Smithsonian Institution Last Updated 6/1/2016 845AM EE

Office of Planning Design & Construction

PROJECT: NMNH Roof Repairs & Improvements, F16SOL10043

SI RFI Number Date Company Request for Information SI Response

S001 Grunley 1 1. The RFP requires tape bound submission. Can there be an alternative means of submitting the proposal?

A three ring binder is acceptable. Tape binding is preferred.

Grunley 2 2. The RFP requires that we provide a project-specific Contractor Quality Control

Plan. Can the CQC Plan be bound separately from the Technical Proposal?

Yes.

Grunley 3 3. The RFP requires that we provide a preliminary job-site safety plan. Can this plan be bound separately from the Technical Proposal?

Yes.

Grunley 4 4. L.14.3 is titled Past Performance, but the requirements are listed to respond to an approach to schedule management not past performance. Please clarify if the title needs to be changed or if the content should be related to past performance?

Your response should show your firm's track record of managing project schedules.

We do apologize for the confusion.

Grunley 5 With regard to the Key Personnel and Subcontractors section (L.14.2) of the RFP, please specify the positions for which resumes should be provided by the subcontractors (i.e., Project Manager, Foreman)?

The key personnel resumes for subcontractors are not set in stone, but should at a minimum include representatives from key trades as you deem necessary for successful completion of the project.

Grunley 6 For the References section (L.14.4) of the RFP, it indicates the inclusion of "three references/former clients. Include relevant project information . . . " Can you please clarify what project information needs to be included?

The reference information should include anything from the past project that you think is relevant to our selection process.

Grunley 7 The RFP indicates the provisions of Sections G, H, and K, but these sections are not specified in the documents. Can you please indicate or provide these sections?

Please accept our apologies for the confusion. The Sections in Exhibit A are as follows: Section G is Contract Administration; Section H is Special Contract

Requirements; and Section K is Representations & Warranties.

Grunley 8 The deadline for technical clarifications is stated in Section L.13.8 as June 3, 2016.

What does this mean?

Generally, all questions relating to the bid should be sent well in advance of the bid date to allow us reasonable time to respond. However, any significant technical concern identified during your review should be sent as soon as feasible.

Grunley 9 Please provide the HazMat report for this project. A HazMat report specific to this project was not prepared. Please follow the specifications for hazardous materials protocols. Areas with suspected lead based paint or ACM include: steel dunnage supporting cooling towers, original waterproofing under monumental stair ramps, pipe insulation, and the steel support structure at the Infinity Sculpture. OSHEM IH will come and perform testing upon request for suspected hazmat.

S002

Grunley 1

Per the note on sheet G1 01 we are to construct stairs fron 2nd floor terrace to 5th floor terrace in a planter. The note goes on to say demo and replace new trees and landscaping. Please provide a plant list of all items required to be replaced.

Contractor is to remove (8) crepe myrtle trees from (4) east side planters, and remove all other plantings present. SI will replace all plantings.

Office of Planning Design & Construction

PROJECT: NMNH Roof Repairs & Improvements, F16SOL10043

SI RFI Number Date Company Request for Information SI Response

Grunley 2

Please clarify if the FY2016 and FY2017 Funding Increment breakdowns on pages

12 and 13 of the RFP are to include costs for the base bid only or base bid and options?

Yearly increment break down should cover the base bid only.

Grunley 3

Please provide the correct proposal delivery address because page 16 of the RFP conflicts with the SF 1442.

Smithsonian Facilities/Capital Gallery West/600 Maryland Avenue SW/Suite

5001/Washington, DC 20024/ATTN: EVE ERRICKSON

Grunley 4 Please confirm that a bid guarantee is required per page 39 of the RFP. This currently conflicts with the SF 1442 checkbox.

A bid guarantee is required.

Grunley 5

Please provide the wage scale to be used for this solicitation as mentioned in the

RFP part L43.

The wage determination DC2 current as of May 28, 2016.

Grunley 6

Page 74 of the RFP states that the base bid work is to be complete by May 1, 2017.

Do you have an anticipated award date and revised completion date to be used in the technical proposal schedule?

Our current schedule lists anticipated award date by September 30, 2016; substantial completion for the project must be achieved by Sept 30, 2017. The May 1st deadline will be required for completion of the west terrace and the front entry. This is reflected in notes #8 and 9, page BB-G103.

Grunley 7

Please consider postponing the bid date 1 week to allow for sufficient subcontractor participation in the bid pricing and technical approach process required for this bid.

The bid due date is extended to June 9, 2016, 3 pm EST.

Grunley 8

Please confirm that Options 2, 3 & 5 of this bid will not be exercised prior to or without Option 4 as indicated per the RFP, page 14, Part C.3.

Correct. Options 2, 3, and 5 will not be exercised prior to, or without, Option 4.

S003

Grunley 1

Reference Sheet No.34 (OPT4-A108). Demolition Note 3 says to remove precast concrete pavers to be reinstalled and demo pedestals. Does this note refer to just the PCC Walkway Pavers (2000 SF) or all the 4th Floor Roof PCC Pavers (11,000

SF)?

The 4th floor roof PCC pavers (11,000sf) are the ones on pedestals (south and west sides of the building). These pedestals are to be demolished and new provided.

Remove and Reinstall all of these PCC pavers. The walkway PCC pavers (north and east sides of the building) are sitting on top of the Hydrogaurd without pedestals. If

PCC paver is cracked and requires replacement, demo and provide new. Otherwise, there is no work to the walkway PCC pavers.

Grunley 2

Reference Sheet No.34 (OPT4-A108). Key Note says to clean vertical brick face and stone coping of parapet wall. This divisional breakdown on the bid form does not indicate any masonry costs for this Option. Please revise the divisional breakdown form to include Masonry costs.

Please see attached.

Grunley 3

Please confirm that the contractor will be able to leave exhibit protection installed in space and / or closed to the public (especially when abatement work is being done) until all work is complete in locations indicated per drawings BB-A1-03 and

OP4-A4-01 or will all protection need to be removed at the end of every night's work?

1. OP4-A-401: Protection within all collections storage areas can remain throughout the duration of the work. Protection must be installed between the hours of 9am-

5pm for curatorial supervision. Work within collections storage areas may then take place during normal work hours.

2. OP4-A-401: Work within the director's elevator lobby must take place during off-hours, before 8:30am. Protection must be removed or moved to the side in a manner satisfactory to the COTR during business/office hours. See updated Note #16 on

Sheet OP4-A-108 (ATTACHED)

3. BB-A-103: All protection can remain in place. Protection must be installed between the hours of 9am-5pm for curatorial supervision. Work within the area can then take place during normal work hours.

Office of Planning Design & Construction

PROJECT: NMNH Roof Repairs & Improvements, F16SOL10043

SI RFI Number Date Company Request for Information SI Response

Grunley 4

Bid documents indicate plaster work on this project, but no specification section was provided. Please provide this specification section or confirm whether or not the plaster is 3-coat on metal lath or veneer plaster on gyp substrates.

Plaster in America on the Move is 3/4" on metal lath.

Grunley 5

Option 1 divisional breakdown on the bid form indicates that both Plumbing &

Electrical work are not applicable (NOT USED) to this Option, but the drawings indicate some work for these trades. Please revise the division breakdown for

Option 1 to include Plumbing and Electrical costs.

Please see attached.

Grunley 6

Option 4 divisional breakdown on the bid form indicates that Exterior

Improvement work is not applicable (NOT USED) to this Option, but there is landscaping work at the 2nd floor terrace planter needed in this option to accommodate the stair tower access. Please revise the division breakdown for

Option 4 to include Exterior Improvement costs.

Please see attached.

Grunley 7

Option 5 divisional breakdown on the bid form indicates that Electrical work is not applicable (NOT USED) to this Option, but the drawings indicate some work for this trades. Please revise the division breakdown for Option 5 to include Electrical costs.

Please see attached.

Grunley 8

For RFI response number #2 in Amendment 1 regarding the FY funding increment breakdown to include base bid only in lieu of base bid & options, can you please re-issue the bid form revising the following verbiage on the current bid form: "The total of FY 16 and FY 17 increments should equal the Roof Repairs and

Improvements Base and Options Cost Proposal Total (above)." to reflect the RFI response in Amendment 1.

Please see attached.

S004

Grunley 1

Drawing BB ED1 01 shows a number of GFI receptacles to be removed. On BB E1

01, there are a number of new GFI receptacles shown in the locations of the ones to be removed. Are these new receptacles to be replacements installed in the same box as the ones removed utilizing existing wiring?

Replace the GFCI receptacles, boxes, and covers. Reuse the existing conductors and raceways.

Office of Planning Design & Construction

PROJECT: NMNH Roof Repairs & Improvements, F16SOL10043

SI RFI Number Date Company Request for Information SI Response

Grunley 2

Please provide catalog information for the new step light fixtures. Attached is product data for the step light. Basis of design is the Winona STEP-13-WL-

9LONG-L-LST2A-WHT50K-MVOLT-BSS, 120-volt, 300 lumen minimum, 5000 degree

Kelvin color temperature, die-cast housing, stainless steel faceplate with slotted louver, integral driver, listed for wet location. Interior surfaces shall have ribbed design with matte black finish.

Grunley 3

Drawing BB E401 (Detail 1 & 2) show time switches in Nema 4X enclosures. Please provide details for the components of these time switches. What are they controlling, how are they controlled, and how many circuits.

The time switches shall control the step lights. Basis of design is a Tork #EWZ201 time switch as it is two-channel. (One channel will be spare). The time switches are specified in Section 260553. The corrected model number is indicated in the specification excerpt below (it was incorrect in the bidding documents), and the cut sheet is attached.

2.24 TIME-BASED CONTROL DEVICES

A. Digital time switch: Equal to TORK, EWZ201, electronic 7-day microprocessor-based, solid-state, two-channel control, with 24-hour programming capability and feature to provide automatic tracking of sunrise and sunset times in order to automatically turn lights On at dusk and Off at dawn, selectable to channel.

1. Provide one additional On and Off event per channel as well as selectable daylight savings time adjustment and automatic leap year correction.

2. Include Offset to sunrise and sunset, and Manual Override, independently programmable for each channel.

3. Latitude: Adjustable from 10 to 60 degrees northern or southern hemisphere.

4. Clock format: 12 (AM/PM).

5. Unit shall be capable of operating during a power outage for 96 hours with a capacitor.

6. Mount time switch in a NEMA 4X stainless-steel enclosure, equal to Hoffman No.

A16H1206SSLP, 406 mm high by 305 mm wide by 152 mm deep.

a. Enclosure shall have a stainless-steel back mounting panel, equal to Hoffman No.

A16P12SS6, 330 mm by 229 mm.

Grunley 4

The revised bid form issued with Amendment 2 (page 12 of 81) still states that

"The total of FY 16 and FY 17 increments should equal the Roof Repairs and

Improvements Base and Options Cost Proposal Total (above)." This conflicts with

RFI S002 - 2. Please review and revise the bid form.

We are still going to need the final increments to reflect the option work for each FY increment. The revision included a spot to develop the options cost for each FY. We have made a revision to re-institute the "Other" line on the FY increment bid sheets in hopes that this may clarify things. Please let us know if not.

Office of Planning Design & Construction

PROJECT: NMNH Roof Repairs & Improvements, F16SOL10043

SI RFI Number Date Company Request for Information SI Response

Grunley 5

Detail 1 / drawing BB-A503 indicates the terrace egress stairs get Geoform underneath the walking surface, but detail 2 / drawing BB-S101 indicates rigid installation & gravel at these locations. Please confirm which detail the appropriate detail for this job.

1/BB-A503 should be followed.

End of RFIs

WIRING DIAGRAMS

SPECIFICATION SHEET

EWZ SERIES

MULTIPURPOSE CONTROL

1 OR 2 CHANNELS

24 DAY TIME SWITCH

APPLICATIONS

•Outdoorsigns.
•Lightingsecurity.
•Heatingandairconditioning.

FEATURES

SCHEDULING:

20ON&OFFsetpoints
forindividualprogramsforeachdayoftheweek.Minimumsettingis1minute.

SunSet ASTRONOMIC:

Adjustsdailytochangesinsunsettimes.Adjustable10°-60°Northernor
Southernlatitudes.Canbeindividuallyoffset+/-1-240minutesfromboth
sunsetandsunrisetimes.

DAYLIGHT SAVING:

Automatic (can be omitted).

LEAP YEAR:

Automatic Compensation.

MANUAL OVERRIDE:

Until the next regularly scheduled ON or OFF, automatic operation then resumes.

CLOCK FORMAT:

AM/PM.

POWER OUTAGE BACKUP:

Permanent schedule retention. Supercapacitor provides 4 days of real time backup.

MOMENTARY OPTION:

Formechanicallyheldcontactors:ModelEWZ201only.Configurewithsimple
jumperchangeforsingle-channelmomentaryoperation.

SPECIFICATIONS

TIMING ACCURACY:

Line Frequency.

INPUT VOLTAGE:

120 - 277VAC, 50/60Hz (automatic detection).

TERMINAL RANGE:

#8 - #16AWG.

OPERATING TEMPERATURE:

-40 °F to 149 °F (-40 °C to 65 °C).

POWER CONSUMPTION:

6VA Max.

ENCLOSURE:

PolycarbonateIndoor/OutdoorNEMA3Risstandardwithlockablehasp.Suffix
-MBwithoutenclosureandincludesmountingbracket.

OPTIONS:

Suffix-QQuartzcrystaltiming.Maintainsaccuratetimingwhere50or60Hzisnot
consistentsuchason-sitegeneratorproducedpower.Consultfactoryforminimum
ordersize.

9730 Northcross Center Court Huntersville, NC 28078 P: 800.321.5847 www.nsiindustries.com

CONTACT RATINGS

ORDERING INFO

SPST

LOAD

120/277VAC

EWZ101

1 2

NL N

TIMER

SUPPLY

EWZ201

momentary configuration

EWZ201 ONLY: UNIT MUST BE

CONFIGURED FOR MOMENTARY OPTION

CH 1

TIMER

SUPPLY

3 5 6

120/277VAC

PULSE ON PULSE OFF

L N

1 2

CH 1 CH 2

SPST SPST

TIMER

SUPPLY

120/277VAC

3 4 5

SPDT

EWZ120

1 2

L N

LOAD LOAD

N N

DPSTTIMER

SUPPLY

3 5 6

120/277VAC

L LN N N

LOAD LOAD

LOAD

1 2

EWZ103

DPSTTIMER

SUPPLY

3 5 6

208 OR 240VAC

L1 L2

1 2

SPST

LOAD

120/277VAC

EWZ101

1 2

NL N

TIMER

SUPPLY

EWZ201

momentary configuration

EWZ201 ONLY: UNIT MUST BE

CONFIGURED FOR MOMENTARY OPTION

CH 1

TIMER

SUPPLY

3 5 6

120/277VAC

PULSE ON PULSE OFF

L N

1 2

CH 1 CH 2

SPST SPST

TIMER

SUPPLY

120/277VAC

3 4 5

SPDT

EWZ120

1 2

L N

LOAD LOAD

N N

DPSTTIMER

SUPPLY

3 5 6

120/277VAC

L LN N N

LOAD LOAD

LOAD

1 2

EWZ103

DPSTTIMER

SUPPLY

3 5 6

208 OR 240VAC

L1 L2

1 2

SPST

LOAD

120/277VAC

EWZ101

1 2

NL N

TIMER

SUPPLY

EWZ201

momentary configuration

EWZ201 ONLY: UNIT MUST BE

CONFIGURED FOR MOMENTARY OPTION

CH 1

TIMER

SUPPLY

3 5 6

120/277VAC

PULSE ON PULSE OFF

L N

1 2

CH 1 CH 2

SPST SPST

TIMER

SUPPLY

120/277VAC

3 4 5

SPDT

EWZ120

1 2

L N

LOAD LOAD

N N

DPSTTIMER

SUPPLY

3 5 6

120/277VAC

L LN N N

LOAD LOAD

LOAD

1 2

EWZ103

DPSTTIMER

SUPPLY

3 5 6

208 OR 240VAC

L1 L2

1 2

SPST

LOAD

120/277VAC

EWZ101

1 2

NL N

TIMER

SUPPLY

EWZ201

momentary configuration

EWZ201 ONLY: UNIT MUST BE

CONFIGURED FOR MOMENTARY OPTION

CH 1

TIMER

SUPPLY

3 5 6

120/277VAC

PULSE ON PULSE OFF

L N

1 2

CH 1 CH 2

SPST SPST

TIMER

SUPPLY

120/277VAC

3 4 5

SPDT

EWZ120

1 2

L N

LOAD LOAD

N N

DPSTTIMER

SUPPLY

3 5 6

120/277VAC

L LN N N

LOAD LOAD

LOAD

1 2

EWZ103

DPSTTIMER

SUPPLY

3 5 6

208 OR 240VAC

L1 L2

1 2

CAT.

NO.

UPC

CODE

INPUT SUPPLY

(VAC) 50/60Hz

NO. OF

CHANNELS

OUTPUT

DRY CONTACTS

EWZ101 82470 120-277 1 SPST

EWZ103 82473 120-277 1 DPST

EWZ120 82471 120-277 1 SPDT

EWZ201 82472 120-277 2 SPST

EWZ101-MB 82263 120-277 1 SPST

EWZ103-MB 82269 120-277 1 DPST

EWZ120-MB 82275 120-277 1 SPDT

EWZ201-MB 82281 120-277 2 SPST

TYPE

EWZ101,EWZ103, EWZ201 EWZ120

VOLTAGE

(VAC)

RATING VOLTAGE

(VAC)

RATING

NO NO NC

General Purpose 120-277 40A 120-277 30A 30A

Inductive 120-277 40A 120-277 30A 30A

Ballast 120 30A 120 30A 10A 208-277 20A 208-277 20A 10A

Tungsten 120 15A 120 15A 2A

Pilot Duty 120-277 720VA 120-277 720VA 720VA

Motor

120 1HP 120 1HP 1HP

208 1 1/2HP 208 1 1/2HP 1 1/2HP

240-277 2HP 240-277 2HP 2HP

Resistive 28VDC 30A 28VDC 30A 30A

Wall-Mount EnclosurEs Wall-Mount EnclosurEs and accEssoriEs

Spec-00374 H EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEstainlEss stEEl1

Spec-00374H763.422.2211763.422.2600 stainlEss stEEl Wall-Mount EnclosurEs Wall-Mount EnclosurEs and accEssoriEs continuous HingE WitH claMps, typE 4X inDustry stanDarDs

UL 508A Listed; Type 3R, 4, 4X, 12; File No. E61997 cUL Listed per CSA C22.2 No 94; Type 3R, 4, 4X, 12; File No.

E61997

NEMA/EEMAC Type 3, 3R, 4, 4X, 12, 13 CSA File No. 42186: Type 4, 4X, 12

IEC 60529, IP66

Meets NEMA Type 3RX requirements application For use in indoor and outdoor corrosive environments that require a water-tight seal, this enclosure’s seamless foam-in-place gasket and screw-down clamps provide a secure seal against contaminants.

spEciFications

•14 gauge Type 304 or Type 316L stainless steel bodies and doors
•Seams continuously welded and ground smooth
•Seamless foam-in-place gasket
•Rolled lip around three sides of door
•Stainless steel door clamp assembly
•Hasp and staple for padlocking
•Door removed by pulling stainless steel continuous hinge pin
•Data pocket is high-impact thermoplastic
•Collar studs provided for mounting optional panels
•Exterior hardware on Type 316L stainless steel enclosures

matches enclosure material

• Bonding provision on door; grounding stud on body

FinisH Door, sides, top and bottom have smooth #4 brushed finish.

accEssoriEs Fast-Operating Clamp Assembly Panels for Type 3R, 4, 4X, 12 and 13 Enclosures Junction Box and Wall-Mount Enclosure Swing Out Panel Kit Steel and Stainless Steel Window Kits H2OMIT Vent Drains, Type 4X H2OMIT Thermoelectric Dehumidifier

MoDiFication anD custoMiZation Hoffman excels at modifying and customizing products to your specifications. Contact your local Hoffman sales office or distributor for complete information.

Bulletin: A4S

Standard Product

Catalog Number AxBxC in./mm Stainless Steel Type Steel Panel

Conductive Steel Panel

Stainless Steel Panel

Panel Size D x E in./mm

F in./mm

Clamps Qty.

Data Pocket

A16H1206SSLP 16.00 x 12.00 x 6.00 406 x 305 x 152

304 A16P12 A16P12G A16P12SS6 13.00 x 9.00 330 x 229

1.25

4 Small

A16H1206SS6LP 16.00 x 12.00 x 6.00 406 x 305 x 152

316L A16P12 A16P12G A16P12SS6 13.00 x 9.00 330 x 229

1.25

4 Small

A16H1606SSLP 16.00 x 16.00 x 6.00 406 x 406 x 152

304 A16P16 A16P16G A16P16SS6 13.00 x 13.00 330 x 330

3.00

4 Small

A16H1606SS6LP 16.00 x 16.00 x 6.00 406 x 406 x 152

316L A16P16 A16P16G A16P16SS6 13.00 x 13.00 330 x 330

3.00

4 Small

A16H2006SSLP 16.00 x 20.00 x 6.00 406 x 508 x 152

304 A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A16H2006SS6LP 16.00 x 20.00 x 6.00 406 x 508 x 152

316L A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A20H1606SSLP 20.00 x 16.00 x 6.00 508 x 406 x 152

304 A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A20H1606SS6LP 20.00 x 16.00 x 6.00 508 x 406 x 152

316L A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A20H2006SSLP 20.00 x 20.00 x 6.00 508 x 508 x 152

304 A20P20 A20P20G A20P20SS6 17.00 x 17.00 432 x 432

3.00

4 Small

A20H2006SS6LP 20.00 x 20.00 x 6.00 508 x 508 x 152

316L A20P20 A20P20G A20P20SS6 17.00 x 17.00 432 x 432

3.00

4 Small

A24H2006SSLP 24.00 x 20.00 x 6.00 610 x 508 x 152

304 A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

5 Small

A24H2006SS6LP 24.00 x 20.00 x 6.00 610 x 508 x 152

316L A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

5 Small

A24H2406SSLP 24.00 x 24.00 x 6.00 610 x 610 x 152

304 A24P24 A24P24G A24P24SS6 21.00 x 21.00 533 x 533

3.00

5 Small

A24H2406SS6LP 24.00 x 24.00 x 6.00 610 x 610 x 152

316L A24P24 A24P24G A24P24SS6 21.00 x 21.00 533 x 533

3.00

5 Small

PH 763.422.2211 • • FAX 763.422.2600 • • PentAirProtect.comEQUIPMENT PROTECTION stainlEss stEEl 2

Catalog Number AxBxC in./mm Stainless Steel Type Steel Panel

Conductive Steel Panel

Stainless Steel Panel

Panel Size D x E in./mm

F in./mm

Clamps Qty.

Data Pocket

A16H1208SSLP 16.00 x 12.00 x 8.00 406 x 305 x 203

304 A16P12 A16P12G A16P12SS6 13.00 x 9.00 330 x 229

1.25

4 Small

A16H1208SS6LP 16.00 x 12.00 x 8.00 406 x 305 x 203

316L A16P12 A16P12G A16P12SS6 13.00 x 9.00 330 x 229

1.25

4 Small

A20H1608SSLP 20.00 x 16.00 x 8.00 508 x 406 x 203

304 A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A20H1608SS6LP 20.00 x 16.00 x 8.00 508 x 406 x 203

316L A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A20H2008SSLP 20.00 x 20.00 x 8.00 508 x 508 x 203

304 A20P20 A20P20G A20P20SS6 17.00 x 17.00 432 x 432

3.00

4 Small

A20H2008SS6LP 20.00 x 20.00 x 8.00 508 x 508 x 203

316L A20P20 A20P20G A20P20SS6 17.00 x 17.00 432 x 432

3.00

4 Small

A20H2408SSLP 20.00 x 24.00 x 8.00 508 x 610 x 203

304 A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

4 Small

A20H2408SS6LP 20.00 x 24.00 x 8.00 508 x 610 x 203

316L A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

4 Small

A24H1608SSLP 24.00 x 16.00 x 8.00 610 x 406 x 203

304 A24P16 A24P16G A24P16SS6 21.00 x 13.00 533 x 330

3.00

5 Small

A24H1608SS6LP 24.00 x 16.00 x 8.00 610 x 406 x 203

316L A24P16 A24P16G A24P16SS6 21.00 x 13.00 533 x 330

3.00

5 Small

A24H2008SSLP 24.00 x 20.00 x 8.00 610 x 508 x 203

304 A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

5 Small

A24H2008SS6LP 24.00 x 20.00 x 8.00 610 x 508 x 203

316L A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

5 Small

A24H2408SSLP 24.00 x 24.00 x 8.00 610 x 610 x 203

304 A24P24 A24P24G A24P24SS6 21.00 x 21.00 533 x 533

3.00

5 Small

A24H2408SS6LP 24.00 x 24.00 x 8.00 610 x 610 x 203

316L A24P24 A24P24G A24P24SS6 21.00 x 21.00 533 x 533

3.00

5 Small

A24H3008SSLP 24.00 x 30.00 x 8.00 610 x 762 x 203

304 A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

7 Small

A24H3008SS6LP 24.00 x 30.00 x 8.00 610 x 762 x 203

316L A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

7 Small

A30H2008SSLP 30.00 x 20.00 x 8.00 762 x 508 x 203

304 A30P20 A30P20G A30P20SS6 27.00 x 17.00 686 x 432

3.00

5 Small

A30H2008SS6LP 30.00 x 20.00 x 8.00 762 x 508 x 203

316L A30P20 A30P20G A30P20SS6 27.00 x 17.00 686 x 432

3.00

5 Small

A30H2408SSLP 30.00 x 24.00 x 8.00 762 x 610 x 203

304 A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A30H2408SS6LP 30.00 x 24.00 x 8.00 762 x 610 x 203

316L A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A30H3008SSLP 30.00 x 30.00 x 8.00 762 x 762 x 203

304 A30P30 A30P30G A30P30SS6 27.00 x 27.00 686 x 686

3.00

7 Large

A30H3008SS6LP 30.00 x 30.00 x 8.00 762 x 762 x 203

316L A30P30 A30P30G A30P30SS6 27.00 x 27.00 686 x 686

3.00

7 Large

A36H2408SSLP 36.00 x 24.00 x 8.00 914 x 610 x 203

304 A36P24 A36P24G A36P24SS6 33.00 x 21.00 838 x 533

3.00

5 Large

A36H2408SS6LP 36.00 x 24.00 x 8.00 914 x 610 x 203

316L A36P24 A36P24G A36P24SS6 33.00 x 21.00 838 x 533

3.00

5 Large

A36H3008SSLP 36.00 x 30.00 x 8.00 914 x 762 x 203

304 A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A36H3008SS6LP 36.00 x 30.00 x 8.00 914 x 762 x 203

316L A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A42H3608SSLP 42.00 x 36.00 x 8.00 1067 x 914 x 203

304 A42P36 A42P36G A42P36SS6 39.00 x 33.00 991 x 838

3.00

8 Large

A42H3608SS6LP 42.00 x 36.00 x 8.00 1067 x 914 x 203

316L A42P36 A42P36G A42P36SS6 39.00 x 33.00 991 x 838

3.00

8 Large

A48H3608SSLP 48.00 x 36.00 x 8.00 1219 x 914 x 203

304 A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A48H3608SS6LP 48.00 x 36.00 x 8.00 1219 x 914 x 203

316L A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A20H1610SSLP 20.00 x 16.00 x 10.00 508 x 406 x 254

304 A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A20H1610SS6LP 20.00 x 16.00 x 10.00 508 x 406 x 254

316L A20P16 A20P16G A20P16SS6 17.00 x 13.00 432 x 330

3.00

4 Small

A24H2010SSLP 24.00 x 20.00 x 10.00 610 x 508 x 254

304 A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

5 Small

A24H2010SS6LP 24.00 x 20.00 x 10.00 610 x 508 x 254

316L A24P20 A24P20G A24P20SS6 21.00 x 17.00 533 x 432

3.00

5 Small

A30H2410SSLP 30.00 x 24.00 x 10.00 762 x 610 x 254

304 A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A30H2410SS6LP 30.00 x 24.00 x 10.00 762 x 610 x 254

316L A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A36H2410SSLP 36.00 x 24.00 x 10.00 914 x 610 x 254

304 A36P24 A36P24G A36P24SS6 33.00 x 21.00 838 x 533

3.00

5 Large

A36H2410SS6LP 36.00 x 24.00 x 10.00 914 x 610 x 254

316L A36P24 A36P24G A36P24SS6 33.00 x 21.00 838 x 533

3.00

5 Large

A36H3010SSLP 36.00 x 30.00 x 10.00 914 x 762 x 254

304 A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large http://www.pentairprotect.com

EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEstainlEss stEEl3

Catalog Number AxBxC in./mm Stainless Steel Type Steel Panel

Conductive Steel Panel

Stainless Steel Panel

Panel Size D x E in./mm

F in./mm

Clamps Qty.

Data Pocket

A36H3010SS6LP 36.00 x 30.00 x 10.00 914 x 762 x 254

316L A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A42H3010SSLP 42.00 x 30.00 x 10.00 1067 x 762 x 254

304 A42P30 A42P30G A42P30SS6 39.00 x 27.00 991 x 686

3.00

8 Large

A42H3010SS6LP 42.00 x 30.00 x 10.00 1067 x 762 x 254

316L A42P30 A42P30G A42P30SS6 39.00 x 27.00 991 x 686

3.00

8 Large

A48H3610SSLP 48.00 x 36.00 x 10.00 1219 x 914 x 254

304 A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A48H3610SS6LP 48.00 x 36.00 x 10.00 1219 x 914 x 254

316L A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A24H2412SSLP 24.00 x 24.00 x 12.00 610 x 610 x 305

304 A24P24 A24P24G A24P24SS6 21.00 x 21.00 533 x 533

3.00

5 Small

A24H2412SS6LP 24.00 x 24.00 x 12.00 610 x 610 x 305

316L A24P24 A24P24G A24P24SS6 21.00 x 21.00 533 x 533

3.00

5 Small

A30H2412SSLP 30.00 x 24.00 x 12.00 762 x 610 x 305

304 A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A30H2412SS6LP 30.00 x 24.00 x 12.00 762 x 610 x 305

316L A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A36H3012SSLP 36.00 x 30.00 x 12.00 914 x 762 x 305

304 A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A36H3012SS6LP 36.00 x 30.00 x 12.00 914 x 762 x 305

316L A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A36H3612SSLP 36.00 x 36.00 x 12.00 914 x 914 x 305

304 A36P36 A36P36G A36P36SS6 33.00 x 33.00 838 x 838

3.00

7 Large

A36H3612SS6LP 36.00 x 36.00 x 12.00 914 x 914 x 305

316L A36P36 A36P36G A36P36SS6 33.00 x 33.00 838 x 838

3.00

7 Large

A48H3612SSLP 48.00 x 36.00 x 12.00 1219 x 914 x 305

304 A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A48H3612SS6LP 48.00 x 36.00 x 12.00 1219 x 914 x 305

316L A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A60H3612SSLP 60.00 x 36.00 x 12.00 1524 x 914 x 305

304 A60P36 A60P36G A60P36SS6 57.00 x 33.00 1448 x 838

3.00

9 Large

A60H3612SS6LP 60.00 x 36.00 x 12.00 1524 x 914 x 305

316L A60P36 A60P36G A60P36SS6 57.00 x 33.00 1448 x 838

3.00

9 Large

A30H2416SSLP 30.00 x 24.00 x 16.00 762 x 610 x 406

304 A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A30H2416SS6LP 30.00 x 24.00 x 16.00 762 x 610 x 406

316L A30P24 A30P24G A30P24SS6 27.00 x 21.00 686 x 533

3.00

5 Large

A36H3016SSLP 36.00 x 30.00 x 16.00 914 x 762 x 406

304 A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A36H3016SS6LP 36.00 x 30.00 x 16.00 914 x 762 x 406

316L A36P30 A36P30G A36P30SS6 33.00 x 27.00 838 x 686

3.00

7 Large

A48H3616SSLP 48.00 x 36.00 x 16.00 1219 x 914 x 406

304 A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A48H3616SS6LP 48.00 x 36.00 x 16.00 1219 x 914 x 406

316L A48P36 A48P36G A48P36SS6 45.00 x 33.00 1143 x 838

3.00

8 Large

A60H3616SSLP 60.00 x 36.00 x 16.00 1524 x 914 x 406

304 A60P36 A60P36G A60P36SS6 57.00 x 33.00 1448 x 838

3.00

9 Large

A60H3616SS6LP 60.00 x 36.00 x 16.00 1524 x 914 x 406

316L A60P36 A60P36G A60P36SS6 57.00 x 33.00 1448 x 838

3.00

9 Large

Purchase panels separately. Optional composite and aluminum panels are available for most sizes.

PH 763.422.2211 • • FAX 763.422.2600 • • PentAirProtect.comEQUIPMENT PROTECTION stainlEss stEEl 4

Popular Cooling Products Enclosure Depth (C Dimension) Thermoelectric Controller 6 in. (152 mm) TE090624011 8 in. (203 mm) TE162024011 10 in. (254 mm) TE162024011 12 in. (305 mm) TE162024011 16 in. (406 mm) TE162024011 *important: Visit tools.hoffmanonline.com/attachments to access our cooling selection tool to determne the appropriate cooling solution for your application.

Popular Accessories Enclosure Width (B Dimension) Lights Hole Seals Window Kits 12 in. (305 mm) LEDPUCK AS050SS APWK53NFSS 16 in. (406 mm) LEDA2M35 AS050SS APWK53NFSS 20 in. (508 mm) LED24V15 AS050SS APWK53NFSS 24 in. (610 mm) LED24V15 AS050SS APWK53NFSS 30 in. (762 mm) LED24V15 AS050SS APWK53NFSS 36 in. (914 mm) LED24V15 AS050SS APWK53NFSS http://www.pentairprotect.com

Winona Lighting • 3760 West Fourth Street • Winona, MN 55987 • 800.328.5291 • www.winonalighting.com

Rev. 06/23/15 STEP13_9LONG© 2015 Acuity Brands Lighting, Inc. All Rights Reserved. “Winona” is a registered trademark of Acuity Brands Lighting. Products herein may be covered by one or more U.S. Patents and Patents Pending. Specifications subject to change without notice.

Project:

Qty:

SPECIFICATIONS

Type:

9-LONG

STEP

STEP 13

GREEN CMYK:

C - 50 M - 0 Y - 100 K - 25

GREY CMYK:

C - 0 M - 0 Y - 0 K - 50

GREY RGB:

R - 147 G - 149 B - 152

GREEN RGB:

R - 109 G - 157 B - 49

BLACK CMYK:

C - 0 M - 0 Y - 0 K - 100

BLACK RGB:

R - 35 G - 31 B - 32

WHITE CMYK:

C - 0 M - 0 Y - 0 K - 0

WHITE RGB:

R - 255 G - 255 B - 255 color Accepted color combinations

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

Construction Die-cast housing with solid aluminum, brass, or stainless steel faceplate. Step13-9 is a surface mount step light that mounts over a Steel City 2-1/8” deep, rectangular box H4BD or equivalent (by others).

Interior option faceplate mounts with no visible fasteners.

Source Light source consists of six powerful LEDs available in five white color temperatures and six colored LED choices.

Optics A concealed optic provides a long light distribution for illumination of large areas.

Electrical Integral electronic drivers are multi volt input 120- 277V, and available in standard or 0-10V dimming.

Non-dimming units consume 8.04W. Dimming units consume 18W.

Environment ETL / cETL listed dry location or optional wet location.

Finish Recessed surfaces have a ribbed design with matte black finish to reduce glare. Faceplates are available in five metal finishes with protective clear coat or one of seven polyester powder coat painted finishes. A primer only finish is also available for field painting.

Warranty 5-year limited warranty. Complete warranty terms located at www.acuitybrands.com/ CustomerResources/Terms_and_conditions.aspx

Actual performance may differ as a result of end-user environment and application.

All values are design or typical values, measured under laboratory conditions at 25 °C.

Assembled in America (Buy American Act Compliant)

STEP13 INT 9LONG L LST2A WHT30K MVOLT BA

Series Environment Length Distribution Source Color Temperature

STEP13 Step 13 WL Wet Location INT Interior

9LONG 9 inch nominal length L Long LST2A LED Step 2 WHT27K White (27K) WHT30K White (30K) WHT35K White (35K) WHT40K White (40K) WHT50K White (50K) AMB Amber

BLU Blue GRN Green RED Red CYN Cyan RDO Red-Orange

Notes

• *Available by modification only. Consult factory.

Describe Modification:

CATALOG NUMBER

Example:

Voltage Driver Finish Special

MVOLT Multi Volt 120V thru 277V (Blank) Standard Driver DMD Dimming Driver

BA Brushed Aluminum BB Brushed Brass BSS Brushed Stainless Steel PB Polished Brass PSS Polished Stainless Steel

ABP Antique Brass Paint BBP Brushed Brass Paint LBPS Light Bronze Paint Smooth LSP Light Silver PGP Pale Gold

SGB Semi Gloss Black SGW Semi Gloss White PRM Primer Only CPF* Custom Paint Finish CMF* Custom Metal Finish

MOD* Modification / Consult Factory

0.1 0.5 1.0 2.0 4.0 8.0

Typical Distribution Based on WHT30K

9 inch - Long Distribution

Grid in 1' increments

18"

L Approx 10'-0"

Steel City H4BD or equivalent (by others)

Ribbed design with matte black finish reduces glare

5.50"

11.50"

Ribbed design with matte black finish reduces glare

Exposed fasteners for Wet Location Only

CROSS SECTION

Integral driver

2.125" box min.

LED module with concealed optic

See page 3 for lighting facts labels.

Performance Data

Size Dist. Lumens Watts LPW

9LONG Long 310 8.04 38.6

Performance data based on WHT30K non dimming.

www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx

Type:

Qty:

Project:

SPECIFICATIONS

9-LONG

STEP

STEP13

Winona Lighting • 3760 West Fourth Street • Winona, MN 55987 • 800.328.5291 • www.winonalighting.com

Rev. 06/23/15 STEP13_9LONG© 2015 Acuity Brands Lighting, Inc. All Rights Reserved. “Winona” is a registered trademark of Acuity Brands Lighting. Products herein may be covered by one or more U.S. Patents and Patents Pending. Specifications subject to change without notice.

GREEN CMYK:

C - 50 M - 0 Y - 100 K - 25

GREY CMYK:

C - 0 M - 0 Y - 0 K - 50

GREY RGB:

R - 147 G - 149 B - 152

GREEN RGB:

R - 109 G - 157 B - 49

BLACK CMYK:

C - 0 M - 0 Y - 0 K - 100

BLACK RGB:

R - 35 G - 31 B - 32

WHITE CMYK:

C - 0 M - 0 Y - 0 K - 0

WHITE RGB:

R - 255 G - 255 B - 255 color Accepted color combinations

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIRING & DIMMING

Dimming drivers require a 0-10V fluorescent-type dimming control.

Read all instructions before installation. Do not make live connections!

POWER SUPPLY / DIMMING

NON-DIMMING INSTALLATIONS

Connect STEP WHITE wire to power NEUTRAL.

Connect STEP BLACK wire to power HOT.

Connect STEP GREEN wire to power GROUND.

WHITE

BLACK

GREEN

120V or

277V

W H

IT

E

B

LA

C K

G R

E E

N

W H

IT

E

B

LA

C K

G R

E E

N

W H

IT

E

B

LA

C K

G R

E E

N

W H

IT

E

B

LA

C K

G R

E E

N

To other

STEP

fixtures

W H

IT

E

B

LA

C K

G R

E E

N

V

IO

LE

T

G R

E Y

To other

STEP

fixtures 0-10V (+)

Dimmer (-)

V

IO

LE

T

G R

E Y

V

IO

LE

T

G R

E Y

V

IO

LE

T

G R

E Y

V

IO

LE

T

G R

E Y

VIOLET

GREY

WHITE

BLACK

GREEN

120V or

277V

W H

IT

E

B

LA

C K

G R

E E

N

W H

IT

E

B

LA

C K

G R

E E

N

W H

IT

E

B

LA

C K

G R

E E

N

W H

IT

E

B

LA

C K

G R

E E

N

To other

STEP

fixtures

W H

IT

E

B

LA

C K

G R

E E

N

DIMMING INSTALLATIONS

The integral dimming driver is designed to the 0-10V IEC dimming specification 60929 and is compatible with common 0-10V dimmers and dimming systems.

Do NOT connect line voltage to dimming input wires.

Connect STEP WHITE wire to power NEUTRAL.

Connect STEP BLACK wire to power HOT.

Connect STEP VIOLET wire to POSITIVE INPUT of Dimming Control.

Connect STEP GREY wire to NEGATIVE INPUT of Dimming Control.

Type:

Qty:

Project:

SPECIFICATIONS

9-LONG

STEP

STEP13

Winona Lighting • 3760 West Fourth Street • Winona, MN 55987 • 800.328.5291 • www.winonalighting.com

Rev. 06/23/15 STEP13_9LONG© 2015 Acuity Brands Lighting, Inc. All Rights Reserved. “Winona” is a registered trademark of Acuity Brands Lighting. Products herein may be covered by one or more U.S. Patents and Patents Pending. Specifications subject to change without notice.

GREEN CMYK:

C - 50 M - 0 Y - 100 K - 25

GREY CMYK:

C - 0 M - 0 Y - 0 K - 50

GREY RGB:

R - 147 G - 149 B - 152

GREEN RGB:

R - 109 G - 157 B - 49

BLACK CMYK:

C - 0 M - 0 Y - 0 K - 100

BLACK RGB:

R - 35 G - 31 B - 32

WHITE CMYK:

C - 0 M - 0 Y - 0 K - 0

WHITE RGB:

R - 255 G - 255 B - 255 color Accepted color combinations

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

WIN NA

solutions forms light

LIGHTING FACTS

F16SOL10043

EXHIBIT A

BASE AND OPTIONS COST PROPOSAL TOTAL –

Roof Repairs and Improvements p/n 1303101 (Must equal the total of the base plus all options totals. Express in Words and Figures)

B.3.2. Multi-year FY Funding Increments – Funding for this construction project will be spread over

Fiscal Years 2016 and 2017 (FY16 and FY17), therefore the cost proposal is required to reflect the division of costs over these two Fiscal Years. The construction project has been partially funded for FY16, and the remainder of the project will be funded on January 15, 2017 (or when FY17 federal funds become available). The Smithsonian has identified $6,000,000.00 to fund performance of the awarded contract for the first Fiscal Year (FY). Additional funding is anticipated. The Smithsonian Institution’s obligation under this contract beyond that amount is contingent upon the availability of appropriated funds from which payment for contract purposes can be made. No legal liability on the part of the Smithsonian Institution for any payment may arise for performance under this contract beyond $6,000,000 unless and until funds are made available to the Contracting Officer for performance and the Contractor receives notice of availability of funds, to be confirmed in writing by the Contracting Officer. The Contractor shall not be obligated to continue performance beyond the funds allocated under this contract. Offerors are reminded that they must include in their proposal a termination cost in the event that subsequent year funds are not appropriated. Smithsonian Institution will not be liable for any costs in excess of the termination cost

(cancellation charge). The total of FY 16 and FY 17 increments should equal the Roof Repairs and

Improvements Base and Options Cost Proposal Total (above).

FY2016 FUNDING INCREMENT ($6M available):

General Requirements (approx. 5 months) $___________________________

Submittals & Shop Drawings $___________________________

Site Mobilization and Staging Prep $___________________________

Existing Conditions and Hazmat Removal $___________________________

Demolition $___________________________

Concrete & Masonry $___________________________

Metals, Wood, Plastics, Composites $___________________________

Thermal and Moisture Protection $___________________________

Protection of Collections and Furnishings $___________________________

Plumbing, Mechanical, Electrical $___________________________

SUBTOTAL $___________________________

OTHER – Offerors shall clearly and completely describe items exceeding the base bid proposed for

FY2016 Funding Phase $___________________________

(Attach pages as necessary)

OPTIONS – Offerors shall clearly and completely describe items exceeding the base bid proposed for FY2016 Funding Phase $___________________________

Termination Cost (Cancellation Charge) $___________________________

TOTAL-FY2016___________________________________________________$___________

(Express in Words and Figures)

FY2017 FUNDING INCREMENT: (assume remainder of funding available in Jan 2017) General Requirements $___________________________

Submittals & Shop Drawings $___________________________

Site Mobilization and Staging Prep $___________________________

Existing Conditions and Hazmat Removal $___________________________

Demolition $___________________________

Concrete & Masonry $___________________________

Metals, Wood, Plastics, Composites $___________________________

Thermal and Moisture Protection $___________________________

Finishes $___________________________

Equipment $___________________________

Protection of Collections and Furnishings $___________________________

Fire Suppression $___________________________

Plumbing $___________________________

Heating, Ventilating, and Air Conditioning $___________________________

Electrical and Lighting $___________________________

Electronic Safety and Security $___________________________

Unit Paving $___________________________

SUBTOTAL $___________________________

OTHER – Offerors shall clearly and completely describe items exceeding the base bid proposed for

FY2017 Funding Phase $___________________________

OPTIONS – Offerors shall clearly and completely describe items exceeding the base bid proposed for FY2017 Funding Phase

Termination Cost (Cancellation Charge) $___________________________

TOTAL-FY2017___________________________________________________$___________

B.4. Options: The option shall include all related costs (including but not limited to supervision, labor, materials, coordination, overhead, profit, and bonds). The Contractor shall hold the Option price for a period of ninety (90) calendar days from the date of award. Please see p/n 1300103 Specifications Volume

1, Section 010000.

B.4.1 OPTION 1 (ADD) – STAIR RAMP WATERPROOFING & SNOW MELT PIPING REMOVAL

B.4.2 OPTION 2 (ADD) – FALL PROTECTION WORK AT 4TH FLOOR ROOF/FIFTH FLOOR TERRACE AND FIFTH FLOOR ROOF

B.4.3 OPTION 3 (ADD) – FALL PROTECTION WORK AT PENTHOUSE ROOFS,

B.4.4 OPTION 4 (ADD) WORK AT 4TH FLOOR ROOF/5TH FLOOR TERRACE, 5TH FLOOR ROOF, AND PENTHOUSE ROOFS

B.4.5 OPTION 5(ADD) – ALL FIRE SUPPRESSION WORK

B.6. Schedule of Unit Prices – NOT USED