Exhibit A Emergency Power.pdf

PDF 191 KB Posted

Attached to
Power System Maintenance Services for US Consulate General Frankfurt, Germany
Solicitation number
19GE5022R0088
Issued by

View the file

Other files

File Type Posted
Att 5 Detailed equip list.xlsx XLSX spreadsheet
QandA 22R0088.pdf PDF
22R0088 0001 OrigSig.pdf PDF
Solicitation 22R0088.pdf PDF
Cover Letter 22R0088.pdf PDF
Att. 2 Past Performance.docx DOCX document
Exhibit B LM Voltage Switchgear.pdf PDF
Exhibit C Equipment List.pdf PDF
Exhibit D LOTO Policy.pdf PDF
Att. 1 Pricing.xlsx XLSX spreadsheet
Att. 4 W-14.pdf PDF
Att. 3 Key Personnel.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Consulat Anlage ( Servicevertrag) Wartungsplan NEA

Monthly test run, 2 hours respectively W1 x

Annual load test run including provision of load bank, assembling, dismantling and cable connection x

G055.050.01 Valve control Check valve clearance W3 x

G083.051.03 Fuel twin filter Replace spin-on filter W3 x

G083.101.15 Clean fuel pre-filter W3 x

G180.000.04 Motor oil Take used oil sample and inspect W3 x

G180.000.05 Change motor oil after 2 years respectively, at the latest after 500 operating hours for oil category 2

W3 x after 1000 operating hours for oil category 3 W3 x

G183.052.03 Replace motor oil filter W3 x together with motor oil change W3 x

G202.000.05 Take motor coolant sample, and inspect W3 x

Replace motor coolant, refer to MTU fuel specifications W3 x

G202.051.01 G202.051.01 Motor coolant pump Check relief opening for consistency

W3 x

G203.000.07 Charge-air coolant Take sample, and inspect W3 x

Change coolant, refer to MTU fuel specifications W3 x

G203.051.01 Charge-air coolant pump Check relief opening for consistency

W3 x

G205.051.01 Motor coolant heat exchanger W3 x

(High temperature cycle) W3 x

Check cooler elements for external fouling W3 x G205.051.03 Motor coolant heat exchanger W3 x

(low temperature cycle) W3 x

Check cooler elements for external fouling W3 x

Electrical inspections Drive motor and tank system

Check deactivation criteria x Check reports and messages x Check controller behavior x Check starter and generator x Check functionality of stopping solenoid x Check fuel pump between tank and aggregate x Check fuel filling pump x Check pre-lubrication, check pre-lubrication and break periods x

Exhaust system Visual inspection x

Cooling system Check thermostat x annuallyItem numbers Maintenance work Maintenance level monthly

Seite 1 von 3 7/15/2022

Check ventilation of engine room, x Check supply and exhaust air louvers for functionality and smooth running x

Check cooling water circulation pump x Check cooling water preheating, adjust if required x Check cooling water level in compensation tank x Check limit value transmitter and filling level monitor x

Measuring devices Check temperature control switch, remote thermometer, x oil pressure gauge and oil pressure sensor x Check display/measuring instruments in the switch cabinet x

Starter battery and charger Check battery charging and density and re-charge if required x

Check connections, clean and grease if required x Check charging state of individual cells x Check all functions of battery charger x Check battery undervoltage and overvoltage detector, adjust if required x

Control of emergency power system Functional check of operating modes x Automatic x Test x Manual with/without load x Check emergency shut-off function x Synchronization: Check automatic/manual x Check-resynchronization x Check network disconnection/protection x Check network/generator voltage monitor, adjust if required x

Execute power failure test x Check start delay time, adjust if required. x Check takeover time of emergency power system, adjust if required x

Check reset delay after power recovery x Execute a test start. If required, connect consumers via push button control x

Start via starter switch x Check horn with disconnection x Check signal lamps x Simulate or stimulate all error messages x Check switch contacts for loss of contact material x Check connections and ground connections x Check remote signaling x Clean active and inactive parts x

Generator Check constant voltage unit, check regulation x Check connections of power cables with torque x Re-lubricate roller bearings in accordance with lubrication regulations x

Check coil for dust deposits and remove dust x by blowing out x Check connections at controller x

General Check the aggregate room x

Seite 2 von 3 7/15/2022

Check groundings x Check labelings and room markings x Check that circuit diagrams are complete x Check completeness of safety resources (fire extinguishers, emergency lighting, flashing light) x

Complete inspection records x

The scope of work specified in the maintenance plan applies for various network systems and need not comply completely with the machine to be serviced in this specific case.

Seite 3 von 3 7/15/2022