FA255024Q0024_Delta 8 B300 SST COOP Conduit Install_QnA.xlsx

XLSX spreadsheet 13 KB Posted

Attached to
Delta 8 B300 Conduit Install
Solicitation number
FA255024Q0024
Issued by

About this file

This document is a Question and Answer (Q&A) sheet related to the Solicitation Number FA255024Q0024 for the Delta 8 B300 Conduit Install project. The project requires the installation of (2) 2" rigid conduits with sealed fittings, approximately 250 feet of 2" x 4" wire basket tray, a ground system, and (3) wall-mounted cabinets with fiber optic LIUs. It also includes the procurement of necessary equipment and cleanup/trash removal. The Q&A addresses various requirements and specifications, such as the preferred conduit and grounding system, raceway sizes, wall penetrations, staging areas, and cabinet details. No wage determination or weekly certified payroll reports are required for this project. The Q&A sheet indicates that all answers will be posted to the solicitation on SAM.gov on July 24, 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

FA255020Q0024 Delta 8 B300 SST COOP Conduit Install
QUESTIONSDate ReceivedANSWERS
1. Are pathways to be used free, straight, and clear for the to-be-installed PDS and cable trays?18-JulAssume no, You were given the opprotunity to inspect above the ceilings during the site walk.
2. Is there a requirement to weld, compression seal, or chemically seal the PDS?18-JulChemically seal is prefered
3. Is there an existing building ground to be tied to?18-JulYes in the electrical room
4. Are wall penetrations already installed? If not, we need wall type details, such as standard drywall, Kane screened, SCIF rated ....18-JulStandard drywall metal studs
5. Will answers to all questions be posted to bidders?18-JulYes, answers will be posted to the solicitation on SAM.gov on Wednesday, 24 July, 2024
6. Are there is requirement to cable each workstation pictured in the provided documentation.18-JulNo that is being taken care of separately
7. Requirements/Purpose: “Installation of (2) 2” rigid conduit with sealed fittings”. Is Rigid Conduit with epoxy sealed fittings acceptable for this requirement?18-JulYes
8. It the 2” rigid conduit above or below the drop ceiling in the hallway?18-JulAbove
9. Requirements/Purpose: “Installation of ground system to include convenance, ground bar, and grounding of pathways” Can the government please explain the ground system – wire size, location, connect to building steel, water pipe, etc.18-JulThe expectation is the installer will determine the design of the ground system to meet the appropriate need and building code standards. This cable tray will be housing CAT5 and CAT6 Plenum rated cable based on the room layouts referenced in the SOW. My understanding is the ground system will be connected to building steel inside the electrical room located on the south east side of the building.
10. Can the government please provide information on the (3) wall-mounted cabinets? Make, model, etc.18-JulYes locking and yes swinggate. Please see attached spec sheet for dimentions.
11. Can the government provide raceway size from cabinets to cable trays?18-Jul4inch width is acceptable
12. Paragraph 4.3 - is this the only requirement on this project? Are all other paragraphs part of a different solicitation?18-JulParagraph 4.3 is not the only requirement. You will abide by the entire SOW.
13. Is there a current Wage Determination for use with this project?18-JulNo, there is not.
14. Are weekly certified payroll reports required?18-JulNo, they are not required
15. What is the preferred path of travel for fiber to individual rooms?18-JulThrought the PDS into apporpriate raceway and cable manegment
16. Can we receive pictures above the tiles to discern if the space is congested in each room?18-JulAssume congestion, no pictures are authorized. You were given the opprotunity to inspect above the ceilings during the site walk.
17. Is it preferred to have the cable tray above or below the tiles to facilitate the drops?18-JulAbove the ceiling as it will conflict with modular wall.
18. Is the preference to hammer drill a cable tray or is it preferred to have it anchored? Any noise constraints?18-JulNo noise constraint. No preference
19. Will a staging area be assigned for the materials?18-JulRoom 242, 243, 246, and 248 can all be used for staging
20. Specifications on the cabinets -will it require locking mech and or swing gate?18-JulYes locking and yes swinggate. Please see attached spec sheet for dimentions.

File details come from the government source that posted it. Updated .