Exhibit_2_-_CWS_Performance_Tests.pdf
PDF 2 MB Posted
- Attached to
- Camping World Stadium Playing Field Replacement
- Solicitation number
- RFP26-0497
- Issued by
- Orange County, Orlando City, Florida
About this file
This is a field test report prepared by Sports Labs LLC documenting performance testing conducted at Camping World Stadium in Orlando, Florida on April 22, 2026, in support of the City of Orlando's Playing Field Replacement project. The testing was performed to evaluate the water infiltration rate of the installed synthetic turf system using the EN 12616:2013 test method. The report details specifications for the 3G Air Performance synthetic turf surface with Brockfill infill material installed over a shockpad underlayment and dynamic stone substrate. Testing was conducted under dry conditions with ambient air temperature of 74°F, surface temperature of 76°F, and 42 percent humidity. The report documents test results from five measurement locations across the field, with measurements recorded using a double ring infiltrometer method.
The infiltration testing results revealed significant variability across the five tested locations, with porosity measurements ranging from 60 to 2,299 inches per hour, and an average porosity of 1,194 inches per hour after temperature correction. Location 1 demonstrated notably higher infiltration rates (2,299 in/hr) compared to locations 2 through 5, which ranged from 60 to 121 in/hr, indicating inconsistent water infiltration performance across the field surface. The report was finalized on June 2, 2026, and certified by Ashley Chasse, Operations Director, and Kieran O'Donnell, Director of Sports Labs LLC. The testing results serve as documentation of the field's drainage performance characteristics as part of the broader project evaluation to ensure the synthetic turf system meets the City's performance and safety requirements established in coordination with NFL and NFLPA specifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIELD TEST
REPORT
Report Number: 10431-3031
Report Status: Final
Issue Date: 6/2/2026
CAMPING WORLD
STADIUM
PERFORMANCE
TESTS
Specification(s) tested:
EN 12616:2013
Report Number: [Report Number]
Revision Number: 1 Date: 6/2/2026 Note of Amendment: N/A This report supersedes the previous report: No
Camping World Stadium 1 Citrus Bowl Place Orlando, Florida 32805 United States of America
Activitas Inc 70 Milton Street Dedham, MA, 02026 United States of America
Foreword
Sports Labs LLC prepared this report with all reasonable skill, care, and diligence within the contract terms with the Client and within the limitations of the resources devoted to it. This report is confidential to the Client and Sports Labs LLC accepts no responsibility whatsoever to third parties to whom this report, or any part thereof, is made known. Any such party relies upon the report at their own risk.
This report shall not be reproduced except in full without the approval of the laboratory to ensure that parts of a report are not taken out of context.
This report shall not be used for engineering or contractual purposes unless signed by the Author and Checker and the report status is “Final”. Draft reports may be subject to change.
Sports Labs LLC provides this report for informational purposes, and it is intended to convey the results obtained from testing conducted on the date indicated. The results and conclusions documented in this report are valid only as of the date of testing and the specific site conditions on that date. Any changes in the testing environment, materials, equipment, or procedures could affect the results' accuracy and relevance. As such, the conclusions and data contained in this report may not necessarily apply to different circumstances or conditions. Any deviations from the testing procedure have been previously discussed and agreed upon with the client, with the understanding that such deviations may affect the accuracy of the results.
If the measurement lies within the lower and upper specification limit the result is accepted as meeting the required criteria. If it falls outside of this range, the result is rejected as non-conforming. Measurement uncertainty is not applied as a guard band in this decision-making process.
This report is not an official National Governing Body report and does not imply NGB approval.
*Not all the tests may be within our current ISO 17025 scope of accreditation.
REPORT CREATED BY
Ashley Chasse Operations Director 6/2/2026
REPORT CHECKED BY
Kieran O'Donnell Director 6/2/2026
Date: 6/2/2026
Introduction
Sports Labs conducted on-site performance testing at Camping World Stadium per the EN and ASTM test methods listed below.
Test methods
• EN 12616:2013 – Determination of Water Infiltration Rate
Table of Contents
Foreword Introduction Test methods Table of Contents Field Information and Test Conditions Results Summary ....................................................................................................................... Error! Bookmark not defined.
Test Results ................................................................................................................................. Error! Bookmark not defined.
Photos
Field Information and Test Conditions
System Details Testing Conditions
Testing Date 4/22/2026 Testing Time AM Carpet Product 3G Air Temperature (F) 74 Performance Infill Brockfill Surface Temperature (F) 76 Stabilizing Infill None Humidity (%) 42 Test Condition Dry Wind Speed (m/s) 0 Underlayment Shockpad Weather Conditions Sunny Substrate Type Dynamic Stone Field Orientation End A = East Primary Sport Football Operator AC Method of Sealing Weight/Tamp Device Double Ring Infiltrometer
Date: 6/2/2026
Figure one: Camping World Stadium
Infiltration Test Results
Infiltration Results
Location 1 2 3 4 5 Average Average Fall Time
20mm (sec): 1.19 16.53 24.34 22.07 34.47 19.74
Temperature Correction: 0.767 0.767 0.767 0.767 0.767 0.767
Porosity (in/hr): 2299 121 86 101 60 1194
Figure four: Infiltration map
Date: 6/2/2026
Photos
END OF REPORT
+1 (706) 406 2070 kieran@sportslabs.com www.sportslabs.com
50 Business Depot Drive, Ringgold, Georgia, 30736, USA
| Foreword |
| Introduction |
| Test methods |
| Table of Contents |
| Field Information and Test Conditions |
| Infiltration Test Results |
| Photos |