Amend 03 Atch 2B Revised Electrical (8 Sep 21).pdf
PDF 2 MB Posted
- Solicitation number
- FA252121B0007
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL ELECTRICAL CONSTRUCTION/INSTALLATION MUST BE IN
ACCORDANCE WITH NFPA 70, 70E AND UFC 3-501-01.
2. ALL CONSTRUCTION WILL BE GOVERNED BY THE PLANS,
SPECIFICATIONS, AND ALL APPLICABLE BUILDING AND SAFETY CODES,
LAWS, AND ORDNANCES.
3. CONTRACTOR MUST BE FAMILIAR WITH THE SITE, THE WORK
REQUIRED, THE CUSTOMER'S WORK PROCEDURES, AND ALL OTHER
CONDITIONS THAT MAY AFFECT THE SUCCESSFUL COMPLETION OF THE
JOB PRIOR TO COMMENCEMENT OF WORK.
4. FIELD LOCATE ALL EXISTING UTILITIES AS TO LOCATION AND
ELEVATION. NOTIFY THE CONTRACTING OFFICER OF ANY AND ALL
CONFLICTS PRIOR TO BEGINNING CONSTRUCTION.
5. ALL SPECIFIC MATERIALS AND PRODUCTS IDENTIFIED IN THE PLANS
ARE INCLUDED AS THE BASIS OF DESIGN. CONTRACTOR MAY SUBMIT
EQUIVALENT PRODUCTS IN COMPLIANCE WITH THE PROJECT
SPECIFICATIONS FOR APPROVAL INSTEAD OF THOSE SPECIFIED.
6. SEAL ALL NEW PENETRATIONS IN WALL ASSEMBLIES WITH UL RATED
AND APPROVED SEALANT TO MATCH WALL ASSEMBLY RATING.
REFERENCE ARCHITECTURAL PACKAGE FOR DETAILS.
7. ALL NEW CONDUIT MUST BE MINIMUM 3/4 INCH.
8. ALL NEW INTERIOR CONDUIT MUST BE EMT UNLESS OTHERWISE
NOTED.
9. ALL NEW EXTERIOR ABOVE GROUND CONDUIT MUST BE RGS UNLESS
OTHERWISE NOTED. ALL NEW EXTERIOR UNDERGROUND CONDUIT
MUST BE SCHEDULE 40 PVC UNLESS OTHERWISE NOTED, TRANSITIONS
FROM UNDERGROUND CONDUIT TO ABOVE GROUND CONDUIT MUST BE
MADE USING PVC TO RGS TRANSITION ELBOWS.
10. ALL NEW ELECTRICAL CONDUCTORS INSTALLED MUST BE COPPER,
INSULATION TYPE THHN-THWN-2 UNLESS OTHERWISE NOTED.
11. ROUTE ALL NEW CIRCUITS UNDER RAISED FLOOR TO GREATEST
EXTENT PRACTICABLE. MOUNT CONDUITS UNDER RAISED FLOOR TO
STRUT SUPPORTS.
12. LABEL ALL RECEPTACLES AND END APPLIANCES WITH SUPPLY PANEL
AND CIRCUIT NUMBER.
13. REFER TO PANEL SCHEDULES INCLUDED IN THIS DRAWING SET FOR
BRANCH CIRCUIT, BREAKER, CONDUCTOR AND CONDUIT INFORMATION .
14. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS AND
RACEWAYS INSTALLED AS PART OF THIS PROJECT.
15. ENSURE ALL NEW/MODIFIED PANELBOARDS RECEIVE NEW, TYPED
PANEL SCHEDULES REFLECTING AS-BUILT CONDITIONS. INSTALL PANEL
SCHEDULES ON THE INSIDE OF THE PANEL DOOR OR IN A SIMILAR
CONSPICUOUS LOCATION.
16. CONTACTOR MUST REPAIR ALL DAMAGE DONE TO ZINC COATING.
GENERAL NOTES:
1. DE-ENERGIZE ALL ITEMS TO BE DEMOLISHED OR REMOVED. PERFORM
LOCKOUT/TAGOUT IN ACCORDANCE WITH OSHA 29 CFR 1910.147 AND
NFPA 70E.
2. CONTRACTOR MUST TAKE NECESSARY PRECAUTIONS AND PROVIDE
PROTECTION AS REQUIRED TO PRESERVE CONDITION OF EXISTING
UTILITIES, EQUIPMENT, FURNISHINGS, AND SURFACES NOT INDICATED
FOR REMOVAL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO WORK
AROUND THE EXISTING CONDITIONS TO ACCOMPLISH THE WORK.
3. COVER ALL OPENINGS OR PENETRATIONS IN ELECTRICAL ENCLOSURES
RESULTING FROM DEMOLITION ACTIVITIES WITH METAL PLUGS
MANUFACTURED FOR THAT PURPOSE.
4. SEAL ALL WALL PENETRATIONS RESULTING FROM DEMOLITION
ACTIVITIES WITH UL RATED AND APPROVED SEALANT TO MATCH
WALL ASSEMBLY RATING.
GENERAL NOTES - DEMOLITION:
29 CFR 1926 OSHA STANDARDS FOR CONSTRUCTION
NFPA 70 NATIONAL ELECTRICAL CODE, 2020
NFPA 70E STANDARDS FOR ELECTRICAL SAFETY, 2018
NFPA 90A STANDARDS FOR THE INSTALLATION OF AIR-CONDITIONING
AND VENTILATING SYSTEMS, 2018
UFC 3-501-01 UNIFIED FACILITIES CRITERIA, ELECTRICAL ENGINEERING
UFC 3-520-01 UNIFIED FACILITIES CRITERIA, INTERIOR ELECTRICAL
SYSTEMS
45 SWI 17-213 45TH SPACE WING INSTRUCTION, COMMUNICATION ROOMS
INSTALLATION STANDARDS
CODES AND STANDARDS:
1. REPLACE CURRENT INTERIOR LIGHTING WITH LED DAYLIGHT TYPE
LIGHTING AND DESIGN LIGHTING PLAN FOR BUILDING EXTERIOR AND
NEW ADDITIONS.
2. PROVIDE POWER SUPPLY FOR GARAGE DOORS ELECTRIC MOTORS, AIR
CURTAINS, WATER HEATERS AND A/C.
SCOPE OF WORK:
1. SUPPLY AND INSTALL MELAMINE PLASTIC LABELS SHOWN BELOW AND
IN ACCORDANCE WITH SPECIFICATIONS 26 05 00.00 40.
2. LABELS SHALL BE PROVIDED WITH A BLACK BACKGROUND AND WHITE
LETTERS.
3. LABELS SHALL BE AFFIXED TO EQUIPMENT VIA SCREWS.
4. LABEL EXAMPLES BY EQUIPMENT TYPE SHOWN BELOW.
EQUIPMENT LABELING:
ABBREVIATIONS:
A AMPERE
AFF ABOVE FINISHED FLOOR
AWG AMERICAN WIRE GAUGE
CKT CIRCUIT
COMM COMMUNICATIONS
CU CONDENSING UNIT
DC DIRECT CURRENT
DIA DIAMETER
DOA DEDICATED OUTSIDE AIR UNIT
ECB ENCLOSED CIRCUIT BREAKER
EMT ELECTRO METALLIC TUBING
EPR ETHYLENE-PROPYLENE RUBBER
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
FC FOOT CANDLES
FCU FAN COIL UNIT
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
HZ HERTZ
INTG INTEGRATED
KAIC THOUSAND AMPS INTERRUPTING CURRENT
KCMIL THOUSAND CIRCULAR MILLS
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUG ONLY
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
P POLE
PNL PANEL
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RGS RIGID GALVANIZED STEEL
SCH SCHEDULE
SS STAINLESS STEEL
SPD SURGE PROTECTION DEVICE
SWBD SWITCHBOARD
THHN THERMOPLASTIC HIGH HEAT RESISTANT NYLON
THWN-2 THERMOPLASTIC HEAT AND WATER RESISTANT NYLON
TMGB TELECOMMUNICATIONS MAIN GROUND BAR
TYP TYPICAL
UL UNDERWRITER'S LABORATORIES
USAF UNITED STATES AIR FORCE
V VOLT
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
W WATT
XFMR TRANSFORMER
POWER/LIGHTING LEGEND:
HOME RUN TO PANEL AND CIRCUIT AS NOTED
(PNL)-(CKT)
120V, 20 AMP DUPLEX RECEPTACLE
EXISTING PANELBOARD
SINGLE POLE, 120V, 20 AMP LIGHT SWITCH
FIXTURE F - RED LED EXIT LIGHT WITH EMERGENCY LAMPS, WALL MOUNTED
(HATCHING DENOTES ILLUMINATED FACE DIRECTION)
FIXTURE A - 48-INCH X 20-INCH, HIGH BAY LIGHT FIXTURE
FIXTURE A - 48-INCH X 20-INCH, HIGH BAY LIGHT FIXTURE
WITH BATTERY PACK
PNL XXX
S
3 120V, 20 AMP 3-WAY SWITCHS
120V, 20 AMP GFCI DUPLEX RECEPTACLEGFCI
E 12 X 4 INCH BY 1/4 INCH THICK COPPER GROUND PLATE,
WALL MOUNTED
120V, 20 AMP GFCI SIMPLEX RECEPTACLE FOR
INSTANTANEOUS ELECTRIC WATER HEATER
EWH
120V, 20 AMP GFCI DUPLEX RECEPTACLE FOR
ELECTRIC WATER COOLER
EWC
M
TWO POLE, 240VAC, 20A, MOTOR RATED TOGGLE SWITCHS
EXIT
4 120V, 20 AMP 4-WAY SWITCHS
FIXTURE G - 26-INCH X 7-INCH, LED FIXTURE
FIXTURE G - 26-INCH X 7-INCH, LED FIXTURE WITH BATTERY PACK
208V, 30 AMP, 4P, NEMA L18-30R RECEPTACLE
208V, 30 AMP, 2P, NEMA L6-30R RECEPTACLE
FIXTURE D - 2-FOOT X 2-FOOT, LED LIGHT FIXTURE
FIXTURE D - 2-FOOT X 2-FOOT, LED LIGHT FIXTURE
WITH BATTERY PACK
FIXTURE C - 6-INCH CAN LED LIGHT FIXTURE WITH
FIXTURE C - 6-INCH CAN LED LIGHT FIXTURE WITH BATTERY PACK
FIXTURE E - 10-INCH X 9-INCH, LED FLOODLIGHT
120V, 20 AMP GFCI DUPLEX RECEPTACLE WITH
IN-USE WEATHERPROOF COVER
WP
G
COUNTERPOISE
GROUND TEST WELL
LIGHTNING PROTECTION CONDUCTOR
AIR TERMINAL
DOWN CONDUCTOR
3-WP
120V, 20 AMP 3-WAY SWITCH MOUNTED IN SST NEMA 4X WEATHERPROOF ENCLOSURES
DISCONNECT SWITCH
A
A
D
D
C
C
E
G
G
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N O
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri to
A
C
H
I T
E
S
T H
S P
A C
E W
IN
G
C C
A F
S F
L
A s i n d ic a te d
/8
/2
:5
:0
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-001
E L
E C
T R
IC
A
L G
E N
E R
A L
N O
T E
S
L E
G E
N D
A N
D A
B B
R E
V
IA
T
IO
N S
D B
E H
-1
E -0
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
D/S CU-1 - 240VAC
FED FROM
PANEL-LP2 CKT 13,15
PANEL-LP2
120/208VAC
FED FROM
PANEL-LP CKT 17,19,21
FIXTURE ID LOCATION MANUFACTURER MODEL # FIXTURE TYPE MOUNTING WATTAGE VOLTAGE
A INTERIOR HIGH BAY COOPER HBLED-LD5-12SE-W-UNV-L850-ED1-U 48" X 20" LED HIGH BAY FIXTURE PENDANT 77 UNV
A INTERIOR HIGH BAY COOPER HBLED-LD5-12SE-W-UNV-L850-EL14W-ED1-U 48" X 20" LED HIGH BAY FIXTURE WITH BATTERY PACK PENDANT 77 UNV
B
C INTERIOR BATHROOM COOPER HC610D010-HM612935-61MDH 6" LED FIXTURE RECESSED 10.1 UNV
C INTERIOR BATHROOM COOPER HC610D010REM14-HM612935-61MDH 6" LED FIXTURE WITH BATTERY PACK RECESSED 10.1 UNV
D INTERIOR OFFICE COOPER 22ID-30-CFD1-L850-U 2'X2' LED FIXTURE RECESSED 24.2 UNV
D INTERIOR OFFICE COOPER 22ID-30-CFD1-EL14W-L850-U 2'X2' LED FIXTURE WITH BATTERY PACK RECESSED 24.2 UNV
E EXTERIOR CGF DESIGN INC AM-9-WT-LED25-AMB-UNV-BK 10"X9"X9" LED AMBER FIXTURE WALL 25 UNV
F INTERIOR COOPER APC7RSQ 20-5/16" X 5-5/8" LED EXIT AND EMERGENCY LIGHTS WALL 3.7 UNV
G INTERIOR STORAGE COOPER 2VT2-LD5-2-DR-UNV-L850-CD1-WL-U 26" X 7" LED FIXTURE SURFACE 17 UNV
G INTERIOR STORAGE COOPER 2VT2-LD5-2-DR-UNV-EL14W-L850-CD1-WL-U 26" X 7" LED FIXTURE WITH BATTERY PACK SURFACE 17 UNV
LIGHTING FIXTURE SCHEDULE
NOT USED
MARK DESCRIPTION DATE APPR
A REMOVAL OF CLIN2 BID OPTION 05/27/21 SJ
B AURAL WARNING SYSTEM REMOVAL AND TELECOMM
GROUND BUS ADDITION
09/08/21 SJ
B
1 2 3 654
B
A.3
A.6
EXISTING EDGE OF PAVEMENT
EXISTING TEMPORARY
ELECTRICAL PANEL
EXISTING A/C PAD
DISCONNECT SWITCH A/C-1 (ETR)
5 PANEL LP (ETR)
MAIN DISCONNECT SWITCH (ETR)
1 2 3 654
A
B
A.3
A.6
EXISTING EDGE OF PAVEMENT
PA EQ. CABINET (ETR)
SPD (ETR)
COMM CABINET (ETR)
SPD (ETR)
COMM CABINET (ETR)
COMM RACK (ETR)
1 2 3 654
A
B
A.3
A.6
6 7
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
/8
/8
/2
:5
:2
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
ED-101
E L
E C
T R
IC
A
L D
E M
O L
IT
IO
N P
L A
N
D B
E H
-1
E D
-1
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
1/8" = 1'-0"ED-101
B2 ELECTRICAL DEMOLITION PLAN
PLAN NORTH
KEY NOTES:
1. DEMOLISH ALL INTERIOR AND EXTERIOR LIGHTING CIRCUITS INCLUDING
FIXTURES, SWITCHES, CONDUCTORS AND CONDUITS BACK TO SOURCE
PANELBOARDS. PRESERVE FLOOD LIGHTS CONDUIT FOR REUSE.
2. DEMOLISH RECEPTACLES SPECIFIED IN THIS SHEET INCLUDING DEVICE,
CONDUCTORS AND CONDUIT BACK TO SOURCE.
3. DEMOLISH EXISTING 208V, 1PH PANELBOARD SUPPLYING BATHROOM
TRAILER INCLUDING ALL CONDUCTORS AND CONDUIT BACK TO SOURCE.
4. PRESERVE EXISTING COMM CABINETS AND RACK, P/A EQUIPMENT, SURGE
PROTECTION DEVICES, MAIN DISCONNECT SWITCH AND PANEL LP WITH
CABLES AND CONDUITS.
5. EXISTING LOADS IN PANEL LP IDENTIFIED BELOW TO REMAIN. CIRCUIT AND
LOADS IDENTIFIED BELOW ARE BASED ON EXISTING PANEL SCHEDULES,
FIELD VERIFY CIRCUITS AND LOCATIONS. COORDINATE ADDITIONAL CIRCUITS
TO REMAIN WITH CONTRACTING OFFICER PRIOR TO DEMOLITION:
A. CKT 2: W. RECEPTACLE
B. CKT 4: RECEPTACLE
C. CKT 7: UPS ESS
D. CKT 8: P/A SYSTEM
E. CKT 9: SEC ACCESS
F. CKT 12: N. RECEPTACLE
G. CKT 18/20/22: AIR CONDITIONER SYSTEM
H. CKT 24/26/28: SPD???
04 8 16268
SCALE: 1/8"=1'-0"
6. DEMOLISH ALL COMPONENTS ASSOCIATED WITH THE LIGHTNING
PROTECTION SYSTEM AND COUNTERPOISE IN THEIR ENTIRETY. THIS
INCLUDES DOWN CONDUCTORS AND ANY THRU-ROOF POINTS OF
CONNECTION. FACILITY GROUND PLATES AND DOWNSTREAM EQUIPMENT
CONNECTIONS SHALL REMAIN. CONFIRM EXISTING SYSTEM POINTS OF
CONNECTION PRIOR TO DEMOLITION.
7. DEMOLISHED EXISTING EXTERIOR AURAL WARNING SYSTEM SPEAKERS
INCLUDING CONDUIT AND CONTUCTORS.
MARK DESCRIPTION DATE APPR
REF.
EWH
E W
C
E W
H
1 2 3 654
A
B
A.3
A.6
OFFICE
GARAGE
STORAGE
TOILET
SHOWER
104B
HALL
CU-1
FCU-2
EF-1
EF-2
FCU-1
DOOR 2 OPERATOR
MOTOR UNIT
DOOR 3 OPERATOR
MOTOR UNIT
MAIN DISCONNECT SWITCH (ETR)
PA EQ. CABINET (ETR)
SPD (ETR)
PANEL LP (ETR)
COMM CABINET (ETR)
COMM RACK (ETR)
SPD (ETR)
COMM CABINET (ETR)
(PNL LP) - (30,32)
(PNL LP) - (29,31)
(PNL LP2) - (13,15)
PANEL LP2
DISCONNECT SWITCH CU-1
(PNL LP2) - (1)
(PNL LP2) - (3)
(PNL LP2) - (7)
(PNL LP) - (38,40,42)
BATTERY CHARGER8
E
GROUNDING BUSBAR (ETR)
E
GROUNDING
BUSBAR (ETR)
E
GROUNDING
BUSBAR (ETR)
E TGB
GROUNDING BUSBAR (ETR)
NEW TGB 9
B
B
B
B
B
A
B
A.3
A.6
MEZZANINE RAILING
STORAGE
TWH-1
(PNL LP2) - (5)
DISCONNECT SWITCH
TWH-1
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
/8
/8
/2
:5
:0
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-102
E Q
U
IP
M E
N T
P L
A N
D B
E H
-1
E -1
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
PLAN NORTH
04 8 16268
SCALE: 1/8"=1'-0"
KEY NOTES:
1. INSTALL NEW 100A, 208/120VAC, 10 KAIC, MCB, SURFACE MOUNTED
PANELBOARD "LP2". SUPPLY NEW PANELBOARD FROM BRANCH CIRCUIT
BREAKER IN PANELBOARD "LP".
2. INSTALL NEW 2P, MINIMUM 240VAC, 10A, HEAVY-DUTY RATED DISCONNECT
SWITCH TO SUPPLY NEW GARAGE DOOR 2 OPERATOR.
3. INSTALL NEW 2P, MINIMUM 240VAC, 10A, HEAVY-DUTY RATED DISCONNECT
SWITCH TO SUPPLY NEW GARAGE DOOR 3 OPERATOR.
4. INSTALL NEW 2P, MINIMUM 240VAC, 20A, HEAVY-DUTY RATED DISCONNECT
SWITCH IN NEMA 4X SST ENCLOSURE TO SUPPLY NEW CU-1.
5. INSTALL NEW 2P, MINIMUM 240VAC, 20A, MOTOR RATED TOGGLE SWITCH IN
SINGLE GANG BOX AS LOCAL MEANS OF DISCONNECT AT EACH FCU.
6. PROVIDE 120V, 20 AMPS, LOCK-ON BREAKER TO SUPPLY FIRE ALARM
CONTROL PANEL IN ACCORDANCE WITH UFC 3-320-01.
7. INSTALL NEW 1P, MINIMUM 120VAC, 20A, HEAVY DUTY RATED DISCONNECT
SWITCH TO SUPPLY NEW TANKED ELECTRIC WATER HEATER.
8. INSTALL IMPAQ BATTERY CHARGER, P/N EI3-KP-4G AS MANUFACTURED BY
ENERSYS, AT 4'-0" AFF. REFERENCE OWNER'S MANUAL FOR MOUNTING
DETAILS. CONTRACTOR TO COORDINATE #3/0 DC CABLING LENGTH WITH
OWNER.
9. INSTALL NEW 12 X 2 INCH X 1/4 INCH THICK COPPER TELECOMMUNICATIONS
GROUNDING BUSBAR (TGB) ERICO MODEL# TGBA12L06P OR APPROVED
EQUAL USING INSULATED MOUNTING BRACKETS. LOCATION SHOWN IS
NOTIONAL, COORDINATE SPECIFIC INSTALLATION LOCATION WITH
CONTRACTING OFFICER. BOND NEW TGB TO EXISTING FACILITY GROUND
BUSBAR USING TWO HOLE COMPRESSION LUGS AND #3/0 AWG BARE
COPPER CONDUCTOR. BOND EXISTING COMMUNICATIONS RACK AND
CABINET TO NEW TGB USING TWO-HOLE COMPRESSION LUGS AND #6 AWG
COPPER CONDUCTORS WITH GREEN INSULATION.
GENERAL NOTES:
1. REFER TO PANEL SCHEDULES ON SHEETS E-701 FOR CIRCUIT BREAKER,
BRANCH CONDUCTOR AND CONDUIT INFORMATION.
2. COORDINATE FINAL LOCATION AND HEIGHT OF DEDICATED RECEPTACLES
FOR ELECTRIC WATER HEATERS AND ELECTRIC WATER COOLER WITH
PLUMBING CONTRACTOR.
3. BOND NEW PANELBOARD GROUND BUS TO EXISTING GROUND PLATE USING
#4/0 AWG BARE COPPER CONDUCTOR.
1/8" = 1'-0"E-102
B1 GROUND LEVEL EQUIPMENT PLAN
1/8" = 1'-0"E-102
B4 MEZZANINE LEVEL EQUIPMENT PLAN
PLAN NORTH
MARK DESCRIPTION DATE APPR
A REMOVAL OF CLIN2 BID OPTION 05/27/21 SJ
B AURAL WARNING SYSTEM REMOVAL AND TELECOMM
GROUND BUS ADDITION
09/08/21 SJ
GFCI
1 2 3 654
A
B
A.3
A.6
OFFICE
GARAGE
STORAGE
TOILET
SHOWER
104B
HALL
(PNL LP) - (4)
RECEPTACLE
(ETR)
(PNL LP) - (2)
RECEPTACLE
(ETR)
MAIN DISCONNECT SWITCH (ETR)
PA EQ. CABINET (ETR)
SPD (ETR)
RECEPTACLE
(ETR)
(PNL LP2) - (19,21,23)
(PNL LP2) - (25,27)
(PNL LP2) - (10)
GFCI
(PNL LP2) - (4)
(PNL LP2) - (18)
(PNL LP2) - (2)
(PNL LP2) - (8)
(PNL LP2) - (6)
(PNL LP2) - (20,22,24)
(PNL LP2) - (26,28)
(PNL LP) - (12)
PANEL LP (ETR)
COMM CABINET (ETR)
COMM RACK (ETR)
SPD (ETR)
COMM CABINET (ETR)
B
B
B
B
A
B
A.3
A.6
MEZZANINE RAILING
STORAGE
(PNL LP2) - (17)
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
/8
/8
/2
:5
:1
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-103
P O
W E
R P
L A
N
D B
E H
-1
E -1
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
1/8" = 1'-0"E-103
C1 GROUND LEVEL POWER PLAN
1/8" = 1'-0"E-103
C4 MEZZANINE LEVEL POWER PLAN
04 8 16268
SCALE: 1/8"=1'-0"
KEY NOTES:
1. INSTALL NEW 120V, 20 AMP DUPLEX GFCI RECEPTACLE 6 INCHES
ABOVE COUNTER TOP.
2. COORDINATE WITH FIRE PROTECTION TO RELOCATE RECEPTACLE
WITH A MINIMUM CLEARANCE OF THREE (3) FEET FROM FIRE RISER.
GENERAL NOTES:
1. REFER TO PANEL SCHEDULES ON SHEETS E-701 FOR CIRCUIT
BREAKER, BRANCH CONDUCTOR AND CONDUIT INFORMATION.
2. SURFACE MOUNT ALL NEW RECEPTACLES ON CONCRETE WALLS.
FLUSH MOUNT RECEPTACLES ON GYPSUM WALLS.
PLAN NORTH PLAN NORTH
MARK DESCRIPTION DATE APPR
A REMOVAL OF CLIN2 BID OPTION 05/27/21 SJ
B AURAL WARNING SYSTEM REMOVAL AND TELECOMM
GROUND BUS ADDITION
09/08/21 SJ
B
A.3
A.6
EDGE OF ROOF
G
G
G
G
TYP.
TYP.
TYP.
TYP.
BUILDING 35420
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
/8
/8
/2
:5
:1
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-104
L
IG
H T
N
IN
G P
R O
T E
C T
IO
N
A N
D G
R O
U N
D
IN
G P
L A
N
D B
E H
-1
E -1
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
GENERAL NOTES:
1. GROUND RODS SHALL BE 3/4 INCH DIAMETER, 10 FOOT LENGTH SOLID
COPPER RODS CONFORMING TO A-A-55804, TYPE II, CLASS B RODS.
GROUND RODS SHALL BE DRIVEN TO A DEPTH OF AT LEAST 10 FEET WITH
THE TOP OF THE GROUND ROD NOT LESS THAN 18 INCHES BELOW
FINISHED GRADE. SEE GROUND ROD DETAIL ON SHEET E-501.
2. EACH DOWN CONDUCTOR SHALL BE INSTALLED IN SCH 80 PVC CONDUIT
FROM 12 INCHES BELOW GRADE TO 72 INCHES ABOVE GRADE.
3. BOND STRUCTURAL FOUNDATION REBAR TO COUNTERPOISE IN
COMPLIANCE WITH NEC ARTICLE 250.52. REUSE EXISTING COPPER
CONDUCTORS WHERE POSSIBLE.
4. BOND FACILITY GROUND BARS TO NEW FACILITY COUNTERPOISE UTILIZING
EXISTING COPPER CONDUCTORS WHERE POSSIBLE.
5. THE INTENT OF THIS DRAWING IS TO PROVIDE THE FACILITY WITH A NEW
COUNTERPOISE AND LIGHTNING PROTECTION SYSTEM. FIELD CONFIRM
EXISTING LIGHTNING PROTECTION AND COUNTERPOISE SYSTEM POINTS OF
CONNECTION PRIOR TO DEMOLITION. REESTABLISH ALL OTHER EXISTING
CONNECTION POINTS NOT DEPICTED ON THIS SHEET.
KEY NOTES:
1. INSTALL NEW #4/0 AWG BARE COPPER COUNTERPOISE SYSTEM AT A
MINIMUM DEPTH OF 18 INCHES BELOW FINISHED GRADE AND BETWEEN 24
AND 72 INCHES FROM FOUNDATION.
2. INSTALL GROUND RODS AND EXOTHERMICALLY WELD TO THE
COUNTERPOISE AT DISTANCES NOT LESS THAN 20 LINEAR FEET NOR
GREATER THAN 40 LINEAR FEET ALONG COUNTERPOISE.
3. INSTALL A TOTAL OF FOUR (4) TEST WELLS, ONE WITHIN 10 FEET OF EACH
CORNER OF THE FACILITY. REFERENCE SHEET E-501 FOR GROUND TEST
WELL DETAIL.
4. INSTALL LIGHTNING PROTECTION AIR TERMINALS ON ROOF PERIMETER.
EACH AIR TERMINAL SHALL BE SOLID COPPER, A MINIMUM OF 18 INCHES IN
HEIGHT AND HAVE A MINIMUM DIAMETER OF 3/8 INCHES. AIR TERMINAL
SPACING SHALL NOT EXCEED 20 LINEAR FEET OF PERIMETER. REFERENCE
SHEET E-501 FOR AIR TERMINAL DETAIL.
5. INSTALLED LIGHTNING PROTECTION AIR TERMINALS ON RIDGE LINE OF ROOF
AS INDICATED.
6. INSTALL COPPER PERIMETER ROOF CONDUCTOR NOT LESS THAN 57,400
CIRCULAR MILS IN DIAMETER TO CONNECT ALL PERIMETER AIR TERMINALS.
SECURE PERIMETER CONDUCTOR TO ROOF WITH CABLE CLAMP AT MINIMUM
OF EVERY 6 LINEAR FEET OF CABLE.
7. INSTALL A COPPER ROOF CONDUCTOR NOT LESS THAN 57,400 CIRCULAR
MILS IN DIAMETER ALONG ROOF CAP TO CONNECT AIR TERMINALS ON THE
ROOF CAP. FIELD ROUTE ROOF CONDUCTOR AROUND ROOF PENETRATIONS
AND ROOF MOUNTED EQUIPMENT AND SECURE TO ROOF WITH CABLE CLAMP
AT A MINIMUM OF EVERY 6 LINEAR FEET OF CABLE.
8. INSTALL A TOTAL OF (4) DOWN CONDUCTORS, ONE WITHIN TEN FEET OF
EACH CORNER OF THE FACILITY, FROM THE PERIMETER ROOF CONDUCTOR
TO THE FACILITY COUNTERPOISE. EXOTHERMICALLY WELD DOWN
CONDUCTORS TO COUNTERPOISE.
04 8 16268
SCALE: 1/8"=1'-0"
1/8" = 1'-0"E-104
A3
LIGHTNING PROTECTION AND GROUNDING
PLAN
PLAN NORTH
A REMOVAL OF CLIN2 BID OPTION 05/27/21 SJ
A
B
A.3
A.6
STAIRWELL TO MEZZANINE
GARAGE
MEZZANINE RAILING
(PNL LP) - (1)
(PNL LP) - (23)
(PNL LP) - (5)
(PNL LP) - (10) E
X
IT
(PNL LP) - (6)
A A A A A A A
A A A A A A A
A A A A A A A
E
E
E
E
E
E
E
E
TYP.
(PNL LP) - (3)
TO CARPORT FIXTURES
A
B
A.3
A.6
OFFICE
HALL
STORAGE
TOILET
SHOWER
104B
E X
IT
(PNL LP) - (6)
C C
C C
C C
C
(PNL LP2) - (14)
(PNL LP2) - (16)
DDD
D D D
D D D
D D D
E
E
E
E
(PNL LP2) - (9)
(PNL LP2) - (11)
(PNL LP2) - (12)
G
G
G
G
G
G
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
/8
/8
/2
:5
:1
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-201
L
IG
H T
IN
G
P L
A N
D B
E H
-1
E -2
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
1/8" = 1'-0"E-201
C1 LIGHTING PLAN
GENERAL NOTES:
1. REFER TO PANEL SCHEDULES ON SHEETS E-701 FOR CIRCUIT BREAKER,
BRANCH CONDUCTOR AND CONDUIT INFORMATION.
2. LIGHT LEVELS ARE IN ACCORDANCE WITH THE LATEST IESNA STANDARDS.
3. MOUNT ALL LIGHTS IN HIGH BAY PORTION OF WAREHOUSE AT 15 FEET AFF,
UNLESS OTHERWISE NOTED.
4. SEE SHEET E-001 FOR THE LIGHTING FIXTURE SCHEDULE.
KEY NOTES:
1. INSTALL NEW AMBER LED FIXTURE IN DEMOLISHED FIXTURE LOCATION,
ENSURE A MAXIMUM MOUNTING HEIGHT OF EIGHT (8) FEET ABOVE FINISHED
GRADE. SUPPLY NEW FIXTURE USING NEW CONDUCTORS AND EXISTING
CONDUIT.
2. INSTALL LIGHTING FIXTURES AT 7 FOOT - 6 INCHES ABOVE MEZZANINE LEVEL.
1/8" = 1'-0"E-201
C4 OFFICE LIGHTING PLAN
PLAN NORTH PLAN NORTH
04 8 16268
SCALE: 1/8"=1'-0"
COPPER GROUND ROD
#4/0 BARE COPPER CONDUCTOR
EXOTHERMIC WELD
GROUND TEST WELL
AIR TERMINAL
#4/0 BARE COPPER CONDUCTOR
CABLE CLAMP
AIR TERMINAL BASE
MOUNTED HORIZONTALLY
EXOTHERMIC WELD
STRUCTURAL STEEL COLUMN
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
A s i n d ic a te d
/8
/2
:5
:1
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-501
E L
E C
T R
IC
A
L D
E T
A
IL
S
D B
E H
-1
E -5
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
NTSE-501
A1 GROUND TEST WELL DETAIL
NTSE-501
A3 AIR TERMINAL DETAIL
NTSE-501
A5 STRUCTURAL STEEL GROUNDING DETAIL
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
A s i n d ic a te d
/8
/2
:5
:1
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-501
E L
E C
T R
IC
A
L D
E T
A
IL
S
D B
E H
-1
E -5
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
KEY NOTES:
1. #4/0 BARE COPPER CONDUCTOR, EXOTHERMICALLY WELDED TO VERTICAL
STRUCTURAL COLUMN AND TO FACILITY COUNTERPOISE.
MARK DESCRIPTION DATE APPRMARK DESCRIPTION DATE APPR
PANEL NAME LP
TYPE MCB 225 AMP ROOM: BUILDING 35420 - GARAGE
VOLTAGE 208/120VAC MINIMUM AIC RATING 10 KA FED FROM: MAIN D/S
T R
IP
A
M P
S
P O
L E
S
DESIGNATION WIRE
N E
U T
R A
L
G N
D
C O
N D
K V
A
C A
T E
G O
R Y
N O
P H
A S
E A
P H
A S
E B
P H
A S
E C
N O
C A
T E
G O
R Y
K V
A
C O
N D
G N
D
N E
U T
R A
L
WIRE DESIGNATION
P O
L E
S
T R
IP
A
M P
S
20 1 BAY LIGHTS NORTH #12 #12 #12 3/4" 0.5 L 1 0.7 2 R 0.2 - - - - W RECEPTACLE 1 20
20 1 SPARE 3 1.0 4 R 0.7 3/4" #12 #12 #12 S RECEPTACLES 1 20
20 1 AMBER EXTERIOR LIGHTS #12 #12 #12 - 0.2 L 5 0.3 6 L 0.1 3/4" #12 #12 #12 EXIT LIGHTS 1 20
20 1 UPS ESS - - - - 0.5 G 7 1.5 8 G 1.0 - - - - P/A SYSTEM 1 20
20 1 SEC ACCESS - - - - 0.3 G 9 0.8 10 L 0.5 3/4" #12 #12 #12 BAY LIGHTS SOUTH 1 20
20 1 SPARE 11 0.7 12 R 0.7 3/4" #12 #12 #12 N RECEPTACLES 1 20
20 2 SPARE
13 0.0 14
SPARE 2 20
15 0.0 16
100 3 PANEL LP2 #1 #1 #6 1-1/4"
7.2 G 17 12.2 18 M 5.0
- - - - AIR CONDITIONER SYSTEM 3 807.2 G 19 12.2 20 M 5.0
7.2 G 21 12.2 22 M 5.0
20 1 BAY LIGHTS CENTER #12 #12 #12 3/4" 0.5 L 23 0.5 24 L 0.0
- - - - SPD 3 40
100 2 SPARE
25 0.0 26 R 0.0
27 0.0 28 R 0.0
15 2 DOOR 2 MOTOR OPERATOR #12 #12 #12 3/4"
0.5 M 29 1.0 30 M 0.5
3/4" #12 #12 #12 DOOR 3 MOTOR OPERATOR 2 15
0.5 M 31 1.0 32 M 0.5
SPACE 33 0.0 34 SPACE
SPACE 35 0.0 36 SPACE
SPACE 37 4.8 38
SPARE 39 4.8 40 BATTERY CHARGER
SPACE 41 4.8 42
TOTAL 20.21 19.54 19.55 TOTAL CONNECTED LOAD 59.30 KVA
DEMAND KVA
R RECEPTACLE<10KW 100% 2.3 DEMAND 164.60 AMPS
R RECEPTACLE >10KW 50% 0.0
L LIGHTS 125% 2.7 EXISTING CIRCUITS
G GENERAL EQUIPMENT 100% 37.8
H HEATER 125% 0.0
M MOTORS LESS LARGEST 100% 17.0
M LARGEST MOTOR 125% 0.0
TOTAL 59.8
1" #10 - #8
G 4.8
G 4.8
G 4.8
3 50
PANEL NAME LP2
TYPE MCB 100 AMP ROOM: OFFICE 101
VOLTAGE 208/120VAC MINIMUM AIC RATING 10 KA FED FROM: PANEL LP
T R
IP
A
M P
S
P O
L E
S
DESIGNATION WIRE
N E
U T
R A
L
G N
D
C O
N D
K V
A
C A
T E
G O
R Y
N O
P H
A S
E A
P H
A S
E B
P H
A S
E C
N O
C A
T E
G O
R Y
K V
A
C O
N D
G N
D
N E
U T
R A
L
WIRE DESIGNATION
P O
L E
S
T R
IP
A
M P
S
20 1 EWH-1 KITCHEN #12 #12 #12 3/4" 1.5 H 1 2.0 2 R 0.5 3/4" #12 #12 #12 HALL RECEPTACLES 1 20
20 1 EWH-2 BATHROOM #12 #12 #12 3/4" 2.4 H 3 3.0 4 R 0.6 3/4" #12 #12 #12 REFRIGERATOR 1 20
20 1 DS TWH-1 #12 #12 #12 3/4" 2.0 H 5 2.7 6 R 0.7 3/4" #12 #12 #12 OFFICE 101 N RECEPTACLES 1 20
20 1 EWC-1 REC. #12 #12 #12 3/4" 0.7 G 7 1.4 8 R 0.7 3/4" #12 #12 #12 OFFICE 101 S RECEPTACLES 1 20
20 1 SHOWER LIGHTS #12 #12 #12 3/4" 0.1 L 9 0.8 10 R 0.7 3/4" #12 #12 #12 STORAGE RECEPTACLES 1 20
20 1 OFFICE LIGHTS #12 #12 #12 3/4" 0.2 L 11 0.7 12 L 0.5 3/4" #12 #12 #12 STORAGE LIGHTS 1 20
30 2 CU-1 #10 #10 #10 1"
1.3 M 13 1.4 14 L 0.1 3/4" #12 #12 #12 BATHROOM LIGHTS 1 20
1.3 M 15 1.4 16 L 0.1 3/4" #12 #12 #12 HALL LIGHTS 1 20
20 1 MEZZANINE RECEPTACLES #12 #12 #12 3/4" 0.7 R 17 0.9 18 R 0.2 3/4" #12 #12 #12 KITCHEN RECEPTACLE 1 20
30 3 208V 3 PHASE S RECEPTACLE #10 #10 #10 1"
0.5 R 19 1.0 20 R 0.5
1" #10 #10 #10 208V 3 PHASE N RECEPTACLE 3 300.5 R 21 1.0 22 R 0.5
0.5 R 23 1.0 24 R 0.5
30 2 208V 1 PHASE S RECEPTACLE #10 #10 #10 1"
0.5 R 25 1.0 26 R 0.5
1" #10 #10 #10 208V 1 PHASE N RECEPTACLE 2 30
0.5 R 27 1.0 28 R 0.5
20 1 SPARE 29 0.0 30 SPARE 1 20
20 1 SPARE 31 0.0 32 SPARE 1 20
20 1 SPARE 33 0.0 34 SPARE 1 20
20 1 SPARE 35 0.0 36 SPARE 1 20
20 1 SPARE 37 0.0 38 SPARE 1 20
20 1 SPARE 39 0.0 40 SPARE 1 20
20 1 SPARE 41 0.5 42 G 0.5 3/4" #12 #12 #12 FIRE ALARM CONTROL PANEL 1 20
TOTAL 6.83 7.17 5.84 TOTAL CONNECTED LOAD 19.84 KVA
DEMAND KVA
R RECEPTACLE<10KW 100% 9.2 DEMAND 59.87 AMPS
R RECEPTACLE >10KW 50% 0.0
L LIGHTS 125% 1.3
G GENERAL EQUIPMENT 100% 1.2
H HEATER 125% 7.4
M MOTORS LESS LARGEST 100% 2.5
M LARGEST MOTOR 125% 0.0
TOTAL 21.6
SHEET
IDENTIFICATION
1 2 3 4 5
D
C
B
A
C O
N T
R A
C T
N
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
D E
L
IV
E R
Y O
R D
E R
N O
C
K D
B Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
T R
A C
E S
T E
C H
N
IC
A L R
A N
G E
A R
C H
IT
E
C T
U R
A L E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S
A A rh o d e s b ri
T H
S P
A C
E W
IN
G
C C
A F
S F
L
/8
/2
:5
:1
P
M
R E
N O
V A
T
IO
N S
T O
S T
O R
M A
G A
G
F A
C
IL
IT
Y
B
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
E-701
P A
N E
L S
C H
E D
U L
E S
D B
E H
-1
E -7
F A
-1
-F
A
S E
P T
E M
B E
R
F A
F A
F A
-1
-F A
J P
B H
S J
S J
GENERAL NOTES:
1. UNKNOWN EXISTING CIRCUITS ARE ASSUMED TO BE 25% OF CIRCUIT
BREAKER RATING FOR LOAD CALCULATIONS. WIRE AND CONDUIT SIZES
ARE ESTIMATED PER NFPA 70.
PANEL LP SCHEDULE
PANEL LP2 SCHEDULE
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES, LEGEND AND ABBREVIATIONS |
| ED-101 - ELECTRICAL DEMOLITION PLAN |
| E-102 - EQUIPMENT PLAN |
| E-103 - POWER PLAN |
| E-104 - LIGHTNING PROTECTION AND GROUNDING PLAN |
| E-201 - LIGHTING PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-701 - PANEL SCHEDULES |
File details come from the government source that posted it. Updated .