNCTIONS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM THE ENTIRE FIRE ALARM SYSTEM AND ALL FUNCTIONS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM CONTRACTOR SHALL PROVIDE A WRITTEN REPORT OF THE TEST TO EGLIN AFB THAT INDICATES ALL EXISTING FIRE ALARM DEFICIENCIES. ALL EXISTING FIRE ALARM DEFICIENCIES SHALL BE REPAIRED BY EGLIN AFB.

AutoCAD SHX Text 2,650

AutoCAD SHX Text 2,150

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text 2,200

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text 2,820

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

MARK

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

TOTAL AIR (CFM)

AutoCAD SHX Text

AHU-8

AutoCAD SHX Text 8,200

AutoCAD SHX Text

AHU-7

AutoCAD SHX Text 6,000

AutoCAD SHX Text

AHU-6

AutoCAD SHX Text 5,800

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text DUCT SMOKE DETECTOR NOTES: - PROVIDE SUPPLY SIDE (PER NFPA 90A) DUCT SMOKE PROVIDE SUPPLY SIDE (PER NFPA 90A) DUCT SMOKE DETECTOR, AHU INTERFACE (RELAY MODULE), AND REMOTE TEST STATION, AS REQUIRED FOR EACH AHU LISTED IN THE DUCT DETECTOR LOCATION TABLE. - REWORK/EXTEND/INSTALL FIRE ALARM CONDUCTORS AND REWORK/EXTEND/INSTALL FIRE ALARM CONDUCTORS AND CONDUIT TO NEW DEVICES. INTEGRATE NEW DEVICES INTO THE EXISTING SYSTEM AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM. IF EXISTING CIRCUITS CANNOT BE UTILIZED, THEN INSTALL NEW CIRCUITS BACK TO THE EXISTING FIRE ALARM PANEL AS REQUIRED. - THE DUCT SMOKE DETECTOR ASSEMBLY SHALL BE THE DUCT SMOKE DETECTOR ASSEMBLY SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. - PER UFC 3-600-01, DUCT SMOKE DETECTORS ARE NOT PER UFC 3-600-01, DUCT SMOKE DETECTORS ARE NOT REQUIRED WHERE AIR DISTRIBUTION SYSTEMS ARE INCAPABLE OF SPREADING SMOKE BEYOND THE ENCLOSING WALLS, FLOORS AND CEILINGS OF THE ROOM OR SPACE IN WHICH THE SMOKE IS GENERATED. - SEE SHEET FA-100 FOR LOCATIONS OF AHU'S.SEE SHEET FA-100 FOR LOCATIONS OF AHU'S.

AutoCAD SHX Text

MECH. ROOM 209

AutoCAD SHX Text

MECH. ROOM 209

AutoCAD SHX Text

MECH. ROOM 114

AutoCAD SHX Text

MECH. ROOM 111

AutoCAD SHX Text

DUCT SMOKE DETECTOR LOCATION

AutoCAD SHX Text

MECH. ROOM 111

AutoCAD SHX Text

MECH. ROOM 111

AutoCAD SHX Text

MECH. ROOM 209

AutoCAD SHX Text

MECH. ROOM 201

AutoCAD SHX Text 8,200

AutoCAD SHX Text

AHU-9

AutoCAD SHX Text

MECH. ROOM 201

AutoCAD SHX Text 8,200

AutoCAD SHX Text

AHU-10

AutoCAD SHX Text

MECH. ROOM 205

AutoCAD SHX Text 8,200

AutoCAD SHX Text

AHU-11

AutoCAD SHX Text

MECH. ROOM 205

AutoCAD SHX Text 8,200

AutoCAD SHX Text

VESDA SYSTEM GENERAL NOTES

AutoCAD SHX Text THE ENTIRE BUILDING HAS MULTIPLE ACTIVE VESDA SMOKE DETECTION SYSTEMS. THE FOLLOWING PROCEDURES SHALL BE FOLLOWED TO PROTECT THE EXISTING VESDA SYSTEMS DURING THE HVAC REPLACEMENT. 1. THE EXISTING VESDA SYSTEM SHALL BE PROTECTED FROM DAMAGE DURING THE EXTENT OF THE PROJECT. THE GENERAL CONTRACTOR SHALL BE THE EXISTING VESDA SYSTEM SHALL BE PROTECTED FROM DAMAGE DURING THE EXTENT OF THE PROJECT. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH ALL DISCIPLINES TO PROTECT THE EXISTING VESDA SYSTEMS FROM DAMAGE. 2. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR SHUTTING DOWN ALL VESDA SYSTEMS AND COVERING ALL SAMPLING POINTS TO THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR SHUTTING DOWN ALL VESDA SYSTEMS AND COVERING ALL SAMPLING POINTS TO PREVENT DEBRIS AND WELDING/SOLDERING SMOKE FROM ENTERING THE SAMPLING TUBING. THE FIRE ALARM CONTRACTOR SHALL NOTIFY THE THE FIRE ALARM CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER AND THE BUILDING FACILITY MANAGER 30 DAYS BEFORE SHUTTING DOWN THE VESDA SYSTEMS. 3. THE IMPAIRMENT PROCEDURES FOR FIRE ALARM SYSTEMS OUTLINED IN NFPA 72 CHAPTER 10.21 SHALL BE FOLLOWED. THE IMPAIRMENT PROCEDURES FOR FIRE ALARM SYSTEMS OUTLINED IN NFPA 72 CHAPTER 10.21 SHALL BE FOLLOWED. 4. THE GENERAL CONTRACTOR SHALL PROVIDE A FIRE WATCH DURING WORKING HOURS WHEN WORKERS ARE PRESENT AND THE VESDA SYSTEMS ARE THE GENERAL CONTRACTOR SHALL PROVIDE A FIRE WATCH DURING WORKING HOURS WHEN WORKERS ARE PRESENT AND THE VESDA SYSTEMS ARE DISABLED. 5. DURING OTHER PERIODS WHEN THE BUILDING IS UNOCCUPIED AND THE VESDA SYSTEM IS DISABLED, THE GOVERNMENT SHALL BE RESPONSIBLE DURING OTHER PERIODS WHEN THE BUILDING IS UNOCCUPIED AND THE VESDA SYSTEM IS DISABLED, THE GOVERNMENT SHALL BE RESPONSIBLE FOR PROVIDING A FIRE WATCH OR OTHER MITIGATING MEASURES APPROVED BY THE AHJ. 6. UPON COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETELY CLEANING THE VESDA SYSTEMS PER UPON COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETELY CLEANING THE VESDA SYSTEMS PER MANUFACTURER'S INSTRUCTIONS INCLUDING SAMPLING POINTS, PIPING/TUBING, FILTERS, ETC.. THE REPLACEMENT OF THE FILTERS IN THE VESDA SYSTEMS SHALL BE WITNESSED BY THE FIRE ALARM SHOPS AT THE FINAL INSPECTION. 7. AFTER CLEANING THE VESDA SYSTEMS, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING REACCEPTANCE TESTING IN AFTER CLEANING THE VESDA SYSTEMS, THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING REACCEPTANCE TESTING IN ACCORDANCE WITH NFPA 72. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE TESTS ARE TO BE CONDUCTED. THE THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER 30 DAYS BEFORE THE TESTS ARE TO BE CONDUCTED. THE TESTS SHALL BE IN ACCORDANCE WITH THE APPROVED TESTS PROCEDURES IN THE PRESENCE OF THE CONTRACTING OFFICER. THE FIRE ALARM CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERSONNEL REQUIRED FOR THE TESTS. 8. THE FIRE ALARM CONTRACTOR PERSONNEL PERFORMING THE WORK ASSOCIATED WITH THE VESDA SYSTEMS SHALL HAVE A MINIMUM OF FOURS THE FIRE ALARM CONTRACTOR PERSONNEL PERFORMING THE WORK ASSOCIATED WITH THE VESDA SYSTEMS SHALL HAVE A MINIMUM OF FOURS YEARS EXPERIENCE AND BE FACTORY TRAINED IN THE INSTALLATION, ADJUSTMENT, TESTING, AND OPERATION OF THE EXISTING VESDA SYSTEMS. 9. THE FIRE ALARM PERSONNEL TESTING THE VESDA SYSTEMS SHALL MEET THE REQUIREMENTS OF "TEST TECHNICIAN" AS DETAILED IN SPECIFICATION THE FIRE ALARM PERSONNEL TESTING THE VESDA SYSTEMS SHALL MEET THE REQUIREMENTS OF "TEST TECHNICIAN" AS DETAILED IN SPECIFICATION 28 31 76. 10. ALL VESDA SYSTEMS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM CONTRACTOR SHALL PROVIDE A WRITTEN ALL VESDA SYSTEMS SHALL BE TESTED BEFORE ANY WORK IS PERFORMED AT THE SITE. THE FIRE ALARM CONTRACTOR SHALL PROVIDE A WRITTEN REPORT OF THE TEST TO EGLIN AFB THAT INDICATES ALL EXISTING VESDA SYSTEM DEFICIENCIES. ALL EXISTING VESDA SYSTEM DEFICIENCIES SHALL BE REPAIRED BY EGLIN AFB.

AutoCAD SHX Text

96 CEG, OFFICE FORM 002, FY2013

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

BY

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

EGLIN AIR FORCE BASE, FLORIDA

AutoCAD SHX Text

CENM

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJ. ENGR.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

INDEX NO.

AutoCAD SHX Text

SPEC. NO.

AutoCAD SHX Text

PROJ. NO.

AutoCAD SHX Text

FTFA 20-RC03

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

FILE NO.

AutoCAD SHX Text

96 CEG/CEN

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

CONTENTS

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BLDG 12722 HVAC REPLACEMENT

AutoCAD SHX Text

AS SHOWN

AutoCAD SHX Text

22 JULY 2021

AutoCAD SHX Text

PETERSON ENGINEERING INC.

AutoCAD SHX Text

75 SOUTH "F" STREET

AutoCAD SHX Text

PENSACOLA, FLORIDA 32502

AutoCAD SHX Text

(850) 434-0513

AutoCAD SHX Text

(PROF. ENG. #: 3600)

AutoCAD SHX Text

PEI 2020100

AutoCAD SHX Text

AutoCAD SHX Text

21AC

AutoCAD SHX Text

21AC

AutoCAD SHX Text

AS-BUILT

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text J

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text K

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text No. 90730 9073090730

STATE OF

D P

R O

J E C

T

B l d g

H

V A

C

R e p l a c e m e n t D

W G

M e c h

F A d w g

A

M

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 110A

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text

AHU-7

AutoCAD SHX Text

AHU-9

AutoCAD SHX Text

AHU-8

AutoCAD SHX Text

AHU-11

AutoCAD SHX Text

AHU-10

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text

AHU-6

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text

AutoCAD SHX Text

TYP. OF 3

AutoCAD SHX Text

AutoCAD SHX Text

TYP. OF 2

AutoCAD SHX Text

AutoCAD SHX Text

TYP. OF 2

AutoCAD SHX Text PROVIDE SUPPLY SIDE (PER NFPA 90A) DUCT SMOKE DETECTOR, AHU INTERFACE (RELAY MODULE), AND REMOTE TEST STATION, AS REQUIRED. REWORK/EXTEND/INSTALL FIRE ALARM CONDUCTORS AND CONDUIT TO NEW DEVICES. INTEGRATE NEW DEVICES INTO THE EXISTING SYSTEM AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM. IF EXISTING CIRCUITS CANNOT BE UTILIZED, THEN INSTALL NEW CIRCUITS BACK TO THE EXISTING FIRE ALARM PANEL AS REQUIRED.

AutoCAD SHX Text

SHEET NOTES

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text DUCT DETECTOR-DEMO SHUT-DOWN RELAY MODULE-DEMO DUCT DETECTOR-NEW SHUT-DOWN RELAY MODULE-NEW FIRE ALARM CONTROL PANEL-EXISTING

AutoCAD SHX Text

LEGEND

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text

FACP

AutoCAD SHX Text

AutoCAD SHX Text

AHU-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 110A

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text

AHU-2

AutoCAD SHX Text

AHU-3

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text

FACP

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text

AutoCAD SHX Text

TYP. OF 3

AutoCAD SHX Text

AutoCAD SHX Text

AHU-7

AutoCAD SHX Text

AHU-9

AutoCAD SHX Text

AHU-8

AutoCAD SHX Text

AHU-11

AutoCAD SHX Text

AHU-10

AutoCAD SHX Text

AHU-5

AutoCAD SHX Text

AHU-6

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text R

AutoCAD SHX Text

THE DUCT SMOKE DETECTOR ASSEMBLY SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72.

AutoCAD SHX Text

THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT

AutoCAD SHX Text

LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.

AutoCAD SHX Text

OBSTRUCTION

AutoCAD SHX Text

BEND OR OTHER

AutoCAD SHX Text

AIR DUCT

AutoCAD SHX Text

ANY DUCT OVER 3' WIDE, SAMPLE TUBE

AutoCAD SHX Text

MUST GO THRU THE DUCT AND BE CAPPED.

AutoCAD SHX Text

LOCATION

AutoCAD SHX Text

6~10 DUCT

AutoCAD SHX Text

WIDTH

AutoCAD SHX Text

TYPICAL DUCT DETECTOR INSTALLATION

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

AUX

AutoCAD SHX Text

FUNC

AutoCAD SHX Text

FMCP

AutoCAD SHX Text

DISPLAY

AutoCAD SHX Text

MONACO TRANSMISSION

AutoCAD SHX Text

SUPERVISING STATION

AutoCAD SHX Text

EVAC

AutoCAD SHX Text

MASS NOTIFICATION SYSTEM

AutoCAD SHX Text

AUDIO/VISUAL

AutoCAD SHX Text

SUPERVISORY BY DEVICE

AutoCAD SHX Text

AUDIO/VISUAL TROUBLE

AutoCAD SHX Text

INDICATION BY DEVICE

AutoCAD SHX Text

XMIT ALARM SIGNAL - PULL

AutoCAD SHX Text

STATION TO SS

AutoCAD SHX Text

XMIT TROUBLE SIGNAL TO SS

AutoCAD SHX Text

XMIT SUPERVISORY SIGNAL

AutoCAD SHX Text

TO SS

AutoCAD SHX Text

FIRE ALARM STROBES

AutoCAD SHX Text

THROUGHOUT

AutoCAD SHX Text

GEN. EVAC MESSAGE

AutoCAD SHX Text

THROUGHOUT

AutoCAD SHX Text

ENERGIZE STROBES

AutoCAD SHX Text

FOR MNS

AutoCAD SHX Text

DE-ENERGIZE FIRE ALARM

AutoCAD SHX Text

STROBES

AutoCAD SHX Text

SILENCE LOC

AutoCAD SHX Text

MICROPHONES

AutoCAD SHX Text

SILENCE FIRE ALARM

AutoCAD SHX Text

EVACUATION MESSAGE

AutoCAD SHX Text

PRE-REC MESSAGE

AutoCAD SHX Text

THROUGHOUT

AutoCAD SHX Text

LIVE VOICE THROUGHOUT

AutoCAD SHX Text

ALARM SIGNALS

AutoCAD SHX Text

AUDIO/VISUAL ALARM

AutoCAD SHX Text

INDICATION BY DEVICE

AutoCAD SHX Text

SUPERVISORY SIGNAL IF

AutoCAD SHX Text

OVERIDING FIRE ALARM

AutoCAD SHX Text

XMIT ALARM SIGNAL - BUILDING

AutoCAD SHX Text

FLOW SWITCH TO SS

AutoCAD SHX Text

XMIT ALARM SIGNAL -SMOKE

AutoCAD SHX Text

DETECTOR TO SS

AutoCAD SHX Text

SHUTDOWN AFFECTED AIR

AutoCAD SHX Text

HANDLER

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

DUCT DETECTOR

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

XMIT ALARM SIGNAL -

AutoCAD SHX Text

ULTA-SENSITVE TO SS

AutoCAD SHX Text

XMIT ALARM SIGNAL - CARBON

AutoCAD SHX Text

MONOXIDE DETECTOR TO SS

AutoCAD SHX Text

XMIT ALARM SIGNAL - CLEAN

AutoCAD SHX Text

AGENT

AutoCAD SHX Text

XMIT ALARM SIGNAL -ROOM FLOW

AutoCAD SHX Text

SWITCH TO SS

AutoCAD SHX Text NOTES: THE EXISTING FIRE ALARM SYSTEM SHALL OPERATE THE SAME EXCEPT THE FIRE ALARM CONTRACTOR SHALL REPROGRAM THE FA CONTROL PANEL TO PERFORM THE FUNCTIONS LISTED IN THE ABOVE MATRIX WHEN THE NEW DUCT SMOKE DETECTORS ARE ACTIVATED.

AutoCAD SHX Text

FA-100

AutoCAD SHX Text

LBT

AutoCAD SHX Text

FIRE ALARM PLANS AND DETAILS

AutoCAD SHX Text

AutoCAD SHX Text

EK

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%U1ST FLOOR FIRE ALARM PLAN - DEMO

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 2ND FLOOR FIRE ALARM PLAN-DEMO

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%U1ST FLOOR FIRE ALARM PLAN - NEW WORK

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UBLDG 12722 2ND FLOOR FIRE ALARM PLAN-NEW WORK

AutoCAD SHX Text

96 CEG, OFFICE FORM 002, FY2013

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

BY

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

EGLIN AIR FORCE BASE, FLORIDA

AutoCAD SHX Text

CENM

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJ. ENGR.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

INDEX NO.

AutoCAD SHX Text

SPEC. NO.

AutoCAD SHX Text

PROJ. NO.

AutoCAD SHX Text

FTFA 20-RC03

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

FILE NO.

AutoCAD SHX Text

96 CEG/CEN

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

CONTENTS

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BLDG 12722 HVAC REPLACEMENT

AutoCAD SHX Text

AS SHOWN

AutoCAD SHX Text

22 JULY 2021

AutoCAD SHX Text

PETERSON ENGINEERING INC.

AutoCAD SHX Text

75 SOUTH "F" STREET

AutoCAD SHX Text

PENSACOLA, FLORIDA 32502

AutoCAD SHX Text

(850) 434-0513

AutoCAD SHX Text

(PROF. ENG. #: 3600)

AutoCAD SHX Text

PEI 2020100

AutoCAD SHX Text

AutoCAD SHX Text

21AC

AutoCAD SHX Text

21AC

AutoCAD SHX Text

AS-BUILT

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text J

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text K

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text No. 90730 9073090730

STATE OF

Φ

AutoCAD SHX Text M-001

AutoCAD SHX Text

GENERAL MECHANICAL NOTES, LEGEND AND ABBREVIATIONS

AutoCAD SHX Text

AutoCAD SHX Text

96 CEG, OFFICE FORM 002, FY2013

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

APPR'D

AutoCAD SHX Text

BY

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

EGLIN AIR FORCE BASE, FLORIDA

AutoCAD SHX Text

CENM

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJ. ENGR.

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

INDEX NO.

AutoCAD SHX Text

SPEC. NO.

AutoCAD SHX Text

PROJ. NO.

AutoCAD SHX Text

FTFA 20-RC03

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

FILE NO.

AutoCAD SHX Text

96 CEG/CEN

AutoCAD SHX Text

BASE CIVIL ENGINEER

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

CONTENTS

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BLDG 12722 HVAC REPLACEMENT

AutoCAD SHX Text

AS SHOWN

AutoCAD SHX Text

22 JULY 2021

AutoCAD SHX Text

PETERSON ENGINEERING INC.

AutoCAD SHX Text

75 SOUTH "F" STREET

AutoCAD SHX Text

PENSACOLA, FLORIDA 32502

AutoCAD SHX Text

(850) 434-0513

AutoCAD SHX Text

(PROF. ENG. #: 3600)

AutoCAD SHX Text

PEI 2020100

AutoCAD SHX Text

AutoCAD SHX Text

21AC

AutoCAD SHX Text

21AC

AutoCAD SHX Text

AS-BUILT

AutoCAD SHX Text No. 34088

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text Y

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text

ABBREVIATIONS

AutoCAD SHX Text

HVAC GENERAL NOTES

AutoCAD SHX Text

1. INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS INSTALL A COMPLETE AND OPERABLE MECHANICAL SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE. 2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. 3. INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. 4. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. 5. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT LOCATIONS AND FITMENT CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT LOCATIONS AND FITMENT 6. COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE COORDINATE EQUIPMENT CLEARANCES (AS RECOMMENDED BY MANUFACTURER) WITH ALL DISCIPLINES BEFORE INSTALLATION. 7. COORDINATE AND PROVIDE ALL DUCTS AND PIPING TRANSITION REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO COORDINATE AND PROVIDE ALL DUCTS AND PIPING TRANSITION REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT, VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION. 8. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH THE LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH THE STRAIGHT SECTION OF PIPE OR DUCT UPSTREAM AND DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER. 9. ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND REQUIRED TO PROVIDE A VIBRATION-FREE INSTALLATION. 10. LOCATIONS AND SIZES OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER LOCATIONS AND SIZES OF ALL FLOOR, WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES INVOLVED. 11. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION. 12. THERMOSTATS INDICATED ADJACENT TO DOORWAYS SHALL BE LOCATED WITHIN 18” OF JAMB AT LOCATIONS WITH THERMOSTATS INDICATED ADJACENT TO DOORWAYS SHALL BE LOCATED WITHIN 18” OF JAMB AT LOCATIONS WITH OF JAMB AT LOCATIONS WITH LIGHT SWITCHES AND MOUNT THERMOSTAT 48" AFF. LOCATE THERMOSTAT SUCH THAT LIGHT SWITCH IS BETWEEN THERMOSTAT AND JAMB. VERIFY THERMOSTAT LOCATION WITH SYSTEM FURNITURE LAYOUT PRIOR TO INSTALLING THERMOSTATS. 13. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING THICKNESS. 14. AVOID ROUTING DUCTWORK AND MECHANICAL EQUIPMENT OVER LIGHTS WHEREVER POSSIBLE. MAINTAIN MINIMUM 6” AVOID ROUTING DUCTWORK AND MECHANICAL EQUIPMENT OVER LIGHTS WHEREVER POSSIBLE. MAINTAIN MINIMUM 6” CLEARANCE BETWEEN MECHANICAL EQUIPMENT AND DUCT INSULATION TO TOP OF LIGHTS. PROVIDE CLEARANCE AND ACCESS ALL AROUND AND BELOW MECHANICAL EQUIPMENT AS REQUIRED FOR ROUTINE MAINTENANCE. 15. SEAL ALL DUCT PENETRATIONS OF WALLS AIRTIGHT, REGARDLESS OF WHETHER WALLS ARE FIRE RATED OR NOT. SEAL ALL DUCT PENETRATIONS OF WALLS AIRTIGHT, REGARDLESS OF WHETHER WALLS ARE FIRE RATED OR NOT. 16. MOUNT DUCTWORK AS HIGH AS POSSIBLE WHERE EXPOSED, UNLESS OTHER WISE NOTED. MOUNT DUCTWORK AS HIGH AS POSSIBLE WHERE EXPOSED, UNLESS OTHER WISE NOTED. 17. ALL SUPPLY AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE ALL SUPPLY AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 2"W.G., SEAL CLASS A, EXTERNALLY INSULATED. METAL DUCT INSULATION RATING PER ASHRE 90.1. METAL DUCT INSULATION RATING PER ASHRE 90.1. METAL DUCT INSULATION RATING PER ASHRE 90.1. 18. ALL RETURN AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE ALL RETURN AIR DUCTWORK ABOVE CEILINGS SHALL BE LOW PRESSURE RECTANGULAR, SMACNA STATIC PRESSURE CLASS 1” W.G., SEAL CLASS A, EXTERNALLY INSULATED. METAL DUCT INSULATION RATING PER ASHRE 90.1. W.G., SEAL CLASS A, EXTERNALLY INSULATED. METAL DUCT INSULATION RATING PER ASHRE 90.1. 19. ALL CONDENSATE DRAIN LINES SHALL BE INSULATED. ALL CONDENSATE DRAIN LINES SHALL BE INSULATED. 20. ALL FLEXIBLE DUCT TO BE A MAXIMUM OF 6' LONG. ALL FLEX DUCT CONNECTIONS TO BE SEALED WITH MASTIC ALL FLEXIBLE DUCT TO BE A MAXIMUM OF 6' LONG. ALL FLEX DUCT CONNECTIONS TO BE SEALED WITH MASTIC RECOMMENDED BY MANUFACTURER. 21. ALL METAL DUCT INSULATION RATING PER ASHRE 90.1. ALL METAL DUCT INSULATION RATING PER ASHRE 90.1. 22. ALL ELECTRICAL PANELS TO BE RELABELED WITH NEW CIRCUIT INFORMATION. ALL ELECTRICAL PANELS TO BE RELABELED WITH NEW CIRCUIT INFORMATION. 23. ALL CONDENSING UNIT COILS TO BE COATED FOR SALT WATER, MARINE ENVIRONMENT. ALL CONDENSING UNIT COILS TO BE COATED FOR SALT WATER, MARINE ENVIRONMENT. 24. ALL DRAIN PANS TO HAVE DUAL CUTOFF SWITCHES. ALL DRAIN PANS TO HAVE DUAL CUTOFF SWITCHES. 25. PROVIDE ACCESS DOORS IN DUCTWORK FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME PROVIDE ACCESS DOORS IN DUCTWORK FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN DUCTWORK THAT REQUIRE SERVICE/INSPECTION. 26. ALL EQUIPMENT REQUIRING CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, ALL EQUIPMENT REQUIRING CONDENSATE DRAIN LINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND PIPED TO THE NEAREST DRAIN AS INDICATED 27. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH REELECTED CEILING PLANS, LIGHTING, AND OTHER COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH REELECTED CEILING PLANS, LIGHTING, AND OTHER CEILING MOUNTED EQUIPMENT AND MODIFY DUCTWORK TO SUIT. 28. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY LOUVER DIMENSIONS INDICATED DOES NOT INCLUDE EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY LOUVER DIMENSIONS INDICATED DOES NOT INCLUDE FRAME OR FLANGES 29. EXPOSED DUCTWORK IN OCCUPIED SPACES SHALL BE DOUBLE-WALL WITH SOLID LINER. PROVIDE GALVANIZED EXPOSED DUCTWORK IN OCCUPIED SPACES SHALL BE DOUBLE-WALL WITH SOLID LINER. PROVIDE GALVANIZED FINISHED SUITABLE FOR PAINTING. 30. ALL OUTSIDE AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR,SMACNA STATIC PRESSURE CLASS 1 ALL OUTSIDE AIR DUCTWORK SHALL BE LOW PRESSURE RECTANGULAR,SMACNA STATIC PRESSURE CLASS 1 W.G.,SEAL CLASS A 31. PROVIDE ALL 90-DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES AND PROVIDE ACCESS DOORS PROVIDE ALL 90-DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES AND PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH TURNING VANES. 32. CONCRETE HOUSE KEEPING PADS TO SUIT MECHANICAL EQUIPMENT, MINIMUM CONCRETE PAD THICKNESS SHALL BE CONCRETE HOUSE KEEPING PADS TO SUIT MECHANICAL EQUIPMENT, MINIMUM CONCRETE PAD THICKNESS SHALL BE 6 INCHES PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 6 INCHS ON ALL SIDES. 33. CONTRACTOR TO PROTECT SITE INSTRUMENTATION FROM DUST AND DEBRIS DURING ALL PHASES OF CONSTRUCTION CONTRACTOR TO PROTECT SITE INSTRUMENTATION FROM DUST AND DEBRIS DURING ALL PHASES OF CONSTRUCTION

AutoCAD SHX Text WxH

AutoCAD SHX Text 8"%%c

AutoCAD SHX Text HVAC LEGEND RECTANGULAR DUCTWORK, SIZES SHOWN ARE INTERNAL CLEAR DIMENSIONS. (WIDTH x HEIGHT) FIRST FIGURE IS SIDE SHOWN. DUCT SECTION, POSITIVE PRESSURE, FIRST FIGURE IS TOP DIMENSION DUCT SECTION, NEGATIVE PRESSURE, FIRST FIGURE IS TOP DIMENSION ROUND BRANCH DUCT TAKEOFF FROM RECTANGULAR DUCT MAIN.

This is the start of the file's text. The full file is on GovTribe.