Exhibit B_2025-08-04 C3 Civic Center TI Set.pdf
PDF 14 MB Posted
- Attached to
- Commerce City Civic Center Remodel CMGC State and local contract opportunity
- Solicitation number
- RFP-PW-25-020
- Issued by
- Adams County, Colorado Springs City, Colorado
About this file
This is a tenant improvement project for the City of Commerce City Civic Center Restructure located at 7887 E 60th Avenue, Commerce City, Colorado 80022. The project involves partial interior renovation of a three-story, 92,494 GSF building with renovation work limited to the ground floor and second story totaling 35,306 SF of scope. The building consists of B, A-3, and S-1 occupancies with Type II-B construction and includes comprehensive architectural, mechanical, and electrical improvements. The design team includes D2C Architects as the architect/landscape architect, PKMR Engineering as both mechanical and electrical engineer, with Scott Springstead from the City of Commerce City serving as the Facilities Project Manager.
The project encompasses extensive demolition and construction work including new partition systems, ceiling installations, flooring materials (carpet, VCT, luxury vinyl tile), lighting fixtures, electrical systems, and HVAC modifications. Key spaces being renovated include individual and open offices, conference rooms, training facilities, storage areas, and circulation spaces with specific room finish schedules and equipment requirements detailed throughout the drawings. The electrical work includes new lighting plans, power distribution, panelboard modifications, and control systems, while mechanical systems require coordination with existing building infrastructure. The drawings are marked "NOT FOR CONSTRUCTION" and include comprehensive specifications for materials, installation requirements, and coordination between trades.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Exhibit E - Special Conditions CC Remodel.pdf | ||
| CMGC Preconstruction Sample Civic Center.pdf | ||
| 020 CMGC RFP Civic Center Remodel_FINAL.pdf | ||
| Exhibit A Scope of Services.pdf | ||
| Exhibit F General Conditions.pdf | ||
| Q&A Document 1.pdf | ||
| Exhibit C _ D Payment and Performance Bonds.pdf | ||
| CMGC Sample Construction Agreement CC.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT SITE
PROJECT SITE
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
/4
/2
:2
:0
P
M
G -0
A U
G U
S T
D e s ig n e r
K S
B D
G-001
B C
V
IC
IN
IT
Y M
A P
A N
D D
E S
IG
N
T E
A M
D
IR
E C
T O
R Y
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
Contact:
PKMR ENGINEERING
Chris Ahern Principal
1550 Wewatta St p: 720.739.4500 e: chris.ahern@pkmreng.com
PLUMBING
ENGINEER
Suite 200
Denver, Colorado 80202
Contact:
PKMR ENGINEERING
Chris Ahern Principal
1550 Wewatta St p: 720.739.4500 e: chris.ahern@pkmreng.com
ELECTRICAL
ENGINEER
Suite 200
Denver, Colorado 80202
Contact:
PKMR ENGINEERING
Chris Ahern Principal
1550 Wewatta St p: 720.739.4500 e: chris.ahern@pkmreng.com
MECHANICAL
ENGINEER
Suite 200
Denver, Colorado 80202
Contact:
D2C ARCHITECTS, INC
Brian Duggan, AIA Contact Title
1580 Lincoln Street p: 303.952.4802 e: bduggan@d2carchitects.com
ARCHITECT/LANDSCAPE
Suite 1110
Denver, Colorado 80203
Contact:
CITY OF COMMERCE CITY
Scott Springstead Facilities Project Manager
8602 Rosemary St p: 720.692.4278 e: sspringstead@c3gov.com
OWNER
Commerce City, Colorado 80022
TENANT IMPROVEMENT
CITY OF COMMERCE CITY
CIVIC CENTER RESTRUCTURE
7887 E 60TH AVENUE, COMMERCE CITY, CO 80022
N
T R
U E
N
O R
T H
N
T R
R
T
HG-001 12" = 1'-0"
1 VICINITY MAP
G-001 12" = 1'-0"
2 LOCATION MAP
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
/4
/2
:2
:0
P
M
G -0
A U
G U
S T
D e s ig n e r
K S
B D
G-002
B C
S H
E E
T I
N D
E X
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
SHEET INDEX
SHEET
NUMBER SHEET TITLE
GENERAL
G-001 VICINITY MAP AND DESIGN TEAM DIRECTORY
G-002 SHEET INDEX
G-003 PROJECT GENERAL NOTES
GI101 CODE ANALYSIS
GI102 CODE ANALYSIS PLANS - LEVEL 1
GI103 CODE ANALYSIS PLAN - LEVEL 2
GI104 CODE ANALYSIS PLANS - LEVEL 3
ARCHITECTURAL
A-001 ARCHITECTURAL ABBREVIATIONS, SYMBOLS AND MATERIALS
A-011 PARTITION TYPES AND DETAILS
AD111 PARTIAL FLOOR PLAN - LEVEL 2, DEMOLITION
AD112 PARTIAL FLOOR PLAN - LEVEL 3, DEMOLITION
AD211 PARTIAL REFLECTED CEILING DEMO PLAN - LEVEL 2
AD212 PARTIAL REFLECTED CEILING DEMO PLAN - LEVEL 3
A-111 PARTIAL FLOOR PLAN - LEVEL 2
A-112 PARTIAL FLOOR PLAN - LEVEL 3
A-211 PARTIAL REFLECTED CEILING PLAN - LEVEL 2
A-212 PARTIAL REFLECTED CEILING PLAN - LEVEL 3
A-231 CEILING DETAILS
A-423 STAIR DETAILS
A-701 SCHEDULES
A-711 DOOR SCHEDULE
A-901 3D AXONOMETRICS
A-902 3D AXONOMETRICS
A-903 3D AXONOMETRICS
A-904 3D AXONOMETRICS
INTERIORS
I-111 PARTIAL FLOOR FINISH PLAN - LEVEL 2
I-112 PARTIAL FLOOR FINISH PLAN - LEVEL 3
asdf
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
GENERAL REQUIREMENTS
1. ATTENTION ALL USERS OF THESE DRAWINGS,
GENERAL CONTRACTORS, SUB
CONTRACTORS, MANUFACTURERS,
SUPPLIERS: CAREFULLY AND THOROUGHLY
REVIEW THESE GENERAL NOTES. IT IS YOUR
RESPONSIBILITY TO KNOW AND ADHERE TO
THESE REQUIREMENTS.
2. DO NOT PRESUME THAT YOUR SCOPE OF
WORK IS SINGULARLY DEFINED. YOUR SCOPE
OF WORK IS DEFINED THROUGHOUT THE
ENTIRE SET OF DRAWINGS AND
SPECIFICATIONS AND IS NOT CONTAINED IN
JUST ONE SERIES OF DRAWINGS OR DIVISION
OF SPECIFICATIONS. YOU MUST REVIEW THE
ENTIRE SET OF CONTRACT DOCUMENTS TO
DETERMINE YOUR SCOPE OF WORK.
3. EVERY EFFORT HAS BEEN MADE TO MAKE
THESE DOCUMENTS CONCISE AND
COORDINATED, TO DEFINE WORK IN THE MOST
LOGICAL PLACE AND TO ELIMINATE
REDUNDANCY. KEEP IN MIND HOWEVER THAT
YOUR SCOPE OF WORK CAN BE CONTAINED IN
VARIOUS PLACES, WITH VARYING
DESCRIPTIONS. DO NOT CONSIDER THAT
THERE IS ONE CUSTOMARY PLACE TO LOCATE
YOUR WORK. THERE IS A DANGER OF
OMITTING WORK FROM YOUR SCOPE
BECAUSE THE ENTIRE SET OF DOCUMENTS
WAS NOT REVIEWED.
4. MECHANICAL AND ELECTRICAL DRAWINGS
SHOW INFORMATION IN A DIAGRAMMATIC
FASHION WITHOUT DIMENSIONING. THE
GENERAL CONTRACTOR IS TO COORDINATE
THE LOCATIONS OF ALL MECHANICAL AND
ELECTRICAL EQUIPMENT WITH RESPECT TO
THE ARCHITECTURAL AND STRUCTURAL
DETAILING OF SHAFTS, CHASES, AND SUCH.
5. THE CONTRACTOR SHALL VISIT THE SITE AND
BECOME FAMILIAR WITH SITE CONDITIONS AS
THEY MAY AFFECT CARRYING OUT THE WORK
AS DESCRIBED IN THESE CONTRACT
DOCUMENTS. THE CONTRACTOR SHALL
INVESTIGATE, VERIFY, AND BE RESPONSIBLE
FOR ALL CONDITIONS OF THE PROJECT, AND
NOTIFY THE ARCHITECT OF ANY CONDITIONS
THAT REQUIRE MODIFICATION BEFORE
PROCEEDING WITH THE WORK.
6. THE CONTRACTOR SHALL PROVIDE ALL
MATERIALS, EQUIPMENT, LABOR, AND
SERVICES NECESSARY TO COMPLETE THE
WORK.
7. ALL PERSONS DIRECTLY OR INDIRECTLY
ASSOCIATED WITH THE PROJECT SHALL BE
FAMILIAR WITH THE RULES AND REGULATIONS
OF THE OCCUPATIONAL SAFETY AND HEALTH
ACT, AND IMPLEMENT THOSE RULES AS THEY
APPLY TO THIS PROJECT.
8. ALL WORK PERFORMED SHALL BE IN
ACCORDANCE WITH THE BUILDING CODES AS
NOTED ON CODE SHEETS AND/OR DIRECTED
BY THE BUILDING DEPARTMENT OR BUILDING
OFFICIAL.
9. CONTRACTOR SHALL SUBMIT CONFIRMATION
OF ORDERED MATERIALS OR ITEMS
NECESSARY TO COMPLETE THE PROJECT
WITH PROJECTED DELIVERY DATE GREATER
THAN FOUR WEEKS.
10. ALL SUBCONTRACTORS SHALL SUBMIT SHOP
DRAWINGS AS REQUIRED FOR ARCHITECTS
APPROVAL PRIOR TO COMMENCING ANY
WORK.
11. FIELD VERIFY ALL DIMENSIONS PRIOR TO
CASEWORK FABRICATION.
12. THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR THE COORDINATION OF
ALL TRADES AND THE PREVENTION OF
CONFLICT BETWEEN ALL TRADES.
13. THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR LOCATING AND
PROTECTING ALL UTILITY LINES. LOCATIONS
SHOWN ARE APPROXIMATE. REPAIR ALL
DAMAGE TO UTILITY LINES CAUSED BY
CONSTRUCTION OPERATIONS AT NO COST TO
THE OWNER.
14. PRIOR TO BEGINNING ANY WORK, THE
CONTRACTOR SHALL CONDUCT A WALK THROUGH
INSPECTION WITH THE OWNER AND A&E
DETERMINE IN WRITING THE CONDITION OF THE
WORK ALREADY IN PLACE. THE CONTRACTOR IS
RESPONSIBLE FOR REPAIRING OR REPLACING
EQUIPMENT PRESENTLY IN PLACE THAT IS
DAMAGED DURING CONSTRUCTION.
15. THE GENERAL CONTRACTOR SHALL FIELD VERIFY
ALL PATCH AND REPAIR REQUIREMENTS OF
EXISTING SURFACES TO RECEIVE NEW FINISHES.
THE COST FOR ALL SUCH WORK IS TO BE COVERED
BY THE BID.
16. IT IS THE GENERAL CONTRACTOR AND THEIR
SUBCONTRACTOR'S RESPONSIBILITY TO PROVIDE A
COMPLETE, FUNCTIONING AND FULLY
OPERATIONAL SOLUTION SURROUNDING ANY AND
ALL ASPECTS OF THIS PROJECT. SHOULD ASPECTS
AND/OR ELEMENTS BE MISSING FROM THE
DOCUMENTS THAT PREVENT SUCH, CONTRACTOR
SHALL INCLUDE IN THEIR ORIGINAL BID, FEE TO
PROVIDE SOLUTIONS TO MEET SUCH
REQUIREMENTS. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO OBTAIN CLARIFICATION ON ANY
AND ALL ITEMS THAT ARE UNCLEAR WITHIN THE
DOCUMENTS, PRIOR TO BID, SO THAT THE
CONTRACTOR'S BID ACCOUNTS FOR ALL ASPECTS
AND ELEMENTS OF THIS PROJECT.
17. SHOULD CONTRACTOR NEED ADDITIONAL
CLARIFICATION OR SUPPLEMENTAL INFORMATION
ON ANY ASPECT OF THE DOCUMENTS, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO REQUEST
WRITTEN INFORMATION THROUGH AN INDUSTRY
STANDARD REQUEST FOR INFORMATION (RFI) OR
SEEK SUPPLEMENTAL INFORMATION THROUGH AN
INDUSTRY STANDARD ARCHITECT SUPPLEMENTAL
INFORMATION (ASI). SHOULD THE CONTRACTOR
FAIL TO REQUEST SUCH CLARIFICATION
INFORMATION IN A TIMELY MANNER THAT RESULTS
IN A NEGATIVE EFFECT ON THE PROJECT'S
SCHEDULE OR BUDGET, THE CONTRACTOR
ASSUMES ANY AND ALL LIABILITY ASSOCIATED
WITH THE PROJECT SCHEDULE AND MONETARY
ASPECTS SURROUNDING RESOLUTION.
18. NOT ALL FIRE RATED ASSEMBLIES AND/OR UL
LISTED ASSEMBLIES FOR ALL INSTANCES ARE
PROVIDED, OR DETAILED FOR THIS PROJECT. IT IS
THE CONTRACTORS' RESPONSIBILITY TO INQUIRE
WITH THE ARCHITECT, BUILDING DEPARTMENT,
FIRE DEPARTMENT, CODE OFFICIAL, CODE
INSPECTOR AND OTHER AUTHORITIES HAVING
JURISDICTION APPLICABLE FOR CLARIFICATION AND
SPECIFIC DETAILS AS NECESSARY TO ENSURE A
COMPLIANT APPLICATION WILL BE USED/ HAS BEEN
INSTALLED AND MEETS ALL REQUIRED CODES.
19. SEQUENCE OF CONSTRUCTION IS A “MEANS AND
METHODS” AND THEREFORE THE RESPONSIBILITY
OF THE CONTRACTORS. IMPACTS TO THE
SCHEDULE AND/OR DELAYS DUE TO SEQUENCING
ARE THE CONTRACTORS' RESPONSIBILITY. AS
SUCH, CONTRACTOR ASSUMES ANY AND ALL
LIABILITY ASSOCIATED WITH SUCH, INCLUDING
MONETARY ASPECTS SURROUNDING RESOLUTION.
20. THE SPECIFICATIONS AND DRAWINGS (CONTRACT
DOCUMENTS) MAY NOT BE COMPLETE IN EVERY
DETAIL. CONTRACTOR AND THEIR
SUBCONTRACTORS SHALL COMPLY WITH THE
INTENT OF THE CONTRACT DOCUMENTS AND
GENERAL PURPOSE, TAKEN AS A WHOLE, AND
SHALL NOT MAKE USE OF CLAIM ON ANY ERRORS
OR OMISSIONS THEREIN TO THE DETRIMENT OF
THE DESIGN TEAM OR WORK. SHOULD ANY
CONFLICT, PRESUMED ERROR OR OMISSION, OR
DISCREPANCY APPEAR IN THE DRAWINGS,
SPECIFICATIONS OR INSTRUCTIONS IN WORK DONE
BY OTHERS OR IN SITE CONDITIONS, CONTRACTOR
SHALL NOTIFY THE ARCHITECT IN WRITING AT
ONCE. FAILURE TO NOTIFY THE ARCHITECT
IMMEDIATELY, ALLEVIATES ALL LIABILITY FROM
ARCHITECT, DESIGN TEAM AND OWNER AND
PLACES ALL LIABILITY WITH THE CONTRACTOR. IF
CONTRACTOR PROCEEDS WITH ANY OF THE WORK
IN QUESTION PRIOR TO DIRECTION FROM OWNER
AND/ OR ARCHITECT, THEN REQUIRED
CORRECTIONS SHALL BE AT THE CONTRACTOR'S
EXPENSE AND SHALL NOT BE REIMBURSABLE.
21. ALL CODE MANDATED SIGNAGE SHALL BE
PROVIDED BY GENERAL CONTRACT, INCLUDED
WITHIN BID, UNLESS OTHERWISE NOTED.
GENERAL REQUIREMENTS DRAWINGS AND DIMENSIONS CONSTRUCTION NOTES
1. THE CONTRACT DOCUMENT DRAWINGS HAVE
BEEN PREPARED USING REVIT SOFTWARE IN A
MICROSOFT WINDOWS ENVIRONMENT. A
BUILDING INFORMATION MODEL (BIM) WAS
DEVELOPED SOLELY TO COMMUNICATE THE
DESIGN INTENT TO THE OWNER AND IS NOT
SUITABLE FOR ANY OTHER PURPOSE. FOR
EXAMPLE THE REVIT MODEL IS NOT SUITABLE
FOR COST ESTIMATING, SYSTEMS
PERFORMANCE, COORDINATION,
SCHEDULING, OR FACILITIES MANAGEMENT.
2. THESE DOCUMENTS WERE PRODUCED USING
THE CONSTRUCTION SPECIFICATIONS
INSTITUTE'S UNIFORM DRAWING SYSTEM AND
THE NATIONAL CAD STANDARD AS GUIDES.
3. ANY INDICATION OF PROJECT LIMITS OR LINES
OF DEMARCATION ARE SHOWN FOR THE
CONVENIENCE OF THE CONTRACTOR, AND
ARE NOT TO BE TAKEN LITERALLY. ACTUAL
CONTRACT LIMITS ARE TO BE DETERMINED BY
THE CONTRACTOR AND APPROVED BY THE
OWNER BEFORE ACTUAL CONSTRUCTION
WORK BEGINS.
4. DRAWINGS ARE PREPARED USING
DIMENSIONS AND PRODUCT CONFIGURATIONS
OR DETAILS OF SPECIFIC MANUFACTURERS.
DIMENSIONS AND DETAILS FOR SPECIFIC
PRODUCTS MAY CHANGE BEFORE THEY ARE
ACTUALLY INCORPORATED INTO THE WORK,
AND PRODUCTS BY OTHER MANUFACTURERS
MAY ALSO BE ACCEPTABLE. THEREFORE,
ACTUAL INSTALLATION DETAILS AND
DIMENSIONS MAY DIFFER FROM THOSE
SHOWN. CONTRACTOR SHALL VERIFY
INSTALLATION REQUIREMENTS FOR ALL
PRODUCTS TO BE INCORPORATED IN THE
WORK (INCLUDING PARTITION THICKNESS FOR
RECESSED OR SEMI-RECESSED PRODUCTS),
AND IS RESPONSIBLE FOR ACCOMMODATING
AND COORDINATING CHANGES TO OTHER
MATERIALS OR PRODUCTS THAT ARE
NECESSARY BECAUSE OF THESE
DIFFERENCES.
5. THE DRAWINGS AND SPECIFICATIONS ARE
SEPARATED INTO DISCIPLINES FOR THE
CONVENIENCE OF THE ARCHITECT AND THE
CONTRACTOR. THE SEPARATIONS USED
HEREIN ARE USED ONLY FOR THE PURPOSES
OF CONVENIENCE AND REFERENCE AND IN NO
WAY DO THEY DEFINE OR LIMIT THE SCOPE OR
INTENT OF ANY PART OF THE DRAWINGS, OR
OF THE DRAWINGS AND SPECIFICATIONS AS A
WHOLE. THE FACT THAT THE DRAWINGS ARE
SEPARATED IN NO WAY SUGGESTS THAT THE
WORK IS NOT TO BE CONSTRUCTED AS A
COMPLETE, INTEGRATED AND UNIFIED WHOLE.
6. THE DRAWINGS AND SPECIFICATIONS,
INCLUDING DRAWINGS PREPARED BY
SPECIFIC ENGINEERING DISCIPLINES (SUCH
AS CIVIL, STRUCTURAL, MECHANICAL,
ELECTRICAL, ETC.) ARE COMPLEMENTARY;
ITEMS SHOWN IN ANY ONE LOCATION IN THE
DRAWINGS SHALL BE CONSIDERED TO BE
REQUIREMENTS OF THE CONTRACT FOR
CONSTRUCTION. IN THE EVENT OF AN
INCONSISTENCY BETWEEN THE DRAWINGS
AND SPECIFICATIONS, OR WITHIN EITHER
DOCUMENT, THE CONTRACTOR SHALL SEEK
CLARIFICATION OR INTERPRETATION FROM
THE ARCHITECT PRIOR TO BIDDING. WHERE
INCONSISTENCIES ARE NOT CLARIFIED PRIOR
TO BIDDING, AND WHERE THE ACTUAL
SOLUTION OR INTENT CANNOT BE
REASONABLY INFERRED, THE CONTRACTOR
SHALL PROVIDE THE BETTER QUALITY OR
GREATER QUANTITY OF WORK.
7. USE OF THE WORD "VERIFY" POINTS OUT A
SITUATION WHICH MUST BE CONFIRMED
PRIOR TO PROCEEDING WITH THE WORK,
FABRICATION OF EQUIPMENT, OR ORDERING
MATERIAL. NOTIFY THE ARCHITECT OF ANY
DISCREPANCY
8. THE FIRE SPRINKLER SYSTEM WILL BE
DESIGNED BY THE INSTALLING SUB
CONTRACTOR. THE GENERAL CONTRACTOR
SHALL COORDINATE LAYOUT, CLEARANCES,
AND LOCATION OF HEAD HEIGHTS WITH THE
STRUCTURE, MECHANICAL DUCTWORK,
ELECTRICAL LIGHTING, DRAINAGE PIPING, AND
THE ARCHITECTURAL REFLECTED CEILING
PLANS. THE SPRINKLER DESIGN MUST BE
COORDINATED WITH THE PROVISIONS OF ALL
ENGINEERING AND ARCHITECTURAL
DOCUMENTS SHOULD NOT RELY SOLELY ON
ONE SERIES OF DRAWINGS OR ONE
DISCIPLINE. SPRINKLER SYSTEMS LOCATED IN
UNHEATED SPACES SHALL BE A DRY PIPE
SYSTEM UNLESS NOTED OTHERWISE.
9. ARCHITECTURAL, MECHANICAL, AND
ELECTRICAL DRAWINGS SHOW WHERE
EXPOSED DUCTWORK IS TO BE INSTALLED AT
A SPECIFIC ELEVATION IN A CONTROLLED
PATTERN. THE CONTRACTOR MUST RELY ON
ALL OF THESE DISCIPLINES TO COMPLETE THE
WORK AND SHOULD NOTIFY THE ARCHITECT
OF ANY DISCREPANCIES.
10. THE GENERAL CONTRACTOR SHALL
COORDINATE THE WORK OF ALL TRADES
INSTALLING THEIR RESPECTIVE EQUIPMENT IN
THE CEILING PLENUMS. MECHANICAL,
ELECTRICAL, STRUCTURAL, AND FIRE
SPRINKLER SYSTEMS ALL SHARE THIS SAME
SPACE. EACH SUB CONTRACTOR IS TO
REVIEW THE REQUIREMENTS OF THEIR WORK
WITH THE AWARENESS OF THE OTHER
TRADES THAT NEED TO SHARE THESE SPACES
MUST NOT ASSUME THAT THEIR INSTALLATION
HAS BEEN CONSIDERED IN THE DESIGN AND
SHOP DRAWINGS OF THE OTHER TRADES.
11. THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR NOTIFYING THE
ARCHITECT IMMEDIATELY SHOULD ANY
DISCREPANCIES BE FOUND IN THE DRAWINGS
AND SPECIFICATIONS.
12. THE GENERAL CONTRACTOR IS RESPONSIBLE
FOR CHECKING ALL FIELD CONDITIONS AND
DIMENSIONS AS THEY RELATE TO THIS
PROJECT. SHOULD DISCREPANCIES EXIST
BETWEEN THE WORK INDICATED AND ACTUAL
FIELD CONDITIONS NOTIFY THE ARCHITECT
PRIOR TO PROCEEDING WITH THE WORK.
13. DO NOT SCALE THE DRAWINGS. DRAWING
SCALES AS INDICATED ARE FOR REFERENCE
ONLY AND ARE NOT INTENDED TO
ACCURATELY DEPICT ACTUAL OR
DESIGNATED CONDITIONS. WRITTEN
DIMENSIONS SHALL GOVERN.
14. ALL DIMENSIONS INDICATED ARE TO FACES OF
CMU/STUD/STRUCTURAL MATERIALS OR
COLUMN GRID LINES UNLESS NOTED
OTHERWISE. MASONRY DIMENSIONS ARE
MODULAR IN THAT THEY INCLUDE THE GROUT
JOINT. ROUGH OPENINGS ALLOW FOR SHIM
SPACE.
15. REFER TO THE ARCHITECTURAL REFLECTED
CEILING PLAN FOR EXACT LOCATIONS OF ALL
CEILING FIXTURES. REFER TO MECHANICAL
AND ELECTRICAL DRAWINGS FOR COMPLETE
CONSTRUCTION REQUIREMENTS.
16. THE TERM "ALIGN" REFERS TO LOCATING
DIFFERENT COMPONENTS OF CONSTRUCTION
TO PROVIDE A FLUSH FINISH SURFACE.
17. CONTRACTOR SHALL LAY OUT ALL
PARTITIONS PER THE DIMENSIONS SHOWN ON
THE PLAN. VERIFY PARTITION LAYOUT WITH
EXISTING WINDOWS, COLUMNS, DOORS,
EQUIPMENT AND CEILING SYSTEMS. NOTIFY
THE ARCHITECT OF ANY DISCREPANCIES
PRIOR TO STARTING CONSTRUCTION.
1. TOP OF CONCRETE FIRST FLOOR SLAB IS
ASSUMED AT EL. 100'-0 (ELEVATION 100'-0
EQUATES TO USGS DATUM ELEVATION OF
XXXX.XX').
2. ALL VERTICAL AND HORIZONTAL PIPES,
CONDUITS, DUCTS, ETC. IN FINISHED ROOMS
OR AREAS THROUGHOUT THE BUILDING SHALL
BE FURRED IN TO MATCH THE ROOM FINISH,
UNLESS NOTED OTHERWISE.
3. METAL STUD PARTITIONS SHALL BE OF
SUFFICIENT WIDTH TO ADEQUATELY ENCLOSE
PIPING, CONDUITS, AND RECESSED
EQUIPMENT.
4. PROVIDE 24" X 24" ACCESS PANELS IN
PARTITIONS WHERE REQUIRED FOR
MECHANICAL EQUIPMENT EXCEPT WHERE
SIZES ARE OTHERWISE NOTED. COORDINATE
EXACT LOCATIONS WITH ARCHITECT IN FIELD
OR VIA SHOP DRAWINGS.
5. PROVIDE PLUMBING CLEANOUTS IN
PARTITIONS AS NECESSARY. COORDINATE
ALL WALL LOCATIONS AND PLACEMENT OF
COVER PLATES WITH ARCHITECT IN FIELD OR
VIA SHOP DRAWINGS.
6. PROVIDE BLOCKING WITHIN PARTITIONS AT
ALL LOCATIONS WHERE ITEMS WILL BE
MOUNTED ON PARTITIONS.
7. PROVIDE GYPSUM BOARD CONTROL JOINTS IN
PARTITIONS AND CEILINGS AT 30'-0" MAX.
SPACING. COORDINATE TO MEET FIRE
RESISTIVE RATINGS OF THE ASSEMBLY,
FIRESTOP JOINTS AT RATED PARTITIONS.
8. CONTRACTOR SHALL ADJUST OR ADD FIRE
SPRINKLER HEADS TO ACCOMMODATE
PARTITION LAYOUT. CENTER THE HEAD IN THE
ACOUSTICAL PANEL, HEAD SPACING AND
PLACEMENT SHALL MEET CODE
REQUIREMENTS.
9. WALL, CEILING, BASE, AND FLOOR FINISHES
ARE TO BE PROVIDED IN EVERY ROOM
UNLESS THE DRAWINGS SPECIFICALLY
INDICATE THAT A ROOM OR PORTION
THEREOF IS TO REMAIN "UNFINISHED." IF
ROOM FINISHES ARE NOT SPECIFICALLY
INDICATED, PROVIDE THE SAME FINISHES AS
ARE PROVIDED IN THE ROOM ADJACENT TO
THE ROOM IN QUESTION, OR OBTAIN
CLARIFICATION FROM THE ARCHITECT PRIOR
TO BIDDING.
10. WHERE MECHANICAL WORK PENETRATES ANY
COMPONENT OF THE FIRE-RATED ASSEMBLY,
PROVIDE THE APPROPRIATE FIRE AND/OR
SMOKE DAMPERS. IF IT IS NOT CLEAR
WHETHER DUCTWORK PENETRATES A
PORTION OF THE RATED ASSEMBLY, OBTAIN
CLARIFICATION FROM THE ARCHITECT PRIOR
TO BIDDING.
11. PROVIDE SEALANT AT ALL JOINTS OR CRACKS
WHICH OCCUR WHERE DISSIMILAR MATERIALS
INTERSECT PERPENDICULAR TO EACH OTHER,
AND THE INTERSECTION IS EXPOSED TO VIEW,
UNLESS INDICATED OTHERWISE ON THE
DRAWINGS.
12. PROVIDE CONTINUOUS PERIMETER BUILDING
INSULATION AT ALL EXTERIOR WALLS.
13. PAINT ALL EXPOSED STEEL UNLESS NOTED
OTHERWISE.
14. ALL MATERIAL COLORS TO BE SELECTED BY
ARCHITECT, UNLESS NOTED OTHERWISE.
15. PROVIDE FIRE-RETARDANT WOOD WHEREVER
WOOD BLOCKING IS SHOWN ON THE
DRAWINGS.
16. THE ARCHITECTURAL AND STRUCTURAL
DRAWINGS BOTH DESCRIBE VARIOUS FLOOR
SLAB SLOPE REQUIREMENTS, RECESSES, AND
EDGE CONDITIONS. USE BOTH SETS OF
DRAWINGS WHEN INSTALLING THE FLOOR
SLAB.
17. FLOOR DRAINS IN TOILET ROOMS SHALL BE
LOCATED UNDER TOILET PARTITION PRIVACY
PANEL TO AVOID CONFLICT WITH SUPPORT
PILASTERS. COORDINATE FLOOR DRAINS IN
MECHANICAL ROOMS TO AVOID CONFLICT
WITH HOUSEKEEPING PADS. HOUSEKEEPING
PADS ARE FOR GENERAL REFERENCE AND
SHALL BE COORDINATED TO SIZE OF ACTUAL
EQUIPMENT.
18. PROVIDE SLIP JOINT CONNECTIONS AT ALL
PARTITIONS THAT EXTEND TO STRUCTURE
ABOVE. ALL PARTITIONS TO SUPPORT
LATERAL LOADS OF NOT LESS THAN 5#/SF.
PROVIDE BRACING ABOVE AS REQUIRED.
19. WHERE DOORS IN PARTITIONS ARE NOT
DIMENSIONALLY LOCATED ON THE PLANS
PROVIDE A MINIMUM HINGE SIDE JAMB
DIMENSION OF 6" FROM DOOR OPENING TO
ADJACENT PERPENDICULAR WALL.
20. PROPOSED CONSTRUCTION SHALL LINE UP
WITH AND MATCH EXISTING WORK EXCEPT
WHERE OTHERWISE DETAILED OR
DIMENSIONED.
21. INFILL OPENINGS IN EXISTING PARTITIONS
WHERE MECHANICAL ITEMS HAVE BEEN
REMOVED WITH CONSTRUCTION TO MATCH
EXISTING.
22. SEAL AROUND ALL PENETRATIONS THROUGH
EXISTING AND PROPOSED FIRE RATED
PARTITIONS. PROVIDE UL APPROVED
FIRESTOP SYSTEM TO MEET REQUIRED
RATING.
23. PROVIDE FLOOR LEVELER AT EXISTING
CONCRETE SLAB WHERE FLOOR DRAINS HAVE
BEEN REMOVED.
24. PROVIDE HOISTWAY BEAM AND REINFORCING
AT TOP OF ELEVATOR SHAFT.
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
/4
/2
:2
:0
P
M
G -0
A U
G U
S T
D e s ig n e r
K S
B D
G-003
B C
P R
O J E
C T
G E
N E
R A
L N
O T
E S
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
CODE ANALYSIS
Civic Center Restructure Commerce City, Colorado
APPLICABLE CODES:
2021 International Building Code (IBC) 2021 International Existing Building Code (IEBC) 2021 International Mechanical Code (IMC) 2021 International Plumbing Code (IPC) 2021 International Fuel Gas Code (IFGC) 2021 International Energy Conservation Code (IECC) 2023 National Electrical Code (NEC)
PROJECT DESCRIPTION:
Partial interior renovation of the Commerce City Civic Center. The Civic Center is a three-story, 92,494 GSF building with a basement and two above-ground levels. Renovation will be limited to the ground floor story and second story, with the lower level being out of scope and to remain as-is. The building consists of B, A-3, and S-1 occupancies. The building is Type II-B construction.
TOPIC IBC REFERENCE REQUIREMENT
BUILDING: Currently designed as 3-story, 92,494 GSF, fully sprinkled.
Scope of work for the renovations on the ground floor and second story is 35,306 SF.
Occupancy Classification Section 302.1 Group B, A-3, and S-1
Occupancy Separations Table 508.4 None
Construction Type Table 601 Type II-B
Allowable Height and Table 504.3 Based on B, A-3, and S-1, most restrictive Building Areas 3 Stories Maximum
17,500 SF (per Story)
Area Modifications with Section 506.1 Aa = { At + [ At x If ] + [At x Is] } Automatic Sprinkler System Aa = { 17,500 + [ 17,500 x 0.61 ] + 17,500 x 2 } and Open Space Width (min. 30') Aa = 63,175 (Per Story) Maximum Allowed
Section 506.2 If = [ F / P - 0.25 ] W / 30 If = [ 729 / 847 - 0.25 ] 30 / 30 If = 0.61
GENERAL INFORMATION:
Incidental Use Areas Table 509.1 Storage rooms over 100 square feet do not need to be provided with a 1-hour separation if an automatic fire-extinguishing system is provided. They shall be separated from the remainder of the building by construction capable of resisting the passage of smoke.
Allowable Areas for Openings Section 705.8.1 Building has fire separation of more than 15' (First Story) at the first floor. Unlimited protection openings are permitted.
Elevator Lobby Section 707.14.1 Not required for a building with less than three floors (2 story building)
Fire Alarm and Detection Systems Section 907.2.1 Manual Fire Alarm boxes are not required (Group A, Required) where an automatic sprinkler system and notification appliances are installed throughout.
Exit Doorway Arrangement Section 1007.1.1 Minimum distance between exit doors not to Exception 2 exceed one-third diagonal dimension of area served because fully sprinkled.
Stairway Area of Refuge Section 1009.3.3 Area of refuge not required at unenclosed exit Exception 2 stairways because fully sprinkled.
Minimum Clear Height Section 1003.2 90" for means of egress
Stairway Clear Width Section 1007.3 48" clear width at exit stairways not required Exception 3 because fully sprinkled
Exit Access Travel Distance Table 1017.2 A-3 = 250' fully sprinkled
Corridor Fire-resistance Table 1020.2 Fully sprinkled, no rated corridors required
Minimum Egress Width Section 1020.3 44" Minimum
Minimum Number of Exits Table 1006.3.3 3 Exits Required First Story (Occupant load 501-1,000 (persons per story))
Vertical Exit Enclosures Section 1006.3.3 2 Exits Required Second Story Exception 9. (Occupant Load 1-500 (persons per story))
Section 1020.1 Fully sprinkled building with interior egress stairway Exception 9 serving only the first and second story not required to be enclosed. Unenclosed exit stairways shall be remotely located as required in section 1015.2
Occupancy Load "A-3" 574 "B" 254 "S-1" 9 Total 837
Plumbing Fixtures Table 2902.1
WC Count Total Total Required Provided
"A-3" 574 Male 287(1 per 125) = 3 Female 287(1 per 65) = 5
"B" 254 Male 127(1 per 25 first 50) + 1 per 50 remaining = 4 Female 127(1 per 25 first 50) + 1 per 50 remaining = 4
"S-1" 9 Male 5 (1 per 100) = 1 Female 5 (1 per 100) = 1 Male 3 + 4 + 1 = 8 8 14 Female 5 + 4 + 1 = 10 10 14
Lavatory Count "A-3" 574 Male 287 (1 per 200) = 2
Female 287 (1 per 200) = 2 "B" 254 Male 127 (1 per 40 first 80) + 1 per 80 remaining = 3
Female 127(1 per 40 first 80) + 1 per 80 remaining = 3 "S-1" 9 Male 5 (1 per 100) = 1
Female 5 (1 per 100) = 1 Male 2 + 3 + 1 = 6 6 6 Female 2 + 3 + 1 = 6 6 8
Unisex Toilet Existing unisex toilet to remain 0 2
Drinking Fountains "A-3" 574 574 (1 per 500) = 2 "B" 254 254 (1 per 100) = 3 "S-1" 9 9 (1 per 1,000) = 1
Totals 2 + 3 + 1 = 6 6 6
Service Sinks "A-3" 574 574 (1 Service sink) = 1 "B" 254 254 (1 Service sink) = 1 "S-1" 9 9 (1 Service sink) = 1
Totals 1 + 1 + 1 = 3 3 2
Notes:
1. Individual room occupancy calculations figured per Table 1004.1.1 "Maximum Floor Area
Allowances Per Occupant" for individual spaces. Spaces are then groups for occupancy listed is the general use occupancy for plumbing fixtures calculations per [P] Table 2902.1
"Minimum Number of Required Plumbing Fixtures.
2. Installation of showers per owner requirements and for LEED requirements. Building Code does not provide guidance for minimum number of showers.
3. Urinal substitution does not exceed 67% of the water closet requirement (IPC Section 419.2).
4. The existing toilets at the entry are to be updated with new finishes and water efficient fixtures and faucets. These toilet rooms cannot be retrofitted to be fully ADA/ANCI 117.1 compliant without significant cost implications. The other (3) new toilet groups are all designed to be fully accessible.
Accessible Parking Spaces Table 1106.2 Of the 215 spaces provided (between 201 and 300), 7 are required to be accessible (2 of which shall be van-accessible).
Accessible Lockers Section 1110.14 At least 5% of lockers must be accessible.
Accessible Toilet and Section 1110.2 1 of each fixture type shall be accessible for Bathing Facilities each men and women within the new toilet rooms.
Accessible Signage Section 1112.1 Required.
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
/4
/2
:2
:0
P
M
G I1
A U
G U
S T
D e s ig n e r
K S
B D
GI101
B C
C O
D E
A N
A L
Y S
IS
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
S. Meehan
D. Davenport/ D. Weidert
10291028
1030 1033
10261025
111611171118
10041003
FACILITIES
WOMEN
CHANGING
SWAT
LOCKERS
PATROL
LOCKERS
ARSENAL P/E EVIDENCE
PROCESSING
OFFICE
PROP
RETURN
EVIDENCE
STOR
CORRIDOR
CORRIDOR
CORRIDOR
HC
HOLDING
DUI
BOOKING
HOLDING
HOLDING
HOLDING
HOLDING
HOLDING
HOLDING
MECH
CSI OFFICE
HALLWAY
INTERVIEWINTERVIEW
OBSERV.
INTERVIEW CSI LAB
MEN
CHANGING
SLEEPSLEEP
VEST
MEN RR/
SHOWERS
MEN RR/
SHOWERS
VEST
VEST
EXERCISE
WOMEN
SHOWERS
WOMEN
SHOWERS
WOMEN
VESTIBULE
WOMEN
CHANGING
HALLWAY
HALLWAY
HOLDINGHOLDINGHOLDING
HOLDING
HOLDING
MEN
CHANGING
RECEIVING
HALLWAY
ELECTRICAL
ELECTRICAL
ARCHIVE
STOR
MECHANICAL
ELECTRICALJAN
STORAGE
HALLWAY
HALLWAY
UP
UP
1134 1135
P/E EVIDENCEGARAGE
BAY
CSO
STORAGE
BICYCLE
STORAGE
SALLY PORT
STAIR
C
VESTIBULE
DOCK
STAIR
B UP
UP
1134 1135
P/E EVIDENCEGARAGE
BAY
CSO
STORAGE
BICYCLE
STORAGE
SALLY PORT
STAIR
C
VESTIBULE
DOCK
STAIR
B
OCCUPANCY LOAD
EGRESS LOAD
EGRESS PATH
1 HR FIRE RATED PARTITION
SMOKE RESISTIVE PARTITION
PER INCIDENTAL USE REQ.
2 HR FIRE RATED PARTITION
CODE ANALYSIS LEGEND
FIRE PROTECTION RATING REQUIREMENTS SHOWN ON BUILDING CODE
DATA CHART AND BUILDING CODE PLANS ON CODE SHEETS. THERE IS A
SCHEDULE OF WHAT COMPONENTS ARE FIREPROOFED AND WHAT UL
TEST MUST BE USED FOR EACH COMPONENT IN THE PROJECT MANUAL
FIREROOFING SECTION 07250 ALL DETAILING ON THE DRAWINGS IS
INTENDED TO COMFORM TO THE REQUIREMENTS OF THE TEST CITED
AND THE BUILDING CODE.
FIRE PROTECTION RATING REQUIREMENTS FOR BUILDING AND
STRUCTURAL COMPONENTS ARE REFEREED TO IN THE CODE DATA
CHART ON THE CODE DRAWING SHEET. THIS CHART IS TAKEN FROM
CODE TABLE 602 OF THE MAIN CODE, AND LIST THE APPLICABLE
PRIMARY ASPECTS OF THE BUILDING. THIS CHART IS REPEATED IN THE
SPECIFICATION SECTION 07811 "SPRAYED FIRE RESTRICTIVE
MATERIALS", TO REQUIRE THIS LEVEL OF FIRE PROTECTION FOR THE
BUILDING.
TYPICALLY:
a. ALL FIRE PROTECTION OF STRUCTURAL MEMBERS IS DONE WITH
SPRAYED MATERIALS.
b. ALL EXPOSED STRUCTURE AND DECK MORE THAN 20 FEET ABOVE
THE FLOOR IS NOT FIREPROOFED.
c. ALL CONCEALED STRUCTURE AND ROOF DECK IS FIREPROOFED.
d. ALL FLOOR DECK (WHETHER CONCEALED OR NOT) IS NOT
FIREPROOFED.
e. ALL "FIRE SEPARATION ASSEMBLIES" ARE TO BE CONSTRUCTED
WITH SHEATHING TO OBTAIN APPROPRIATE RATING.
THE SPECIFICATIONS REQUIRE THE FIREPROOFING SUBCONTRACTOR
TO SUBMIT A SCHEDULE LISTING ALL COMPONENTS TO BE
FIREPROOFED, AND THE U.L. TEST (OR OTHER RECOGNIZED TEST) THAT
DESCRIBES THE FIREPROOFING TO ACHIEVE THE RATING.
FIRE PROTECTION NOTES
NOT IN SCOPE
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
A s i n d ic a te d
/4
/2
:2
:0
P
M
G I1
A U
G U
S T
D e s ig n e r
K S
B D
GI102
B C
C O
D E
A N
A L
Y S
IS
P
L A
N S
L
E V
E L
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
GI102 1" = 20'-0"
A1 CODE ANALYSIS PLAN - LEVEL 1
0' 10' 20' 40' e f.
R e f.
Ref.Ref.
UP
UP
UP
OCCUPANCY LOAD
EGRESS LOAD
EGRESS PATH
1 HR FIRE RATED PARTITION
SMOKE RESISTIVE PARTITION
PER INCIDENTAL USE REQ.
2 HR FIRE RATED PARTITION
CODE ANALYSIS LEGEND
FIRE PROTECTION RATING REQUIREMENTS SHOWN ON BUILDING CODE
DATA CHART AND BUILDING CODE PLANS ON CODE SHEETS. THERE IS A
SCHEDULE OF WHAT COMPONENTS ARE FIREPROOFED AND WHAT UL
TEST MUST BE USED FOR EACH COMPONENT IN THE PROJECT MANUAL
FIREROOFING SECTION 07250 ALL DETAILING ON THE DRAWINGS IS
INTENDED TO COMFORM TO THE REQUIREMENTS OF THE TEST CITED
AND THE BUILDING CODE.
FIRE PROTECTION RATING REQUIREMENTS FOR BUILDING AND
STRUCTURAL COMPONENTS ARE REFEREED TO IN THE CODE DATA
CHART ON THE CODE DRAWING SHEET. THIS CHART IS TAKEN FROM
CODE TABLE 602 OF THE MAIN CODE, AND LIST THE APPLICABLE
PRIMARY ASPECTS OF THE BUILDING. THIS CHART IS REPEATED IN THE
SPECIFICATION SECTION 07811 "SPRAYED FIRE RESTRICTIVE
MATERIALS", TO REQUIRE THIS LEVEL OF FIRE PROTECTION FOR THE
BUILDING.
TYPICALLY:
a. ALL FIRE PROTECTION OF STRUCTURAL MEMBERS IS DONE WITH
SPRAYED MATERIALS.
b. ALL EXPOSED STRUCTURE AND DECK MORE THAN 20 FEET ABOVE
THE FLOOR IS NOT FIREPROOFED.
c. ALL CONCEALED STRUCTURE AND ROOF DECK IS FIREPROOFED.
d. ALL FLOOR DECK (WHETHER CONCEALED OR NOT) IS NOT
FIREPROOFED.
e. ALL "FIRE SEPARATION ASSEMBLIES" ARE TO BE CONSTRUCTED
WITH SHEATHING TO OBTAIN APPROPRIATE RATING.
THE SPECIFICATIONS REQUIRE THE FIREPROOFING SUBCONTRACTOR
TO SUBMIT A SCHEDULE LISTING ALL COMPONENTS TO BE
FIREPROOFED, AND THE U.L. TEST (OR OTHER RECOGNIZED TEST) THAT
DESCRIBES THE FIREPROOFING TO ACHIEVE THE RATING.
FIRE PROTECTION NOTES
197' - 2"C
158' - 9"B
28' - 2"F1
27' - 9"E1
117' - 10"A
160' - 9"D
NOT IN SCOPE
OFFICE
OCCUPANCY LEGEND
ASSEMBLY
STORAGE
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
A s i n d ic a te d
/4
/2
:2
:2
P
M
G I1
A U
G U
S T
D e s ig n e r
K S
B D
GI103
B C
C O
D E
A N
A L
Y S
IS
P
L A
N
L E
V E
L
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
GI103 1" = 20'-0"
1 CODE ANALYSIS PLAN - LEVEL 2
AREA OF WORK
IBC OCCUPANCY
CLASSIFICATION AREA
OCCUPANCY
LOAD FACTOR
OCCUPANT
QUANTITY
ASSEMBLY 3912 SF 15 261
OFFICE 29421 SF 150 196
STORAGE 1973 SF 300 7
0' 10' 20' 40'
PATH OF TRAVEL
Mark Length
A 117'-10"
B 158'-9"
C 197'-2"
D 160'-9"
E1 27'-9"
E2 157'-7"
F1 28'-2"
F2 153'-9"
4'-5 1/2 "
3217 3211
3201B 3219
3108C
3201A
3207A
3207B
3205B
:1
S L O P E
ROOF
MONITOR
1/2 :1
S
LO
P E
:1
1/4:12
1/ 4:
1/ 4:
RE: A102C FOR
LOWER ROOF PLAN
ELEV 2
ROOF
:1
:1
:1
:1
:1
:1
:1
1/4:12
1/4:12
:1
:1
:1
:1
:1
1/4:12
1/4:12
1/4:12
1/4:12
1/4:12
1/4:12
:1
COMPUTER
RM
ROOM
OFFICE
OFFICE
OFFICE
WORK
RM
OFFICE
WOMEN'S
RR
JAN
MEN'S
RR
HALLWAY
HALLWAY
LUNCH
ROOM
STAIR
B
ELEV 1
FEC
FEC
FEC
DN
OCCUPANCY LOAD
EGRESS LOAD
EGRESS PATH
1 HR FIRE RATED PARTITION
SMOKE RESISTIVE PARTITION
PER INCIDENTAL USE REQ.
2 HR FIRE RATED PARTITION
CODE ANALYSIS LEGEND
FIRE PROTECTION RATING REQUIREMENTS SHOWN ON BUILDING CODE
DATA CHART AND BUILDING CODE PLANS ON CODE SHEETS. THERE IS A
SCHEDULE OF WHAT COMPONENTS ARE FIREPROOFED AND WHAT UL
TEST MUST BE USED FOR EACH COMPONENT IN THE PROJECT MANUAL
FIREROOFING SECTION 07250 ALL DETAILING ON THE DRAWINGS IS
INTENDED TO COMFORM TO THE REQUIREMENTS OF THE TEST CITED
AND THE BUILDING CODE.
FIRE PROTECTION RATING REQUIREMENTS FOR BUILDING AND
STRUCTURAL COMPONENTS ARE REFEREED TO IN THE CODE DATA
CHART ON THE CODE DRAWING SHEET. THIS CHART IS TAKEN FROM
CODE TABLE 602 OF THE MAIN CODE, AND LIST THE APPLICABLE
PRIMARY ASPECTS OF THE BUILDING. THIS CHART IS REPEATED IN THE
SPECIFICATION SECTION 07811 "SPRAYED FIRE RESTRICTIVE
MATERIALS", TO REQUIRE THIS LEVEL OF FIRE PROTECTION FOR THE
BUILDING.
TYPICALLY:
a. ALL FIRE PROTECTION OF STRUCTURAL MEMBERS IS DONE WITH
SPRAYED MATERIALS.
b. ALL EXPOSED STRUCTURE AND DECK MORE THAN 20 FEET ABOVE
THE FLOOR IS NOT FIREPROOFED.
c. ALL CONCEALED STRUCTURE AND ROOF DECK IS FIREPROOFED.
d. ALL FLOOR DECK (WHETHER CONCEALED OR NOT) IS NOT
FIREPROOFED.
e. ALL "FIRE SEPARATION ASSEMBLIES" ARE TO BE CONSTRUCTED
WITH SHEATHING TO OBTAIN APPROPRIATE RATING.
THE SPECIFICATIONS REQUIRE THE FIREPROOFING SUBCONTRACTOR
TO SUBMIT A SCHEDULE LISTING ALL COMPONENTS TO BE
FIREPROOFED, AND THE U.L. TEST (OR OTHER RECOGNIZED TEST) THAT
DESCRIBES THE FIREPROOFING TO ACHIEVE THE RATING.
FIRE PROTECTION NOTES
157' - 7"E2
153' - 9"F2
NOT IN SCOPE
OFFICE
OCCUPANCY LEGEND
ASSEMBLY
STORAGE
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
A s i n d ic a te d
/4
/2
:2
:3
P
M
G I1
A U
G U
S T
D e s ig n e r
K S
B D
GI104
B C
C O
D E
A N
A L
Y S
IS
P
L A
N S
L
E V
E L
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
AREA OF WORK
IBC OCCUPANCY
CLASSIFICATION AREA
OCCUPANCY
LOAD FACTOR
OCCUPANT
QUANTITY
ASSEMBLY 3912 SF 15 261
OFFICE 29421 SF 150 196
STORAGE 1973 SF 300 7
GI104 1" = 20'-0"
1 CODE ANALYSIS PLAN - LEVEL 3
0' 10' 20' 40'
PATH OF TRAVEL
Mark Length
A 117'-10"
B 158'-9"
C 197'-2"
D 160'-9"
E1 27'-9"
E2 157'-7"
F1 28'-2"
F2 153'-9"
A/C AIR CONDITIONING
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
A&E ARCHITECT AND ENGINEERS
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITIES HAVING
JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATIVE
ALT TRANS ALTERNATIVE TRANSPORTATION
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BB BULLETIN BOARD
BD BOARD
BG BUMPER GUARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BO BOTTOM OF
BRG BEARING
CB CATCH BASIN
CBB CEMENTITIOUS BACKER
BOARD
CER CERAMIC
CF CUBIC FEET
CFCI CONTRACTOR FURNISH
CONTRACTOR INSTALL
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD, CEILING
GRILLE
C & G CURB & GUTTER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNITS
CO CLEANOUT(S)
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
CP CONCRETE PIPE
CPT CARPET
CRS COLD ROLLED STEEL
CS CAST STONE
CSB CONCRETE SPLASH BLOCK
CSI CONSTRUCTION
SPECIFICATIONS INSTITUTE
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CY CUBIC YARD
D DRYER
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DISP DISPENSER
DIV DIVISION
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
(E) EXISTING
EA EACH
EF EXHAUST FAN
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATED
ETS EXPOSED TO STRUCTURE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF & E FURNITURE FIXTURES & EQUIPMENT
FIN FINISH
FIXT FIXTURE
FL FLOW LINE
FLR FLOOR
FLUOR FLUORESCENT
FO FINISH OPENING
FOS FACE OF STUD
FR FIRE RATED
FSP FIRE STANDPIPE
FT FOOT / FEET
FTG FOOTING
FURR FURRING
FV FIELD VERIFY
FVC FIRE VALVE CABINET
FWC FABRIC WALLCOVERING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GF CMU GROUND FACE CMU
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GL BLK GLASS BLOCK
GLU LAM GLUE LAMINATED WOOD
GND GROUND
GT GROUT
GYP BD GYPSUM BOARD
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIB
HC HOLLOW CORE
HCP HANDICAPPED
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR, HANDRAIL
HT HEIGHT
HVAC HEATING, VENTILATING & AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IG INSULATING GLASS
IN INCH
INCAN INCANDESCENT
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
ITG INSULATED TEMPERED GLASS
JAN JANITOR
J-BOX JUNCTION BOX
JT JOINT
L LONG
LAV LAVATORY
LB(S) # POUND(S)
LF LINEAL FEET
LLV LONG LEG VERTICAL
LT LIGHT
LVR LOUVER
M & BH MOP AND BROOM HOLDER
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEPF MECHANICAL, ELECTRICAL, PLUMBING,
FIRE PROTECTION (CONDUIT)
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MSB MOP SERVICE BASIN
MTD MOUNTED
MTL METAL
T TREAD, TEMPERED
TB TACKBOARD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
TD TUBULAR DAYLIGHTING DEVICE
TEL TELEPHONE
TEMP TEMPERATURE
TG TEMPERED GLASS,
TONGUE & GROOVE,
TRANSFER GRILLE
THRU THROUGH
TO TOP OF
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
URN URINAL
VB VINYL WALL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDP WOOD PANELING
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WATER HEATER
WR WASTE RECEPTACLE,
WATER RESISTANT
WS WATER STOP
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
N NORTH
NA NOT APPLICABLE
NECY NECESSARY
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER,
OVERFLOW DRAIN
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
OH OPPOSITE HAND
OPN OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PLASTIC
PARTN PARTITION
PBD PARTICLE BOARD
PCC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PT CONC POST-TENSIONED CONCRETE
PTD PAPER TOWEL DISPENSER
PTL PORCELAIN TILE
PVC POLYVINYL CHLORIDE
QA QUALITY ASSURANCE
QT QUARRY TILE
R R-VALUE (INSULATION),
RADIUS, RISER
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE: REFERENCE
REBAR REINFORCING BAR
REC RECESSED
RECPT RECEPTACLE
REF REFRIGERATOR
REG REGISTER
REINF REINFORCE
REQD REQUIRED
RESIL RESILIENT
REV REVISION
RH ROOF HATCH
RM ROOM
RO ROUGH OPENING
RT RUBBER STAIR TREAD
S SOUTH
SAF SEAMLESS ACRYLIC FLOORING
SAP SUSPENDED ACOUSTICAL PANELS
SAT SUSPENDED ACOUSTICAL TILE
SB SPLASHBLOCK
SC SEALED CONCRETE, SOLID CORE
SCHED SCHEDULE
SCP SCUPPER
SD SOAP DISPENSER
SEAL SEALER
SECT SECTION
SF SQUARE FOOT
SF CMU SPLIT-FACE CMU
SHWR SHOWER
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SLV SHORT LEG VERTICAL
SND SANITARY NAPKIN DISPOSER
SNV SANITARY NAPKIN VENDOR
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
SYS SYSTEM
ARCHITECTURAL ABBREVIATIONS
INCANDESCENT WALL MOUNTED LIGHTING
INCANDESCENT SURFACE MOUNT LIGHTING
SURFACE MOUNTED
FLUORESCENT
TRACK LIGHTING
RECESSED FLUORESCENT
HVAC RETURN AIR GRILLE
HVAC SUPPLY DIFFUSER
PENDANT LIGHT
ACCESS PANEL
EXIT LIGHTING
PARKING LOT LIGHTING
HYDRANT
UTILITY POLE
S
D
SPEAKER
SMOKE DETECTOR
INCANDESCENT RECESSED LIGHTING
REFLECTED CEILING PLAN LEGEND
XX-XX
XX
X
X XXXX
X
X
X XXXXX
PARTITION TYPE
IDENTIFIER
FRAME IDENTIFIER
EQUIPMENT IDENTIFIER
REVISION INDICATOR
BUILDING SECTION
REFERENCE
SECTION REFERENCE
EXTERIOR ELEVATION
REFERENCE
INTERIOR ELEVATION
REFERENCE
ELEVATION INDICATION
DRAWING NUMBER
SHEET WHERE DETAIL
IS LOCATED
DRAWING NUMBER
SHEET WHERE DETAIL
IS LOCATED
DRAWING NUMBER DETAIL
SHEET WHERE DETAIL
IS LOCATED
A-101
A-101
A-101
NORTH ARROW
HANDICAP
SYMBOL
1337A
PROPOSED DOOR
AND DOOR
NUMBER
EXISTING DOOR TO BE
REMOVED
EXISTING DOOR TO REMAIN
COLUMN GRID
IDENTIFIER
MATCH LINE
FIRE EXTINGUISHER
CABINET
AUTOMATED EXTERNAL
DEFIBRILLATOR
FEC
AED
ROOM IDENTIFIER
SHEET LOCATION
VIEW NUMBER
XX KEYNOTE
DETAIL REFERENCE
EXISTING COLUMN
GRID IDENTIFIER
1 View Name A101
S1
BUILDING
OBJECT
REFERENCE
D
FINISH
FLOOREL. = 100'-0"
FINISH
FLOOREL. = 100'-0"
EXISTING ELEVATION
INDICATION
8'-0" AFF SPOT ELEVATION
INDICATION
SPECIALTIES AND
EQUIPMENT IDENTIFIER
XX
OBJECT
REFERENCED
/SEE DRAWING
MATCHLINE
## X###
A-101
N
T R
R
T H
ROOM NAME
101 ROOM NAME
ROOM NUMBER
ARCHITECTURAL DRAWING SYMBOLS
RIGID INSULATION
BLOCKING OR SHIMMING
FINISH WOOD
ROUGH WOOD FRAMING CERAMIC TILE
PLYWOOD
PARTICLE BOARD
ACOUSTIC TILE
EARTH
CONCRETE
GRAVEL STEEL
CONCRETE
MASONRY UNIT
ALUMINUM
BRASS / BRONZE
BATT INSULATION
GYPSUM BOARD
SAND / MORTAR /
PLASTER / CEMENT
GYP. BD. CLG.
OPEN GRID CLG.
PRECAST CONCRETE
BRICK
ACOUSTIC TILE SECTION
MATERIALS LEGEND
REMOVE EXISTING
DOOR & HM FRAME.
SALVAGE DOOR &
HARDWARE FOR
REUSE
REMOVE EXISTING
WIRE MESH
PARTITIONS.
SALVAGE FOR
REUSEREMOVE EXISTING
CMU PARTITION IN
ITS ENTIRETY
PROVIDE STEEL
LINTEL AND REMOVE
AND REMOVE CMU
AS REQUIRED FOR
OPENING
REMOVE EXISTING
METAL STUD
PARTITION IN ITS
ENTIRETY
REMOVE
EXISTING
WINDOW IN ITS
ENTIRETY
REMOVE
EXISTING
CONCRETE SLAB
AS INDICATED
FOR PROPOSED
WORK SEE
STRUCTURAL
DEMOLITION LEGEND
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
/4
/2
:2
:3
P
M
A -0
A U
G U
S T
D e s ig n e r
K S
B D
A-001
B C
A R
C H
IT
E
C T
U R
A L
A B
B R
E V
IA
T
IO
N
S
S Y
M B
O L
S A
N D
M A
T E
R
IA
L S
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
1. DIMENSIONS SHOWN ON PLANS ARE FROM FINISH SURFACE TO
FINISH SURFACE. MASONRY DIMENSIONS GIVEN ARE NOMINAL. "MO"
(MASONRY OPENING) REFERS TO NOMINAL OPENINGS IN MASONRY
UNIT CONSTRUCTION. "RO" (ROUGH OPENING) REFERS TO ACTUAL
OPENINGS BETWEEN METAL STUDS IN METAL STUD CONSTRUCTION.
2. PARTITION TYPES ARE INDICATED ON THE FLOOR PLANS. NUMBERS
REFER TO THE PARTITION TYPE, LETTERS INDICATE VARIATIONS TO
THE BASE CONDITION DRAWN. UNMARKED PARTITIONS SHALL
MATCH ADJACENT PARTITION TYPE.
3. ALL PARTITIONS SHALL EXTEND STRUCTURE TO STRUCTURE
UNLESS OTHERWISE NOTED. REFER TO PARTITION HEAD DETAILS.
4. FIRE-RATED PARTITIONS AND SOUND ISOLATION PARTITIONS ARE
INDICATED ON REFLECTED CEILING PLANS.
5. CONSTRUCTION OF FIRE-RATED PARTITIONS, INCLUDING TAPING
AND FINISHING OF GYPSUM BOARD FOR FULL HEIGHT TO
STRUCTURE ABOVE, SHALL BE IN ACCORDANCE WITH
MANUFACTURERS DIRECTIONS TO ACHIEVE THE RATING INDICATED.
6. SOUND ISOLATION PARTITIONS SHALL BE SEALED AIRTIGHT FOR
FULL HEIGHT TO PREVENT PASSAGE OF AIRBORNE SOUND. TAPE
AND FINISH ALL GYPSUM BOARD JOINTS AND FASTENERS. PROVIDE
SEALANT AT PERIMETER AND AT ALL PENETRATIONS.
7. WHEREVER LENGTH OF MASONRY PARTITION EXCEEDS 8'-0"
BETWEEN LATERAL SUPPORTS, INSTALL 3" x 3" x 0'-6" x 12 GAUGE
FORMED STEEL ANGLES EACH SIDE AT 4'-0" O.C. MAX. ANCHOR EACH
ANGLE TO STRUCTURE WITH TWO 1/8" X 15/16" DRIVE PINS. MASONRY
SHALL STOP 1" FROM STRUCTURE, AND 1" SPACE SHALL BE FILLED
WITH INCOMBUSTIBLE COMPRESSIBLE FILLER.
8. HOLLOW METAL FRAMES IN METAL STUD PARTITIONS SHALL HAVE 4
STUD ANCHORS PER JAMB MINIMUM FOR FRAME HEIGHT OF 7'-2" OR
LESS, AND ONE ADDITIONAL ANCHOR PER JAMB FOR EACH
ADDITIONAL 2'-0" OR FRACTION. HOLLOW METAL FRAMES IN
MASONRY SHALL HAVE 3 MASONRY ANCHORS PER JAMB MINIMUM
FOR FRAME HEIGHT OF 7'-4" OR LESS, AND ONE ADDITIONAL ANCHOR
PER JAMB FOR EACH ADDITIONAL 2'-0" OR FRACTION. ALL HOLLOW
METAL FRAMES SHALL HAVE ONE FLOOR CLIP PER JAMB, WITH TWO
ANCHORS INTO FLOOR AT EACH FLOOR CLIP.
9. PROVIDE JOINT REINFORCEMENT IN ALL MASONRY PARTITIONS,
CONTINUOUS HORIZONTALLY AND SPACED NOT OVER 16" ON
CENTER VERTICALLY, BEGINNING WITH THE JOINT 8" ABOVE THE
FLOOR AND IN THE FIRST AND SECOND JOINTS ABOVE AND BELOW
OPENINGS EXTENDING NOT LESS THAN 24" BEYOND EACH SIDE OF
THE OPENING.
10. PROVIDE FIRE-RETARDANT TREATED WOOD OR SHEET STEEL
BLOCKING FOR PARTITION MOUNTED EQUIPMENT AND CASEWORK.
11. PARTITION TYPES DESCRIBE THE PRIMARY MEMBER AND
SHEATHING. REFER TO FINISH SCHEDULE FOR ALL PARTITION FINISH
DESIGNATIONS.
12. PROVIDE TYPE WR WATER RESISTANT GYPSUM BOARD IN ALL WET
AREAS SUCH AS TOILET ROOMS, SHOWER ROOMS, KITCHENS AND AT
EWC'S.
13. PROVIDE 5/8" CONCRETE BACKER BOARD AT ALL CERAMIC TILE
FINISHES TO ALIGN WITH 5/8" TYPE WR GYPSUM BOARD ABOVE.
14. PROVIDE SLIP JOINT CONNECTIONS AT THE TOPS OF ALL PARTITIONS
WHICH INTERSECT THE STRUCTURE ABOVE. PROVIDE FIRE SAFING
AT ALL SLIP JOINT CONNECTIONS IN FIRE RATED PARTITIONS.
15. WHERE NOTED TO PROVIDE SOUND ISOLATION MATERIAL IN WALLS,
PROVIDE A STRIP OF ISOLATION BLANKET ABOVE THE CONJOINING
WALLS.
16. PROVIDE 16 GA. SHEET METAL BLOCKING WALL SHEATHING AT ALL
WALL MOUNTED ITEMS AT STUD WALLS AND PARTITIONS. ITEMS
SUCH AS SHOWER SEATS AND GRAB BARS ARE TO BE ABLE TO
WITHSTAND A VERTICAL FORCE OF 250 LBS.
PARTITION TYPE NOTES
TYPE GRAPHIC SYMBOL CONSTRUCTION DESCRIPTION
S2
S1
5/8" Gypsum Wallboard
5/8" Gypsum Wallboard 3 5/8" Metal Studs @ 16" O.C.
5/8" Gypsum Wallboard 7/8" Hat Channel
PARTITION TYPES
3 5/8" STUD 6" STUD
12' WALL 362S125-30 @ 16" 600S125-30 @ 16"
16' WALL 362S162-43 @ 16" 600S125-30 @ 16"
20' WALL 362S162-68 @ 12" 600S125-33 @ 16"
24' WALL NA 600S162-43 @ 16"
28' WALL NA 600S162-54 @ 12"
NOTE: THESE STUD SIZES ARE FOR REFERENCE ONLY. PROVIDE SHOP
DRAWINGS FOR PROPOSED WALLS REQUIRING ADDITIONAL STUD
ENGINEERING DUE TO STUD HEIGHT. INCLUDE STUD SPACING, GAUGE
AND HEIGHT INFORMATION. PROVIDE MANUFACTURERS INFORMATION
FOR SELECTED PRODUCTS.
HEIGHT
INTERIOR STUD SIZING GUIDE
A. 1 1/2" SOUND ATTENUATION BLANKET FLOOR TO CEILING. WHERE
PARTITION MEETS CEILING SYSTEM PROVIDE 1 1/2" SOUND
ATTENUATION BLANKET ABOVE CEILING 2'-0" EACH SIDE OF
PARTITION. SEE ACOUSTICAL PARTITION HEAD.
B. PROVIDE 3 1/2" BATT INSULATION FLOOR TO CEILING/STRUCTURE.
C. PROVIDE 20 GA. METAL STUDS @ 16" O.C.
D. PROVIDE 5/8" CEMENT BACKER BOARD AT CERAMIC TILE WITH 5/8"
WATER RESISTANT GYPSUM BOARD ABOVE.
E. PROVIDE 6" 25 GA. METAL STUDS AT 16" O.C.
F. PROVIDE 6" CONCRETE MASONRY UNITS.
PARTITION TYPE SUFFIX
PARTITION TYPE
FLOOR STRUCTURE
3-1/2" x 3-1/2" x 1/4" STEEL ANGLE FULL
HEIGHT OF WALL @ 4'-0" O.C. WELDED
TO 12" HORIZ. SECTIONS BOLTED TO
FLOOR. SCREW VERTICALS TO STUDS,
TYP.
(2) 1/2" BOLTS THRU TO STEEL ANGLE
2-1/2" x 2-1/2" x 2'-0" x 1/4" STEEL
ANGLE PERPENDICULAR TO
PARTITION
WELD TO METAL DECK
STL. STUDS BEHIND GYP. BD.
FILL CAVITY W/ BATT INSULATION
DEEP RUNNER CHANNEL
TRACK, 2" FLANGES
METAL STUDS PERPENDICULAR
WITH FRAMING
STRUCTURE ABOVE
STEEL BEAM
CEILING SURFACE (IN AREAS W/O
CEILINGS, EXTEND GYP. BD. AND
SOUND ATTENUATION BLANKET TO
STRUCTURE ABOVE).
SLIP ANCHOR
STRUCTURE ABOVE
PARTITION TYPE
M
IN
4"
3 1/2" SOUND ATTENUATION
BLANKET (WHEN INDICATED W/
SUFFIX "A")
SEALANT EACH SIDE, TYP.
METAL TRIM BOTH SIDES
CEILING RE: FINISH SCHEDULE
FASTEN RUNNER
TO CEILING
PARTITION TYPE
METAL STUDS BEHIND GYP.
BD.
FILL CAVITY W/ BATT INSULATION
STEEL STUDS PERPENDICULAR
WITH FRAMING
BAR JOIST
STRUCTURE ABOVE
DEEP RUNNER
TRACK, 2" FLANGES
CEILING SURFACE
RUNNER TRACK
PARTITION TYPE
METAL TRIM BOTH SIDES
SLIP CONNECTION
STRUCTURE ABOVE
DEEP RUNER TRACK, 2" FLANGES
1-1/2" METAL CHANNEL
STUD REINFORCING
PARTITION TYPE
SCREW FASTEN GYPSUM BOARD
1" BELOW RUNNER TRACK TO
ALLOW FOR VERTICAL MOVEMENT
1" 1"
1"
1'
M A
X
2"
EXTEND STUDS 1" INTO RUNNER
TRACK, LEAVE 1" CLEARANCE FOR
VERTICAL MOVEMENT. CUT TRACK
FLANGE AND FOLD AGAINST SIDES
OF STUDS
CEILING SURFACE
STRUC. ABOVE
PARTITION TYPE-
CONTINUE GYP. BD. TO
SLIP ANCHOR ABOVE
WHERE NO CEILING IS
INDICATED
M
IN
4"
CONTRACTORS
OPTION 3-5/8"
METAL STUD
BRACE 4'-0" O.C.
EACH WAY
RUNNER TRACK T.O.
PARTITION, OPTION
SLIP ANCHOR
1 2 3 4 5
D
C
B
A
SHEET
IDENTIFICATION
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
C K
D B
Y x
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
D2C ARCHITECTS, INC.
DENVER, COLORADO
COPYRIGHT © YYYY
THESE DRAWINGS AND PLANS ARE
COPYRIGHTED AND ARE NOT TO BE USED
OR REPRODUCED WHOLLY OR IN PART
WITHOUT THE WRITTEN PERMISSION OF
D2C ARCHITECTS, INC.
NOT FOR
CONSTRUCTION
D
C P
R O
J E
C T
N U
M B
E R
C O
N S
U L
T A
N T
S P
R O
J E
C T
A s i n d ic a te d
/4
/2
:2
:3
P
M
A -0
A U
G U
S T
D e s ig n e r
K S
B D
A-011
B C
P A
R T
IT
IO
N T
Y P
E S
A N
D D
E T
A
IL
S
C
IT
Y O
F C
O M
M E
R C
E C
IT
Y
C
IV
IC
C
E N
T E
R R
E S
T R
U C
T U
R E
E
0T H
A V
E N
U E
, C O
M M
E R
C E
C
IT
Y , C
O
TENANT
IMPROVEMENT
P ro je c t
N u m b e r
0' 4" 8" 1'-4"
0' 4" 8" 1'-4"
0' 4" 8" 1'-4"
A-011 1 1/2" = 1'-0"
A4 HALF HEIGHT PARTITION BASE DETAIL
A-011 1 1/2" = 1'-0"
C3 PARTITION HEAD AT BEAM
A-011 1 1/2" = 1'-0"
C4 ACOUSTICAL PARTITION HEAD
A-011 1 1/2" = 1'-0"
B3 PARTITION HEAD AT CEILING
A-011 1 1/2" = 1'-0"
A3 PARTITION HEAD AT JOIST
A-011 1 1/2" = 1'-0"
A2 PARTITION HEAD C
A-011 1 1/2" = 1'-0"
B2 SLIP ANCHOR
A-011 1 1/2" = 1'-0"
B4 TYPICAL PARTITION HEAD
0' 4" 8" 1'-4"
0' 4" 8" 1'-4"
0' 4" 8" 1'-4"0' 4" 8" 1'-4"
0' 4" 8" 1'-4"
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P e f.
R e f.
UP
SELECTIVE DEMO TO KEEP
EXISTING COUNTERTOP
DEMOLITION FLOOR PLAN NOTES
1. VERIFICATION OF EXISTING CONDITIONS: IN AS MUCH AS THE
REMODELING AND/OR REHABILITATION OF AN EXISTING BUILDING
REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING
EXISTING CONDITIONS, AND BECAUSE SOME OF THESE
ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING
ADDITIONAL SUMS OF MONEY, OR DESTROYING OTHERWISE
ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THE
ARCHITECT IS NOT RESPONSIBLE FOR CONDITIONS DISCOVERED
DURING CONSTRUCTION WHICH DIFFER FROM THOSE INDICATED
ON THESE DRAWINGS.