Exhibit_B_Schedule-Sound_(4).pdf
PDF 62 KB Posted
- Attached to
- CI-171 Chiller for Campus
- Solicitation number
- 0000000903
- Issued by
- Ventura County, California
About this file
This file appears to be an Air Cooled Chiller Schedule specification sheet detailing technical requirements for HVAC equipment. The schedule specifies a single Daikin AWS300CDH chiller unit (CH-1) with a cooling capacity of 286.8 tons and an IPLV (Integrated Part Load Value) of 18.4 EER. The unit has physical dimensions of 325 inches length, 88 inches width, and 100 inches height, with a total weight of 23,350 pounds.
The technical specifications indicate the chiller operates on 460V/60Hz/3-phase power, uses R134-a refrigerant with a 420-pound charge, and features two screw compressors. The evaporator specifications show a water flow rate of 383.6/876.2 GPM, with a pressure drop of 6.6 ft H2O, entering water temperature (EWT) of 60°F, leaving water temperature (LWT) of 42°F, and is designed to operate with water as the fluid type. The condenser is specified to operate at an ambient temperature of 90°F.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Exhibit_D.pdf | ||
| IFB.pdf | ||
| Exhibit_A_.pdf | ||
| Exhibit_E.pdf | ||
| Exhibit_C_Bid_Form.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Condenser
Length Width Height Type Charge (lbs.) Type NO. Flow (GPM)
PD
(ft H2O)
EWT
(°F)
LWT
(°F)
Fluid Type Ambient (°F)
CH-1 Daikin AWS300CDH 286.8 18.4 325 88 100 23350 460/60/3 R134-a 420 Screw 2 383.6/876.2 6.6 60 42 Water 90
Air Cooled Chiller Schedule
VoltageTag Compressor
IPLV (EER)
EvaporatorRefrigerentDimensions (in.)
Weight (lbs.)Capacity (ton)ModelMfg.
Chiller
File details come from the government source that posted it. Updated .