Exhibit B - Modification Inspection Report.docx

DOCX document 237 KB Posted

Attached to
Master Agreement AZ|CTR067133
Contract number
CTR067133
Issued by
Arizona

About this file

This document is an Exhibit B Modification Inspection Report from the Arizona Department of Environmental Quality (ADEQ) for an Underground Storage Tank (UST) system modification. The report is a comprehensive inspection form designed to document detailed technical specifications, modifications, and compliance testing for underground storage tank systems, focusing on various components such as spill buckets, piping, dispensers, sumps, and release detection equipment.

The inspection report covers technical details of UST system modifications, including assessments of tank types, materials, corrosion protection, secondary containment, leak detection methods, and compliance with federal and state regulations (specifically 40 Code of Federal Regulations and Arizona Revised Statutes). The document meticulously tracks installation, testing, and verification of each UST system component, with specific attention to pressure tests, hydrostatic testing, interstitial monitoring, and ensuring compatibility with stored regulated substances. Key regulatory requirements include secondary containment standards, release detection protocols, and performance standards for new UST systems, with particular emphasis on preventing environmental contamination and ensuring system integrity.

View the file

Other files

File Type Posted
2023-1-1 Williams Co 18-214731 GAUWPP.pdf PDF
Attachment_-_Supplement_Insurance (1).pdf PDF
BPM005267 Attachment 1 Offer and Acceptance Form.pdf PDF
BPM005267 Past Performance Questionnaire Williams Co Consulting_SWB-6-21-23.pdf PDF
BPM005267 Solicitation Requirements.pdf PDF
CTR066266_BAFO_Document.pdf PDF
CTR0670133_Energy_EnvironmentalAdvisors_Contract_Extension_Amendment__1.pdf PDF
Email to confirm new RFP Requested for Existing Contract.pdf PDF
Exhibit A - UST Field Inspection Report.docx DOCX document
Exhibit E - UST Interior Lining Inspection Report.docx DOCX document
PDS - Jason Kocer.pdf PDF
PDS Non ADEQ Employee - Stephen Johnson.pdf PDF
State of Arizona Mail - Fwd_ 5622937 QUOTE Solicitation Advertisement Quote Request.pdf PDF
State of Arizona Mail - Re_ BPM005267 UST Inspections - Clarification Request (Environmental Technology).pdf PDF
CTR0670133_Energy_EnvironmentalAdvisors_Key_Personnel_Amendment__3.pdf PDF
2024.1.1 Energy & Environmental Advisors, Inc. GAUWCPP.pdf PDF
2026-1-1 Energy & Environmental Advisors, Inc. GAUWCPP.pdf PDF
Attachment___6.0_Certificates_Licenses.pdf PDF
Attachment___6.0_Certificates_Licenses_2.pdf PDF
BPM005267 Contract Award and Executive Summary_Determination - Executed.pdf PDF
BPM005267 Determination of Not Susceptible for Award.pdf PDF
BPM005267 Unsuccessful Letter.docx DOCX document
BPM005267_Solicitation_Attachments.docx DOCX document
CTR0670133_Energy_EnvironmentalAdvisors_Contract_Extension_Amendment__2.pdf PDF
Exhibit C - UST Closure Inspection Report.docx DOCX document
Exhibit F - Contractor Performance Report_ADEQ_July2019.docx DOCX document
PDS - Joey Kiker.pdf PDF
2024-01-01 Williams & Co Consulting GAUWCPP.pdf PDF
BPM005267 Award CTR066266.docx DOCX document
Procurement Request.pdf PDF
State of Arizona Mail - RE_ BPM005267 UST Inspections - Clarification Request (Williams & Co Consulting).pdf PDF
2025-1-1 Energy & Environmental Advisors, Inc. GAUWCPP.pdf PDF
Attachment_-_Company_Experience.pdf PDF
BPM005267 BAFO Consensus Evaluation Report - Executed.pdf PDF
BPM005267 BAFO.pdf PDF
BPM005267 Consensus Evaluation Report - Executed.pdf PDF
BPM005267 Executive Summary_Determination of Award - Executed.pdf PDF
BPM005267 Offer and Acceptance_CTR066266_Williams Co Consulting.pdf PDF
BPM005267 Responsibility Responsiveness Form.xlsx XLSX spreadsheet
BPM005267-UST_Inspections_-_Pricing_Sheet.xlsx XLSX spreadsheet
CTR066266_Williams___Co_Consulting_Pricing_Sheet.xlsx XLSX spreadsheet
Consent_to_Assignment_Executed_20230811.pdf PDF
Exhibit D - UST INSTALLATION INSPECTION REPORT.docx DOCX document
Exhibit G - QUALITY ASSURANCE PROJECT PLAN (QAPP) Checklist.docx DOCX document
State of Arizona Mail - RE_ 5622937 QUOTE Solicitation Advertisement.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BPM005267 Exhibit B

UST MODIFICATION INSPECTION REPORT

ARIZONA DEPARTMENT OF ENVIRONMENTAL QUALITY

1110 West Washington Street, Phoenix, Arizona 85007 ADEQ Help Line (In-State Only) 1-800-234-5677

INSPECTION INFORMATION
ADEQ Plan #
MD
Type(s) of Modification
☐ Spill Bucket(s)

☐ Overfill Prevention Device ☐ STP Sump(s) ☐ Piping ☐ Dispensers ☐ UDC Sumps(s) ☐ Entry Boots ☐ Other:

Reason for Modification

Closure of Existing System Components Date

Arrival Time

Departure Time

Pre-Burial Date

Arrival

Departure Time

Final Installation Date

Arrival

Departure Time

FACILITY INFORMATION

Facility Name

ADEQ Facility ID
0-0

Facility Address

City & ZIP

Facility County
Choose an item.
Tank Usage
Choose an item.Facility Status
Choose an item.
OWNER INFORMATION

UST Owner Name

Mailing Address

Owner Contact Name

Contact Title

Owner Contact Email

Contact Phone #

Owner Type
Choose an item.

SERVICE PROVIDER INFORMATION

Service Provider Company

Service Provider Address

Primary Contact

Position

Email Address

Primary Phone #

ENVIRONMENTAL COMPANY INFORMATION

Environmental Company

Company Address

Registered Professional

Office Phone #

Registered Professional Email

Primary Phone #

On-Site Rep Name / Title

On-Site Rep Email Address

Primary Phone #

Additional On-Site Personnel

Documented Depth to Groundwater?
‘ BGS

AZDEQ REPRESENTATIVE INFORMATION

AZDEQ Representative

AZDEQ Rep Title

Email
@azdeq.gov
Phone Number

Accompanied by

Title

UST INFORMATION - Complete one column for each compartment

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Tank Gallon Capacity
Compartmentalized Tank
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Compartment Sizes
Manifolded Tank
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Manifolded with (T#)
Method of Manifold
☐ Vent lines

☐ Product Lines ☐ Siphon Line ☐ Vent lines ☐ Product Lines ☐ Siphon Line ☐ Vent lines ☐ Product Lines ☐ Siphon Line ☐ Vent lines ☐ Product Lines ☐ Siphon Line ☐ Vent lines ☐ Product Lines ☐ Siphon Line

Location of Manifold

Tank Manufacturer

Tank Wall Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Tank Material Construction
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Tank Corrosion Protection
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Annular Space
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
COMMENTS

Complete for the installation or replacement of SPILL BUCKET(s) & ANCILLARY EQUIPMENT Complete one column for each containment sump

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
EXISTING SPILL BUCKET & ANCILLARY EQUIPMENT

Manufacturer & Model

Spill Containment Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
If Double Wall,

type of gauge

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Spill Containment

Size (Gallons)

Fill Cap / Adapter Manufacturer & Model

Overfill Device
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Does UST have both

ball float and flapper?

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Vapor Recovery

Cap / Adapter Manufacturer & Model

REPLACEMENT SPILL BUCKET & ANCILLARY EQUIPMENT

Manufacturer & Model

Spill Containment Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
If Double Wall,

type of gauge

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Spill Containment

Size (Gallons)

Reference: PEI/RP100-17, Section 7.2: SPILL CONTAINMENT

Spill Containment Integrity Test Date

Spill Containment Integrity Test Method
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Spill Containment was tested according to
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Is water within 1.5 inches of the top of the spill bucket?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
PRE-test Height

POST-test Height

Did the water level drop 1/8 inch or MORE
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Was a 30-inch water column of vacuum attained to start the test?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Is the ending vacuum level 26 inches water column or greater?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Spill Containment Integrity Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Fill Cap / Adapter Manufacturer & Model
Overfill Device
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Overfill Device Condition
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Does UST have both

ball float and flapper?

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Vapor Recovery

Cap / Adapter Manufacturer & Model

COMMENTS

Complete for the installation or replacement of STP SUMP(s) & ANCILLARY EQUIPMENT Complete one column for each STP sump

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
EXISTING STP SUMP & ANCILLARY EQUIPMENT

STP Containment Sump Manufacturer

STP Containment Sump Model

STP Sump Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
If Double Wall,

Type of annular space

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
If Double Wall,

Type of IM sensor

Entry Boot Manufacturer

REPLACEMENT STP CONTAINMENT SUMP & ANCILARY EQUIPMENT

STP Containment Sump Manufacturer

STP Containment Sump Model

STP Sump Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
If Double Wall,

Type of annular space

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
If Double Wall,

Manufacturer of IM sensor

If Double Wall, Model of IM sensor

Entry Boot Manufacturer

Entry Boot Model

Adhesive Manufacturer & Product Name

Adhesive Compatible with Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Reference: PEI/RP100-17, Section 8.5.4: CONTAINMENT SUMP TESTING.

STP Containment Hydrostatic Test Date

Is the water a minimum of 4 inches above the highest wall penetration?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
PRE-test Height

POST-test Height

Did the water level drop 1/8 inch or MORE
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
STP Containment Hydrostatic Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
GENERAL COMMENTS about STP Containment Sump Hydrostatic Testing

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
STP Turbine Manufacturer

STP Turbine Model

Line Leak Detector Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
STP Piping Connector
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
STP Corrosion Protection
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
STP Equipment Compatible with Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.

COMMENTS regarding STP SUMP and ANCILLARY EQUIPMENT

Complete for the replacement or addition of PIPING Complete one column for each PRODUCT

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
EXISTING PIPING INFORMATION
Existing Piping System Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Existing Piping Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Existing Piping Wall Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Existing Piping Material
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
(a): Length of existing piping
(b): Length of piping to be removed
-
-
-
-
-
(c): Length of replacement piping
+
+
+
+
+
(d): Length of new piping being added to the system
+
+
+
+
+

(e): Length of piping after modification/s:

(a) – (b) + (c) + (d)

=
=
=
=
=

(f): total length for replacement and new piping: (c) + (d)

(g): Percentage of new piping to total linear feet of all connected piping:

divide (f) by (a)

%
%
%
%
%

If the Existing Piping System Type is pressurized, and the Existing Piping Type is underground, and the Existing Piping Wall Type is single wall, and (g) is 50% or more, the existing piping must be brought into compliance with the secondary containment and release detection requirements for hazardous substance underground storage tank systems in 40 Code of Federal Regulations section 280.42 and the interstitial monitoring requirements in 40 Code of Federal Regulations section 280.43, subsection G

A.R.S. 49-1009 Tank Performance Standards (C) – Beginning January 1, 2009, a personal shall not install a new piping component that is twenty-five percent or more of the total linear footage of all connected piping of the underground storage tank unless all connected piping of the underground storage tank that conveys a regulated substance under pressure is brought into compliance with the secondary containment and release detection requirements for hazardous substance underground storage tank systems in 40 Code of Federal Regulations section 280.42 and the interstitial monitoring requirements in 40 Code of Federal Regulations section 280.43, subsection G. [THIS REQUIREMENT WAS UPDATED IN AZ HB 2043.]

AZ HB 2043 requires an underground storage tank system (UST) to comply with certain federal performance standards in effect on January 1, 2020, and requires the following to comply with the secondary containment performance standards for new USTs and release detection requirements for interstitial monitoring in 40 Code of Federal Regulations Section 280.43(g) and in effect on January 1, 2020:

(a) newly installed USTs; and

(b) any newly installed piping component that is 50% or more of the total linear footage of all connected piping in the UST and conveys a regulated substance.

NEW or REPLACEMENT PIPING INFORMATION

Piping Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Piping Wall Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Piping Material
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Piping Manufacturer

Adhesive (Glue) Brand

Is Piping Compatible with Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Pressure Test Date

PRIMARY

Test Pressure at START of Pressure Test

psi
psi
psi
psi
psi

PRIMARY

Test Pressure at END of Pressure Test

psi
psi
psi
psi
psi

PRIMARY

Pressure Test Results

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Pressure Test Date

SECONDARY

Test Pressure at START of Pressure Test

psi
psi
psi
psi
psi

SECONDARY

Test Pressure at END of Pressure Test

psi
psi
psi
psi
psi

SECONDARY

Pressure Test Results

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
COMMENTS

Complete for the addition or replacement of DISPENSERS or UNDER-DISPENSER CONTAINMENT SUMPS

EXISTING DISPENSER EQUIPMENT (BEFORE modification)

Dispenser Description
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Number of Dispensers

Dispenser Manufacturer (if available)

Dispenser Model

Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
UDC Sump Manufacturer

UDC Sump Model

UDC Sump Wall Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
UDC Sump Constr Material
Choose an item.
Choose an item.
Choose an item.
Choose an item.
Choose an item.
Piping Connector in UDC
Choose an item.
Choose an item.
Choose an item.
Choose an item.
Choose an item.

Piping Connector Mfgr

Shear Valve Manufacturer

Shear Valve Model

Quantity of Shear Valves

40 CFR 280.20(f) Dispenser systems. Each UST system must be equipped with under-dispenser containment for any new dispenser system installed after April 11, 2016.

(1) A dispenser system is considered new when both the dispenser and the equipment needed to connect the dispenser to the underground storage tank system are installed at an UST facility. The equipment necessary to connect the dispenser to the underground storage tank system includes check valves, shear valves, unburied risers or flexible connectors, or other transitional components that are underneath the dispenser and connect the dispenser to the underground piping.

(2) Under-dispenser containment must be liquid-tight on its sides, bottom, and at any penetrations. Under-dispenser containment must allow for visual inspection and access to the components in the containment system or be periodically monitored for leaks from the dispenser system.

NEW or REPLACEMENT DISPENSER EQUIPMENT (AFTER modifications)

Dispenser Description
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Number of Dispensers

Dispenser Manufacturer

Dispenser Model

Dispenser Condition
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Product at Dispenser
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
UDC Sump Manufacturer

UDC Sump Model

UDC Sump Wall Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
UDC Sump Constr Material
Choose an item.
Choose an item.
Choose an item.
Choose an item.
Choose an item.

Entry Boot Manufacturer

Entry Boot Model

Adhesive Manufacturer & Product Name

Adhesive Compatible with Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Piping Connector in UDC
Choose an item.
Choose an item.
Choose an item.
Choose an item.
Choose an item.

Piping Connector Mfgr

Piping Connector Model

Shear Valve Manufacturer

Shear Valve Model

Quantity of Shear Valves

COMMENTS

SAMPLING OF PIPING and DISPENSING AREAS
DISPENSERS
PIPING
Is water present beneath the piping or dispensers?
Choose an item.Choose an item.
Is sheen or free product observed beneath the piping or dispensers?
Choose an item.Choose an item.
If water or sheen is present, was the water sampled?
Choose an item.Choose an item.
Documented number of water samples collected in the Piping and Dispensing Area
If groundwater is present in the piping and dispensing areas, were soil samples collected from native soils along the excavation walls at the soil-water interface?
Choose an item.Choose an item.
Bedrock or Caliche encountered beneath the piping or dispensers?
Choose an item.Choose an item.
If bedrock or caliche was encountered beneath the piping or dispensers, were samples of fine grained backfill material collected?
Choose an item.Choose an item.
X’ from grade to native soil in piping and dispensing areas.
‘ BGS
‘ BGS
Time between removing the piping and sampling
N/A
Were soil samples collected every 20 linear feet?
Choose an item.Choose an item.
Were soil samples collected in native soil beneath each elbow, joint, fitting, dispenser, ancillary equipment, and area of corrosion?
Choose an item.Choose an item.
Were multi-depth samples collected in the piping and dispensing areas?
Choose an item.Choose an item.
Range of documented sample collection depths beneath the piping and dispensers
From ‘ BGS to

‘ BGS

From ‘ BGS to

‘ BGS

Documented number of soil samples collected beneath dispensers and piping
Dispensers:
Piping:
The LOWEST PID reading of a sample collected in the piping and dispensing areas
ppm

‘ BGS

ppm

‘ BGS

The HIGHEST PID reading of a sample collected in the piping and dispensing areas
ppm

‘ BGS

ppm

‘ BGS

Evidence of Release in the Piping and Dispensing Areas? (add comments below)
☐ NONE

☐ Stained Soil ☐ Odor ☐ Elevated PID reading ☐ Vapor ☐ Sheen ☐ Free Product on Groundwater

☐ NONE

☐ Stained Soil ☐ Odor ☐ Elevated PID reading ☐ Vapor ☐ Sheen ☐ Free Product on Groundwater

Additional soil samples were collected below the initial set of samples where Evidence of Release occurred (add comments below)
Choose an item.Choose an item.
Inspector & consultant discussed collecting dual depth samples at each sampling location
Choose an item.
Inspector & consultant discussed the use of PID meter to field assess each soil sample
Choose an item.
Inspector & consultant coordinated sampling locations prior to collecting samples
Choose an item.
Sample Preservation Method
Choose an item.
Are required analytical laboratory methods for soil and/or groundwater samples accounted for on sample Chain-of-Custody?
Choose an item.
Comments regarding Sampling and/or Evidences of Release in the Piping and Dispensing Area

UDC & TRANSITION SUMP HYDROSTATIC TESTING

Reference: PEI/RP100-17, Section 8.5.4: CONTAINMENT SUMP TESTING.

SUMP Designation

Hydro Test Date

Is the water a minimum of 4 inches above the highest wall penetration?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
PRE-test Height

POST-test Height

Did the water level drop 1/8 inch or MORE?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Hydro Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
SUMP Designation

Hydro Test Date

Is the water a minimum of 4 inches above the highest wall penetration?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
PRE-test Height

POST-test Height

Did the water level drop 1/8 inch or MORE?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Hydro Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
SUMP Designation

Hydro Test Date

Is the water a minimum of 4 inches above the highest wall penetration?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
PRE-test Height

POST-test Height

Did the water level drop 1/8 inch or MORE?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Hydro Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
SUMP Designation

Hydro Test Date

Is the water a minimum of 4 inches above the highest wall penetration?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
PRE-test Height

POST-test Height

Did the water level drop 1/8 inch or MORE?
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Hydro Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
COMMENTS regarding UDC Sump Hydrostatic Testing

RELEASE DETECTION INFORMATION

Per R18-12-220. Performance Standards for New UST Systems (A) Owners and operators of a new UST system shall meet the requirements described in this Section in order to prevent releases due to structural failure, corrosion, or spills and overfills for as long as the UST system is used to store regulated substances. In addition, except for suction piping that meets the requirements of R18-12-241(C)(2)(a) through (e), tanks and piping installed or replaced after January 1, 2009 shall be secondarily contained and use interstitial monitoring in accordance with R18-12-243(G). Secondary containment shall be able to contain regulated substances leaked from the primary containment until they are detected and removed and prevent the release of regulated substances to the environment at any time during the operational life of the UST system. For cases where the piping to be replaced exceeds the percentage in A.R.S. § 49-1009(C), the entire piping run shall be secondarily contained.

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Automatic Tank Gauge (ATG)
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
ATG Manufacturer

ATG Model

Tank Annular Space
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Tank Interstitial Monitoring (IM)
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Tank IM Sensor Model

ATG Probe Model

Piping Leak Detector Type
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Piping IM
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Line Leak Detection Method
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Piping IM Sensors used in
Choose an item.Manufacturer

Model

Piping IM Sensors used in
Choose an item.Manufacturer

Model

Piping IM Sensors used in
Choose an item.Manufacturer

Model

Piping IM Sensors used in
Choose an item.Manufacturer

Model

Do all IM sensors rest on the base of the sump?
Choose an item.Are all IM sensors at the lowest point of the sump?
Choose an item.Are all IM sensors mounted in a true vertical position?
Choose an item.
Are jumpers used to connect sections of secondary containment of the piping
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
The secondary containment of the piping is open in
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Method used to open the secondary containment of the piping
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
GENERAL COMMENTS

about release detection and IM sensors

FINAL INSPECTION SYSTEM TESTING INFORMATION

Complete the items directly related to the modifications.

Tank ID #

Product
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Line Tightness Test Date
Line Tightness Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Line Leak Detector

Test Date

Line Leak Detector Test Results

Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Overfill Prevention Device Test Date
Overfill Prevention Device Test Result
Choose an item.Choose an item.Choose an item.Choose an item.Choose an item.
Leak Detection System Test Date
Leak Detection System Test Results
Choose an item.
Monitoring Certification Date
Monitoring Certification Result
Choose an item.
Testing Company

Testing Company Address

Testing Technician

ADEQ Testing Certification #

Technician’s Email

Primary Phone #

GENERAL COMMENTS about system testing

CLOSURE INSPECTION GENERAL COMMENTS

Service Provider’s Name

ADEQ Certification #

Service Provider’s Email

Primary Phone

Service Provider’s Signature

Date

Inspector’s Name

Inspector’s Email

Primary Phone

Inspector’s Signature

Date

PRE-BURIAL INSPECTION GENERAL COMMENTS

_______ I (the service provider) have personally verified that all UST system components installed for this inspection are compatible with the fuels that will be stored and are installed according to manufacturers’ instructions and the applicable installation standards and codes of practice in R18-12-220 and R18-12-281.

Concluded inspection. Debriefed service provider. Finalized report. Submitted report from site.

Service Provider’s Name

ADEQ Certification #

Service Provider’s Email

Primary Phone

Service Provider’s Signature

Date

Inspector’s Name

Inspector’s Email

Primary Phone

Inspector’s Signature

Date

FINAL INSPECTION GENERAL COMMENTS

_______ I (the service provider) have personally verified that all UST system components installed for this inspection are compatible with the fuels that will be stored and are installed according to manufacturers’ instructions and the applicable installation standards and codes of practice in R18-12-220 and R18-12-281.

Concluded inspection. Debriefed service provider. Finalized report. Submitted report from site.

Service Provider’s Name

ADEQ Certification #

Service Provider’s Email

Primary Phone

Service Provider’s Signature

Date

Inspector’s Name

Inspector’s Email

Primary Phone

Inspector’s Signature

Date

Modification Inspection, Page 15