This document contains a solicitation for a federal contract opportunity to replace three mission essential systems in a Central Utility Plant building. The 50th Civil Engineer Squadron is seeking proposals to: replace transformers and associated equipment in the transformer yard; replace eight roof mounted exhaust fans and louvers; and replace obsolete generator synchronizers, load controllers, PLC based generator controller, and generator operator HMI computer and programming. The solicitation number is FA255019RA010 and opportunity type is a solicitation from the Department of the Air Force Space Command for replacement of systems in building 600 to support mission essential power generation capabilities.
Manual Mode B600
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRANSFER LOAD TO UTILITY/STOP GENERATORS IN
MANUAL MODE
CENTRAL UTILITY PLANT (B600)
STEP 1: CLOSE “M”/”N” Feeder Breaker Switchgear A on U2SA/U2SA1
STEP 2: CLOSE “B” Feeder Breaker Switchgear B on U2SB
STEP 3: PLACE Utility Selector Switch to “AA” or “BB”
***NOTE: Generators will start matching with commercial power then
Breaker Control Switch 52-U2M1/52-U1M1 will CLOSE
STEP 4: LOWER MASTER IMPORT CONTROL Switch to remove power off the generators and onto utility. Once power is lower than 200kw TRIP all Breaker Control
Switches 52-G1 through 52-G7
STEP 5: PLACE all ENGINE CONTROL SWITCHES to AUTO
STEP 6: PLACE all SYNCHRONIZED LOAD SELECTOR Switches to AUTO
***NOTE: After a 5-15 minute cool down, generators will automatically shut down
STEP 7: OPEN FEEDER Breakers CB-GSB and CB-GSA/CB-GSA1
NOTIFY ATCC THAT THE BASE IS NOW ON UTILITY POWER
STEP 8: Conduct Post-OP inspection of all generators
21 August 2019