RFI_HAZMAT_Container.docx

DOCX document 14 KB Posted

Attached to
Modular HAZMAT Storage Container Federal contract opportunity
Solicitation number
F1C0RH4216A007
Issued by
Department of the Air Force Pacific Air Forces

View the file

Other files for this federal contract opportunity

Other files attached to Modular HAZMAT Storage Container, newest first.
File Type Posted
RFI_5.docx DOCX document
HAZMAT_Container_RFI_4.docx DOCX document
HAZMAT1.pdf PDF
HAZMAT_Container_RFI_3.docx DOCX document
HAZMAT_Container_RFI_3.docx DOCX document
HAZMAT1.pdf PDF
ADDITIONAL_INFORMATION.docx DOCX document
554_RHS_HAZMAT_CONTAINER_REQUIREMENTS_PROSPECTUS_(As_of_15_Sep_14).docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI HAZMAT Container

Q: What is "CLIN 0001" defined as? The scope of work "requirements prospectus" includes a column for "Required Items" (31ft x 9ft x 8ft container with one open bay concept) as well as "Optional/Suitable Substitutes" (67ft x 25ft x 11ft container with multiple compartments).

A: CLIN 0001 lists the minimum and maximum nominal size of the container.

Q: Are the minimum and maximum sizes listed the interior or exterior dimensions? If these are interior dimensions, are there limits to the exterior dimensions?

A: (MINIMUM SIZES)

Nominal: 31ft x 9ft x 8ft

Exterior: 30ft x 8ft x 7ft

Internal: 29ft x 7ft x 6ft

(MAXIMUM SIZES)

Nominal: 67ft x 25ft x 11ft

Exterior: 66ft x 24ft x 10ft

Internal: 65ft x 23ft x 9ft

Q: What will the container be placed on (eg. a concrete pad, etc.)? This will dictate the type of anchor bolts used.

A: Concrete Pad

Q: Page 6 of the "requirements prospectus" lists chemicals that will be stored in the container. Please provide the total volume of these chemicals or a volume per container. This information will be important for establishing the design fire load and subsequently, the fire protection system used in the container.

A: The total volume of chemicals for the entire container will be no more than 4,400 gallons and no less than 2,000 gallons. NOTE: If measuring per compartment within the container, there will be no more 1,100 gallons per container but no less than 500 gallons.

Q: Please confirm whether a 2 or 4 hour fire-rated building and partition walls are required. The specs reference 2 or 4 hour fire-rated partition walls, but do not confirm which fire-rating is required. Also, please confirm the fire-rating for the building.

A: The 4 hr due to the possibility of storing pesticides.