D7 Fire Panel - Critical Infrastructure
Solicitation number
24-494DOT-FINAD-B-41692
Issued by
Edgar County, Illinois

About this file

This document is an exhibit listing the equipment and quantities required for a fire alarm system upgrade project for critical infrastructure facilities in Illinois. The project covers facilities in Effingham County and includes the replacement of a main fire alarm control panel, cellular communicator, remote annunciators, smoke and heat detectors, pull stations, modules, and audible/visual devices. The document provides estimates for the quantity of each device needed, along with details on the existing wiring infrastructure and power requirements. The project is a state and local contract opportunity identified as "D7 Fire Panel - Critical Infrastructure" for the State of Illinois.

The pricing and contractual terms are not explicitly stated in this document. However, the exhibit suggests this is part of a larger procurement process, and additional information such as funding sources, set-asides, and incumbent providers may be available in the full solicitation package.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Device List

Estimated number of devices based on previous system and may not be a complete list.

**If not listed below, must include necessary devices necessary to have a fully functioning system**

Description Quantity Main Fire Panel – Addressable Fire Releasing 1 Cellular Communicator – To Monitoring Company 1 LCD Remote Annunciator - Red Enclosure 3 Digital Alarm Communicator Technology (DACT) 1 Batteries for Battery Backup for Fire Panel – Assumed 12V 8A 8 Network and Power Expander Panel (Repeater / Extender) 3 Photoelectric Smoke Detector – Photo Detector 155 6” Detector Base 165

Heat Detector 10 Duct Detector w/ Relay 12 Sampling Tube for Addressable Duct Detector 12 Addressable Pull Station 17 Single Input Module 12 Relay Module 6 Selectable Horn/Strobe – Red 75 Selectable Strobe – Red 30

Circuits:

Voltage: 120V 20A

Class: Class 4 Style Y

Currently Installed Wiring:

Device Wire: 14/2 Solid Wire – Red – Fire/Life Safety Control Cable

Network/Phone: CAT5e Cabling

Power/Network Extender Panels:

Extender Panel #1 – Main Building by Main Panel = 4 NAC Branches

Extender Panel #2 – Annex Building = 3 NAC Branches

Extender Panel #3 – OPs/Survey Building = 4 NAC Branches