This solicitation from the 50th Civil Engineer Squadron seeks proposals to replace three mission essential systems at building 600 of the Central Utility Plant. The contractor will be required to: replace six existing transformers, common generator grounding resistor, and interconnecting lines in the transformer yard; replace eight roof mounted exhaust fans connected to seven wall louvers controlled by thermostats in the power generation area; and replace existing obsolete Woodward synchronizers, load controllers, generator controller, and generator operator HMI computer and programming. The solicitation is seeking these replacements to ensure continued power generation capabilities at the facility. The Department of the Air Force Space Command is the issuing agency.

RFI 003 Answers

View the file

Other files

File Type Posted
4 B600 Upgrade drawing.pdf PDF
1 Solicitation Amendment - FA255019RA0100001.pdf PDF
2 GLEN18-1101_SOW_06Jan2020.pdf PDF
3 18-1101 RFI 005.pdf PDF
5 WD_CO20200002_ 01-03-2020.pdf PDF
RFI_004.pdf PDF
MCC-1_AE_Comments.pdf PDF
3_-_Design_Drawings_PDF_Exhaust_Fans_AE_Comments.pdf PDF
RFI_002.pdf PDF
GLEN_18-1107_SOW_Addendum_2.pdf PDF
GLEN_18-1107_SOW_Addendum.pdf PDF
RFI_001_18-1101_Answered.pdf PDF
Transformer_Pad.pdf PDF
Binder1RS1.pdf PDF
Exhaust_Fans_Electrical_One_Line.pdf PDF
Transfer_to_emergency_(with_load)_in_Manual_Mode_B600_2019.pdf PDF
Sign_In_Sheet.pdf PDF
Site_Visit_MFR.pdf PDF
Transfer_to_commercial_(with_load)_in_Manual_Mode_B600_2019.pdf PDF
7_-_GLEN18-1101_AF_66_Form.xls XLS spreadsheet
3_-_Design_Drawings_PDF_Exhaust_Fans.pdf PDF
0_-_GLEN18-1101_SOW_10July19.pdf PDF
9_Wage_Determination.pdf PDF
4_-_Design_Drawings_PDF_Transformers_Replacement(RS).pdf PDF
5_-_Design_Guide_Version_March_2017.pdf PDF
00_Solicitation_-_FA255019RA010.pdf PDF
1_-_01_55_04_-_SAFB_Security_Requirements.pdf PDF
2_-_Design_Analysis_Exhaust_Fans_Redacted(RS).pdf PDF
8_-_SOW_Environmental_Supplement.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GLEN 18-1101 B600 Upgrade RFI 003

Exhaust Fan drawing E-201 - Combine empty space between G and K into K on MCC-3, to make K larger. MCP breaker is acceptable, and control voltage will need to be confirmed on site.

MCC-1 AE - Recommend that space A of 02F be used as well to make room. I and K of 06F would appear to be spares for A C E or G of 06F.