Text version
US Consulat Anlage ( Servicevertrag) Wartungsplan Netz
General Data relating to Maintenance Contract
1.01 Quarterly Meeting of Facility Management US Consulate and Contractor
4.00 pces. x
1.02 365 days /24 hours on-call service including Saturdays/Sundays and public holidays for the switchgears
12.00 pces. x
1.03 Procurement of spare parts 365 days / 24 hours including Saturdays/Sundays and public holidays
12.00 pces. x
1.04 Project management and coordination 12.00 pces. x
1.05 Certified staff already checked by the Consulate x x x
1.06 Scope of Delivery and Services includes the specific
circumstances relevant for the Consulate.
x x x
1.07 Estimated incidentals for extra and additional expenses 5,000.00 Euro x
PCS 7 Station Maintenance of PCS 7 Station
2.01 Annual maintenance, inspection and securing of data 1.00 pces. x
2.02 Provision of PC S7 staff with know-how of local situation in case of failure x x x
Maintenance / Inspection
Inspection of low-voltage switches "Visual inspection and cleaning of switches at US Consulate" (once a year)
3.01 3WE circuit breaker 86.00 pces. x
3.02 3WE circuit breaker KV boxes 72.00 pces. x
3.03 3WL circuit breaker 30.00 pces. x
3.04 3VL circuit breaker 15.00 pces. x
3.05 Reserve circuit breaker various 3 WE 36.00 pces. x
Check that short-circuiting and grounding devices comply with rated values for the switchgear, are appropriately labeled and functional. Cleaning and inspection of stations
5.00 pces. x once every 4 years annuallyItem numbers Service Contract Performances monthly quarterlyQuantities Unit
Seite 1 von 2 7/15/2022
US Consulat Anlage ( Servicevertrag) Wartungsplan Netz once every 4 years annuallyItem numbers Service Contract Performances monthly quarterlyQuantities Unit
Inspection of medium voltage field "Visual inspection and cleaning of switches at US Consulate" (once a year)
4.01 Station 319 medium voltage 8.00 fields x
4.02 Station 320 medium voltage 5.00 fields x
4.03 Station 336 medium voltage 5.00 fields x
4.04 Station 337 medium voltage 7.00 fields x
4.05 Check that short-circuiting and grounding devices comply with rated values for the switchgear, are appropriately labeled and functional. Cleaning and inspection of stations
4.00 pces. x
4.06 Inspection of safety and warning signs to ensure updated status and correct application.
4.00 pces. x
Medium voltage protection testing
5.01 Periodic protection tests (once every 4 years) 18.00 pces. x
Maintenance of battery systems
6.01 Check battery charging and density, and re-charge if required x
6.02 Check connections, clean and grease if required x
6.03 Check the charge state of individual cells x
6.04 Check all functions of the battery charger x
6.05 Check battery undervoltage and overvoltage detector, and adjust accordingly if required x
Transformers Maintenance of a transformer comprising cleaning the insulating parts and transformer room, including supply of cleaning agents
11.00 pces. x
Oil measurement at the transformer Insulating agent inspection in accordance with VDE 0370 Part 2 Inspection of water content, dielectric strength (insulation strength) color index, odor and ...
1.00 pces. x
The scope of work specified in the maintenance plan applies for various network systems and need not comply completely with the machine to be serviced in this specific case.
Seite 2 von 2 7/15/2022