Exhibit P_Design Review Checklist - Electrical.pdf

PDF 122 KB Posted

Attached to
X1AA--36C24722R0028 | Goose Creek Specialty Care Clinic | New Lease RLP
Solicitation number
36C24722R0028
Issued by

View the file

Other files

File Type Posted
Exhibit E_GSA3517B-16.pdf PDF
Exhibit M_Design Review Checklist - HVAC.pdf PDF
Exhibit C_ Security Level II Standards.pdf PDF
Exhibit V_Design Manual - HVAC.pdf PDF
Exhibit Q_Design Review Checklist - Architectural.pdf PDF
Exhibit CC_VA Handbook 0730 - Security and Law Enforcement.pdf PDF
Exhibit A_36C24722L0006 - Template Lease.pdf PDF
Exhibit S_Design Manual - Physical Security and Resiliency.pdf PDF
Exhibit D_GSA 3516-12.pdf PDF
Exhibit J_ Seismic Offer Forms.pdf PDF
Exhibit B_ Agency Space Requirements - Rev 1.pdf PDF
36C24722R0028_3.docx DOCX document
Exhibit EE_Design Guide - OIT - Standards Alert.pdf PDF
Exhibit Z_Space Planning - Eye Clinic.pdf PDF
Exhibit DD_Design Guide - Room Finishes.pdf PDF
Exhibit X_ Design Manual - Fire Protection.pdf PDF
Exhibit AA_Space Planning - Pulmonary.pdf PDF
Exhibit F_GSA 1364 - Proposal to Lease Space.pdf PDF
Exhibit G_GSA 1217 - Lessors Annual Cost Statement.pdf PDF
Exhibit W_Design Manual - Electrical.pdf PDF
Exhibit H_GSA12000-11.pdf PDF
Exhibit K_Telecommunications and Video Surveillance Services or Equipment.pdf PDF
Exhibit FF_Design Guide - OIT - Infrastructure Standard for Telecom Spaces.pdf PDF
Exhibit T_Design Manual - Lighting.pdf PDF
Exhibit Y_Design Manual - Architectural.pdf PDF
Exhibit U_Design Manual - Interior Design.pdf PDF
36C24722R0028.pdf PDF
Exhibit BB_VHA Directive 1061 - Legionella and Scald Prevention.pdf PDF
Exhibit R_Design Manual Plumbing.pdf PDF
Exhibit N_Design Review Checklist - Telecommunications.pdf PDF
Exhibit L_Other Standards and Requirements.pdf PDF
Exhibit I _ Davis Bacon Wage Rate.pdf PDF
Exhibit O_Design Review Checklist - Plumbing.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

June 1, 2020

ELECTRICAL

Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines:

Architectural, Electrical, Heating, Ventilating, and Air Conditioning

(HVAC),

Incineration/Solid Waste, Plumbing, Fire Protection, and Sanitary, Site and Landscape, Steam Distribution, Steam Generation, and Structural.

Reviewers should - Ensure that A/E Submission Instructions

(PG-18-15) for Schematic, Design Development, and Construction Documents are followed for various types of VA construction projects.

Reviewers should - Ensure that every VA construction project is in compliance with all life safety issues.

Reviewers should - Be aware that these checklists are not all-inclusive but only provide minimum review items.

DESIGN REVIEW CHECKLIST

TITLE________________________________PROJECT NO. ______________

LOCATION___________________________________DATE ______________

REVIEWED BY ___________________________________________________

ORGANIZATION _________________________________________________

The reviewer should be thoroughly familiar with the following VA standards before conducting a design review. These are available on the CFM Internet Web site: https://www.cfm.va.gov/til

ITEM DESCRIPTION

1. DESIGN MANUALS (PG-18-10)

2. MASTER CONSTRUCTION SPECIFICATIONS (PG-18-1)

3. STANDARD DETAILS (PG-18-4)

4. DESIGN AND CONSTRUCTION PROCEDURES (PG-18-3)

5. DESIGN GUIDES (PG-18-12)

6. DESIGN ALERTS

7. A/E SUBMISSION INSTRUCTIONS, PROGRAM GUIDE (PG-18-15)

8. VA & CAD STANDARDS

GENERAL INFORMATION FOR REVIEWERS

NO. ELECTRICAL – SCHEMATICS ITEM

COMMENTS/

YES/NO/NA

1 General Provisions for New Buildings - In addition to items given below check all requirements for buildings, switchgear rooms, transformer rooms, elevator machine rooms, electrical closets, telecommunications rooms, etc. per Design and Construction Procedures Topic 8 and the Electrical Design Manual.

a. Dual means of egress from transformer vaults, switchgear rooms, switchboard (over 1200 amps) rooms and generator rooms or buildings.

b. Stack Electrical Closets and Telecommunications Rooms vertically. Telecommunication Rooms shall not be located adjacent to Electrical closets which have transformers.

c. Show quantity of electrical closets on a floor: Maximum distance of the farthest branch circuit to the nearest closet shall not exceed 75 ft.

d. All closets shall be free of columns inside.

e. Electrical rooms shall be located above grade and above the Base

Flood Elevation – Refer to Physical Security Design Manual.

Electrical rooms shall not be located beneath toilets, showers, laboratories, kitchens, sinks, open courtyards, planters, roof drain leaders, cooling towers, or other areas where water service is provided. Pipes containing liquids or gases shall not pass through these rooms.

f. Provide doors that open under simple pressure leading from the switchgear rooms, electrical rooms, transformer vaults, generator rooms and elevator machine rooms. The doors shall swing in the direction of exit travel.

SCHEMATICS

NO. ELECTRICAL – SCHEMATICS ITEM

COMMENTS/

YES/NO/NA

g. Emergency Feeder-circuit Wiring shall meet the fire rating requirements per NEC 700.

2 Electrical metering for buildings as required in the VA Electrical Design Manual.

3 Coordinate drawings with other technical disciplines 4 Compliance with VA National CAD Standard Application Guide and applicable National CAD Standard modules

NO. ELECTRICAL – DESIGN DEVELOPMENT ITEM

YES/NO/NA

1 All electrical rooms, transformer vaults and closets shall not be located directly below showers, laboratories, kitchens, dishwashing areas or other areas where water service is provided. Pipe containing liquids or gases shall not pass through these rooms. See Physical Security Design Manual.

2 Compliance to Design and Construction Procedures/ NEC/…

a. Requirements for Essential Electrical system distribution follow

NEC 517-30/517-40 and Electrical Design Manual.

b. Requirements for Primary and Secondary transformation and distribution equipment are per Electrical Design Manual.

c. Receptacles, mounting heights as required in different areas (see Electrical Design Manual)

d. Raceways required in Fluoroscopic, Radiographic and Deep Therapy rooms (see Electrical Design Manual).

e. Raceway systems as required in Electrical Design Manual.

(1) All wiring shall be installed in raceways.

(2) Underground raceways shall be encased in concrete.

3 Alarms: Nonflammable medical gas and medical- surgical vacuum systems. See Electrical Design Manual and NFPA 99.

a. Master alarm panels required at the telephone switchboard and engineering control center or boiler plant.

b. Area alarms provided at nurses’ stations where medical gas systems are installed.

4 Miscellaneous Alarms (see Electrical Design Manual), such as Blood Bank refrigeration, Medical Gas System Alarm and others.

5 Electrical sub-metering equipment as required by the Electrical Design Manual, and sustainability requirements.

6 Lightning Protection System: See Electrical Design Manual.

DESIGN DEVELOPMENT

NO. ELECTRICAL – DESIGN DEVELOPMENT ITEM

COMMENTS/

YES/NO/NA

7 Fire Alarm Systems: See Fire Protection Design Manual 8 Coordinate drawings with other technical disciplines 9 Compliance with VA National CAD Standard Application Guide and applicable National CAD Standard modules.

NO. ELECTRICAL – CONSTRUCTION DOCUMENTS ITEM

YES/NO/NA

1 Requirements for Essential and Standby Electrical System distribution

- follow Electrical Design Manual.

2 Requirements for primary and secondary transformation and distribution equipment (see Electrical Design Manual).

3 Receptacles, mounting heights as required in different areas (see Electrical Design Manual).

4 Raceways required in Fluoroscopic, Radiographic and Deep Therapy rooms (see Electrical Design Manual).

5 Raceway systems (see Electrical Design Manual):

a. Install all wiring in raceways.

b. Encase underground raceways in concrete.

6 Alarms: Nonflammable medical gas and medical- surgical vacuum systems (see Electrical Design Manual) and NFPA 99:

a. Master alarm panels required at the Telephone Console Room and Engineering Control Center.

b. Area alarms provided at nurses’ stations where medical gas systems are installed.

7 Miscellaneous Alarm Systems (see Electrical Design Manual): Blood Bank refrigeration, Medical Gas System Alarm and others.

8 Lightning Protection System: (see Electrical Design Manual).

9 Fire Alarm Systems: See Fire Protection Design Manual 10 Coordinate drawings with other technical disciplines 11 Compliance with VA National CAD Standard Application Guide and applicable National CAD Standard modules

CONSTRUCTION DOCUMENTS