Exhibit B LM Voltage Switchgear.pdf

PDF 189 KB Posted

Attached to
Power System Maintenance Services for US Consulate General Frankfurt, Germany
Solicitation number
19GE5022R0088
Issued by

View the file

Other files

File Type Posted
Att 5 Detailed equip list.xlsx XLSX spreadsheet
QandA 22R0088.pdf PDF
22R0088 0001 OrigSig.pdf PDF
Solicitation 22R0088.pdf PDF
Cover Letter 22R0088.pdf PDF
Att. 2 Past Performance.docx DOCX document
Exhibit C Equipment List.pdf PDF
Exhibit A Emergency Power.pdf PDF
Exhibit D LOTO Policy.pdf PDF
Att. 1 Pricing.xlsx XLSX spreadsheet
Att. 4 W-14.pdf PDF
Att. 3 Key Personnel.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Consulat Anlage ( Servicevertrag) Wartungsplan Netz

General Data relating to Maintenance Contract

1.01 Quarterly Meeting of Facility Management US Consulate and Contractor

4.00 pces. x

1.02 365 days /24 hours on-call service including Saturdays/Sundays and public holidays for the switchgears

12.00 pces. x

1.03 Procurement of spare parts 365 days / 24 hours including Saturdays/Sundays and public holidays

12.00 pces. x

1.04 Project management and coordination 12.00 pces. x

1.05 Certified staff already checked by the Consulate x x x

1.06 Scope of Delivery and Services includes the specific

circumstances relevant for the Consulate.

x x x

1.07 Estimated incidentals for extra and additional expenses 5,000.00 Euro x

PCS 7 Station Maintenance of PCS 7 Station

2.01 Annual maintenance, inspection and securing of data 1.00 pces. x

2.02 Provision of PC S7 staff with know-how of local situation in case of failure x x x

Maintenance / Inspection

Inspection of low-voltage switches "Visual inspection and cleaning of switches at US Consulate" (once a year)

3.01 3WE circuit breaker 86.00 pces. x

3.02 3WE circuit breaker KV boxes 72.00 pces. x

3.03 3WL circuit breaker 30.00 pces. x

3.04 3VL circuit breaker 15.00 pces. x

3.05 Reserve circuit breaker various 3 WE 36.00 pces. x

Check that short-circuiting and grounding devices comply with rated values for the switchgear, are appropriately labeled and functional. Cleaning and inspection of stations

5.00 pces. x once every 4 years annuallyItem numbers Service Contract Performances monthly quarterlyQuantities Unit

Seite 1 von 2 7/15/2022

US Consulat Anlage ( Servicevertrag) Wartungsplan Netz once every 4 years annuallyItem numbers Service Contract Performances monthly quarterlyQuantities Unit

Inspection of medium voltage field "Visual inspection and cleaning of switches at US Consulate" (once a year)

4.01 Station 319 medium voltage 8.00 fields x

4.02 Station 320 medium voltage 5.00 fields x

4.03 Station 336 medium voltage 5.00 fields x

4.04 Station 337 medium voltage 7.00 fields x

4.05 Check that short-circuiting and grounding devices comply with rated values for the switchgear, are appropriately labeled and functional. Cleaning and inspection of stations

4.00 pces. x

4.06 Inspection of safety and warning signs to ensure updated status and correct application.

4.00 pces. x

Medium voltage protection testing

5.01 Periodic protection tests (once every 4 years) 18.00 pces. x

Maintenance of battery systems

6.01 Check battery charging and density, and re-charge if required x

6.02 Check connections, clean and grease if required x

6.03 Check the charge state of individual cells x

6.04 Check all functions of the battery charger x

6.05 Check battery undervoltage and overvoltage detector, and adjust accordingly if required x

Transformers Maintenance of a transformer comprising cleaning the insulating parts and transformer room, including supply of cleaning agents

11.00 pces. x

Oil measurement at the transformer Insulating agent inspection in accordance with VDE 0370 Part 2 Inspection of water content, dielectric strength (insulation strength) color index, odor and ...

1.00 pces. x

The scope of work specified in the maintenance plan applies for various network systems and need not comply completely with the machine to be serviced in this specific case.

Seite 2 von 2 7/15/2022

File details come from the government source that posted it. Updated .