About this file
This document is a set of mechanical and electrical specifications and drawings related to a renovation project for the Florida Department of Children and Families' (DCF) District Six offices in Palm Harbor, Florida.
The renovation project includes maintaining the existing wet pipe fire protection system, modifying the existing HVAC ductwork and air distribution, and performing electrical work such as adding new receptacles and lighting. The project requires a licensed professional engineer to design the fire protection, HVAC, and electrical systems in accordance with applicable codes and standards. The contractors must perform testing, adjusting, and balancing of the HVAC systems, and testing of the electrical system. The project also involves upgrading the existing fire alarm system to comply with current codes. The project timeline indicates the bids are due on 5/10/2022 with a planned award to follow.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
FIRE PROTECTION SYSTEM DESIGN CRITERIA (IN ACCORDANCE WITH
61G15-32.004)
1. DESIGN OF WATER BASED FIRE PROTECTION SYSTEMS:
A. THE FIRE PROTECTION DESIGN INCLUDES AUTOMATIC SPRINKLER
SYSTEM DESIGN AND DEDICATED FIRE PROTECTION WATER SOURCE
AND FIRE WATER MAINS.
B. FIRE PROTECTION ENGINEER OF RECORD: MR. W. RONALD MCILVEEN,
P.E. (P.E.#30270). THIS DESIGN IS DELEGATED TO THE FIRE PROTECTION
SYSTEM DELEGATED ENGINEER, IN ACCORDANCE WITH 61G15-30.006
COMPLY WITH 61G15-32.004.
C. GENERAL SCOPE OF WORK: AS PART OF THIS RENOVATION PROJECT,
MAINTAIN A FULLY SPRINKLERED BUILDING. COMPLY WITH NFPA 13
FOR THE TYPE OF HEADS. RE-USE EXISTING HEADS (WHERE THEY
MEET CODE) AND ADD NEW HEADS WHERE ADDITIONAL HEADS ARE
REQUIRED. MATCH THE STYLE AND TYPE OF EXISTING HEADS WHERE
THEY ARE VISIBLE WITHIN AN ENCLOSED ROOM . PROVIDE NEW HEADS,
AS REQUIRED. PROVIDE ALL REQUIRED DOCUMENTATION FOR THE
RENOVATED SPACES (PROVIDE SHOP DRAWINGS AND HYDRAULIC
CALCULATIONS, AS REQUIRED).
D. FOR THIS BUILDING, THE DELEGATED ENGINEER SHALL COMPLY WITH
61G15-32.001. SUBMIT CALCULATIONS AND SHOP DRAWINGS (SIGNED
AND SEALED PER FAC). SUBMIT SUPPLEMENTAL PRODUCT DATA FOR
SYSTEM COMPONENTS, AS REQUESTED BY THE AUTHORITY HAVING
JURISDICTION.
2. FOR THE ENTIRE BUILDING, MAINTAIN AN OPERATIONAL WET PIPE FIRE
PROTECTION SYSTEM IN ACCORDANCE WITH: THE FLORIDA FIRE
PREVENTION CODE 2020, 7TH EDITION; THE FLORIDA BUILDING CODE 2020,
7TH EDITION; AND THE REQUIREMENTS OF THE AUTHORITY HAVING
JURSIDICTION.
3. THIS FIRE PROTECTION DESIGN REQUIRES A LICENSED PROFESSIONAL
ENGINEER, AS PART OF THESE REQUIREMENTS.
4. DESIGN OF WATER BASED FIRE PROTECTION SYSTEM ENGINEERING
DOCUMENTS (PER 61G15-32.004,(A)):
A. POINT OF SERVICE FOR THE FIRE PROTECTION WATER SUPPLY:
EXISTING FIRE PROTECTION SERVICE ENTRANCE 1 OF 2 ENTERING
“ROOM 033 - SPRINKLER” FROM THE 8” WATER SUPPLY THAT SERVES
TWO WET PIPE FLOW SWITCH ZONES AND ONE DRY PIPE FLOW SWITCH
ZONE; AND EXISTING SERVICE ENTRANCE 2 OF 2 ENTERING “ROOM 108
- SPRINKLER” FROM THE 8” WATER SUPPLY THAT SERVES ONE WET
PIPE FLOW SWITCH ZONE.
B. NFPA STANDARDS (PER 2020, 7TH EDITION FLORIDA FIRE PREVENTION
CODE).
NFPA 13 - 2016
C. CLASSIFICATIONS OF HAZARD OCCUPANCY IN ACCORDANCE WITH
NFPA 13, CHAPTER 5:
LIGHT HAZARD OCCUPANCY: OFFICES
D. DESIGN APPROACH:
1) SYSTEM TYPE: WET PIPE SPRINKLER SYSTEM, COMPLYING WITH
NFPA STANDARD PREVIOUSLY REFERENCED.
2) DEVICE TEMPERATURE RATINGS: IN ACCORDANCE WITH NFPA 13
8.3.2.
3) SPRINKLER HEAD SPACING: IN ACCORDANCE WITH NFPA 13
CHAPTER 8
4) PIPING: DO NOT USE THREADABLE LIGHTWALL PIPE.
5) FIRE PROTECTION MATERIALS (PIPING, HANGERS, HEADS, ETC.) IN
UNCONDITIONED AND CONDITIONED AREAS: CORROSION
RESISTANT ONLY. PROVIDE GALVANIZED STEEL PIPING, SCREWED
FITTINGS, HANGERS, TRIM, ALL-THREAD RODS, AND ACCESSORIES.
E. CHARACTERISTICS OF WATER SUPPLY: EXISTING WATER SUPPLY FED
FROM TWO 8” WATER SUPPLIES INTO THE BUILDING.
F. FLOW TEST DATA: OBTAIN NEW TEST
DATE OF TEST:
BY:
HYDRANT #:
HYDRANT COEFFICIENT:
STATIC PRESSURE
RESIDUAL PRESSURE
PIT0OT:
FLOW:
G. VALVING AND ALARM: EXISTING TO REMAIN (EACH WITH CHECK VALVE
AND FLOW SWITCH). MAINTAIN FIRE ALARM FLOW AND TAMPER SWITCH
MONITORING.
H. MICROBIAL INDUCED CORROSION: NO MIC CORROSION WAS
REPORTED. RECONFIRM.
I. BACKFLOW PREVENTION AND METERING: EXISTING TO REMAIN.
IDENTIFY THE DETAILS IN THE FIRE PROTECTION SUBMITTAL.
J. YARD AND INTERIOR FIRE PROTECTION COMPONENTS: EXISTING TO
REMAIN. IDENTIFY THE DETAILS IN THE FIRE PROTECTION SUBMITTAL.
K. FIRE PUMP: NOT REQUIRED.
L. WATER STORAGE TANK: NOT REQUIRED.
M. OWNER'S CERTIFICATE. IN STORAGE OCCUPANCIES, THE OWNER'S
INFORMATION CERTIFICATE IS REQUIRED FROM THE PROPERTY
OWNER AS IT CLEARLY DEFINES THE STORAGE CONFIGURATION OF
THE SPACE FOR THE CURRENT AND FUTURE USE OF THE PROPERTY,
AS REQUIRED BY THE CODES AND STANDARDS SET FORTH IN
SUBSECTION 61G15-32.002(7), F.A.C.
FIRE PROTECTION
NOTES
FP-001
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
INCORPORATED
OA
RA
OUTSIDE AIR
RETURN AIR
SYMBOL DESCRIPTION
EA EXHAUST AIR
CFM CUBIC FEET PER MINUTE
SYMBOL DESCRIPTION
DRAWING NOTE: REFER TO
NOTES ON EACH DRAWING
SA SUPPLY AIR
NEW RETURN AIR INLET
NEW SUPPLY AIR OUTLET
EXISTING ROOFTOP AIR
CONDITIONING UNIT NUMBER
MECHANICAL LEGEND
EXISTING SUPPLY AIR OUTLET
EXISTING RETURN AIR INLET
AC-1
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
GENERAL MECHANICAL (HVAC) NOTES: (ALL "M" DRAWINGS)
M-1 REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR EXCEED
MINIMUM REGULATORY REQUIREMENTS INCLUDING:
FLORIDA BUILDING CODE: 2020, 7TH EDITION
FLORIDA FIRE PREVENTION CODE: 2020, 7TH EDITION
ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS
THAT MAY BE REQUIRED IN ORDER TO MEET CODE, PRIOR TO WORK
(ORDERING, ROUGHING OR INSTALLING).
M-2 COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING
ARCHITECTURAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL FOR
AVAILABLE SPACE, SEQUENCE OF INSTALLATION, AND INSTALLATION
REQUIREMENTS, PRIOR TO COMMENCING CONSTRUCTION. ADVISE THE
ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE
REQUIRED FOR THE WORK TO BE PERFORMED.
M-3 EXISTING FIELD CONDITIONS: THE CONTRACT DOCUMENTS INDICATE THE
DESIGN INTENT USING AVAILABLE INFORMATION. THE CONTRACTOR IS TO
ADVISE THE ARCHITECT IF EXISTING CONDITIONS DIFFER FROM THOSE
SHOWN. ALSO ADVISE THE ARCHITECT IF CODE OR SAFETY CONFLICTS
EXIST. THE CONTRACTOR IS REQUIRED TO INSPECT THE SITE (PRIOR TO
BID) TO BECOME FAMILIAR WITH CONDITIONS AND INSTALLATION DETAILS
THAT WILL AFFECT HIS WORK. CHANGES IN THE CONTRACT SUM AND
CONTRACT TIME WILL NOT BE ALLOWED BECAUSE OF FAILURE TO
INVESTIGATE FIELD CONDITIONS. ALL WORK IS NEW, UNLESS OTHERWISE
NOTED.
M-4 BASIS OF DESIGN: THE MECHANICAL CONTRACT DOCUMENTS HAVE BEEN
PREPARED USING THE FOLLOWING DATA IN THE CALCULATIONS
(SIMPLIFIED FOR PRESENTATION HERE):
INDOOR OUTDOOR
SUMMER 75 DB/50% RH 91 DB/79 WB
WINTER 70 DB 40 DB
WALL U VALUE: EXISTING
ROOF U VALUE: EXISTING
FLOOR U VALUE: EXISTING
GLASS U VALUE: EXISTING
GLASS SHGC VALUE: EXISTING
ADVISE THE ARCHITECT IF MODIFICATIONS TO THE BUILDING
CONSTRUCTION ARE MADE (TO DETERMINE EFFECT ON MECHANICAL
DESIGN AND EFFECT ON BUILDING ENERGY EFFICIENCY CALCULATIONS).
M-5 DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION OF AIR OUTLETS, AIR INLETS, AND OTHER CEILING ITEMS (TO
AVOID CONFLICTS). LOCATE ALL PIPING AND DUCTWORK IN FINISHED
ROOMS OR SPACES WITHIN CONCEALED LOCATIONS (FURRED CHASES OR
SUSPENDED CEILINGS, AS AVAILABLE). DO NOT LOCATE PIPING OR
DUCTWORK ABOVE ELECTRICAL SWITCHBOARDS OR PANELBOARDS.
M-6 SIZES: WHEN A PIPE OR A DUCT SIZE IS NOT INDICATED, SIZE THAT PIPE OR
DUCT USING THE LARGER ADJACENT UPSTREAM SIZE, UNLESS A SMALLER
SIZE IS APPROVED BY THE ARCHITECT. PROVIDE 3/4 INCH MINIMUM PIPE
SIZE, UNLESS SPECIFICALLY NOTED OTHERWISE. FOR SIZES NOT
INDICATED ON PLANS, REFER TO EQUIPMENT DETAILS, FLOW DIAGRAMS,
RISER DIAGRAMS, AND OTHER LOCATIONS IN THE CONTRACT DOCUMENTS
(DRAWINGS AND SPECIFICATIONS) FOR INFORMATION.
M-7 SEALS: REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE
RATED PARTITIONS. SEAL ALL PENETRATIONS OF RATED PARTITIONS.
M-8 VENTILATION:
A. MECHANICAL VENTILATION: THE SPACES ARE MECHANICALLY
VENTILATED. REFER TO SCHEDULE ON DRAWINGS.
MECHANICAL
LEGEND AND NOTES
M-001
MECHANICAL (HVAC) SPECIFICATIONS:
M 1 SCOPE OF WORK:
A. PERFORM A LIMITED TESTING OF THE EIGHT EXISTING ROOFTOP AC
UNITS BEING REUSED WITHOUT MODIFIED BRANCH DUCT SYSTEMS
IN ORDER TO VERIFY THEY COOL AND HEAT PROPERLY AND TO
IDENTIFY THE OPERATING ELECTRICAL CHARACTERISTICS OF THE
UNIT, PRIOR TO DUCT SYSTEM MODIFICATION.
B. PERFORM NEW WORK, AS IDENTIFIED ON THE DRAWINGS
(INCLUDING RELOCATION OF DIFFUSERS AND PROVIDING NEW
DIFFUSERS).
C. PERFORM STANDARD TESTING , ADJUSTING, AND BALANCING OF
THE EIGHT ROOFTOP AC SYSTEMS, AS SPECIFIED. INCLUDE T&B OF
THE UNIT AND EACH AIR OUTLET AND DAMPER IN THOSE SYSTEMS.
D. MAINTAIN OPERATIONAL EXISTING SYSTEMS THAT ARE NOT PART
OF THIS WORK.
M 2 PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW OPERATION OF
EACH SYSTEM WITH OWNER'S REPRESENTATIVE. PROVIDE ONE YEAR
WARRANTY ON ENTIRE SYSTEM. PROVIDE RECORD DRAWING
(CONTRACTOR FURNISHED PRINT). SUBMITTALS: SUBMIT PRODUCT
DATA FOR EACH NEW MECHANICAL DEVICE AND SUBMIT PRELIMINARY
AND FINAL TEST AND BALANCE REPORTS.
M 3 WORK IN EXISTING BUILDINGS:
A. DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE.
B. SALVAGE: RETURN ALL EXISTING NON-REUSED DEVICES TO THE
OWNER AS SALVAGE. REMOVE THESE DEVICES AS TRASH, IF
SPECIFICALLY AND INDIVIDUALLY ADVISED BY OWNER, AS PART OF
BASIC WORK.
C. CONTINUITY: MAINTAIN HVAC SERVICE TO OTHER AREAS
REMAINING IN OPERATION DURING CONSTRUCTION. ADVISE THE
OWNER OF ANY INTENDED INTERRUPTION IN SERVICE AT LEAST 24
HOURS BEFORE INTERRUPTION.
D. EXISTING ITEMS: EXISTING ITEMS WITHOUT WORK ARE SHOWN FOR
CLARITY ONLY. NOTE THAT ADDITIONAL EXISTING ITEMS WITHOUT
WORK MAY ALSO BE PRESENT.
M 4 ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM) PAINTED,
ALUMINUM ACCESS DOOR (WITH FULL HINGE AND KEY) FOR ACCESS TO
VALVES, EQUIPMENT, AND ACCESSORIES IN PLASTER, DRYWALL, OR
INACCESSIBLE CEILINGS OR IN WALLS. PROVIDE INSULATED ACCESS
DOORS (DO NOT SUBSTITUTE PANELS) IN DUCTWORK FOR ACCESS TO
DAMPERS AND OTHER OPERATING DEVICES (INCLUDING UPSTREAM OF
ELECTRIC RESISTANCE DUCT HEATERS AND AT DUCT MOUNTED SMOKE
DETECTORS). GROUP DEVICES AT ON LOCATION, AS AVAILABLE.
M 5 INSULATION:
A. NEW DUCTWRAP INSULATION: NEW SUPPLY AIR AND NEW MIXED
AIR DUCTS SERVING AHU: 2 INCH THICK FOIL FACED OWENS
CORNING FIBERGLASS TYPE 150 (OR AS APPROVED), R=8 (MINIMUM)
OUT-OF-PACKAGE.
B. INSTALLATION: PROVIDE INSULATION AT LOCATIONS WHERE
INSULATION IS INTERRUPTED (SUCH AS AT FIRE DAMPERS AND AT
FLEXIBLE DUCT CONNECTIONS), TO PREVENT CONDENSATION.
M 6 AIR DISTRIBUTION:
A. DUCTWORK:
1. NEW AHU DUCTWORK (SUPPLY AIR, RETURN AIR, MIXED AIR);
GALVANIZED STEEL, SMACNA 2 INCH PRESSURE CLASS,
SMACNA A SEAL CLASS
2. TEST EACH OF THE EIGHT DUCTWORK SYSTEMS FOR LEAKS
BEFORE INSULATING. LIMIT LEAKAGE TO 5 PERCENT.
3. DUCT DIMENSIONS INDICATE AIR FLOW SIZES.
4. AT CONTRACTOR'S OPTION, EQUAL AREA DUCTWORK HAVING A
MAXIMUM 4 TO 1 ASPECT RATIO MAY BE SUBSTITUTED FOR
DUCT DIMENSIONS SHOWN.
5. FLEXIBLE DUCTWORK (USED TO CONNECT TO SUPPLY AIR
OUTLETS: THERMAFLEX TYPE M-KE (OR AS APPROVED).
6. NEW BRANCH DUCT CONNECTIONS (POSITIVE AND NEGATIVE
PRESSURE): ON RECTANGULAR DUCTS, PROVIDE 45 DEGREE
ENTRY FITTINGS; ON CIRCULAR DUCTS, PROVIDE CONICAL TAPS
(WITH DAMPERS). PROVIDE THESE CONNECTIONS ON EACH
BRANCH DUCT CONNECTION FOR EACH SYSTEM; DO NOT
SUBSTITUTE “T” CONNECTIONS.
7. ELBOWS (POSITIVE AND NEGATIVE PRESSURE): PROVIDE LONG
RADIUS (FULL)ELBOWS OR TURNING VANES FOR ALL ELBOWS;
DO NOT SUBSTITUTE SQUARE ELBOWS.
8. INSTALL DUCTWORK AND ACCESSORIES IN ACCORDANCE WITH
SMACNA HVAC DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE (2020 EDITION).
B. AIR OUTLETS AND AIR INLETS: REFER TO SCHEDULE ON DRAWINGS.
1. NEW AIR OUTLET: BASIS OF DESIGN: 24X24 TITUS PAS-AA (OR AS
APPROVED), ALL ALUMINUM, ADJUSTABLE OPPOSED BLADE
DAMPER, TOP INSULATION BLANKET.
2. NEW AIR INLET: BASIS OF DESIGN: 24X24 TITUS PAR-AA (OR AS
APPROVED), WITHOUT RA DUCT CONNECTOR (FOR USE WITH A
CEILING RETURN AIR PLENUM).
M 7 CONTROLS:
A. IDENTIFY LOCATIONS OF EXISTING ROOM TEMPERATURE CONTROLS
FOR EACH OF THE EIGHT MODIFIED AC SYSTEMS.
M 8 TESTING, ADJUSTING AND BALANCING:
A. GENERAL: PERFORM TESTING, ADJUSTING, AND BALANCING OF
EACH THE EIGHT ROOFTOP AC SYSTEMS, INCLUDING THEIR:
1. ROOFTOP AC
2. ROOFTOP AC ELECTRIC HEATER
3. CEILING MOUNTED AIR OUTLETS
4. DUCTWORK MANUAL BALANCING DAMPERS
B. PERFORM TESTING USING AABC TOTAL SYSTEM BALANCE
PROCEDURES. USE DATA FOUND ON AABC FORMS IN THE
SUBMITTALS.
C. FAN SELECTION POINTS REPRESENT DESIGN AIR FLOW RATES,
EXCLUDING DUCT LEAKAGE LOSSES. PROVIDE ADDITIONAL
DUCTWORK SEALS FOR ANY NEW DUCTS THAT CAUSE THE LEAKAGE
RATE TO EXCEED THE 5%.
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
MECHANICAL
NOTES
M-002
NOTES (ALL MECHANICAL DRAWINGS):
1 EXISTING ROOFTOP AIR CONDITIONING UNITS THAT ARE NOT HAVING
DUCTWORK MODIFICATIONS ARE TO REMAIN EXISTING BEING RE-USED.
2 EXISTING ROOFTOP AND INDOOR EXHAUST FANS NOT BEING REWORKED
ARE TO REMAIN EXISTING BEING RE-USED.
10 EXISTING AC-1: TRANE MODEL EAC-240-A4E0A00, SERIAL NO. 14501124JA,
(DECEMBER 2014), 8,000 CFM SA, 400 CFM OA (5% OA). PRIOR TO WORK,
PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
11 EXISTING AC-2: AMERICAN STANDARD MODEL TCH-240-B400JB, SERIAL NO.
721101191D, (MAY 2007), 8,000 CFM SA, 400 CFM OA (5% OA). PRIOR TO
WORK, PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
12 EXISTING AC-10: CARRIER MODEL 50TC-D25-AFB6A0A0A0, SERIAL NO.
2917P28290 (JUNE 2017), 8,000 CFM SA, 400 CFM OA (5% OA). PRIOR TO
WORK, PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
13 EXISTING AC-14: CARRIER MODEL 50HC-D24-AFB6A0K0A0, SERIAL NO.
1720P15560, (APRIL 2020), 8,000 CFM SA, 400 CFM OA (5% OA). PRIOR TO
WORK, PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
14 EXISTING AC-16: AMERICAN STANDARD MODEL THC-240-B400JB, SERIAL NO.
718100502D, (MAY 2007), 8,000 CFM SA, 400 CFM OA (5% OA). PRIOR TO
WORK, PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
15 EXISTING AC-17: CARRIER MODEL 50HC-D24-AFB6A0A0A0, SERIAL NO.
1720P15559, (APRIL 2020), 8,000 CFM SA, 400 CFM OA (5% OA). PRIOR TO
WORK, PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
16 EXISTING AC-26: LENNOX MODEL LCA-088-HMG, SERIAL NO. 5600F00588,
(JUNE 2000), 3,000 CFM SA, 600 CFM OA (20% OA). PRIOR TO WORK,
PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
17 EXISTING AC-31: LENNOX MODEL LCA-036-HNIG, SERIAL NO. 5600F02919,
(JUNE 2000), 1,200 CFM SA, 200 CFM OA (17% OA). PRIOR TO WORK,
PERFORM GENERAL VERIFICATION OF UNIT MODEL NUMBER AND
PERFORMANCE (COOLING AND HEATING OPERATION). AFTER DUCTWORK
SYSTEM MODIFICATIONS, PROVIDE TESTING, ADJUSTING AND BALANCING,
AND SUBMIT RESULTS.
20 NEW AO AND NEW FLEX DUCT TO MAIN DUCT CONNECTION: USE ONLY NEW,
CONICAL CONNECTIONS TO MAIN DUCT (USE CONNICAL CONNECTION
FITTINGS WITHOUT DAMPERS).
21 RELOCATED AIR OUTLET: RE-USE FLEX DUCT IF LENGTH IS SATISFACTORY.
IF LENGTH IS NOT SUFFICIENT, PROVIDE NEW FLEX DUCT AND NEW
CONICAL CONNECTION TO MAIN DUCT. CLEAN EACH EXISTING AIR OUTLET
THAT IS BEING RE-USED IN EACH OF THE AREAS OF RENOVATION / ROOMS
BEING RENOVATED.
22 CONNECT NEW AIR OUTLETS TO EXISTING SUPPLY AIR DUCT MAIN USING A
FLEXIBLE DUCT (WITH SMACNA SUPPORTS) AND CONICAL CONNECTION TO
MAIN. SIZE FLEX DUCTS:
6” DIA, UP TO 130 CFM SA
8” DIA, 131 CFM SA TO 195 CFM SA
23 EIGHT FOOT HIGH PARTITION WALL (NOT FULL HEIGHT) IN FOURTEEN FOOT
HIGH CEILING AREAS. REFER TO ARCHITECTURAL DRAWINGS.
24 EXISTING WALL (AND DOOR, AS APPLICABLE) BEING DEMOLISHED.
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
AC-1
AC-11
AC-13
AC-5
AC-12
AC-9
AC-3 AC-4 AC-6
AC-8 AC-7
AC-19 AC-20
AC-18
AC-15
AC-21AC-24 AC-22
AC-25
AC-23
AC-27AC-30
AC-2
AC-10
AC-14
AC-16
AC-17
AC-31
AC-26
10 11
15 16
17 1
1 1 1
1 1
1 1
M-403
M-403
M-401
M-401
M-401
M-401
M-402
M-404
M-404
M-404
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
MECHANICAL - EXISTING FLOOR PLAN
SCALE: 1" = 20'-0"
N
MECHANICAL
EXISTING
FLOOR PLAN
M-100
REFER TO M-002
FOR KEYED NOTES.
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
BB-107 / WORK AREA
BB-101 / OFFICE
BB-102 / OFFICE
BB-103 /
OFFICE
BB-104 / OFFICE
BB-105 / OFFICE
BB-106 / OFFICE
AC-1
8X4 12X14 15X14 20X14 12X14 7X14
X1
X1
19X1418X1214X129X12 16X14
AC-10
21 (TYP.)
EXISTING
350 CFM
EXISTING
285 CFM
EXISTING
280 CFM
EXISTING
280 CFM
EXISTING
280 CFM
EXISTING
280 CFM
ERR
280 CFM
EXISTING
280 CFM
NEW
130 CFM
6"Ø
(AC-1)
NEW
130 CFM
6"Ø
(AC-1)
NEW
130 CFM
6"Ø
(AC-1)
EXISTING
350 CFM
ERR
280 CFM
ERR
280 CFM
EXISTING
280 CFM
EXISTING
280 CFM
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
ERR
ERR
ERREXISTING
22 (TYP.)
BB-108 / OFFICE
TO AC-2
EXISTING
260 CFM EXISTING
BB-111 / OFFICE
BB-112 / OFFICE
AC-26
26X14
X1
ERR
NEW
EXISTING
300 CFM
EXISTING
200 CFM
BB-109 / OFFICE BB-110 / OFFICE
24 24
TO AC-14 TO AC-14
ERR
250 CFM
NEW NEW
ERR
250 CFM
E EXISTING DEVICE TO REMAIN
ER EXISTING DEVICE TO BE
REMOVED
ERR EXISTING DEVICE REMOVED
AND RE-USED
N NEW DEVICE
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
MECHANICAL - PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
MECHANICAL
FLOOR PLANS
BASE BID
M-401
MECHANICAL -
PARTIAL FLOOR PLAN
N
MECHANICAL -
PARTIAL FLOOR PLAN
N
MECHANICAL -
PARTIAL FLOOR PLAN
N
REFER TO M-002
FOR KEYED NOTES.
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
BB-107 / WORK AREA
A1-101 / OFFICE
A1-102 / OFFICE
A1-103 / OFFICE
BB-101 / OFFICE
BB-102 / OFFICE
BB-103 /
OFFICE
BB-104 / OFFICE
BB-105 / OFFICE
BB-106 / OFFICE
AC-1
8X4 12X14 15X14 20X14 12X14 7X14
X1
X1
19X1418X1214X129X12 16X14
AC-10
30X14
X1
30X14
(TYP.)
EXISTING
350 CFM
EXISTING
285 CFM
EXISTING
280 CFM
EXISTING
280 CFM
EXISTING
280 CFM
EXISTING
280 CFM
ERR
280 CFM
EXISTING
280 CFM
NEW
130 CFM
6"Ø
(AC-1)
NEW
130 CFM
6"Ø
(AC-1)
NEW
130 CFM
6"Ø
(AC-1)
EXISTING
350 CFM
ERR
280 CFM
ERR
280 CFM
EXISTING
280 CFM
EXISTING
280 CFM
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
ERR
ERR
ERR
EXISTING
NEWNEW
NEW
EXISTING
250 CFMEXISTING
NEW
80 CFM
6"Ø
(AC-10)
NEW
80 CFM
6"Ø
(AC-10)
EXISTING
280 CFM
ERR
280 CFM
22 (TYP.)
E EXISTING DEVICE TO REMAIN
ER EXISTING DEVICE TO BE
REMOVED
ERR EXISTING DEVICE REMOVED
AND RE-USED
N NEW DEVICE
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
MECHANICAL - PARTIAL FLOOR PLAN
N
MECHANICAL
FLOOR PLANS
ALT. 1
M-402
REFER TO M-002
FOR KEYED NOTES.
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
A2-105 / OFFICE
A2-106 / OFFICE
A2-107 / OFFICE
A2-108 / OFFICE
A2-109 / OFFICE
A2-110 /
OFFICE
A2-103 / OFFICE
A2-102 / OFFICE
A2-101 / OFFICE
A2-104 / OFFICE
A2-111 / OFFICE
X1
X1
X1
8X
X1
X1
9X
9X
16X1212X127X12
TO AC-16
8X
TO AC-17TO AC-17
20 21 (TYP.)
ERR
ERR
230 CFM
ERR
EXISTING
ERR ERR
NEW
NEW ERR
NEW
NEW ERR
ERR
230 CFM
EXISTING
230 CFM
EXISTING
230 CFM NEW
130 CFM
6"Ø
(AC-17)
EXISTING
200 CFM
ERR
230 CFM
ERR
230 CFM
ERR
250 CFM
ERR
200 CFM
NEW
130 CFM
6"Ø
(AC-16)
22 (TYP.)
A2-112 / OFFICE
A2-113 / OFFICE
A2-114 / OFFICE
A2-115 / OFFICE
A2-116 / OFFICE
CONNECT TO
EXISTING 14X10
DUCT (AC-16).
8X10
TO
AC-16
8X10
TO
AC-16
EXISTING TO
8X10 DUCT
(AC-16)
NEW
ERR
NEW
NEW
ERR
ERR
250 CFM
NEW
130 CFM
6"Ø
(AC-16)
ERR
250 CFM
ERR
250 CFM
ERR
250 CFM
E EXISTING DEVICE TO REMAIN
ER EXISTING DEVICE TO BE
REMOVED
ERR EXISTING DEVICE REMOVED
AND RE-USED
N NEW DEVICE
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
MECHANICAL - PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
MECHANICAL
FLOOR PLANS
ALT. 2
M-403
MECHANICAL -
PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
REFER TO M-002
FOR KEYED NOTES.
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
A3-1212 /
WORK AREA
AC-31
16X12
X1
X1
EXISTING
300 CFM
EXISTING
300 CFM
EXISTING
EXISTING
EXISTING
300 CFM
EXISTING
300 CFM
A3-101 / WORK AREA
X1
X1
X1
X1
TO AC-10
30X14
EXISTING
350 CFM
EXISTING
EXISTING
EXISTING
EXISTING
200 CFM
EXISTING
150 CFM
EXISTING
250 CFM
A3-103 / WORK AREA
A3-102 / WORK AREA 23
X1
X1
X1
X1
9X
X1
X14TO AC-17 TO AC-17
(TYP.)
ERR
250 CFM
EXISTING
EXISTING
EXISTING
ERR
NEW
EXISTING
250 CFM
EXISTING
250 CFM
EXISTING
450 CFM
EXISTING
450 CFM
EXISTING
175CFM
ERR
200 CFM
NEW
200 CFM
8"Ø
(AC-17)
NEW NEW
EXISTING
400 CFM
E EXISTING DEVICE TO REMAIN
ER EXISTING DEVICE TO BE
REMOVED
ERR EXISTING DEVICE REMOVED
AND RE-USED
N NEW DEVICE
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
MECHANICAL
FLOOR PLANS
ALT. 3
M-404
MECHANICAL - PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
MECHANICAL - PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
MECHANICAL - PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
N
REFER TO M-002
FOR KEYED NOTES.
1 1
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
ELECTRICAL LEGEND
SYMBOL DESCRIPTION MOUNTING OR
AS INDICATED
CEILING LIGHTING FIXTURE. N/A
DRAWING NOTE: REFER TO NOTES ON
EACH DRAWING
N/A
NEW CONDUIT AND CONDUCTOR. N/A
RECEPTACLE 18" AFF OR
AS NOTED
J
EMERGENCY EXIT LIGHTING FIXTURE. N/A
JUNCTION BOX N/A
LIGHTING FIXTURE TYPE N/AA
COMMUNICATION OUTLET
VOICE / DATA / CATV
18" AFF OR
AS NOTED
SMS WALL SWITCH / MOTION SENSOR 48" AFF
CEILING LIGHTING FIXTURE WITH
EMERGENCY BATTERY PACK.
N/A
2214 / 22116
ISSUE DATE
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
ELECTRICAL
LEGEND AND NOTES
E-001
ELECTRICAL SPECIFICATIONS:
E 1 SCOPE OF WORK:
A. PRIOR TO WORK, FIELD IDENTIFY EACH EXISTING CIRCUIT SERVING
THE AREAS / ROOMS BEING RE-WORKED. IDENTIFY IF ANY CIRCUITING
IS DIFFERENT THAN IDENTIFIED ON THE CONTRACT DOCUMENTS
(SUBMIT DISCREPANCIES FOR REVIEW).
B. PROVIDE NEW CIRCUITING, AS INDICATED. INCREASE RECEPTACLE
BRANCH CIRCUIT SIZES FOR LONG DISTANCES, AS SPECIFIED.
C. PROVIDE NEW RECEPTACLES AND NEW RECEPACLE CIRCUITS, AS
INDICATED. RE-USE EXISTING BRANCH CIRCUITS WHERE
MODIFICATIONS ARE PERFORMEDON ON A BRANCH CIRCUIT, AS
INDICATED. REMOVE AND REWORK CIRCUITING IN WALLS WHERE
EXISTING RECEEPTACLES WERE LOCATED AND WILL BE REMOVED.
MAINTAIN CIRCUIT CONTINUITY, AS PART OF BASIC WORK.
D. PROVIDE NEW LIGHTING, AS INDICATED. PROVIDE RELOCATED
EXISTING FIXTURES, AS INDICATED. CLEAN ALL EXISTING LIGHTING
FIXTURES IN EACH OF THE AREAS OF RENOVATION / ROOMS BEING
RENOVATED. VERIFY THAT EACH MODIFIED LIGHTING CIRCUIT HAS AN
OPERABLE WALL SWITCH OR CONTROL, AS PART OF BASIC WORK.
E 2 PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW OPERATION OF
EACH SYSTEM WITH OWNER'S REPRESENTATIVE. PROVIDE ONE YEAR
WARRANTY ON ENTIRE SYSTEM. PROVIDE RECORD DRAWING
(CONTRACTOR FURNISHED PRINT). SUBMITTALS: SUBMIT PRODUCT DATA
FOR EACH NEW ELECTRICAL DEVICE.
E 3 WORK IN EXISTING BUILDINGS:
E. DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE.
F. SALVAGE: RETURN ALL EXISTING NON-REUSED DEVICES TO THE
OWNER AS SALVAGE. REMOVE THESE DEVICES AS TRASH, IF
SPECIFICALLY AND INDIVIDUALLY ADVISED BY OWNER, AS PART OF
BASIC WORK.
G. CONTINUITY: MAINTAIN ELECTRICAL SERVICE TO OTHER AREAS
REMAINING IN OPERATION DURING CONSTRUCTION. ADVISE THE
OWNER OF ANY INTENDED INTERRUPTION IN SERVICE AT LEAST 24
HOURS BEFORE INTERRUPTION.
H. EXISTING ITEMS: EXISTING ITEMS WITHOUT WORK ARE SHOWN FOR
CLARITY ONLY. NOTE THAT ADDITIONAL EXISTING ITEMS WITHOUT
WORK MAY ALSO BE PRESENT.
E 4 ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM) PAINTED
ALUMINUM ACCESS DOOR (WITH FULL HINGE AND KEY) FOR ACCESS TO
ELECTRICAL DEVICES, PULL BOXES, JUNCTION BOXES, AND ACCESSORIES
IN PLASTER, DRYWALL, OR INACCESSIBLE CEILINGS OR IN WALLS. GROUP
DEVICES AT ONE LOCATION, AS AVAILABLE.
E 5 WIRING: PROVIDE ONLY DUAL RATED THWN/THHN COPPER CONDUCTORS.
MINIMUM SIZE: NUMBER 12. DO NOT INSTALL MORE THAN THREE
CONDUCTORS (NOT COUNTING NEUTRAL) IN A RACEWAY THAT REQUIRES
NEC 310.15,(B),(2),(a) DERATING. INCREASE RECEPTACLE BRANCH CIRCUIT
SIZES WHERE THE CONDUCTOR LENGTH IS LONGER THAN 75 FT (CHANGE
FROM #12 CU TO #10 CU FOR LENGTHS BETWEEN 76 FT AND 150 FT, AND
CHANGE FROM #10 CU TO #8 CU FOR LENGTHS BETWEEN 151 FT AND 225
FT).
E 6 GROUNDING: PROVIDE A SEPARATE INSULATED GROUNDING CONDUCTOR;
IN RACEWAYS.
E 7 CONDUITS: INSTALL ALL WIRING IN METALLIC CONDUIT (EMT IN DRY
AREAS). MC CABLE MAY BE USED IN CONCEALED INDOOR LOCATIONS. THIS
PROJECT USES RETURN AIR CEILING PLENUMS.
E 8 DEVICES:
A. WALL SWITCH OCCUPANCY SENSOR: BASIS OF DESIGN: ACUITY
WSX-PDT-VA-WH (OR AS APPROVED). 1,200 VA LIMIMT, AT 277V, LISTED.
E 9 LIGHTING FIXTURES:
A. FURNISH AND INSTALL COMPLETE SYSTEM OF LIGHTING FIXTURES,
LAMPS, BALLASTS, ACCESSORIES, AND SUPPORT, AS INDICATED.
REFER TO DRAWINGS.
B. NEW TYPE “M” LIGHTING FIXTURE IN ROOMS WITH 14'-0” HIGH
CEILINGS: LITHONIA EPANL-2X4-7200LMHE-MVOLT, T-BAR CEILING
MOUNTING, 7200 LUMENS, 35K, 80CRI, LISTED, OR AS APPROVED. 50VA,
277V.
C. NEW TYPE “ME” LIGHTING FIXTURE IN ROOMS WITH 14'-0” HIGH
CEILINGS: LITHONIA EPANL-2X4-7200LMHE-MVOLT-E10WCP, T-BAR
CEILING MOUNTING, 7200 LUMENS, 35K, 80CRI, EM BATTERY PACK AND
REMOTE CLG TEST IN ADJ CLG TILE, LISTED, OR AS APPROVED. 50VA,
277V.
D. NEW TYPE “EXE” EXIT SIGN: LITHONIA LQM-S-W-R-MVOLT-ELN, T-BAR
CEILING MOUNTING, WHITE THERMOPLASTIC HOUSING, RED LETTERS
(MATCHING EXISTING EXITS), EM BATTERY PACK, LISTED, OR AS
APPROVED. 5 VA, 277V.
E. NOTE THAT THE NEW EMERGENCY LIGHTING FIXTURES AND NEW EXIT
SIGNS HAVE BEEN SPECIFIED WITH EMERGENCY BATTERY PACKS
EVEN THOUGH THEY ARE CONNECTED TO THE GENERATOR BACK-UP
POWER SYSTEM, FOR RELIABILITY REASONS. DO NOT DELETE THESE
EMERGENCY BATTERY BACK-UP POWER SUPPLIES BECAUSE THEY
ARE REQUIRED FOR THIS DESIGN. CODE (2017 NEC 700.10) REQUIRES
THE EMERGENCY POWER FOR EMERGENCY LIGHTING TO BE
COMPLETELY INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT.
ON THIS PROJECT, EXISTING NON-EMERGENCY LOADS ARE
CONNECTED TO PANELS EDP, HVLEM, AND REM1. IN ORDER TO
PROVIDE THE RELIABILITY REQUIRED IN NEC 700.10, EMERGENCY
BATTERY PACKS HAVE BEEN SPECIFIED FOR THE NEW EMERGENCY
LIGHTING SHOWN IN THESE CONTRACT DOCUMENT
E 10 TESTING: TEST MODIFIED ELECTRICAL SYSTEM AFTER COMPLETION AND
SUBMIT RESULTS TO ARCHITECT. TEST FOR GROUNDS AND SHORTS. TEST
ALL REUSED AND REFED EXISTING FIXTURES AND DEVICES. AS PART OF
THIS WORK, INSPECT AND TEST EACH EXISTING NEW DEVICE, WIRE AND
CIRCUIT BREAKER, FOR PROPER OPERATION (AND MEETING PRESENT
CODE REQUIREMENTS). TEST EACH CIRCUIT AND GROUND. ADVISE THE
ARCHITECT IF DEFICIENCIES ARE FOUND.
GENERAL ELECTRICAL NOTES (ALL "E" DRAWINGS)
E-1 REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR EXCEED
MINIMUM REGULATORY REQUIREMENTS INCLUDING:
FLORIDA BUILDING CODE: 2020, 7TH EDITION
FLORIDA FIRE PREVENTION CODE: 2020, 7TH EDITION
(INCLUDING 2017 NEC)
ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS
THAT MAY BE REQUIRED IN ORDER TO MEET CODE, PRIOR TO WORK
(ORDERING, ROUGHING, OR INSTALLATION).
E-2 COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING
ARCHITECTURAL, MECHANICAL, AND FIRE PROTECTION) FOR AVAILABLE
SPACE, SEQUENCE OF INSTALLATION, AND INSTALLATION REQUIREMENTS,
PRIOR TO COMMENCING CONSTRUCTION. ADVISE THE ARCHITECT OF ANY
CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE REQUIRED FOR
THE WORK TO BE PERFORMED.
E-3 EXISTING FIELD CONDITIONS: THE CONTRACT DOCUMENTS INDICATE THE
DESIGN INTENT USING AVAILABLE INFORMATION. THE CONTRACTOR IS TO
ADVISE THE ARCHITECT IF EXISTING CONDITIONS DIFFER FROM THOSE
SHOWN. ALSO ADVISE THE ARCHITECT IF CODE OR SAFETY CONFLICTS
EXIST. THE CONTRACTOR IS REQUIRED TO VISIT THE SITE (PRIOR TO THE
BID) TO BECOME FAMILIAR WITH CONDITIONS AND INSTALLATION DETAILS
THAT WILL AFFECT HIS WORK. CHANGES IN THE CONTRACT SUM AND
CONTRACT TIME WILL NOT BE ALLOWED FOR FAILURE TO INVESTIGATE
FIELD CONDITIONS. ALL WORK IS NEW, UNLESS NOTED OTHERWISE.
E-4 DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
LOCATIONS OF LIGHTING FIXTURES, SPEAKERS AND OTHER CEILING ITEMS.
ALSO COORDINATE LOCATIONS OF SWITCHES AND RECEPTACLES WITH
OTHER WORK. LOCATE ALL CONDUITS AND WIRING IN FINISHED ROOMS OR
SPACES WITHIN CONCEALED LOCATIONS (FURRED CHASES OR SUSPENDED
CEILINGS, AS AVAILABLE), UNLESS SPECIFICALLY NOTED OTHERWISE.
E-5 SIZES: WHEN A CONDUIT OR CONDUCTOR SIZE IS NOT INDICATED, SIZE
THAT CONDUIT OR CONDUCTOR USING THE LARGER ADJACENT UPSTREAM
SIZE (IN ACCORDANCE WITH THE NEC), UNLESS A SMALLER SIZE HAS BEEN
APPROVED BY THE ARCHITECT. PROVIDE 3/4 INCH MINIMUM CONDUIT
SIZE, UNLESS SPECIFICALLY NOTED OTHERWISE. FOR SIZES NOT
INDICATED ON PLANS, REFER TO EQUIPMENT DETAILS, RISER DIAGRAMS,
AND OTHER LOCATIONS IN THE CONTRACT DOCUMENTS (DRAWINGS AND
SPECIFICATIONS) FOR INFORMATION.
E-6 SEALS: REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE
RATED PARTITIONS. SEAL ALL PENETRATIONS OF RATED PARTITIONS.
AutoCAD SHX Text Wannemacher Jensen Architects, Inc.
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
ENGINEERING
Distribution
Project Number
TH
E
AR
CH
IT
EC
T'S C
OM
MO
N
LA
W C
OP
YR
IG
HT
A
ND
OT
HE
R
PR
OP
ER
TY
R
IG
HT
S
AR
E
HE
RE
BY
R
ES
ER
VE
D
IN
T
HE
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
P
RO
DU
CE
D
BY
T
HE
A
RC
HI
TE
CT
TH
ES
E
ID
EA
S, D
ES
IG
NS
, P
LA
NS
, D
RA
W
IN
GS
, A
ND
SP
EC
IF
IC
AT
IO
NS
S
HA
LL
N
OT
B E
RE
PR
OD
UC
ED
O
R
CO
NV
EY
ED
IN
A
NY
M
AN
NE
R
NO
R
AS
SI
GN
ED
T O
AN
Y
TH
IR
D
PA
RT
Y
W
IT
HO
UT
F
IR
ST
O
BT
AI
NI
NG
T
HE
EX
PR
ES
S
W
RI
TT
EN
P
ER
MI
SS
IO
N
OF
T
HE
A
RC
HI
TE
CT
CO
NS
EN
T
IS
H
ER
EB
Y
GR
AN
TE
D
TO
G
OV
ER
NM
EN
TA
L
AG
EN
CI
ES
T O
RE
PR
OD
UC
E
TH
E
CO
NS
TR
UC
TI
ON
DR
AW
IN
GS
IN
C
OM
PL
IA
NC
E
W
IT
H
ST
AT
E
ST
AT
UT
ES
TO
T
HE
B
ES
T
OF
T
HE
A
RC
HI
TE
CT
'S
O R
EN
GI
NE
ER
'S
KN
OW
LE
DG
E, T
HE
P
LA
NS
A
ND
S
PE
CI
FI
CA
TI
ON
S
CO
MP
LY
W
IT
H
TH
E
AP
PL
IC
AB
LE
M
IN
IM
UM
B
UI
LD
IN
G
CO
DE
S
AN
D
TH
E
AP
PL
IC
AB
LE
F
IR
E
SA
FE
TY
ST
AN
DA
RD
S
AS
D
ET
ER
MI
NE
D
BY
T
HE
LO
CA
L
AU
TH
OR
IT
Y
IN
A
CC
OR
DA
NC
E W
IT
H
CH
AP
TE
RS
AN
D
3 O
F
TH
E
FL
OR
ID
A
ST
AT
UT
ES
(7
) 8
-5
St
. P ete rsb ur g, Flo rid a
1-
2 M irr or La ke D riv e N or th, U nit
AR
c
W an ne ma ch er Je ns en
A rch ite cts
, In c.
FL
OR
ID
A
DE
PA
RT
ME
NT
O
F
CH
ILD
RE
N
FA
MI
LIE
S
N or th Flo rid a A ve nu e, Ta mp a, FL
DI
ST
RI
CT
S
IX
O
FF
IC
ES
IN
TE
RI
OR
R
EN
OV
AT
IO
NS
36458 US. HWY 19 N,
PALM HARBOR, FL 34684
(727) 784-1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
AEIFL@aol.com
BIDS & PERMIT 05.10.2022
REVISION 07.15.20221
NOTES (ALL “E” DRAWINGS):
1 EXISTING MAIN SERVICE ENTRANCE ELECTRICAL ROOM TO REMAIN AND
BE RE-USED: “ROOM 027 - MAIN ELECTRICAL ROOM.” REFER TO EXISTING
SWITCHBOARD MDP, PANEL PP6, AND PANEL HVLPE.
2 EXISTING EMERGENCY / STANDBY POWER SUPPLY SYSTEM ROOM TO
REMAIN AND BE RE-USED: “ROOM 028 - EPSS ELECTRICAL ROOM.” REFER
TO PANELS EDP AND LEM (480Y/277) AND PANEL REM1 (208Y/120).
3 EXISTING ELECTRICAL ROOM SERVING THE NW AREA OF THE BUILDING
TO REMAIN AND BE RE-USED: “ROOM 142 - ELECTRICAL ROOM A.” REFER
TO RECEPTACLE PANELS LVLPA, LVLPAA, AND LVLPA3. REFER TO
LIGHTING PANEL HVLPA.
4 EXISTING ELECTRICAL ROOM SERVING THE SW AREA OF THE BUILDING
TO REMAIN AND BE RE-USED: “ROOM 320 - ELECTRICAL ROOM B.” REFER
TO RECEPTACLE PANELS LVLPB, LVLPBB, AND LVLPA3. REFER TO
LIGHTING PANEL HVLPB.
5 EXISTING ELECTRICAL ROOM SERVING THE NE AREA OF THE BUILDING
TO REMAIN AND BE RE-USED: “ROOM 1113 - ELECTRICAL ROOM C.”
REFER TO RECEPTACLE PANEL LVLPC, LVLPC2, AND LVLPC3. REFER TO
LIGHTING PANEL HVLPC.
6 EXISTING ELECTRICAL ROOM SERVING THE SE AREA OF THE BUILDING
TO REMAIN AND BE RE-USED: “ROOM 718 - ELECTRICAL ROOM D.” REFER
TO RECEPTACLE PANELS LVLPD, LVLPDD, AND LVLPD3. REFER TO
LIGHTING PANEL HVLPD.
7 EXISTING MAIN COMMUNICATIONS ROOM TO REMAIN AND BE RE-USED:
“ROOM 101 - TELEPHONE.”
8 EXISTING ELEVATOR EQUIPMENT ROOM TO REMAIN AND BE RE-USED:
“ROOM 023 - ELEVATOR EQUIPMENT ROOM.”
9 EXISTING ROOM CONTAINING THE EDWARDS FIRE ALARM CONTROL UNIT
(FACU): “ROOM 024 - MAINTENANCE.”
10 NEW POWER AND COMMUNICATIONS WORK IN THIS AREA.
11 NEW LIGHTING WORK IN THIS AREA.
20 REMOVE EXISTING POWER POLE AND CIRCUITING. MAINTAIN BRANCH
CIRCUIT CONTINUITY.
30 ROUTE OPEN OFFICE LIGHTING THROUGH A NEW CONTACTOR WITH
NEW TIMECLOCK CONTROL (IN ELECTRICAL ROOM) WITH MANUAL
OVERRIDE TO TURN OFF LIGHTING BASED ON A TIMECLOCK-OFF
SCHEDULE (PER FBC EC C405.2.2).
40 IN EACH OF THE RENOVATED ROOMS / AREAS OF THIS PROJECT, FIELD
IDENTIFY (SURVEY) THE EXISTING CIRCUITS SERVING EXISTING
RECEPTACLES IN EACH OF THE FOUR QUADRANTS OF THE BUILDING:
ELECTRICAL ROOM A (SERVING NW BUILDING AREAS) IN ROOM 142;
ELECTRICAL ROOM B (SERVING SW BUILDING AREAS) IN ROOM 320;
ELECTRICAL ROOM C (SERVING NE BUILDING AREAS) IN ROOM 1113;
ELECTRICAL ROOM D (SERVING SE BUILDING AREAS) IN ROOM 718.
RECIRCUIT USING SPARES, AND UNUSED EXISTING CB'S THAT WERE
MADE AVAILABLE WITH THIS RENOVATION.
50 IN THE RENOVATED ROOMS / AREAS, FIELD IDENTIFY (SURVEY) THE
EXISTING CIRCUITS SERVING THE EXISTING LIGHTING IN EACH OF THE
FOUR QUADRANTS OF THE BUILDING: ELECTRICAL ROOM A (SERVING
NW BUILDING AREAS) IN ROOM 142; ELECTRICAL ROOM B (SERVING SW
BUILDING AREAS) IN ROOM 320; ELECTRICAL ROOM C (SERVING NE
BUILDING AREAS) IN ROOM 1113; ELECTRICAL ROOM D (SERVING SE
BUILDING AREAS) IN ROOM 718. RECIRCUIT USING SPARES, AND UNUSED
EXISTING CB'S THAT WERE MADE AVAILABLE WITH THIS RENOVATION.
60 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-101 THROUGH BB-106, BB-107 WORK AREAS (NW AREA OF
BUILDING) - SEE DRAWING E-301: PROVIDE NEW SUB PANEL LVLPA2 IN
ROOM 142 TO ALLOW NEW POLES FOR NEW CB'S IN EXISTING PANEL
LVLPA IN ROOM 142. SEE DRAWING E-003.
61 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-108 WORK AREAS (SE AREA OF BUILDING) - SEE DRAWING
E-301: PROVIDE NEW SUB PANEL LVLPA2 IN ROOM 142 TO ALLOW NEW
POLES FOR NEW CB'S IN EXISTING PANEL LVLPA IN ROOM 142. SEE
DRAWING E-003.
62 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-111 AND BB-112 WORK AREAS (SE AREA OF BUILDING) -
SEE DRAWING E-301: PROVIDE NEW SUB PANEL LVLPD2 IN ROOM 718 TO
ALLOW NEW POLES FOR NEW CB'S IN EXISTING PANEL LVLPD IN ROOM
718. SEE DRAWING E-003.
63 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-109 AND BB-110 WORK AREAS (SE AREA OF BUILDING) -
SEE DRAWING E-301: PROVIDE NEW SUB PANEL LVLPD2 IN ROOM 718 TO
ALLOW NEW POLES FOR NEW CB'S IN EXISTING PANEL LVLPD IN ROOM
718. SEE DRAWING E-003.
64 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 1
AREAS BB-106, BB-107, A1-101, A1-102 THROUGH A1-103 WORK AREAS
(NW AREA OF BUILDING) - SEE DRAWING E-302: PROVIDE NEW SUB
PANEL LVLPA2 IN ROOM 142 TO ALLOW NEW POLES FOR NEW CB'S IN
EXISTING PANEL LVLPA IN ROOM 142. SEE DRAWING E-003.
65 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 2
AREAS A2-101 THROUGH A2-111 WORK AREAS (SW AREA OF BUILDING) -
SEE DRAWING E-303: PROVIDE NEW SUB PANEL LVLPB2 IN ROOM 320 TO
ALLOW NEW POLES FOR NEW CB'S IN EXISTING PANEL LVLPB IN ROOM
320. SEE DRAWING E-003.
66 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 2
AREAS A2-112 THROUGH A2-116 WORK AREAS (SW AREA OF BUILDING) -
SEE DRAWING E-303: PROVIDE NEW SUB PANEL LVLPB2 IN ROOM 320 TO
ALLOW NEW POLES FOR NEW CB'S IN EXISTING PANEL LVLPB IN ROOM
320. SEE DRAWING E-003.
67 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 3
AREAS A3-101 WORK AREAS (NW AREA OF BUILDING) - SEE DRAWING
E-304.
68 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 3
AREAS A3-102 AND A3-103 WORK AREAS (SW AREA OF BUILDING) - SEE
DRAWING E-304 PROVIDE NEW SUB PANEL LVLPB2 IN ROOM 320 TO
ALLOW NEW POLES FOR NEW CB'S IN EXISTING PANEL LVLPB IN ROOM
320. SEE DRAWING E-003.
69 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 3
AREAS A3-104 AND A3-105 WORK AREAS (NW AREA OF BUILDING) - SEE
DRAWING E-304.
70 NEW NORMAL POWER SERVING NEW LIGHTING CIRCUITING IN BASE BID
AREAS BB-101 THROUGH BB-106, BB-107 WORK AREAS (NW AREA OF
BUILDING) - SEE DRAWING E-301: MAKE CONNECTION TO EXISTING
NORMAL POWER LIGHTING CIRCUITS HVPLA-1,3. PERFORM
VERIFICATION OF NORMAL POWER MAXIMUM LOAD DRAW ON EXISTING
CB BEFORE AND AFTER CONNECTION OF NEW LIGHTING, TO VERIFY THE
CURRENT DEMAND IS LESS THAN 16A (80% OF 20/1 CB).
71 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-108 WORK AREAS (SE AREA OF BUILDING) - SEE DRAWING
E-301: MAKE CONNECTION TO EXISTING NORMAL POWER LIGHTING
CIRCUITS HVPLA-1,3. PERFORM VERIFICATION OF NORMAL POWER
MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
72 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-111 AND BB-112 WORK AREAS (SE AREA OF BUILDING) -
SEE DRAWING E-301: MAKE CONNECTION TO EXISTING NORMAL POWER
LIGHTING CIRCUITS HVPLD-7,9. PERFORM VERIFICATION OF NORMAL
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
73 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN BASE
BID AREAS BB-109 AND BB-110 WORK AREAS (SE AREA OF BUILDING) -
SEE DRAWING E-301: MAKE CONNECTION TO EXISTING NORMAL POWER
LIGHTING CIRCUITS HVPLD-1,3. PERFORM VERIFICATION OF NORMAL
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
74 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 1
AREAS BB-106, BB-107, A1-101, A1-102 THROUGH A1-103 WORK AREAS
(NW AREA OF BUILDING) - SEE DRAWING E-302: MAKE CONNECTION TO
EXISTING NORMAL POWER LIGHTING CIRCUITS HVPLA-1,3. PERFORM
VERIFICATION OF NORMAL POWER MAXIMUM LOAD DRAW ON EXISTING
CB BEFORE AND AFTER CONNECTION OF NEW LIGHTING, TO VERIFY THE
CURRENT DEMAND IS LESS THAN 16A (80% OF 20/1 CB).
75 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 2
AREAS A2-101 THROUGH A2-111 WORK AREAS (SW AREA OF BUILDING) -
SEE DRAWING E-303: MAKE CONNECTION TO EXISTING NORMAL POWER
LIGHTING CIRCUITS HVPLB-2,4. PERFORM VERIFICATION OF NORMAL
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
76 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 2
AREAS A2-112 THROUGH A2-116 WORK AREAS (SW AREA OF BUILDING) -
SEE DRAWING E-303: MAKE CONNECTION TO EXISTING NORMAL POWER
LIGHTING CIRCUITS HVPLB-2,4. PERFORM VERIFICATION OF NORMAL
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
77 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 3
AREAS A3-101 WORK AREAS (NW AREA OF BUILDING) - SEE DRAWING
E-304: MAKE CONNECTION TO EXISTING NORMAL POWER LIGHTING
CIRCUITS HVPLB-11,13. PERFORM VERIFICATION OF NORMAL POWER
MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
78 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 3
AREAS A3-102 AND A3-103 WORK AREAS (SW AREA OF BUILDING) - SEE
DRAWING E-304: MAKE CONNECTION TO EXISTING NORMAL POWER
LIGHTING CIRCUITS HVPLB-7,9,11. PERFORM VERIFICATION OF NORMAL
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
79 NEW NORMAL POWER SERVING NEW RECEPTACLE CIRCUITING IN ALT 3
AREAS A3-104 AND A3-105 WORK AREAS (NW AREA OF BUILDING) - SEE
DRAWING E-304: MAKE CONNECTION TO EXISTING NORMAL POWER
LIGHTING CIRCUITS HVPLB-7,9,11. PERFORM VERIFICATION OF NORMAL
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW LIGHTING, TO VERIFY THE CURRENT DEMAND IS
LESS THAN 16A (80% OF 20/1 CB).
80 NEW EMERGENCY LIGHTING POWER SERVING NEW EMERGENCY
LIGHTING CIRCUITING IN BASE BID AREAS BB-101 THROUGH BB-106,
BB-107 WORK AREAS (NW AREA OF BUILDING) - SEE DRAWING E-301:
MAKE CONNECTION TO EXISTING EMERGENCY POWER LIGHTING
CIRCUITS LEM-1,3,5. RECONFIRM. USE #10 CONDUCTOR FOR
EMERGENCY LIGHTING. PERFORM VERIFICATION OF EMERGENCY
POWER MAXIMUM LOAD DRAW ON EXISTING CB BEFORE AND AFTER
CONNECTION OF NEW EMERGENCY LIGHTING, TO VERIFY THE CURRENT
DEMAND IS LESS THAN 16A (80% OF 20/1 CB).
81 NEW EMERGENCY LIGHTING POWER SERVING NEW RECEPTACLE
CIRCUITING IN BASE BID AREAS BB-108 WORK AREAS (SE AREA OF
BUILDING) - SEE DRAWING E-301: MAKE CONNECTION TO EXISTING
EMERGENCY POWER LIGHTING CIRCUITS LEM-1,3,5. RECONFIRM. USE
#10 CONDUCTOR FOR EMERGENCY LIGHTING. PERFORM VERIFICATION
OF EMERGENCY POWER MAXIMUM LOAD DRAW ON EXISTING CB
BEFORE AND AFTER CONNECTION OF NEW EMERGENCY LIGHTING, TO
VERIFY THE CURRENT DEMAND IS LESS THAN 16A (80% OF 20/1 CB).
82 NEW EMERGENCY LIGHTING POWER SERVING NEW RECEPTACLE
CIRCUITING IN BASE BID AREAS BB-111 AND BB-112 WORK AREAS (SE
AREA OF BUILDING) - SEE DRAWING E-301: MAKE CONNECTION TO
EXISTING EMERGENCY POWER LIGHTING CIRCUITS LEM-7. RECONFIRM.
USE #10 CONDUCTOR FOR EMERGENCY LIGHTING. PERFORM
VERIFICATION OF EMERGENCY POWER MAXIMUM LOAD DRAW ON
EXISTING CB BEFORE AND AFTER CONNECTION OF NEW EMERGENCY
LIGHTING, TO VERIFY THE CURRENT DEMAND IS LESS THAN 16A (80% OF
20/1 CB).
83 NEW EMERGENCY LIGHTING POWER SERVING NEW RECEPTACLE
CIRCUITING IN BASE BID AREAS BB-109 AND BB-110 WORK AREAS (SE
AREA OF BUILDING) - SEE DRAWING E-301: MAKE CONNECTION TO
EXISTING EMERGENCY POWER LIGHTING CIRCUITS LEM-7. RECONFIRM.
USE #10 CONDUCTOR FOR EMERGENCY LIGHTING. PERFORM
VERIFICATION OF EMERGENCY POWER MAXIMUM LOAD DRAW ON
EXISTING CB BEFORE AND AFTER CONNECTION OF NEW EMERGENCY
LIGHTING, TO VERIFY THE CURRENT DEMAND IS LESS THAN 16A (80% OF
20/1 CB).
84 NEW EMERGENCY LIGHTING POWER SERVING NEW RECEPTACLE