Chemical Water Treatment Services for Glenarm Power Plant
Solicitation number
2025-RFP-0311
Issued by
Los Angeles County, Berkeley City, California

About this file

Exhibit E is a technical specification document for the City of Pasadena Water & Power Department's chemical water treatment services procurement at the Glenarm Power Plant in Pasadena, California. The exhibit establishes operating parameters and design data for three generating units (GT-3, GT-4, and GT-5) that must be used for cost calculations. The units operated an average of 892, 719, and 2,860 running hours per year, respectively, based on 2017-2019 historical data. The condenser and cooling tower design specifications detail critical infrastructure parameters, including condenser surface areas ranging from 17,844 square feet for units GT-3 and GT-4 to larger specifications for unit GT-5, with varying tube materials (copper for GT-3 and GT-4; titanium alloy for GT-5) and tube configurations. Cooling water quantity for units GT-3 and GT-4 is specified at 11,614 gallons per minute with an entering water temperature of 80 degrees.

Bidders must complete all cost calculation forms provided in Exhibits B and C using the operating parameters and design data specified in Exhibits A and E. For chemical products not required in the proposed water treatment program, bidders must indicate "NOT REQUIRED" and provide written justification. Pricing must reflect the cost per unit for the quantity and container size that the power plant would reasonably purchase to maintain a maximum 90-day inventory. This specification ensures competitive bids are based on consistent operational assumptions and actual anticipated procurement volumes rather than theoretical minimums or alternative inventory strategies.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXHIBIT E Page 2 of 2 The data and operating parameters in Exhibits A and E must be used for the chemical water treatment services cost calculations required on the forms provided in Exhibits B and C. All of the blanks must be completed on the forms provided. If certain chemical products are not required in your water treatment program, type “NOT REQUIRED” in the applicable space and explain why such particular products are not required. The price that is to be quoted for each chemical product must be the price that you charge for the quantity and container size that the power plant would reasonably be expected to buy for a maximum 90 day inventory.

UNITS RUNNING HOURS PER YEAR

Unit GT-3
Unit GT-4
Unit GT-5
2017
940
683
3094
2018
953
809
3105
2019
783
665
2382
Average Hours/year
892
719
2860

CONDENSER AND COOLING TOWER DESIGN DATA

UNITS GT-3 AND GT-4
UNIT GT-5

Condenser Surface Area

17,844 Sq. ft.

Tube Size
¾” O.D.
0.625” O.D. x 22/24 BWG
Total Number of Tubes
1,341
4704
Effective Tube Length
16’
23’ - 4”
Tube Material
Copper
Titanium Alloy (SB338-GR2)

Cooling Water Quantity

11,614 gpm

Water Entering Temperature
80<Fº
75 Fº
Water Leaving Temperature
95.7<Fº
96.55 Fº

U-Service

535.6 BTU/hr-ft²-°F

Water Velocity in Tubes

6 ft/sec

Total Friction Loss

Absolute Pressure

1.0” Hg

Condensate Temperature

71.5 Fº

Steam Flow Rate

130,300 lbs/hr

Air Flow Rate

33.8 lb/hr

Water Vapor Flow Rate

74.4 lb/hr

Max. Free O2

Cooling Tower Water Volume
12,000 gallons
151,000 gallons
One Circ. Water Pump Discharge
4,200 gpm
12,200 gpm
Two Circ. Water Pumps Disch.
N/A
N/A

MAKE-UP WATER ANALYSIS (TYPICAL)

pH
8.56
--
Specific Conductance, at 25ºC
909
umho/cm
Total Alkalinity as Ca
70
mg/L
Sulfur, Total, as SO4
156
ppm
Chloride, as Cl
98.5
mg/L
Fluoride
0.64
mg/L
Hardness as Ca
264.7
mg/L
Magnesium
25.4
µg/L
Barium, Total, as Ba
0.08
ppm
Strontium, Total, as Sr
0.884
mg/L
Copper, Total, as Cu
<0.05
ppm
Iron, Total, as Fe
0.200
mg/L
Sodium
96.7
mg/L
Potassium
5.75
mg/L
Aluminum, Total, as Al
0.0571
mg/L
Manganese, Total
0.08
µg/L
Nitrite as N
1.75
mg/L
Sulfate
222
mg/L
Phosphate, Total, as PO4
0.34
mg/L
Phosphorous Total
0.4
mg/L
Silica, Total, as SiO2
11
mg/L
Carbon Dioxide
0.4
mg/L
Chlorine, Total
<0.8
ppm
Free Chlorine
<0.1
ppm
Oxidation-reduction potential (ORP)
306
mV

FORMULAS FOR COOLING TOWER WATER PARAMETERS

Number of Concentrations =
Make-up Water (gpm) / Rate of Blowdown (gpm)

or Circulating Water (Calcium Hardness) / Make-up Water (Calcium Hardness)

Make-up Water (gpm) =
Rate of Evaporation (gpm) + Rate of Blowdown (gpm)
Rate of Evaporation (gpm) =
Circulating Water Flow Rate (gpm) x Cooling Range (<F) x 0.0008
Rate of Blowdown (gpm) =
Rate of Evaporation (gpm) / Number of Concentrations - 1

Rate of Drift Loss, which is approximately 0.02 % of the Circulating Water Flow rate, is not considered in the above formulas.

File details come from the government source that posted it. Updated .