Attachment_F_DRWGS_15R4020.pdf

PDF 9 MB Posted

Attached to
Repair HVAC & Interior Bldg. 3017 Federal contract opportunity
Solicitation number
FA2823-15-R-4020
Issued by
Department of the Air Force Materiel Command Test Center

About this file

Drawings 13BR

View the file

Other files for this federal contract opportunity

Other files attached to Repair HVAC & Interior Bldg. 3017, newest first.
File Type Posted
FA2823-15-R-4020_Amendment_3.pdf PDF
FA2823-15-R-4020_Amendment_2.pdf PDF
FA2823-15-R-4020_Consolidated_Q_ _A_090915.pdf PDF
FA2823-15-R-4020_Consolidated_Q_ _A_090815.pdf PDF
HVAC_Bldg_3017_Extension.pdf PDF
FTFA_13-9005_Site_Visit_Sign_in_Sheet.pdf PDF
Q_ _A_PART_1.docx DOCX document
Attachment_C_Financial_Responsibility.docx DOCX document
Attachment_G_WD_15R4020.pdf PDF
Attachment_D_SOW.pdf PDF
Attachment_J_Base_Support_Letter.pdf PDF
Memorandum_Letter.doc DOC document
FA2823-15-R-4020_RFP_RELEASED.pdf PDF
Attachment_E_SPECS_139005_15R4020.pdf PDF
Attachment_I_Hold_Harmless_Agreement_Bldg_3017.pdf PDF
Attachment_B_Past_Performance_Questionnaire.docx DOCX document
ATTACHMENT_E-Affidavit.pdf PDF
Attachment_A_Past_Performance_References.docx DOCX document
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D P R O J E C T

R e p a i r

H V A C a n d

I n t e r i o r

D i n i n g

H a l l

B l d g

D W G M e c h M d w g

P M

D W G

T o

P D F p c

ELECTRICAL PLAN - DEMOLITION - LIGHTING

SCALE: 1/8" = 1'-0"

ELECTRICAL LEGEND - DEMOLITION:

EXISTING COMPACT FLUORESCENT DOWNLIGHT - TO REMAIN - PROVIDE SUPPORT TO HOLD FIXTURE IN PLACE WHILE CEILING

IS DEMOLISHED AND REPLACED - ADJUST LOCATION OF EXISTING FIXTURE AS REQUIRED TO REINSTALL IN NEW CEILING.

EXISTING FLUORESCENT TROFFER - TO REMAIN - PROVIDE SUPPORT TO HOLD FIXTURE IN PLACE WHILE CEILING IS

DEMOLISHED AND REPLACED - ADJUST LOCATION OF EXISTING FIXTURE AS REQUIRED TO REINSTALL IN NEW CEILING.

EXISTING EXIT LIGHT - TO REMAIN - PROVIDE SUPPORT TO HOLD FIXTURE IN PLACE WHILE CEILING IS DEMOLISHED AND

REPLACED - REINSTALL FIXTURE ON NEW CEILING.

EXISTING COMPACT FLUORESCENT DOWNLIGHT - REMOVE AND RELOCATE, AS SHOWN ON NEW WORK PLAN.

EXISTING FLUORESCENT TROFFER - REMOVE.

EXISTING WALL SWITCH - REMOVE.

EXISTING CONDUIT & WIRING - TO REMAIN & BE REUSED, AS SHOWN ON NEW WORK PLAN.

EXISTING CONDUIT & WIRING - REMOVE.

F

F

S

V

J

M

EXISTING JUNCTION BOX - REMOVE.

EXISTING DUPLEX RECEPTACLE - TO REMAIN.

EXISTING DUPLEX RECEPTACLE - REMOVE.

EXISTING COMBINATION MOTOR STARTER/DISCONNECT SWITCH - REMOVE.

EXISTING MOTOR - REMOVE EXISTING ELECTRICAL CONNECTION.

EXISTING FLEXIBLE CONDUIT & WIRING CONNECTION - REMOVE.

EXISTING FIRE ALARM SYSTEM SPEAKER/STROBE - WALL MOUNTED - REMOVE.

EXISTING FIRE ALARM SYSTEM SPEAKER/STROBE - CEILING MOUNTED - REMOVE.

EXISTING PUBLIC ADDRESS SYSTEM SPEAKER - REMOVE & REINSTALL IN NEW CEILING.

EXISTING PUBLIC ADDRESS SYSTEM VOLUME CONTROL - REMOVE & REINSTALL IN NEW WALL.

H

EXISTING ELECTRIC STRIP HEAT - REMOVE EXISTING ELECTRICAL CONNECTION.

(APPLIES TO DRAWINGS E-1 AND E-2.)

FACP

EXISTING FIRE ALARM SYSTEM CONTROL PANEL - FIRE CONTROL INSTRUMENTS # 7200 - REMOVE.

VNP

TR

EXISTING FIRE ALARM SYSTEM VOICE NOTIFICATION PANEL - REMOVE.

EXISTING FIRE ALARM SYSTEM TRANSCEIVER - REMOVE.

GENERAL ELECTRICAL NOTE:

ALL ELECTRICAL WORK AND MATERIAL, UNLESS OTHERWISE NOTED, IS NEW AND SHALL BE

FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

PETERSON ENGINEERING INC.

(850) 434-0513

F

F

F

F

S

V

ELECTRICAL PLAN - DEMOLITION - POWER & AUXILIARY SYSTEMS

SCALE: 1/8" = 1'-0"

J

J

M

M

AHU-1

AHU-2

CWP

HWP

B-1

MU-4

MU-3

MU-2

MU-1

SF-5

SF-4

SF-3

ELECTRICAL PLAN - MEZZANINE - DEMOLITION

SCALE: 1/8" = 1'-0"

M

M

M

M

S

MEZZANINE, ABOVE. SEE "ELECTRICAL PLAN -

MEZZANINE - DEMOLITION," THIS SHEET.

SF-6

M

M

H

H

H

H

V

F

EXISTING PANEL "WEST" - REMOVE &

REINSTALL IN NEW WALL & RECONNECT

EXISTING BRANCH CIRCUITS AS SHOWN

ON "ELECTRICAL PLAN - NEW WORK -

POWER," SHEET E-4.

EXISTING PANEL "EAST" - REMOVE &

REINSTALL IN NEW WALL & RECONNECT

EXISTING BRANCH CIRCUITS AS SHOWN

ON "ELECTRICAL PLAN - NEW WORK -

POWER," SHEET E-4.

EXISTING PANEL "H1"

EXISTING PANEL "E1"

EXISTING PANEL "MDP1"

EXISTING PANEL "MDP2"

EXISTING PANEL "L2"

EXISTING PANEL "LP1"

T

EXISTING ELECTRICAL ROOM LAYOUT

SCALE: 1/8" = 1'-0"

FACP

TR

VNP

TEMPORARILY DISCONNECT EXISTING 120 V. POWER

CONNECTION FROM EXISTING BOILER & RECONNECT

TO NEW BOILER.

WORK NOTES:

REMOVE EXISTING CONDUIT & WIRING BACK TO EXISTING PANEL "MDP2."

2 REMOVE EXISTING CONDUIT & WIRING BACK TO EXISTING PANEL "MDP1."

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

ELECTRICAL PLAN - NEW WORK - LIGHTING

ELECTRICAL LEGEND - NEW WORK:

EXISTING COMPACT FLUORESCENT DOWNLIGHT - ADJUST LOCATION OF EXISTING FIXTURE AS REQUIRED TO REINSTALL IN

NEW CEILING - RECONNECT EXISTING FLEXIBLE CONDUIT WHIP & WIRING TO RELOCATED FIXTURE.

EXISTING FLUORESCENT TROFFER - ADJUST LOCATION OF EXISTING FIXTURE AS REQUIRED TO REINSTALL IN NEW GRID TEE

CEILING - RECONNECT EXISTING FLEXIBLE CONDUIT WHIP & WIRING TO RELOCATED FIXTURE.

EXISTING EXIT LIGHT - TO REMAIN - REINSTALL FIXTURE ON NEW GRID TEE CEILING.

EXISTING COMPACT FLUORESCENT DOWNLIGHT - REINSTALL IN NEW LOCATION & PROVIDE NEW CONDUIT & WIRING, AS SHOWN.

WALL SWITCH - QUIET TYPE - 20 A., 120/277 V., 1 POLE - MTD. 48" A.F.F. TO TOP OF BOX.

EXISTING CONDUIT & WIRING - TO REMAIN & BE REUSED, AS SHOWN ON NEW WORK PLAN.

M

JUNCTION BOX - SIZE AS REQUIRED - CONCEAL ABOVE NEW GRID TEE CEILING.

EXISTING DUPLEX RECEPTACLE - TO REMAIN.

DUPLEX RECEPTACLE - 20 A., 125 V., 2 P., 3 W. - MTD. 18" A.F.F. TO CENTER OF BOX.

MOTOR - FURNISHED BY MECHANICAL CONTRACTOR - CONNECTION BY ELECTRICAL CONTRACTOR.

LIQUID-TIGHT FLEXIBLE CONDUIT & WIRING CONNECTION.

NOTE: TICKMARKS INDICATE NO. OF CONDUCTORS; " " INDICATES FULL SIZE GROUND CONDUCTOR; ARROW INDICATES

HOMERUN TO PANEL; "LP:1" INDICATES PANEL AND CIRCUIT NO.; WIRE IS # 12; CONDUIT IS 1/2" & BREAKER IS 20 A., 1 P., UNLESS NOTED OTHERWISE. ( INDICATES CONCEALED OVERHEAD OR IN WALLS; INDICATES CONCEALED IN

EXISTING PANELBOARD - TO REMAIN.

BRANCH CIRCUIT CONDUIT & WIRING:

OR BELOW FLOOR; INDICATES EXPOSED.)

LP:1

BRANCH CIRCUIT CONDUIT & WIRING:

CONDUIT IS 1/2", UNLESS NOTED OTHERWISE. ( INDICATES CONCEALED OVERHEAD OR IN WALLS; INDICATES EXPOSED.)

NOTE: TICKMARKS INDICATE NO. OF CONDUCTORS; " " INDICATES FULL SIZE GROUND CONDUCTOR; WIRE IS # 12;

MOTOR STARTER - FURNISHED BY MECHANICAL CONTRACTOR - CONNECTION BY ELECTRICAL CONTRACTOR.

DISCONNECT SWITCH - HEAVY DUTY - NON-FUSIBLE.

EXISTING COMPACT FLUORESCENT DOWNLIGHT - TO REMAIN.

J

J

J

J

E

E

E

E

E

E

E

EXISTING BRANCH CIRCUIT CONDUIT & WIRING - INTERCEPT EXISTING CONDUIT & PULL IN NEW WIRING.

EXISTING HOMERUN TO PANEL "H1" TO REMAIN.

(APPLIES TO DRAWINGS E-3, E-4 AND E-5.)

EXISTING HOMERUN TO PANEL "H1" TO REMAIN.

E

EXISTING HOMERUN TO PANEL "H1" TO REMAIN.

R

R

R

T

EXISTING DRY-TYPE TRANSFORMER - TO REMAIN.

EXISTING ELECTRICAL ROOM LAYOUT

SCALE: 1/8" = 1'-0"

E

J

E

E

J1

WORK NOTES:

INSTALL WALL SWITCH IN EXISTING WALL. CUT & PATCH EXISTING WALL AND CEILING AS

REQUIRED TO INSTALL NEW SWITCH AND ASSOCIATED CONDUIT & WIRING.

2 INTERCEPT EXISTING CONDUIT, INSTALL JUNCTION BOX ABOVE CEILING, SPLICE EXISTING

WIRING TO NEW WIRING & EXTEND NEW CIRCUIT TO NEW WALL SWITCH.

TOGGLE TYPE DISCONNECT SWITCH - HORSEPOWER RATED - MOUNT ADJACENT TO MOTOR BEING SERVED.

EXISTING PANEL "H1"

EXISTING PANEL "E1"

EXISTING PANEL "MDP1"

EXISTING PANEL "MDP2"

EXISTING PANEL "L2"

EXISTING PANEL "LP1"

T

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

ELECTRICAL PLAN - NEW WORK - POWER

J

J J

M

M

M

M

M

M

ELECTRICAL PLAN - MEZZANINE - NEW WORK - POWER

SCALE: 1/8" = 1'-0"

J

J

MEZZANINE, ABOVE. SEE "ELECTRICAL PLAN -

MEZZANINE - NEW WORK - POWER," THIS SHEET.

EXISTING PANEL "WEST" - REINSTALL IN NEW WALL & RECONNECT

EXISTING BRANCH CIRCUITS. INSTALL NEW FEEDER (4 # 1 & 1 # 6

GND. - 2" C.) BACK TO EXISTING SWITCH IN ELECTRICAL ROOM.

EXISTING PANEL "EAST" - REINSTALL IN NEW WALL & RECONNECT

EXISTING BRANCH CIRCUITS. INSTALL NEW FEEDER (4 # 1 & 1 # 6

GND. - 2" C.) BACK TO EXISTING SWITCH IN ELECTRICAL ROOM.

E

EXISTING HOMERUN TO PANEL "L2" TO REMAIN.

M

M

B-1

M

M

SEE "LARGE SCALE PLAN - MECHANICAL

EQUIPMENT ROOMS," THIS SHEET.

LARGE SCALE PLAN - MECHANICAL EQUIPMENT ROOMS

SCALE: 1/4" = 1'-0"

EXISTING PANEL "H1"

EXISTING PANEL "E1"

EXISTING PANEL "MDP1"

EXISTING PANEL "MDP2"

EXISTING PANEL "L2"

EXISTING PANEL "LP1"

T

EXISTING ELECTRICAL ROOM LAYOUT

SCALE: 1/8" = 1'-0"

DIT

BOILER PUMP

1 1/2 HP, 208 V., 3Ø

CHWP-1

5 HP, 480 V., 3Ø

HWP-1

2 HP, 480 V., 3Ø

AHU-1

7 1/2 HP, 480 V., 3Ø

AHU-2

7 1/2 HP, 480 V., 3Ø

LDCU-1

FANS (2) 0.77 A., 480 V., 3Ø

HP-1

COMPR. (2) 16.7 RLA, 480 V., 3Ø

FANS (4) 0.8 FLA, 480 V., 3Ø

LDCU-2

FANS (2) 0.77 A., 480 V., 3Ø

LDU-2

(2) 4 HP, 480 V., 3Ø

MU-2

3 HP, 480 V., 3Ø

LDU-1

(2) 4 HP, 480 V., 3Ø

MU-1

3 HP, 480 V., 3Ø

M

M

HP-2

COMPR. (2) 16.7 RLA, 480 V., 3Ø

FANS (4) 0.8 FLA, 480 V., 3Ø

30 A., 3 P., NEMA 3R

30 A., 3 P., NEMA 3R

60 A., 3 P., NEMA 3R

60 A., 3 P., NEMA 3R

30 A., 3 P., NEMA 1

30 A., 3 P., NEMA 1

60 A., 3 P., NEMA 1

60 A., 3 P., NEMA 1

30 A., 3 P., NEMA 1

30 A., 3 P., NEMA 1

11 KVA, 3Ø DRIVE ISOLATION TRANSFORMER -

WALL MOUNTED ABOVE DISCONNECT SWITCH

AND VARIABLE FREQUENCY DRIVE.

30 A., 3 P., NEMA 1

30 A., 3 P., NEMA 1

E

WORK NOTES:

INTERCEPT EXISTING BRANCH CIRCUITS ABOVE LAY-IN CEILING, INSTALL JUNCTION BOX, SPLICE CONDUCTORS &

EXTEND NEW HOMERUN TO (3) EXISTING 20 A., 1 P. BKRS. IN EXISTING PANEL "WEST." (CIRCUIT # 1/3/5)

2 INTERCEPT EXISTING BRANCH CIRCUITS ABOVE LAY-IN CEILING, INSTALL JUNCTION BOX, SPLICE CONDUCTORS &

EXTEND NEW HOMERUN TO (2) EXISTING 20 A., 1 P. BKRS. IN EXISTING PANEL "WEST." (CIRCUIT # 7/9 AND 2/4)

3 INTERCEPT EXISTING BRANCH CIRCUITS ABOVE LAY-IN CEILING, INSTALL JUNCTION BOX, SPLICE CONDUCTORS &

EXTEND NEW HOMERUN TO (3) EXISTING 20 A., 1 P. BKRS. IN EXISTING PANEL "EAST." (CIRCUIT # 1/3/5 AND 2/4/6)

4 INTERCEPT EXISTING BRANCH CIRCUITS ABOVE LAY-IN CEILING, INSTALL JUNCTION BOX, SPLICE CONDUCTORS &

EXTEND NEW HOMERUN TO (2) EXISTING 20 A., 1 P. BKRS. IN EXISTING PANEL "EAST." (CIRCUIT 7/9)

5 INTERCEPT EXISTING BRANCH CIRCUITS ABOVE LAY-IN CEILING, INSTALL JUNCTION BOX, SPLICE CONDUCTORS &

EXTEND NEW HOMERUN TO (1) EXISTING 20 A., 2 P. BKR. IN EXISTING PANEL "EAST." (CIRCUIT 20/22)

EDH-2

15 KW, 480 V., 3Ø

EDH-1

15 KW, 480 V., 3Ø

30 A., 3 P., NEMA 1 - MOUNT ABOVE

CEILING ADJACENT TO DUCT HEATER.

30 A., 3 P., NEMA 1 - MOUNT ABOVE

CEILING ADJACENT TO DUCT HEATER.

HOMERUN TO EXISTING 20 A., 1 P. SPARE

BKR. IN EXISTING PANEL "EAST," CKT. # 8.

HOMERUN TO EXISTING 20 A., 1 P. SPARE

BKR. IN EXISTING PANEL "WEST," CKT. # 12.

EXTEND TO LDU-1 ON MEZZANINE.

EXTEND TO LDU-2 ON MEZZANINE.

EXTEND TO LDCU-1 OUTSIDE.

EXTEND TO LDCU-2 OUTSIDE.

J

INSTALL FLOOR OUTLET W/ DUPLEX RECEPTACLE IN EXISTING CONCRETE

FLOOR. CUT & PATCH EXISTING CONCRETE FLOOR AS REQUIRED TO

INSTALL FLOOR BOX AND CONDUIT & WIRING. VERIFY EXACT LOCATION

W/ CONTRACTING OFFICER AND USER IN FIELD PRIOR TO INSTALLATION.

J

WP

120 V. CONNECTION FOR

CHILLER PIPING HEAT TAPE.

M

HOMERUN TO EXISTING 20 A., 1 P. SPARE

BREAKER IN PANEL "WEST," CKT. # 10.

EXISTING 400 A., 3 P., NEMA 3R

DISCONNECT SWITCH TO

REMAIN. EXTEND NEW 3 # 4/0 & 1

# 4 GND. IN 2" LIQUID TIGHT

FLEXIBLE METAL CONDUIT TO

NEW CHILLER.

EXISTING 100 A., 3 P. DISCONNECT SWITCH MTD. ABOVE

EXISTING DOOR SERVES EXISTING PANEL "WEST." EXTEND

NEW FEEDER (4 # 1 & 1 # 6 GND. - 2" C.) FROM EXISTING

DISCONNECT SWITCH TO RELOCATED PANEL "WEST."

EXISTING 100 A., 3 P. DISCONNECT SWITCH MTD. ABOVE

EXISTING DOOR SERVES EXISTING PANEL "EAST." EXTEND

NEW FEEDER (4 # 1 & 1 # 6 GND. - 2" C.) FROM EXISTING

DISCONNECT SWITCH TO RELOCATED PANEL "EAST."

J

J

6 HOMERUN FROM NEW HOOD SUPPRESSION SYSTEM CONTROL PANELS TO (2) EXISTING 20 A., 1 P. BKRS. IN EXISTING

PANEL "WEST." (CIRCUIT # 6/8)

7 HOMERUN TO EXISTING 20 A., 1 P. BKR. IN EXISTING PANEL "WEST." (CIRCUIT # 11)

HOMERUN TO EXISTING 20 A., 1 P. BKR.

IN PANEL "L2," CKT. # 16.

30 A., 3 P., NEMA 1

HOMERUN TO EXISTING 25 A., 3 P. BKR. IN

EXISTING PANEL "MDP-1."

HOMERUN TO EXISTING 15 A., 3 P. BKR. IN

EXISTING PANEL "MDP-1."

HOMERUN TO EXISTING 15 A., 3 P.

BKR. IN PANEL "MDP2," CKT. # 16.

HOMERUN TO EXISTING 15 A., 3 P.

BKR. IN PANEL "MDP2," CKT. # 18.

HOMERUN 3 # 6 & 1 # 8 GND. - 1" C. TO 50 A., 3 P. BKR. IN

PANEL "MDP1," CKT. # 9. REMOVE EXISTING 90 A., 3 P. BKR.

& INSTALL 50 A., 3 P. BKR. IN EXISTING SIEMENS S5 PANEL.

HOMERUN 3 # 6 & 1 # 8 GND. - 1" C. TO 50 A., 3 P. BKR. IN

PANEL "MDP1," CKT. # 10. REMOVE EXISTING 100 A., 3 P. BKR.

& INSTALL 50 A., 3 P. BKR. IN EXISTING SIEMENS S5 PANEL.

8 HOMERUN 3 # 6 & 1 # 8 GND. - 1" C. TO 50 A., 3 P. BKR. IN PANEL "MDP2" CKT. # 20. REMOVE

EXISTING 15 A., 3 P. BKR. & INSTALL 50 A., 3 P. BKR. IN EXISTING SIEMENS S5 PANEL

9 HOMERUN 3 # 6 & 1 # 8 GND. - 1" C. TO 50 A., 3 P. BKR. IN PANEL "MDP2" CKT. # 22. REMOVE

EXISTING 15 A., 3 P. BKR. & INSTALL 50 A., 3 P. BKR. IN EXISTING SIEMENS S5 PANEL

10 HOMERUN 3 # 10 & 1 # 10 GND. - 3/4" C. TO 30 A., 3 P. BKR. IN PANEL "MDP2" CKT. # 29. REMOVE

EXISTING 40 A., 3 P. BKR. & INSTALL 30 A., 3 P. BKR. IN EXISTING SIEMENS S5 PANEL

11 HOMERUN 3 # 10 & 1 # 10 GND. - 3/4" C. TO 30 A., 3 P. BKR. IN PANEL "MDP2" CKT. # 30. REMOVE

EXISTING 40 A., 3 P. BKR. & INSTALL 30 A., 3 P. BKR. IN EXISTING SIEMENS S5 PANEL

J

J

J

J

HOMERUN TO EXISTING 20 A., 1 P. SPARE

BKR. IN EXISTING PANEL "EAST," CKT. # 10.

CUT & PATCH EXISTING GYP. BOARD WALL

FOR RECEPTACLE AND CONDUIT & WIRING

INSTALLATION. (TYP.)

INSTALL JUNCTION BOXES FOR NEW

RECEPTACLE CIRCUIT ABOVE EXISTING

LAY-IN CEILING (TYP.)

J

J

CUT & PATCH EXISTING GYP. BOARD

WALL FOR RECEPTACLE AND CONDUIT

& WIRING INSTALLATION. (TYP.)

INSTALL JUNCTION BOXES FOR NEW

RECEPTACLE CIRCUIT ABOVE

EXISTING LAY-IN CEILING (TYP.)

HOMERUN TO EXISTING 20 A., 1 P. SPARE

BKR. IN EXISTING PANEL "WEST," CKT. # 13.

DISCONNECT EXISTING ELECTRICAL

CONNECTION TO EXISTING EF-5 &

RECONNECT TO NEW EXHAUST FAN.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

ELECTRICAL PLAN - NEW WORK - AUXILIARY SYSTEMS

F

F

F

PA

S

R

S

R S

T

F

F

F

F

F

F

F

F

F

F

F F

F F F

F F F

F

F

FF

F

F

F

F

FF

F

F

S

S

S

S

SS

S

S

SS

S

SS

S

S S

S S

S

SSS

S

S

S

S

S

S

S

V

F

F

FACP

F

F

FSCP-1

FSCP-2

TR

J

P

A

P A

P

A

P

A

L

O

C

AUXILIARY SYSTEMS LEGEND - NEW WORK:

S

V

EXISTING FIRE ALARM SYSTEM SPEAKER/STROBE - WALL MOUNTED - INSTALL NEW FIRE ALARM STROBE IN EXISTING BOX.

EXISTING FIRE ALARM SYSTEM SPEAKER/STROBE - CEILING MOUNTED - INSTALL NEW FIRE ALARM STROBE.

EXISTING PUBLIC ADDRESS SYSTEM VOLUME CONTROL - REINSTALL IN NEW WALL - MOUNT 48" A.F.F. TO TOP OF BOX.

F

F

F

S

EXISTING PUBLIC ADDRESS SYSTEM SPEAKER - REINSTALL IN NEW GRID TEE CEILING.

EXISTING FIRE ALARM SYSTEM SPEAKER/STROBE - CEILING MOUNTED - INSTALL NEW FIRE ALARM STROBE.

MNSP

LOC

MASS NOTIFICATION SYSTEM - CONTROL PANEL - SEE RISER DIAGRAM.

MASS NOTIFICATION SYSTEM - SPEAKER/AMBER STROBE - CEILING MOUNTED.

MASS NOTIFICATION SYSTEM - LOCAL OPERATORS CONSOLE UNIT - FURNISH UNIT W/ HVAC EMERGENCY SHUTOFF - RED MUSHROOM TYPE CUTOFF

PUSHBUTTON W/ LABELING.

PA

PUBLIC ADDRESS SYSTEM - CONDUIT & WIRING.

FACP

FIRE ALARM SYSTEM CONTROL PANEL - SEE "FIRE ALARM RISER DIAGRAM," SHEET E-7.

(APPLIES TO DRAWINGS E-5 AND E-6.)

EXISTING PUBLIC ADDRESS SYSTEM SPEAKER - RELOCATE TO POSITION SHOWN - EXTEND P.A. CIRCUIT CONDUIT & WIRING TO

RELOCATED SPEAKER AS INDICATED ON "ELECTRICAL PLAN - NEW WORK - AUXILIARY SYSTEMS," SHEET E-5.

TR

FIRE ALARM SYSTEM TRANSCEIVER - SEE "FIRE ALARM RISER DIAGRAM," SHEET E-7.

F

EXISTING FIRE ALARM SYSTEM PULL STATION - WALL MOUNTED - INSTALL NEW PULL STATION IN EXISTING BOX.

S

FIRE ALARM SYSTEM DUCT SMOKE DETECTOR - PHOTO-ELECTRIC TYPE - "S" = SUPPLY; "R" = RETURN.

MASS NOTIFICATION SYSTEM - CONDUIT & WIRING - 3/4" C. MINIMUM.

M

N

MASS NOTIFICATION SYSTEM - SPEAKER/AMBER STROBE - WALL MOUNTED 80" A.F.F. TO BOTTOM OF BOX.

MNSP

PA

EXISTING PUBLIC ADDRESS SYSTEM CONSOLE - TO REMAIN.

T

F

FIRE ALARM CONNECTION TO SPRINKLER SYSTEM FLOW SWITCH.

FIRE ALARM CONNECTION TO SPRINKLER SYSTEM TAMPER SWITCH.

INSTALL A KNOX BOX MODEL

3200 WITHOUT TAMPER SWITCH

ON EXTERIOR WALL.

F

V

P

A

CUT & PATCH EXISTING WALL & CEILING AS REQUIRED TO

INSTALL VOLUME CONTROL SWITCH IN NEW LOCATION &

CONNECT TO EXISTING SPEAKER.

PROVIDE A REMOTE ANNUNCIATOR AT THE DESIGNATED PRIMARY ENTRANCE.

PROVIDE REMOTE ANNUNCIATOR WITH CONTROL FUNCTIONS THE SAME AS THE

MAIN CONTROL PANEL. CONTROL FUNCTIONS SHALL BE ACCESSIBLE ONLY BY

USER CODE OR SECURED BEHIND A LOCKED PANEL.

FIRE ALARM ANNUNCIATOR NOTE:

F

FIRE ALARM SYSTEM - CONDUIT & WIRING.

CUT & PATCH EXISTING CEILING AS REQUIRED TO INSTALL

NEW FIRE ALARM STROBE IN NEW FURRED OUT WALL

ANN

FIRE ALARM SYSTEM ANNUNCIATOR - SEE "FIRE ALARM ANNUNCIATOR NOTE," THIS SHEET.

R

FIRE ALARM SYSTEM AHU SHUT DOWN RELAY.

MEZZANINE, ABOVE. SEE "ELECTRICAL PLAN -

MEZZANINE," THIS SHEET.

ELECTRICAL PLAN - MEZZANINE

SCALE: 1/8" = 1'-0"

R

R

CUT & PATCH EXISTING CEILING AS

REQUIRED TO INSTALL ANNUNCIATOR

AND CONDUIT & WIRING.

CUT & PATCH EXISTING CEILING AS REQUIRED TO

INSTALL LOC AND CONDUIT & WIRING.

T

FIRE ALARM SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL

PRIOR TO ANY WORK IN ACCORDANCE WITH UFC 3-600-01, CHAPTER 5 AND NFPA 72,

PARAGRAPH 10.4.

FIRE ALARM SHOP DRAWINGS NOTE:

M

FIRE ALARM SYSTEM MONITOR MODULE.

MOUNT MONITOR MODULE ADJACENT TO WET CHEMICAL

SUPPRESSION SYSTEM CONTROL PANEL

MOUNT MONITOR MODULE ADJACENT TO WET

CHEMICAL SUPPRESSION SYSTEM CONTROL PANEL

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

FIRE ALARM/MASS NOTIFICATION RISER DIAGRAM

BATTERIES

MNSP

MONACO BT-X TRANSCEIVER W/ 141.3625 MHZ

FREQUENCY & LIVE VOICE CAPABILITIES

NOT TO SCALE

BATTERIES

FACP

F

WIRING & CONDUIT AS REQD.

BY SYSTEM

F

ADDRESSABLE INTELLIGENT

FIRE ALARM CONTROL PANEL

SSSS

EXTERIOR WALL

EXISTING WEATHERHEAD

EXISTING ANTENNA

TRANSCEIVER ZONES:

WORK NOTES:

(TYP.)

20 # 14 - 1/2" C.EXISTING LOW LOSS COAX CABLE IN 1"C. -

RECONNECT TO NEW TRANSCEIVER.

EXISTING

LIGHTNING

ARRESTER

EXISTING GROUND

CONDUCTOR CONNECTION

TO EXISTING GROUND ROD.

EXISTING GROUND CONNECTION

TO MAIN SERVICE

RECONNECT EXISTING FIRE ALARM CIRCUITS TO NEW

CONTROL PANEL. PULL NEW WIRING (IF REQUIRED BY THE

NEW SYSTEM) IN EXISTING CONDUITS TO NEW DEVICES.

2 # 16 AWG STRANDED, TWISTED PAIR FOR FIRE ALARM SIGNALLING

LINE CIRCUIT. SLC SHALL BE INSTALLED IN A LOOPED CONDUIT

SYSTEM. SEE SPECIFICATION SECTION 28 31 76.

2 # 14 AWG THHN FOR NOTIFICATION APPLIANCE CIRCUIT & 2 # 16

AWG UNSHIELDED PAIR FOR MASS NOTIFICATION SPEAKER LOOP.

NAC AND SPEAKER CIRCUITS SHALL BE INSTALLED IN A LOOPED

CONDUIT SYSTEM. SEE SPECIFICATION SECTION 28 31 76.

TIE INTO EXISTING P.A. SYSTEM SO THAT

MASS NOTIFICATION SYSTEM OVERRIDES P.A.

SYSTEM. INSTALL RELAY AT EXISTING P.A.

SYSTEM FOR OVERRIDE CONNECTION.

S

ZONE 1 PULL STATIONS

ZONE 2 SMOKE DETECTOR

ZONE 3 DUCT SMOKE DETECTORS

ZONE 4 KITCHEN HOOD FIRE SUPPRESSION CONTROL PANEL # 1

ZONE 5 KITCHEN HOOD FIRE SUPPRESSION CONTROL PANEL # 2

ZONE 6 SPRINKLER FLOW

ZONE 7 SPRINKLER TAMPERS

ZONE 8 SERVING LINE HOOD WET CHEMICAL HOOD SYSTEMS

ZONE 9 FIRE ALARM SYSTEM TROUBLE

ZONE 10 MASS NOTIFICATION SYSTEM TROUBLE

INTERCEPT EXISTING 120 V. CIRCUIT FEEDING EXISTING FACP & PROVIDE

IN-LINE SERIES SURGE SUPPRESSOR. MOUNT SUPPRESSOR AS CLOSE

TO PANEL AS POSSIBLE.

INTERCEPT EXISTING 120 V. CIRCUIT FEEDING EXISTING VOICE PANEL &

PROVIDE IN-LINE SERIES SURGE SUPPRESSOR. MOUNT SUPPRESSOR AS

CLOSE TO PANEL AS POSSIBLE.

LOC

CONNECT TO AIR HANDLING UNIT MOTOR STARTER FOR SHUT DOWN.

SEE "AHU SHUTDOWN DIAGRAM," THIS SHEET.

FRM-1

ADDRESS

ONES

TENS

LOOP

RELAY

COMMON 2

NORMALLY

CLOSED 2

NORMALLY

OPEN 2

RELAY

COMMON 1

NORMALLY

CLOSED 1

NORMALLY

OPEN 1

ADDRESSABLE FIRE ALARM

CONTROL PANEL "FACP"

AUXILIARY FORM

"C" CONTACTS

AUX

DC

AHU SHUTDOWN DIAGRAM

NOT TO SCALE

FIRE ALARM SYSTEM MICROPROCESSOR-BASED ADDRESSABLE

CONTROL RELAY MODULE (FOR FAN MOTOR SHUTDOWN)

MOUNTED IN 4" SQ. X 2 1/8" DEEP DEVICE BOX. RELAY SHALL

PROVIDE TWO FORM "C" DRY RELAY CONTACTS RATED 2 AMPS

AT 24 VDC AND HAVE NOMINAL OPERATING VOLTAGE OF 15 TO

32 VDC WITH A MAXIMUM CURRENT DRAW OF 6.5 mA

SIGNALLING LINE

CIRCUIT (SLC) LOOP

2#16, 3/4"C.

DATA IN (+)

T3

T3

T2

T1

T2

T1

M

AHU MOTOR

STARTER

STOP

CONTROL

INPUT

MOTOR REQUIREMENTS VARY FOR

ALL EQUIPMENT SUPPLIED. SEE

PLANS FOR ACTUAL MOTOR

HORSEPOWER, VOLTAGE & PHASE

DATA IN (-)

DATA OUT (+) DATA OUT (-)

SIGNALLING LINE

CIRCUIT (SLC) LOOP

2#16, 3/4"C.

TO NEXT

DEVICE OR

"FACP"

2#14, 1/2"C. (VERIFY

WITH EQUIPMENT

MANUFACTURER)

R RR S R

F T T

HOOD SUPPRESSION

SYSTEM CONTROL PANEL

F

MONITOR MODULE FOR HOOD

SUPPRESSION SYSTEM

CONNECT TO AUXILIARY CONTACTS IN HOOD

CONTROL PANEL TO SIGNAL FIRE ALARM CONTROL

PANEL IF THE SUPPRESSION SYSTEM DISCHARGES.

LAY IN CEILING

FIRE ALARM SYSTEM

CONDUIT & WIRING

DETAIL - HOOD SUPPRESSION SYSTEM CONNECTION

N.T.S.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "MDP1," CKT. # 2.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "MDP1," CKT. # 3.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "MDP-2," CKT. # 12.

CONNECT TO ALARM CONTACTS IN EXISTING FIRE SUPPRESSION CONTROL PANEL.

CONNECT TO ALARM CONTACTS IN NEW WET CHEMICAL SYSTEM CONTROL PANEL.

CONNECT TO LIQUID DESSICANT UNIT MOTOR STARTER FOR SHUT

DOWN. SEE "AHU SHUTDOWN DIAGRAM," THIS SHEET.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 27,29.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 31,33.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 35,37.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 24,26.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 28,30.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 32,34.

CONNECT TO SHUNT TRIP CIRCUIT BREAKER IN PANEL "LP1," CKT. # 50,52.

MOUNT LOC 44" ABOVE FINISHED FLOOR

(MAX.) TO TOP MESSAGE BUTTON.

MOUNT ANNUNCIATOR 60" ABOVE FINISHED

FLOOR (MAX.) TO TOP OF ENCLOSURE.

MOUNT FACP AND MNSP 70" (MAX.)

TO TOP OF ENCLOSURES.

MOUNT TRANSCEIVER 60" (MAX.)

TO TOP OF ENCLOSURE.

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

ELECTRICAL ROOF PLAN

WORK NOTES:

EXISTING ALUMINUM LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.

2 EXISTING ALUMINUM AIR TERMINAL.

3 NEW ALUMINUM LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.

4 NEW LIGHTNING PROTECTION SYSTEM MECHANICAL CONNECTOR FOR WIRE TO WIRE

CONNECTIONS.

5 BOND ALUMINUM CONDUCTOR TO CATWALK FRAME WITH BONDING CONNECTOR.

EXISTING EXHAUST FAN (TYP.)

NEW CATWALK SYSTEM (TYP.)

34 5

34 5

LIGHTNING PROTECTION SYSTEM NOTES:

1. ALL WORK SHALL BE IN COMPLIANCE WITH NFPA 780.

2. ALL MATERIALS SHALL BE IN COMPLIANCE WITH NFPA 780 AND UL 96.

3. ALUMINUM ROOF CONDUCTORS SHALL BE 98,600 CIRCULAR MILS WITH A MINIMUM STRANDING OF

14 AWG, AND A WEIGHT OF 95 LBS./1000 FEET. CONDUCTORS SHALL BE ATTACHED TO THE ROOF

WITH CABLE CLAMPS LOCATED 3'-0" ON CENTER (MAXIMUM).

3. WIRE TO WIRE CONNECTORS SHALL BE IN ACCORDANCE WITH DETAILS SHOWN ON THIS SHEET.

4. BONDING CONNECTORS SHALL BE IN ACCORDANCE WITH DETAILS SHOWN ON THIS SHEET.

5. ROOF CONDUCTOR BENDS SHALL BE MADE WITH A MINIMUM RADIUS OF 8".

DETAIL - BONDING CONNECTOR

N.T.S.

5/8" MOUNTING HOLE FOR

MECHANICALLY SECURING

PLATE TO EQUIPMENT

(TYP. OF 2 PER PLATE)

ALUMINUM BONDING PLATE - 3 SQ.

INCH CONTACT SURFACE.

ALUMINUM ROOF CONDUCTOR

BOILER FLUE

DETAIL - WIRE TO WIRE CONNECTIONS

N.T.S.

PARALLEL CONNECTORCROSS RUN CONNECTOR

ALUMINUM ROOF CONDUCTOR

ALUMINUM CONNECTOR

ALUMINUM CONNECTOR

ALUMINUM ROOF CONDUCTOR

ALUMINUM ROOF CONDUCTOR

PENSACOLA, FLORIDA 32502

75 SOUTH "F" STREET

01 FTFA 13-9005 T001
02 FTFA 13-9005 S001
03 FTFA 13-9005 S100
04 FTFA 13-9005 S101
05 FTFA 13-9005 S102
06 FTFA 13-9005 S103
07 FTFA 13-9005 S301
08 FTFA 13-9005 AD101
09 FTFA 13-9005 AD102
10 FTFA 13-9005 A101
11 FTFA 13-9005 A102
12 FTFA 13-9005 A103
13 FTFA 13-9005 A301
14 FTFA 13-9005 A401
15 FTFA 13-9005 I101
16 FTFA 13-9005 I102
17 FTFA 13-9005 I103
18 FTFA 13-9005 I104
19 FTFA 13-9005 P101
20 FTFA 13-9005 P102
21 FTFA 13-9005 M001
22 FTFA 13-9005 M101
23 FTFA 13-9005 M102
24 FTFA 13-9005 M111
25 FTFA 13-9005 M121
26 FTFA 13-9005 M401
27 FTFA 13-9005 M402
28 FTFA 13-9005 M501
29 FTFA 13-9005 M502
30 FTFA 13-9005 M503
31 FTFA 13-9005 M504
32 FTFA 13-9005 M601
33 FTFA 13-9005 M602
34 FTFA 13-9005 M701
35 FTFA 13-9005 M702
36 FTFA 13-9005 M703
37 FTFA 13-9005 M704
38 FTFA 13-9005 M705
39 FTFA 13-9005 E1
40 FTFA 13-9005 E2
41 FTFA 13-9005 E3
42 FTFA 13-9005 E4
43 FTFA 13-9005 E5
44 FTFA 13-9005 E6
45 FTFA 13-9005 E7

File details come from the government source that posted it. Updated .