Exhibit4_640-14-123P_SCI Refresh_STRUCTUALCALC.pdf
PDF 2 MB Posted
- Solicitation number
- 36C26122R0083
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26122R0083 0003.pdf | ||
| 36C26122R0083 0002.pdf | ||
| SITE VISIT LOG 36C26122R0083.pdf | ||
| 36C26122R0083 0001.pdf | ||
| Exhibit1_640-14-123P_SCI Refresh_DRAWINGS.pdf | ||
| S02 - RFI Form - 36C26122R0083.docx | DOCX document | |
| Exhibit 3 ICRA Form.pdf | ||
| 36C26122R0083.pdf | ||
| S02 Attachment C_Contractor Certification RE Safety and EMR.docx | DOCX document | |
| S02 Attachment B_Price Breakdown.xlsx | XLSX spreadsheet | |
| Exhibit2_640-14-123P_SCI Refresh_SPECS.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1440 E Missouri Ave
Suite C195
Phoenix, AZ 85014 p.602.888.0336 www.pangolinstr.com
STRUCTURAL CALCULATIONS
VA Palo Alto Building 7 SCI Refresh
Building 7 VA Palo Alto
3801 Miranda Ave, Palo Alto, CA 94304
21-144
Rev 2 - as clouded11/5/2021
PAMELA E.
SINGLETON
STRUCTURAL
S 005889
EXP. 9/30/2023
11/5/2021
Sheet No. _________________
Project No. _________________
Project Name______________________________________________ Date __________________
Subject __________________________________________________ Computed By __________________
VA Palo Alto B7 SCI Refresh
21-144
9/2021
Project Description
The structural scope for this project involves support of new patient lifts in Wing D, Wing F, Wing C, and Wing A of Building 7.
Existing Conditions:
Wings C and D are 2-story (basement and Level 1) cast-in-place concrete structure built in 1960. The floor and roof are constructed of cast-in-place concrete flat slabs spanning to concrete beams and concrete columns and shear walls.
Wing A was constructed at the same time as Wings C and D and is similar, but floors and roof consist of concrete joists in lieu of flat slabs.
Wing F is a 2-story (basement and level 1) steel framed structure built in approximately 1986. The floor is composite concrete over steel deck spanning between wide flange beams and girders, and the roof consists of 3” x 18GA steel deck spanning between wide flange beams (W12 through W18) spaced at 10’-0” o.c. maximum.
Patient Lifts:
Maxi Sky 2 by ARJO, 600lb capacity
EXIT
LITTER
BATHROOM
SCI/D BED
DN
H-B
EXIT
H-B
KEY PLAN NTS NORTH
WING D
WING F
WING E
WING A
BC
A
D
This area between grids 52 and 47 and Z and W is called Wing C on existing drawings. Is it called part of Wing E now
F
E
Note: The area between grids 52 and 47 and Z and W is noted as Wing C on existing drawings (1986 and earlier) but is now referred to as part of wing E. The area was constructed as Wing C with cast-in-place concrete slabs built in 1960. For the purposes of these calculations based on existing structure, we refer to that area as Wing C as we reference existing structural drawings for Wing C.
Project Name______________________________________________ Date __________________
VA Palo Alto SCI Refresh
9/2021
Lift Supports
Scenario 1: Lift at Existing Concrete Slab - Wings C and D
Max Vertical Load for concrete anchorage design:
1.2*50lb + 1.6*750lbs = 1260 lbs tension
Lift rails hang directly from concrete slab
600lb lift capcity, design load = 750lbs Lift Weight = 27 lbs Design Unistrut Support for 800lbs to include 750lb design load + 27 lb lift weight + 23 lbs track weight tributary
*See Hilti Profis Report for Anchor Design
3/8"Ø THREADED ROD
P1001 X 1'-0" LONG AT EACH
HANGER
UNISTRUT P1000
BRACE WITH P1546
AND 1/2" Ø BOLTS
AND CHANNEL
NUTS EACH END.
BRACE IN BOTH
DIRECTIONS
L4X4X1/4 X 8" WITH (2) 1/2"Ø
EXPANSION ANCHORS -
EMBED 3 1/4" AT 5" O.C.
UNISTRUT BRACE
WITH P1546 AND
1/2"Ø EXPANSION
ANCHOR - EMBED
3 1/4"
EXISTING CONCRETE SLAB
L2X2X1/4 X 4" LONG
3/16
NOTE:
1. BRACING OF EACH LIFT RAIL IN (2) DIRECTIONS
EACH END IS REQUIRED
2. LOCATE EXISTING REINFORCING IN SLAB PRIOR
TO INSTALLING ANCHORS AND AVOID
PATIENT LIFT RAIL
BY OTHERS
FINISHED CEILING - SEE
ARCHITECTURAL
DRAWINGS
P1000T ROD STIFFENER 8"
SHORTER THAN ROD WITH
ROD STIFFENER CLIPS AT
12" O.C.
NOT TO SCALES-301
21-144
201 TYPICAL UNISTRUT SUPPORT DETAIL FOR PATIENT LIFT
(Now Wing D and E) www.hilti.com
Hilti PROFIS Engineering 3.1.1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Specifier's comments:
1 Input data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (3 1/4)
Item number: not available
Effective embedment depth: hef,act = 3.250 in., hnom = 3.625 in.
Material: Carbon Steel
Evaluation Service Report: ESR-1917
Issued I Valid: 1/1/2020 | 5/1/2021
Proof: Design Method ACI 318-14 / Mech
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plateR : lx x ly x t = 4.000 in. x 8.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 6.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
Note: the Kwik Bolt TZ - CS anchor is in the process of phase-out.
Application also possible with Kwik Bolt TZ2 - CS under the selected boundary conditions.
Application also possible with Kwik Bolt TZ2 - CS 1/2 (3 1/4) under the selected boundary conditions.
More information in section Alternative fastening data of this report.
R - The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Geometry [in.] & Loading [lb, in.lb]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
1.1 Design results
Case Description Forces [lb] / Moments [in.lb] Seismic Max. Util. Anchor [%]
1 Combination 1 N = 1,300; Vx = 0; Vy = 0;
Mx = 0; My = 0; Mz = 0;
yes 33
Tension x y2 Load case/Resulting anchor forces
Anchor reactions [lb] Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 1 650 0 0 0 2 650 0 0 0 max. concrete compressive strain: - [‰] max. concrete compressive stress: - [psi] resulting tension force in (x/y)=(0.000/0.000): 1,300 [lb] resulting compression force in (x/y)=(0.000/0.000): 0 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status Steel Strength* 650 8,029 9 OK
Pullout Strength* 650 2,625 25 OK
Concrete Breakout Failure** 1,300 4,023 33 OK
* highest loaded anchor **anchor group (anchors in tension)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
3.1 Steel Strength
Nsa = ESR value refer to ICC-ES ESR-1917 f Nsa ³ Nua ACI 318-14 Table 17.3.1.1
Variables
Ase,N [in.2] futa [psi]
0.10 106,000
Calculations
Nsa [lb] 10,705
Results
Nsa [lb] f steel f nonductile f Nsa [lb] Nua [lb] 10,705 0.750 1.000 8,029 650
3.2 Pullout Strength
N pn,f'c
= Np,2500 l a (fc'/2500)0.5 refer to ICC-ES ESR-1917 f N pn,f'c ³ Nua ACI 318-14 Table 17.3.1.1
Variables f'c [psi] l a Np,2500 [lb] 3,000 1.000 4,915
Calculations
(fc'/2500)0.5
1.095
Results N pn,f'c [lb] f concrete f seismic f nonductile f N pn,f'c
[lb] Nua [lb] 5,384 0.650 0.750 1.000 2,625 650
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
3.3 Concrete Breakout Failure
Ncbg = (ANc ANc0
) y ec,N y ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1b) f Ncbg ³ Nua ACI 318-14 Table 17.3.1.1 ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) ANc0 = 9 h2 ef ACI 318-14 Eq. (17.4.2.1c) y ec,N = ( 1
1 + 2 e'
N 3 hef
) £ 1.0 ACI 318-14 Eq. (17.4.2.4) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-14 Eq. (17.4.2.5b) y cp,N = MAX(ca,min cac
1.5hef cac ) £ 1.0 ACI 318-14 Eq. (17.4.2.7b)
Nb = kc l a √f'c h 1.5 ef ACI 318-14 Eq. (17.4.2.2a)
Variables hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
3.250 0.000 0.000 ∞ 1.000 cac [in.] kc l a f'c [psi]
7.500 17 1.000 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb]
143.81 95.06 1.000 1.000 1.000 1.000 5,455
Results
Ncbg [lb] f concrete f seismic f nonductile f Ncbg [lb] Nua [lb] 8,253 0.650 0.750 1.000 4,023 1,300
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
4 Shear load
Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status Steel Strength* N/A N/A N/A N/A
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* N/A N/A N/A N/A
Concrete edge failure in direction ** N/A N/A N/A N/A
* highest loaded anchor **anchor group (relevant anchors)
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-14, Chapter 17, Section
17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c).
• Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) / Section 17.2.3.5.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a non-yielding attachment. Section 17.2.3.4.3 (d) / Section 17.2.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by w0.
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI 318-14, Section 17.8.1.
Fastening meets the design criteria!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Coordinates Anchor [in.]
Anchor x y c-x c+x c-y c+y
1 0.000 -2.500 - - - - 2 0.000 2.500 - - - -
6 Installation data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (3 1/4) Profile: no profile Item number: not available Hole diameter in the fixture: df = 0.562 in. Maximum installation torque: 480 in.lb Plate thickness (input): 0.250 in. Hole diameter in the base material: 0.500 in.
Recommended plate thickness: not calculated Hole depth in the base material: 4.000 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 6.000 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Hilti KB-TZ stud anchor with 3.625 in embedment, 1/2 (3 1/4), Carbon steel, installation per ESR-1917
6.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Manual blow-out pump • Torque controlled cordless impact tool
• Torque wrench
• Hammer x y
2.000 2.000
2.000 2.000
1.
5.
1.
4.
4.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
7 Alternative fastening
7.1 Alternative fastening data
Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (3 1/4)
Item number: 2210255 KB-TZ2 1/2x4 1/2
Effective embedment depth: hef,act = 3.250 in., hnom = 3.750 in.
Material: Carbon Steel
Evaluation Service Report: ESR-4266
Issued I Valid: 3/1/2021 | 12/1/2021
Proof: Design Method ACI 318-14 / Mech
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plateR : lx x ly x t = 4.000 in. x 8.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 6.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
Max. Utilization with Kwik Bolt TZ2 - CS 1/2 (3 1/4): 33 % Fastening meets the design criteria!
7.2 Installation data
Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (3 1/4) Profile: no profile Item number: 2210255 KB-TZ2 1/2x4 1/2 Hole diameter in the fixture: df = 0.562 in. Maximum installation torque: 602 in.lb Plate thickness (input): 0.250 in. Hole diameter in the base material: 0.500 in.
Recommended plate thickness: not calculated Hole depth in the base material: 4.250 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 5.500 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Hilti KB-TZ2 stud anchor with 3.75 in embedment, 1/2 (3 1/4), Carbon steel, installation per ESR-4266
7.2.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Manual blow-out pump • Torque controlled cordless impact tool
• Torque wrench
• Hammer
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor v2 Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
8 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you.
Project Name______________________________________________ Date __________________
9/2021
Lift Supports
Scenario 2: Fixed Track of Lift Perpendicular to steel roof Framing (Wing F)
600lb lift capcity, design load = 750lbs Lift Weight = 27 lbs Design Unistrut Support for 800lbs to include 750lb design load + 27 lb lift weight + 23 lbs track weight tributary
200200
(E) W14X22
(E) W14X22
(E) W18X119
(E
W X
(E
W X
WORST CASE - LOADED LIFT
OVER TO FIXED TRACK SIDE,
DIRECTLY AT MIDSPAN
Assume Unistrut spanning 10'-0" between beams, 800lb point load at center
P5001:
Span In
Max Allowable
Uniform Load Lbs
24 6,890* 36 6,890* 48 6,890* 60 6,420
72 5,350
84 4,590
96 4,020
108 3,570
120 3,210 x 0.5 (factor for point load at midspan) x 0.54 (factor unbraced length = 10')
= allowable point load = 867 lbs (OK)
P5001 OK for 10' span
Project Name______________________________________________ Date __________________
9/2021
Lift Supports
Scenario 3: Lift at Existing Concrete Joists - Wings A
Max Vertical Load for concrete anchorage design:
1.2*50lb + 1.6*750lbs = 1260 lbs Assume 80% of load to one side of unistrut/anchor = 1008 lbs (conservatively)
Lift rails hang from unistrut between existing concrete joists
600lb lift capcity, design load = 750lbs Lift Weight = 27 lbs Design Unistrut Support for 800lbs to include 750lb design load + 27 lb lift weight + 23 lbs track weight tributary
3/8"Ø THREADED ROD - ALIGN
DIRECTLY ABOVE RAIL SUPPORT
CONNECTION
UNISTRUT RAIL SUPPORT
P1001 X 1'-0" LONG
PATIENT LIFT RAIL BY OTHERS
UNISTRUT P1000 BRACE
WITH P1546 AND 1/2"Ø
BOLTS AND CHANNEL
NUTS EACH END
UNISTRUT P1000 OR EQUIVALENT
NOTE:
BRACING OF EACH LIFT RAIL IN (2)
DIRECTIONS IS REQUIRED
CEILING - SEE
ARCHITECTURAL
CONNECTION OF PATIENT LIFT
RAIL TO UNISTRUT BY OTHERS
CHANNEL NUT AND WASHER
P1000T ROD STIFFENER 8" SHORTER
THAN ROD WITH ROD STIFFENER
CLIPS AT 12" O.C.
UNISTRUT P1026 WITH 1/2"Ø BOLT
WITH CHANNEL NUT TO UNISTRUT
AND 1/2" DIA ADHESIVE ANCHOR
TO EXISTING CONCRETE JOIST -
EMBED 2" - PROVIDE BEVELED
WASHER AS REQUIRED
EXISTING CONCRETE
ROOF JOISTS
UNISTRUT P1026 WITH 1/2"Ø
BOLT WITH CHANNEL NUT
TO UNISTRUT AND 1/2" DIA
EXPANSION ANCHOR TO
EXISTING CONCRETE JOIST -
EMBED 2" - PROVIDE
BEVELED WASHER AS
REQUIRED
M
IN
STAGGER ADJACENT
ANCHORS 2" MIN
UNISTRUT P1000 OR
EQUIVALENT
M
IN
NOT TO SCALES-301
21-144
210 PATIENT LIFT SUPPORT AT EXISTING CONCRETE JOISTS
P1000 - beam loaDing
Span In
Max. Allowable Uniform Load
Lbs
Defl. at Uniform
Load In
24 1,690 0.06 36 1,130 0.13 48 850 0.22
Unistrut spanning 2'-0" between joists, assume 800lb point load at center x 0.5 (factor for point load at midspan) x 1.0 (factor unbraced length = 2')
= allowable point load = 845 lbs (OK)
*See HILTI PROFIS output (anchor ok)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Specifier's comments:
1 Input data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (2)
Item number: not available
Effective embedment depth: hef,act = 2.000 in., hnom = 2.375 in.
Material: Carbon Steel
Evaluation Service Report: ESR-1917
Issued I Valid: 1/1/2020 | 5/1/2021
Proof: Design Method ACI 318-14 / Mech
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plateR : lx x ly x t = 4.000 in. x 4.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 5.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
Note: the Kwik Bolt TZ - CS anchor is in the process of phase-out.
Application also possible with Kwik Bolt TZ2 - CS under the selected boundary conditions.
Application also possible with Kwik Bolt TZ2 - CS 1/2 (2) hnom2 under the selected boundary conditions.
More information in section Alternative fastening data of this report.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
1.1 Design results
Case Description Forces [lb] / Moments [in.lb] Seismic Max. Util. Anchor [%]
1 Combination 1 N = 0; Vx = -1,260; Vy = 0;
Mx = 0; My = 0; Mz = 0;
yes 69
1 x y2 Load case/Resulting anchor forces
Anchor reactions [lb] Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 1 0 1,260 -1,260 0 max. concrete compressive strain: - [‰] max. concrete compressive stress: - [psi] resulting tension force in (x/y)=(0.000/0.000): 0 [lb] resulting compression force in (x/y)=(0.000/0.000): 0 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status Steel Strength* N/A N/A N/A N/A
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
4 Shear load
Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status Steel Strength* 1,260 3,572 36 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1,260 1,844 69 OK
Concrete edge failure in direction x-** 1,260 1,829 69 OK
* highest loaded anchor **anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value refer to ICC-ES ESR-1917 f Vsteel ³ Vua ACI 318-14 Table 17.3.1.1
Variables
Ase,V [in.2] futa [psi] aV,seis
0.10 106,000 1.000
Calculations
Vsa,eq [lb] 5,495
Results
Vsa,eq [lb] f steel f nonductile f Vsa,eq [lb] Vua [lb] 5,495 0.650 1.000 3,572 1,260
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
4.2 Pryout Strength
Vcp = kcp [(ANc ANc0
) y ed,N y c,N y cp,N Nb ] ACI 318-14 Eq. (17.5.3.1a) f Vcp ³ Vua ACI 318-14 Table 17.3.1.1 ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) ANc0 = 9 h2 ef ACI 318-14 Eq. (17.4.2.1c) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-14 Eq. (17.4.2.5b) y cp,N = MAX(ca,min cac
1.5hef cac ) £ 1.0 ACI 318-14 Eq. (17.4.2.7b)
Nb = kc l a √f'c h 1.5 ef ACI 318-14 Eq. (17.4.2.2a)
Variables kcp hef [in.] ca,min [in.] y c,N
1 2.000 4.000 1.000 cac [in.] kc l a f'c [psi]
5.500 17 1.000 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ed,N y cp,N Nb [lb]
36.00 36.00 1.000 1.000 2,634
Results
Vcp [lb] f concrete f seismic f nonductile f Vcp [lb] Vua [lb] 2,634 0.700 1.000 1.000 1,844 1,260
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
4.3 Concrete edge failure in direction x-
Vcb = (AVc AVc0
) y ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1a) f Vcb ³ Vua ACI 318-14 Table 17.3.1.1 AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b) AVc0 = 4.5 c2 a1 ACI 318-14 Eq. (17.5.2.1c) y ed,V = 0.7 + 0.3( ca2 1.5ca1
) £ 1.0 ACI 318-14 Eq. (17.5.2.6b) y h,V = √1.5ca1 ha
³ 1.0 ACI 318-14 Eq. (17.5.2.8)
Vb = (7 ( le da
0.2
√da) l a √f'c c 1.5 a1 ACI 318-14 Eq. (17.5.2.2a)
Variables ca1 [in.] ca2 [in.] y c,V ha [in.] le [in.]
4.000 - 1.000 5.000 2.000 l a da [in.] f'c [psi] y parallel,V
1.000 0.500 3,000 1.000
Calculations
AVc [in.2] AVc0 [in.2] y ed,V y h,V Vb [lb]
60.00 72.00 1.000 1.095 2,862
Results
Vcb [lb] f concrete f seismic f nonductile f Vcb [lb] Vua [lb] 2,612 0.700 1.000 1.000 1,829 1,260
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-14, Chapter 17, Section
17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c).
• Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) / Section 17.2.3.5.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a non-yielding attachment. Section 17.2.3.4.3 (d) / Section 17.2.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by w0.
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI 318-14, Section 17.8.1.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Coordinates Anchor [in.]
Anchor x y c-x c+x c-y c+y
1 0.000 0.000 4.000 10.000 - -
6 Installation data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (2) Profile: no profile Item number: not available Hole diameter in the fixture: df = 0.562 in. Maximum installation torque: 480 in.lb Plate thickness (input): 0.250 in. Hole diameter in the base material: 0.500 in.
Recommended plate thickness: not calculated Hole depth in the base material: 2.625 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 4.000 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Hilti KB-TZ stud anchor with 2.375 in embedment, 1/2 (2), Carbon steel, installation per ESR-1917
6.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Manual blow-out pump • Torque controlled cordless impact tool
• Torque wrench
• Hammer x y
2.000 2.000
2.000 2.000
2.
2.
2.
2.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
7 Alternative fastening
7.1 Alternative fastening data
Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (2) hnom2
Item number: 2210254 KB-TZ2 1/2x3 3/4
Effective embedment depth: hef,act = 2.000 in., hnom = 2.500 in.
Material: Carbon Steel
Evaluation Service Report: ESR-4266
Issued I Valid: 3/1/2021 | 12/1/2021
Proof: Design Method ACI 318-14 / Mech
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plateR : lx x ly x t = 4.000 in. x 4.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 5.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
Max. Utilization with Kwik Bolt TZ2 - CS 1/2 (2) hnom2: 69 %
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
7.2 Installation data
Anchor type and diameter: Kwik Bolt TZ2 - CS 1/2 (2) hnom2
Profile: no profile Item number: 2210254 KB-TZ2 1/2x3 3/4 Hole diameter in the fixture: df = 0.562 in. Maximum installation torque: 602 in.lb Plate thickness (input): 0.250 in. Hole diameter in the base material: 0.500 in.
Recommended plate thickness: not calculated Hole depth in the base material: 2.750 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 4.000 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Hilti KB-TZ2 stud anchor with 2.5 in embedment, 1/2 (2) hnom2, Carbon steel, installation per ESR-4266
7.2.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Manual blow-out pump • Torque controlled cordless impact tool
• Torque wrench
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Hanger Anchor - In Joist Anchor at Hanger
Page:
Specifier:
E-Mail:
Date:
10/12/2021
8 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
Project Name______________________________________________ Date __________________
VA Palo Alto B7 Patient Safety Upgrades
9/2021
Lift Supports
Chanel nut capacity:
Channel
Channel Nut
Size- Thread Gauge
Allowable Pull-Out Strength Lbs (kN)
Resistance to Slip
Lbs (kN)
Torque Ft-Lbs (N•m)
P1000 P3000 P4400 P4526 P5000 P5500
8" - 9 12
2,500 1,700 *125
11.12 7.56 170
4" - 10 12
2,500 1,700 *125
11.12 7.56 170
8" - 11 12
2,500 1,500 *100
11.12 6.67 135
2" - 13 12
2,000 1,500 50
8.90 6.67 70
16" - 14 12
1,400 1,000 35
6.23 4.45 50
8" - 16 12
1,000 800 19
4.45 3.56 25 800 500 11
Allowable tension = 1000 lbs, allowable shear = 800lbs
OK for use in 3/8" hanger rods for lift support, 800 lb max tension
Threaded Rod Loads for Structural Applications
(Based on AISC, Steel Construction Manual, ASD, 14th Edition. Per AISC, Allowed
Tensile Stress = 0.33 * Fu)
Nominal Dia.
Nominal Area In2 (mm2)
Allowed Tension Load
Lbs (kN)
4 0.049 (31.6) 930 (4.14)
8 0.110 (71.0) 2,110 (9.39)
16 0.150 (96.8) 2,870 (12.77)
2 0.196 (126.5) 3,750 (16.68)
Threaded Rod capacity:
3/8" dia hanger rods OK for lift support (800lbs max)
Project Name______________________________________________ Date __________________
9/2021
Lift Supports
Seismic Bracing of Rails:
MOVING RAIL
FIXED RAILFIXED RAIL
20' max
' m ax
*Conservatively, assume patient is present during earthquake:
Design for 830lb seismic weight (conservatively)
Seismic Force at each fixed rail: 778 lbs - see spreadsheet on following page
Out-of-Plane: Brace each end of rail: Horizontal force = 390 lbs, brace force = 1.414*390lbs = 552lbs In-Plane: Brace for 778 lbs; brace force = 1.414*778lbs = 1100lbs
390 lbs390 lbs
390 lbs 390 lbs
778 lbs 778 lbs
Capacity of P1000 brace x 7' long (conservatively) = 1,860 lbs > 1100 (OK)
Unbraced Height
In
Max. Allowable Load at
Slot Face Lbs
Maximum Column Load Applied at C.G.
K = 0.65 Lbs
K = 0.80 Lbs
K =1.0 Lbs
K = 1.2 Lbs
24 3,550 10,740 9,890 8,770 7,740
36 3,190 8,910 7,740 6,390 5,310
48 2,770 7,260 6,010 4,690 3,800
60 2,380 5,910 4,690 3,630 2,960
72 2,080 4,840 3,800 2,960 2,400
84 1,860 4,040 3,200 2,480 1,980
P1000 - COLUMN LOADING
Capacity of P1546 fitting with 1/2" dia bolt and channel nut: 1500 lbs (OK)
Anchor in 6" thick concrete slab:
Design for Ω*Fp = 2.5*778lbs = 1.95k
See Hilti Profis Output, 1/2" dia expansion anchor, embed 3 1/4" in Flat Slab, Embed 2" in side of joist
Note: forces include weight of patient applied entirely to one fixed rail (worst case position). Seismic bracing loads on both fixed rails are not concurrent.
Project No 20-047
Date Jun-20
Project Name VA Palo Alto Computed By PS
Subject Patient Lifts
Lifts Hanging from Roof
Seismic Design Force F p
Fp = (ASCE 7-16, Eq. 13.3-1)
Fp max = 1.6SDSIpWp (ASCE 7-16 Eq. 13.3-2)
Fp min = 0.3SDSIpWp (ASCE 7-16 Eq. 13.3-3)
SDS = 1.359
Ip = 1.5 (Section 13.1.3)
Rp = 2.5 (Table 13.5-1 or 13.6-1) (similar to ceilings) ap= 1 (Table 13.5-1 or 13.6-1) (similar to ceilings) z = 15 (Height of component attachment to structure) h= 16 (Average roof height of structure)
Wp = 830 lbs (Component Weight)
Fp = 778 lbs
Fp max = 2707 lbs
Fp min = 508 lbs
Fp = 778 lbs
)21( 4.0 h z
I
R
WSa p p pDSp +
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Specifier's comments:
1 Input data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (3 1/4)
Item number: not available
Effective embedment depth: hef,act = 3.250 in., hnom = 3.625 in.
Material: Carbon Steel
Evaluation Service Report: ESR-1917
Issued I Valid: 1/1/2020 | 5/1/2021
Proof: Design Method ACI 318-14 / Mech
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.250 in.
Anchor plateR : lx x ly x t = 2.000 in. x 2.000 in. x 0.250 in.; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 6.000 in.
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
Note: the Kwik Bolt TZ - CS anchor is in the process of phase-out.
Application also possible with Kwik Bolt TZ2 - CS under the selected boundary conditions.
Application also possible with Kwik Bolt TZ2 - CS 1/2 (3 1/4) under the selected boundary conditions.
More information in section Alternative fastening data of this report.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
1.1 Design results
Case Description Forces [lb] / Moments [in.lb] Seismic Max. Util. Anchor [%]
1 Combination 1 N = 1,950; Vx = 0; Vy = 1,950;
Mx = 0; My = 0; Mz = 0;
yes 98
Tension
1 x y2 Load case/Resulting anchor forces
Anchor reactions [lb] Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 1 1,950 1,950 0 1,950 max. concrete compressive strain: - [‰] max. concrete compressive stress: - [psi] resulting tension force in (x/y)=(0.000/0.000): 1,950 [lb] resulting compression force in (x/y)=(0.000/0.000): 0 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status Steel Strength* 1,950 8,029 25 OK
Pullout Strength* 1,950 2,625 75 OK
Concrete Breakout Failure** 1,950 2,660 74 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
3.1 Steel Strength
Nsa = ESR value refer to ICC-ES ESR-1917 f Nsa ³ Nua ACI 318-14 Table 17.3.1.1
Variables
Ase,N [in.2] futa [psi]
0.10 106,000
Calculations
Nsa [lb] 10,705
Results
Nsa [lb] f steel f nonductile f Nsa [lb] Nua [lb] 10,705 0.750 1.000 8,029 1,950
3.2 Pullout Strength
N pn,f'c
= Np,2500 l a (fc'/2500)0.5 refer to ICC-ES ESR-1917 f N pn,f'c ³ Nua ACI 318-14 Table 17.3.1.1
Variables f'c [psi] l a Np,2500 [lb] 3,000 1.000 4,915
Calculations
(fc'/2500)0.5
1.095
Results N pn,f'c [lb] f concrete f seismic f nonductile f N pn,f'c
[lb] Nua [lb] 5,384 0.650 0.750 1.000 2,625 1,950
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
3.3 Concrete Breakout Failure
Ncb = (ANc ANc0
) y ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1a) f Ncb ³ Nua ACI 318-14 Table 17.3.1.1 ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) ANc0 = 9 h2 ef ACI 318-14 Eq. (17.4.2.1c) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-14 Eq. (17.4.2.5b) y cp,N = MAX(ca,min cac
1.5hef cac ) £ 1.0 ACI 318-14 Eq. (17.4.2.7b)
Nb = kc l a √f'c h 1.5 ef ACI 318-14 Eq. (17.4.2.2a)
Variables hef [in.] ca,min [in.] y c,N cac [in.] kc l a f'c [psi]
3.250 ∞ 1.000 7.500 17 1.000 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ed,N y cp,N Nb [lb]
95.06 95.06 1.000 1.000 5,455
Results
Ncb [lb] f concrete f seismic f nonductile f Ncb [lb] Nua [lb] 5,455 0.650 0.750 1.000 2,660 1,950
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
4 Shear load
Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status Steel Strength* 1,950 3,572 55 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1,950 7,638 26 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* highest loaded anchor **anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value refer to ICC-ES ESR-1917 f Vsteel ³ Vua ACI 318-14 Table 17.3.1.1
Variables
Ase,V [in.2] futa [psi] aV,seis
0.10 106,000 1.000
Calculations
Vsa,eq [lb] 5,495
Results
Vsa,eq [lb] f steel f nonductile f Vsa,eq [lb] Vua [lb] 5,495 0.650 1.000 3,572 1,950
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
4.2 Pryout Strength
Vcp = kcp [(ANc ANc0
) y ed,N y c,N y cp,N Nb ] ACI 318-14 Eq. (17.5.3.1a) f Vcp ³ Vua ACI 318-14 Table 17.3.1.1 ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) ANc0 = 9 h2 ef ACI 318-14 Eq. (17.4.2.1c) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-14 Eq. (17.4.2.5b) y cp,N = MAX(ca,min cac
1.5hef cac ) £ 1.0 ACI 318-14 Eq. (17.4.2.7b)
Nb = kc l a √f'c h 1.5 ef ACI 318-14 Eq. (17.4.2.2a)
Variables kcp hef [in.] ca,min [in.] y c,N
2 3.250 ∞ 1.000 cac [in.] kc l a f'c [psi]
7.500 17 1.000 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ed,N y cp,N Nb [lb]
95.06 95.06 1.000 1.000 5,455
Results
Vcp [lb] f concrete f seismic f nonductile f Vcp [lb] Vua [lb] 10,911 0.700 1.000 1.000 7,638 1,950
5 Combined tension and shear loads bN bV z Utilization bN,V [%] Status
0.743 0.546 5/3 98 OK
bNV = bz N + bz
V <= 1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-14, Chapter 17, Section
17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c).
• Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) / Section 17.2.3.5.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a non-yielding attachment. Section 17.2.3.4.3 (d) / Section 17.2.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by w0.
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI 318-14, Section 17.8.1.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Address:
Phone I Fax:
Design:
Fastening point:
Bracing Anchor Anchor at Brace
Page:
Specifier:
E-Mail:
Date:
10/12/2021
Coordinates Anchor [in.]
Anchor x y c-x c+x c-y c+y
1 0.000 0.000 - - - -
7 Installation data
Anchor type and diameter: Kwik Bolt TZ - CS 1/2 (3 1/4) Profile: no profile Item number: not available Hole diameter in the fixture: df = 0.562 in. Maximum installation torque: 480 in.lb Plate thickness (input): 0.250 in. Hole diameter in the base material: 0.500 in.
Recommended plate thickness: not calculated Hole depth in the base material: 4.000 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 6.000 in.
Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.
Hilti KB-TZ stud anchor with 3.625 in embedment, 1/2 (3 1/4), Carbon steel, installation per ESR-1917
7.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Manual blow-out pump •…