Flooring Tiles 1.xlsx
XLSX spreadsheet 14 KB Posted
- Attached to
- B284 Raised Flooring
- Solicitation number
- F3YTAG5133AW01
About this file
The file is an Excel spreadsheet detailing flooring specifications for a raised computer floor replacement project at a Department of the Air Force facility. The document provides comprehensive room-by-room measurements and technical requirements for flooring tiles, with specific focus on rooms requiring utility cuts, power/network access, and varying cooling needs. Key rooms include OPS Floor (Phase 109), multiple 111-series rooms, and areas like storage, loading dock, and secure rooms, with tile heights ranging from 14 1/2" to 22" and varying square footage from 26 to 2,080 square feet.
The related federal contract opportunity (Solicitation Number F3YTAG5133AW01) is for replacing raised flooring in Building 284, with the primary purpose of elevating electronic components to facilitate airflow cooling and cable management for server and operational computer equipment. The project is being managed by the Department of the Air Force Materiel Command Air Force Sustainment Center, and the raised flooring is classified as computer support equipment rather than real property. The spreadsheet provides granular details about tile requirements, including ventilation needs, grounding requirements, and specific room configurations to support the overall raised flooring replacement initiative.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BLDG 284 RFI Questions with Answers.docx | DOCX document | |
| Flooring phases.jpg | JPG image | |
| RFQ B284 Raised Flooring.pdf | ||
| SOW B284 flooring.docx | DOCX document | |
| B284 Raised Flooring Floor Plan.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
Room Sq Ft Floor Height Ventilated tiles PARKER, CHRISTOPHER M GS-11 USAF ACC 552 ACNS/DOR: Existing perforated floor tiles. Cooling for server racks with in-floor air flow.
| Cut tiles Utility | |
| PARKER, CHRISTOPHER M GS-11 USAF ACC 552 ACNS/DOR: Tiles that will require cuts for utilities. Most will be for power along the wall in the rooms. | Cut tiles Network & Power |
PARKER, CHRISTOPHER M GS-11 USAF ACC 552 ACNS/DOR: Tiles with access for power and network from the floor. These will be full size tiles, with holes present that can be arranged as needed.
| Carpet over tiles | Grounding Required | Secure Room requiring escort | Notes | Phase | |||||||
| 109 | 14 1/2" | 30 | 13 | 20 | no | YES | YES | OPS Floor - has the most obsticles and cuts required for utilities | 3 | ||
| 111 | 421 | 22 | 0 | 13 | 10 | YES | YES | no | At top of ramp. Ramp will remain | 2 | |
| 111B |
PARKER, CHRISTOPHER M GS-11 USAF ACC 552 ACNS/DOR: No under floor cooling PARKER, CHRISTOPHER M GS-11 USAF ACC 552 ACNS/DOR: Tiles that will require cuts for utilities. Most will be for power along the wall in the rooms.
PARKER, CHRISTOPHER M GS-11 USAF ACC 552 ACNS/DOR: Tiles with access for power and network from the floor. These will be full size tiles, with holes present that can be arranged as needed.
| 450 | 22 | 0 | 13 | 9 | YES | YES | YES | No under-floor cooling | 2 | ||
| 111C | 631 | 22 | 0 | 4 | 6 | no | YES | no | ACNS Storage. No additional cooling requirements, but currently present and active. | 2 | |
| 111D | 749 | 22 | 0 | 2 | 3 | no | YES | no | Loading Dock | 2 | |
| 111E | 26 | 22 | 0 | 3 | 0 | no | no | no | Single toilet restroom with sink | 2 | |
| 111F | 370 | 22 | 0 | 9 | 8 | YES | YES | YES | Secure room, with everything cleared | 2 | |
| 111G | 630 | 22 | 0 | 2 | 14 | YES | YES | no | Under flooring cooling pressent and active | 2 | |
| 111H | 335 | 22 | 0 | 7 | 0 | no | no | no | Hallway area | 2 | |
| 111i | 30 | 22 | 0 | 4 | 0 | no | no | no | access closet to ceiling | 2 | |
| 113 | 554 | 14 1/2" | 0 | 7 | 0 | no | no | no | Hallway area. Includes staircase which will remain | 3 | |
| 113A | 63 | 14 1/2" | 0 | 3 | 0 | no | no | no | Hallway area | 3 | |
| 113B | 299 | 14 1/2" | 0 | 7 | 8 | YES | YES | no | 3 | ||
| 113C | 448 | 14 1/2" | 0 | 8 | 12 | YES | YES | no | 3 | ||
| 113D | 371 | 14 1/2" | 0 | 7 | 10 | YES | YES | no | 3 | ||
| 116 | 1271 | 22 | 20 | 18 | 19 | no | YES | YES | FIT - has the most obsticles and cuts required for utilities | 1 | |
| 117 | 2080 | 42 | 0 | ? | 20 | YES | YES | no | No under-floor cooling. | 1 |
File details come from the government source that posted it. Updated .