Exhibit_1_-_Water_Conserv_II_WRF_Equalization_Pump_Station_Improvements.pdf
PDF 17 MB Posted
- Attached to
- Construction Engineering and Inspection (CEI) Services for Water Conserv II WRF Construction Projects
- Solicitation number
- RQS26-0340
- Issued by
- Orange County, Orlando City, Florida
About this file
This is a comprehensive set of design and construction drawings for the Water Conserv II Water Reclamation Facility (WRF) Equalization Pump Station Improvements project issued for bid by the City of Orlando Department of Public Works, with project engineering by Hazen and Sawyer and civil/site engineering by Civil/Site Engineering, Inc. The project (CIP0199_P) involves significant upgrades to the existing equalization pump station, including demolition of existing equipment and structures, construction of a new electrical building, installation of five new dry-pit submersible pumps with variable frequency drives, replacement of discharge piping and valve systems, installation of new instrumentation and controls, and associated site improvements including grading, drainage, and pavement restoration. The work encompasses civil, structural, mechanical, electrical, HVAC, and instrumentation disciplines, with detailed drawings showing existing conditions, demolition plans, new construction details, and equipment specifications. Normal working hours are 7:00 AM to 3:30 PM Monday through Friday, with advance notice required for after-hours work; the facility operates 24 hours per week, and contractor personnel must obtain picture identification and coordinate all activities through designated supervisors to minimize operational disruption.
The project specifications detail extensive requirements for construction sequencing, temporary bypass pumping systems to maintain facility operations during construction, utility coordination, erosion and sediment control, concrete testing and repair procedures, and comprehensive as-built documentation by a Florida-licensed surveyor. Key construction constraints include mandatory 14-day advance notice to the City for any service disruptions, maximum 2-hour downtime for piping connections unless otherwise specified, coordination with chlorine tank change-outs that occur weekly, compliance with FDEP regulations and City of Orlando engineering standards, and maintenance of tree protection zones with minimum 0.75-foot-per-inch DBH undisturbed radii. The contractor must obtain all required permits including NPDES dewatering permits, perform confirmatory groundwater sampling due to elevated chromium and total organic carbon levels detected in geotechnical reports, and comply with stormwater pollution prevention plans utilizing inlet sediment barriers, silt fencing, floating turbidity barriers, and dust control measures on the 0.29-acre disturbed site that drains to Shingle Creek Canal.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G-00-01
CITY OF ORLANDO
WATER CONSERV II WRF
DEPARTMENT OF PUBLIC WORKS
EQUALIZATION PUMP STATION IMPROVEMENTS
JULY 2025
ISSUED FOR BID
PROJECT NO.: CIP0199_P
LOCATION MAP
NOT TO SCALE
TURNPIKE
FLORIDA
RD.
McLEOD
R D
LA
KE
TU
R
KE
Y
IN
TE
RSTA
TE
VI
NEL
AN
D R
D.
CORY RD.
KI
R
KM
AN
R D
CAIN
LAKE
TURKEY LAKE
MANN
LAKE
LAKE
CLEAR
CATHERINE
LAKE
AMERICANA BLVD.
L.B.
BUDDY DYER
MAYOR
COREY F. KNIGHT, P.E.
DIRECTOR OF PUBLIC WORKS
CHRISTOPHER ANDRES, P.E
WATER RECLAMATION DIVISION MANAGER
KRISTINA L. FRIES, P.E.
PROJECT MANAGER
JIM GRAY
COMMISSIONER DISTRICT 1
TONY ORTIZ
COMMISSIONER DISTRICT 2
ROBERT F. STUART
COMMISSIONER DISTRICT 3
PATTY SHEEHAN
COMMISSIONER DISTRICT 4
SHAN ROSE
COMMISSIONER DISTRICT 5
BAKARI F. BURNS
COMMISSIONER DISTRICT 6
CITY OF ORLANDO
HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
PL
O
T D
AT
E:
6/
/2
1:
P
M B
Y:
K
R O
M
ER
O Fi le : C
:\U
SE
R S\
KR
O
M
ER
O \D
C \A
C C
D O
C S\
H
AZ
EN
A
N D
S
AW
YE
R
\4
-0
_C
O N
SE
R
V
II
W R
F
EQ
P S
FI
N
AL
D
ES
IG
N \P
R O
JE
C
T
FI
LE
S\
_D
ES
IG
N \0
1- H
AZ
EN
\G
EN
ER
AL
\4
-0
-G
-0
S av ed b y K R
O M
ER
O S av e da te
: 6/
/2
1:
P
M
JIM GRAY
COMMISSIONER DISTRICT 1
TONY ORTIZ
COMMISSIONER DISTRICT 2
ROBERT STUART
COMMISSIONER DISTRICT 3
PATTY SHEEHAN
COMMISSIONER DISTRICT 4
SHAN ROSE
COMMISSIONER DISTRICT 5
BAKARI F. BURNS
COMMISSIONER DISTRICT 6
B. UPRETI
M. NIEMIEC
G-00-02
GENERAL
PLANT CONSTRUCTION RULES
AND SHEET INDEXW. MARSHALL
PLANT CONSTRUCTION RULES
1. NORMAL BUSINESS HOURS ARE 7:00 AM TO 3:30 PM. HOWEVER THE FACILITY OPERATES 24
HOURS, 7 DAYS/WEEK.
2. ADVANCE NOTICE (MINIMUM 7 BUSINESS DAYS) IS REQUIRED, IF WORK IS TO BE CONTINUED
AFTER HOURS. WORK REQUESTS TO BE SUBMITTED IN WRITING FOR THE CITY APPROVAL.
3. THE MAINTENANCE SUPERVISOR, WILL BE THE PLANT CONTACT, IF THE MAINTENANCE
SUPERVISOR IS NOT AVAILABLE, THEN THE PLANT MANAGER WILL REPRESENT THE FACILITY.
4. ALL CONTRACTOR’S PERSONNEL, AND SUBCONTRACTORS, MUST OBTAIN & WEAR AT ALL TIMES A
PICTURE ID SUPPLIED BY CONTRACTOR.
5. ALL CONSTRUCTION RELATED EMPLOYEES WILL ENTER AND EXIT THROUGH THE DESIGNATED
CONSTRUCTION GATE. CONTACT THE CONTRACTOR REPRESENTATIVE FOR ENTRY.
CONTRACTOR RESPONSIBLE TO MANAGE GATE ACCESS. CONTRACTOR SHALL MANAGE ALL
UNLOADING AND MINIMIZE IMPACTING TRAFFIC. COMPANY PHOTO ID OF A VALID CONTRACTOR
OR SUB CONTRACTOR IS REQUIRED. THE CONTRACTOR REPRESENTATIVE WILL MAINTAIN A LIST
OF EMPLOYEES, SUB CONTRACTORS AND VENDORS.
6. BE SURE YOU ARE AWARE OF THE DIFFERENCE IN WATER LINES. POTABLE (DRINKING WATER)
AND RECLAIMED (REUSE WATER FROM PLANT EFFLUENT). REUSE LINES ARE ALL
MARKED/PAINTED PANTONE 522C LAVENDER.
7. NO FIREARMS, ALCOHOL, OR DRUGS ON PREMISES.
8. PLACE SIGNS SO DELIVERIES CAN BE MADE TO THE CONSTRUCTION SITE. LOCATIONS TO BE
APPROVED BY MAINTENANCE SUPERVISOR. CONTRACTOR RESPONSIBLE FOR ALL DELIVERIES.
PLANT PERSONNEL WILL NOT ACCEPT CONSTRUCTION DELIVERIES.
9. MAXIMUM SPEED LIMIT THROUGHOUT THE PLANT IS 10 MPH. FULL STOP AT ALL STOP SIGNS IS
REQUIRED. STRICTLY ENFORCED.
10. VEHICLES AND SECURITY: ALL VEHICLES WILL BE PARKED IN ASSIGNED AREAS ONLY AND SHOULD BE LOCKED AT ALL TIMES. CITY WILL NOT BE RESPONSIBLE. CONTRACTOR TO PROVIDE, AND MAINTAIN, DESIGNATED PARKING. ALL STAFF SHALL USE DESIGNATED PARKING.
11. MATERIAL STORAGE IN CONTRACTOR’S TRAILERS: THE CITY IS NOT RESPONSIBLE FOR
SECURITY.
12. CONFINE CONSTRUCTION PERSONNEL TO THE JOB SITE.
13. EMERGENCY SERVICES BY CITY OF ORLANDO POLICE AND FIRE DEPARTMENTS ARE 9-911.
14. CONSTRUCTION PERSONNEL, EXCEPT FOR EMERGENCIES, WILL NOT USE PLANT PHONES.
15. COORDINATE ALL ELECTRICAL/PIPE CONNECTIONS THROUGH MAINTENANCE SUPERVISOR OR
PLANT MANAGER.
16. GENERAL CONTRACTOR WILL BE RESPONSIBLE FOR HIS EMPLOYEES AND SUBCONTRACTORS
EMPLOYEES FOLLOWING PLANT RULES AND VEHICULAR SAFETY. CONTRACTOR SHALL NOT
ADVERSELY IMPACT TRAFFIC FLOW. CONTRACTOR TO REQUEST APPROVAL FOR ALL CHANGES
TO TRAFFIC FLOW. CONTRACTOR TO REQUEST APPROVAL FOR ALL ROADWAY IMPACTS FOR
CONSTRUCTING THE WORK, I.E. CRANE ACCESS.
17. CONTRACTOR WILL FURNISH PORTABLE RESTROOMS. CONTRACTOR PERSONNEL WILL NOT USE
RESTROOMS IN THE PLANT.
18. THE CONTRACTOR’S PERSONNEL WILL NOT USE PLANT LUNCHROOM, FACILITIES, OR GYM.
19. A LIST OF ALL SUBCONTRACTORS WILL BE GIVEN TO THE PLANT MANAGER. CONTRACTOR
RESPONSIBLE TO MAINTAIN CURRENT LIST.
20. A LIST OF EMERGENCY PHONE NUMBERS WILL BE GIVEN TO THE PLANT MANAGER.
21. NO ONE IS ALLOWED IN THE AREA OF THE CHLORINE HANDLING FACILITY DURING CHLORINE TANK CHANGES. PLANT PERSONNEL WILL PLACE SIGNS IN STREETS DURING THESE CHANGE OUT
TIMES. PRIOR TO WORK COMMENCING AN EMERGENCY PLAN WILL BE REVIEWED WITH
CONTRACTOR. CHLORINE CHANGE OUTS AND DELIVERIES GENERALLY OCCUR WEEKLY.
ADVANCE NOTICE WILL BE GIVEN TO THE CONTRACTOR.
22. NO OPEN FIRES ON PLANT GROUNDS.
23. SMOKING IN DESIGNATED AREAS ONLY.
24. TRASH, RUBBLE, ETC. SHOULD BE REMOVED FROM THE PROJECT DAILY. DURING HURRICANE
SEASON, THE CONTRACTOR WILL BE RESPONSIBLE FOR SECURING CONSTRUCTION MATERIALS
DURING STORM EVENTS.
25. CONTRACTORS WILL SUPPLY THEIR OWN DRINKING WATER AND ICE FOR THEIR PERSONNEL.
26. THERE IS A STORM WATER POLLUTION PREVENTION PLAN IN EFFECT AT THIS FACILITY, WHICH
MUST BE FOLLOWED. CONTRACTOR SHALL NOT ADVERSELY IMPACT DRAINAGE COLLECTION.
CONTRACTOR SHALL REGULARLY MAINTAIN ALL GROUNDSKEEPING FOR STORAGE, PARKING AND
WORK AREAS.
PL
O
T D
AT
E:
/2
6/
:2
PM
B Y:
K R
O M
ER
O
Fi le
: C :\U
SE
R
S\
KR
O M
ER
O
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \4
-0
_C O
N
SE
R V
II
W
R F
EQ
P
S
FI
N
AL
D
ES
IG
N
\P R
O
JE
C T
FI
LE
S\
_D
ES
IG
N
\0 1-
H
AZ
EN
\G
EN
ER
AL
\4
-0
-G -0
Sa ve d by K
R O
M
ER
O S av e da te
: 6 /2
6/
:1
PM
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
JULY 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
TELEPHONE NUMBERS (AFTER HOURS):
1. KEITH JORDAN, PLANT MANAGER...................................................................407-325-5653
2. LUIS RAMOS, MAINT. SUPERVISOR....………………………………................... 407-709-3778
3. JOSHUA REYES, CHIEF OPERATOR …................................................…....... 407-272-7476
INDEX OF DRAWINGS
DWG
NUMBER SHEET TITLE
GENERAL
G-00-01 COVER SHEET, LOCATION MAP
G-00-02 PLANT CONSTRUCTION RULES AND SHEET INDEX
G-00-03 GENERAL NOTES
G-00-04 ABBREVIATIONS AND SYMBOLS
CIVIL
C-01-00 EXISTING SITE SURVEY
C-01-01 SITE GEOMETRY, PAVING, GRADING AND DRAINAGE
PLAN
C-01-02 EXISTING SITE PLAN AND DEMOLITION
C-01-03 YARD PIPING
C-01-04 STORMWATER POLLUTION PREVENTION PLAN
C-01-05 STORMWATER POLLUTION PREVENTION PLAN
ARCHITECTURAL
A-10-01 EXISTING AND PROPOSED FLOOR PLANS
A-10-02 EQUALIZATION PUMP STATION EXISTING AND
PROPOSED FLOOR PLANS
A-10-03 EQUALIZATION PUMP STATION ELEVATIONS, DETAILS
AND NOTES
A-20-01 ELECTRICAL BUILDING FLORIDA CODE SUMMARY
A-20-02 ELECTRICAL BUILDING LIFE SAFETY PLAN
A-20-03 ELECTRICAL BUILDING FLOOR PLAN
A-20-04 ELECTRICAL BUILDING ROOF PLAN
A-20-05 ELECTRICAL BUILDING REFLECTED CEILING PLAN
A-20-06 ELECTRICAL BUILDING ELEVATIONS
A-20-07 ELECTRICAL BUILDING BUILDING SECTIONS
A-20-08 ELECTRICAL BUILDING WALL SECTIONS
A-20-09 ELECTRICAL BUILDING DETAILS & SCHEDULES
STRUCTURAL
S-00-01 GENERAL STRUCTURAL NOTES - SHEET 1
S-00-02 GENERAL STRUCTURAL NOTES - SHEET 2
S-00-03 STRUCTURAL GENERAL CONCRETE REPAIR DETAILS
AND NOTES
S-99-01 STRUCTURAL STANDARD DETAILS - SHEET 1
S-99-02 STRUCTURAL STANDARD DETAILS - SHEET 2
S-99-03 STRUCTURAL STANDARD DETAILS - SHEET 3
S-99-04 STRUCTURAL STANDARD DETAILS - SHEET 4
S-10-01 BOTTOM FLOOR - DEMOLITION PLAN
S-10-02 INTERMEDIATE FLOOR- DEMOLITION PLAN AND
SECTIONS
S-10-03 TOP FLOOR - DEMOLITION PLAN AND SECTIONS
S-10-04 BOTTOM FLOOR PLANS
S-10-05 INTERMEDIATE AND TOP FLOOR PLANS
S-10-06 ENLARGED STAIR PLANS
S-10-07 ENLARGED TOP STAIR PLAN AND SECTIONS
S-10-08 STAIR SECTIONS AND DETAILS
S-10-09 DETAILS
S-20-01 ELECTRICAL BUILDING - FLOOR AND ROOF PLAN
S-20-02 ELECTRICAL BUILDING SECTIONS AND DETAILS
MECHANICAL
M-10-01 EQUALIZATION PUMP STATION BOTTOM AND
INTERMEDIATE DEMOLITION PLANS
M-10-02 EQUALIZATION PUMP STATION DEMOLITION SECTIONS
M-10-03 EQUALIZATION PUMP STATION BOTTOM FLOOR
M-10-04 EQUALIZATION PUMP STATION SECTIONS
M-10-05 EQUALIZATION PUMP STATION ISOMETRIC VIEWS
M-10-06 EQUALIZATION PUMP STATION TEMPORARY BYPASS
PUMPING
M-10-07 EQUALIZATION PUMP STATION DETAILS
HVAC
H-00-01 GENERAL NOTES AND SYMBOLS
H-10-01 EQUALIZATION PUMP STATION DEMO PLAN-PUMP
STATION
H-10-02 EQUALIZATION PUMP STATION PLAN-PUMP STATION
H-10-03 EQUALIZATION PUMP STATION PLAN- PUMP STATION
SECTIONS
H-20-01 PLAN ELECTRICAL BUILDING
H-98-01 SCHEDULES & CONTROLS
H-99-01 DETAILS
ELECTRICAL
E-00-00 NOTES, SYMBOLS AND ABBREVIATION
E-00-01 DEMOLITION SITE PLAN
E-00-02 OVERALL SITE PLAN
E-00-03 OVERALL SITE SINGLE LINE DIAGRAM (DEMOLITION)
E-00-04 OVERALL SITE SINGLE LINE DIAGRAM (MODIFICATION)
E-00-05 SWITCHGEAR SINGLE LINE DIAGRAM
E-00-06 EXISTING EQ PUMP STATION MCC & FRONT VIEW
DEMOLITION
E-00-07
PANEL PP-01 - SINGLE LINE DIAGRAM (NEW
ELECTRICAL BUILDING)
E-00-08
PANEL PP-02 - SINGLE LINE DIAGRAM (NEW
ELECTRICAL BUILDING)
E-00-09
PANEL PP-03 - SINGLE LINE DIAGRAM (EXISTING EQ
BUILDING)
E-00-10
PANEL PP-04 - SINGLE LINE DIAGRAM (EXISTING EQ
BUILDING)
E-00-11 SWITCHGEAR FRONT ELEVATION
E-00-12 ELECTRICAL INSTRUMENTATION RISER DIAGRAM &
ELEMENTARIES
E-10-01 EXISTING ELECTRICAL ROOM DEMOLITION &
MODIFICATION PLAN
E-10-02 BOTTOM LEVEL DEMOLITION PLAN
E-10-03 BOTTOM LEVEL EQ PUMP STATION POWER PLAN
E-10-04 BOTTOM LEVEL EQ PUMP STATION LIGHTING PLAN
E-10-05 INTERMEDIATE LEVEL EQ PUMP STATION DEMOLITION
PLAN
E-10-06 INTERMEDIATE LEVEL EQ PUMP STATION POWER
PLAN
E-10-07 INTERMEDIATE LEVEL LIGHTING PLAN
E-20-01 ELECTRICAL ROOM POWER PLAN
E-20-02 ELECTRICAL ROOM LIGHTING PLAN
E-20-03 ELECTRICAL ROOM GROUNDING & LIGHTNING
PROTECTION PLAN
E-20-04 PLAN SCHEDULE
E-20-05 LIGHTING SCHEDULE AND DETAILS
E-20-06 ELECTRICAL DETAILS - SHEET 1
E-20-07 ELECTRICAL DETAILS - SHEET 2
INSTRUMENTATION
I-00-01 LEGEND AND SYMBOLS
I-00-02 EQUALIZATION PUMP STATION - EXISTING NETWORK
DIAGRAM
I-00-03 EQUALIZATION PUMP STATION - PROPOSED NETWORK
DIAGRAM
I-00-04 EQUALIZATION PUMP STATION - P&ID
I-00-05 INSTRUMENTATION EQUALIZATION PUMP STATION
DETAILS
G-00-03
GENERAL
NOTESW. MARSHALL
GENERAL NOTES
1. FOLLOWING NOTES ARE GENERAL AND APPLY TO ALL SHEET OF THESE CONTRACT DOCUMENTS
AS IF THEY WERE WRITTEN IN THEIR ENTIRETY ON EACH SHEET.
2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE STARTING WORK AND SHALL
IMMEDIATELY NOTIFY THE ENGINEER OF ANY DISCREPANCIES. CONTRACTOR SHALL BE
RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS INCLUDING LOCATION AND
DIMENSION OF ALL EXISTING CONSTRUCTION AND UTILITIES. CONTRACTOR SHALL NOTIFY
ENGINEER IF THERE IS A CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND EXISTING
CONSTRUCTION BEFORE PROCEEDING WITH WORK.
3. UNLESS DETAILED, SPECIFIED, OR OTHERWISE INDICATED ON THE DRAWINGS, CONSTRUCTION SHALL BE AS INDICATED IN THE APPLICABLE TYPICAL DETAILS AND GENERAL NOTES, TYPICAL DETAILS SHALL APPLY EVEN THOUGH NOT REFERENCED AT SPECIFIC LOCATIONS ON DRAWINGS.
4. WHERE NO CONSTRUCTION DETAILS ARE SHOWN OR NOTED FOR ANY PART OF WORK, DETAILS
SHALL BE IN THE SAME AS FOR OTHER SIMILAR WORK.
5. CONTRACTOR SHALL COMPLY WITH LOCAL CONSTRUCTION STORM WATER DISCHARGE
REGULATIONS AND REQUIREMENTS.
6. PRIOR TO EXCAVATION FOR NEW STRUCTURES, ELECTRICAL CONDUIT, FABRICATION OF NEW
PIPING AND/OR OTHER PROPOSED UTILITIES, CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING THE LOCATION OF ALL EXISTING PIPING AND UTILITIES IN THE CONSTRUCTION AREA.
THE CONTRACTOR SHALL TEMPORARILY RELOCATE CONFLICTING EXISTING UTILITIES AT
TIE-INCONNECTION LOCATIONS AND REINSTALL THEM AS REQUIRED TO ELIMINATE THE CONFLICT
AT NO ADDITIONAL COST TO THE OWNER.
7. ALL PIPELINES SHALL HAVE A MINIMUM COVER OF 36" UNLESS THE COVER DEPTH IS
SPECIFICALLY INDICATED ON THE DRAWINGS. PIPES SHALL BE ROUTED AS SHOWN UNLESS
MINOR. REVISIONS ARE NECESSARY TO MISS EXISTING PIPES STRUCTURES. ETC. CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING ALL FITTINGS AND ADAPTERS REQUIRED TO MAKE THE
ROUTING CHANGES AT NO ADDITIONAL COST TO THE OWNER CONTRACTOR SHALL INCLUDE
COST FOR THIS IN THE BID.
8. EXISTING FACILITY AND UTILITY INFORMATION SHOWN ON THE DRAWINGS WAS OBTAINED FROM
AVAILABLE RECORDS OR ELECTRONICS FILES, NEITHER THE OWNER NOR ENGINEER ASSUMES
ANY RESPONSIBILITY FOR FACILITIES AND UTILITIES NOT SHOWN OR NOT IN THE LOCATION
SHOWN. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS, SIZES, MATERIAL, TYPES AND
ELEVATIONS SHOWN AROUND OR NEAR AREAS OF NEW CONSTRUCTION PRIOR TO START OF
CONSTRUCTION.
9. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES NECESSARY TO PROTECT FROM DAMAGING EXISTING FACILITIES AND UTILITIES SHOWN OR NOT SHOWN THAT ARE TO REMAIN IN PLACE. ALL FACILITIES DAMAGED BY THE CONTRACTOR'S OPERATIONS SHALL BE EXPEDITIOUSLY
REPAIRED OR RECONSTRUCTED TO THE ORIGINAL OR BETTER CONDITION AT THE
CONTRACTOR'S EXPENSE WITHOUT ADDITIONAL COMPENSATION.
10. CONTRACTOR SHALL MAKE CONNECTIONS TO EXISTING PIPE, EQUIPMENT, ETC. AS REQUIRED AN
SHALL PROVIDE ALL FITTINGS, ADAPTERS, AND APPURTENANCES REQUIRED TO MAKE THE
CONNECTIONS. PROVIDE ALL SUPPORTS REQUIRED FOR A RIGIDLY SUPPORTED COMPLETE AND
WORKING SYSTEM.
11. THE CONTRACTOR SHALL CONTACT THE PROPER UTILITY REPRESENTATIVE FOR QUESTIONS OR
COORDINATION OF CONSTRUCTION RELATED TO EXISTING UTILITIES.
12. CONTRACTOR SHALL VERIFY THAT PIPING SHOWN TO BE ABANDONED OR AS ABANDONED
PREVIOUSLY IS NO LONGER IN SERVICE. LINES IN SERVICE SHALL BE MAINTAINED THROUGHOUT
CONSTRUCTION ACTIVITIES.
13. ALL EXISTING PIPES THAT ARE TO BE ABANDONED IN PLACE OR REMOVED MAY NOT BE SHOWN.
WHERE PIPING IS TO BE ABANDONED AND MUST REMAIN IN SERVICE UNTIL COMPLETION OF
OTHER PHASES OF WORK, AND IT CONFLICTS WITH NEW PIPING, TEMPORARILY RELOCATE PIPING AS REQUIRED TO MAINTAIN SERVICE THROUGHOUT CONSTRUCTION ACTIVITIES, SEE INDIVIDUAL
PUMP STATION SHEETS REQUIRING BYPASS PUMPING FOR DETAILS.
14. CONTRACTOR SHALL REROUTE THE EXISTING PIPING IF REQUIRED TO MISS THE PROPOSED STRUCTURES. THE EXISTING PIPE SHALL REMAIN IN SERVICE UNTIL NEW PIPING IS READY TO BE
PLACED IN TO SERVICE DOWNTIME SHALL BE A MAXIMUM OF 2 HOURS, UNLESS SPECIFIED OR
SHOWN OTHERWISE.
15. THE CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS IN THE VICINITY OF ANY OVERHEAD
ELECTRICAL LINES CONTRACTOR SHALL ABIDE BY THE NATIONAL ELECTRICAL CODE AND ANY
REQUIREMENT BY THE OWNER OF ELECTRIC LINES.
16. PROVIDE ALL SHEETING/SHORING REQUIRED TO PROTECT EXISTING STRUCTURES, PIPES AND
FACILITIES.
17. CONTRACTOR SHALL VERIFY LOCATION OF ALL STRUCTURAL, MECHANICAL, AND ELECTRICAL
ITEMS BEFORE PLACING ANY STRUCTURAL STEEL OR CONCRETE ALSO, STRUCTURAL
DIMENSIONS AND OPENING CONTROLLED BY STRUCTURAL, MECHANICAL, OR ELECTRICAL
EQUIPMENT SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO CONSTRUCTION.
18. MECHANICAL AND ELECTRICAL EQUIPMENT SUPPORTS, ANCHORAGES, OPENINGS, RECESSES, AND REVEALS NOT SHOWN ON THE STRUCTURAL DRAWINGS, THAT ARE REQUIRED BY OTHER
CONTRACT DRAWINGS, SHALL BE PROVIDED PRIOR TO CASTING CONCRETE.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS
INCLUDING LOCATION AND DIMENSIONS OF ALL EXISTING CONSTRUCTION AND UTILITIES
CONTRACTOR SHALL NOTIFY ENGINEER IF THERE IS A CONFLICT BETWEEN THE CONTRACT
DOCUMENTS AND EXISTING CONSTRUCTION BEFORE PROCEEDING WITH WORK.
20. ALL WORK SHALL BE COMPLETED IN ACCORDANCE TO FDEP REGULATIONS AND CITY OF
ORLANDO ENGINEERING STANDARDS.
1. MINIMUM DISTANCE OF AT LEAST 3 FEET HORIZONTALLY SHALL SEPARATE ALL POTABLE WATER MAINS FROM RECLAIMED AND STORM WATER PIPES AND MINIMUM DISTANCE OF AT LEAST 6 FEET
HORIZONTALLY FROM SANITARY SEWER PIPES OR FORCE MAINS. THE DISTANCE SHALL BE
MEASURED FROM OUTSIDE EDGE TO OUTSIDE EDGE. IF IT IS NOT PRACTICAL TO MAINTAIN A 3 FOOT HORIZONTAL SEPARATION DISTANCE BETWEEN A POTABLE LINE AND A RECLAIMED LINE, THEN THE RECLAIMED WATER MAIN SHALL BE LAID IN A SEPARATE TRENCH OR ON A SHELF OF UNDISTURBED EARTH AT LEAST 18 INCHES ABOVE THE TOP OF SEWER PIPES AND 18" BELOW POTABLE WATER PIPES, WHEN A RECLAIMED WATER MAIN PARALLELS A SEWER PIPE, AND A SEPARATION OF AT LEAST 3' CANNOT BE MAINTAINED, ALTERNATE CONSTRUCTION METHODS OR MATERIALS MAY BE
USED WITH APPROVAL OF FDEP AND THE CITY OF ORLANDO.
2. WHERE RECLAIMED WATER PIPES CROSS WATER OR SEWER PIPES, A MINIMUM VERTICAL
SEPARATION OF 18 INCHES SHALL BE MAINTAINED BETWEEN THE BOTTOM OF THE UPPER PIPE AND THE TOP OF THE LOWER PIPE, WITH THE RECLAIMED WATER ON TOP. THE CROSSING SHALL BE ARRANGED SUCH THAT THE PIPE JOINT SHALL BE EQUIDISTANT AND CENTERED ON THE CROSSING.
WHERE A RECLAIMED WATER MAIN PASSES UNDER A SANITARY SEWER OR STORM WATER SEWER,
ADEQUATE STRUCTURAL SUPPORTS SHALL BE PROVIDED FOR THE SEWER PIPE TO MAINTAIN LINE
AND GRADE. WHERE THE 18" SEPARATION IS NOT PRACTICAL, ALTERNATE CONSTRUCTION
METHODS OR MATERIALS MAY BE USED WITH APPROVAL OF FDEP AND THE CITY OF ORLANDO.
3. WHERE A RECLAIMED WATER PIPE CONFLICTS WITH AN EXISTING POTABLE WATER PIPE WITH LESS THAN 18 INCHES VERTICAL CLEARANCE, THEN THE RECLAIMED WATER PIPE SHALL BE DUCTILE IRON PIPE (DIP) AND THE RECLAIMED WATER PIPE SHALL BE ARRANGED TO MEET THE CROSSING
REQUIREMENTS DESCRIBED ABOVE.
4. CONTRACTOR SHALL INSURE THAT ALL REQUIRED PERMITS ARE IN-HAND BEFORE BEGINNING ANY
CONSTRUCTION.
5. ALL CONSTRUCTION SHALL MEET CURRENT REQUIREMENTS OF FDEP, AWWA, CITY OF ORLANDO
AND ORLANDO UTILITIES COMMISSION FOR MATERIALS OF CONSTRUCTION, DESIGN, AND
INSTALLATION.
6. ALL EXISTING UNDERGROUND UTILITIES THAT ARE ACTIVE SHALL REMAIN IN PLACE UNTIL THE NEW
FACILITIES ARE OPERATIONAL.
7. UNDER NO CIRCUMSTANCES SHALL THE ACTIVITIES OF THE CONTRACTOR OR HIS
SUBCONTRACTORS CAUSE ANY INTERRUPTIONS TO THE SERVICE OPERATION OF EXISTING
UTILITIES WITHOUT WRITTEN AUTHORIZATION FROM THE AUTHORIZED REPRESENTATIVE.
8. CONTRACTOR SHALL NOTIFY THE VARIOUS UTILITIES AND TO MAKE THE NECESSARY
ARRANGEMENTS FOR ANY RELOCATION OF THESE UTILITIES, WITH THE OWNER OF THE UTILITY, PRIOR TO THE START OF ANY CONSTRUCTION ACTIVITY. THE CONTRACTOR SHALL INSURE THAT THE UTILITY OWNERS AND THE CITY OF ORLANDO PROJECT MANAGER ARE PROPERLY NOTIFIED OF
ANY TEMPORARY DISRUPTION OF SERVICE AT LEAST 1 WEEK IN ADVANCE.
9. AT LEAST 14 DAYS BEFORE CONSTRUCTION, THE CONTRACTOR SHALL, VERIFY ALL EXISTING PUBLIC AND PRIVATE UTILITY LOCATIONS IN THREE DIMENSIONS AT EACH PROJECT SITE. THE
CONTRACTOR SHALL UTILIZE MANUAL OR NONDESTRUCTIVE (E.G., VACUUM EXCAVATION)
METHODS TO PHYSICALLY EXPOSE UTILITIES FOR MEASUREMENT AND DATA RECORDING.
ACCURACIES SHALL BE TO ONE HALF (0.5) INCH VERTICAL AND TO APPLICABLE HORIZONTAL
SURVEY AND MAPPING ACCURACY. EXCAVATE TEST HOLES EXPOSING THE UTILITY TO BE
MEASURED IN SUCH A MANNER THAT PROTECTS THE INTEGRITY OF THE UTILITY TO BE MEASURED.
COMPLY WITH APPLICABLE UTILITY DAMAGE PREVENTION LAWS, PERMITS, AND SPECIFICATIONS
AND COORDINATE WITH UTILITY AND OTHER INSPECTORS, AS REQUIRED. DETERMINE (A) THE
HORIZONTAL AND VERTICAL LOCATION OF THE TOP AND/OR BOTTOM OF THE UTILITY; (B) THE
ELEVATION OF THE EXISTING GRADE OVER THE UTILITY AT A TEST HOLE; (C) THE OUTSIDE
DIAMETER OF THE UTILITY AND CONFIGURATION OF NON-ENCASED, MULTI-CONDUIT SYSTEMS; (D) THE UTILITY STRUCTURE MATERIAL COMPOSITION, WHEN REASONABLY ASCERTAINABLE; (E) THE BENCHMARKS AND/OR PROJECT SURVEY DATA USED TO DETERMINE ELEVATIONS; (F) THE PAVING THICKNESS AND TYPE, WHERE APPLICABLE; (G) THE GENERAL SOIL TYPE AND SITE CONDITIONS;
AND (H) SUCH OTHER PERTINENT INFORMATION AS IS REASONABLY ASCERTAINABLE FROM EACH TEST HOLE SITE. IF THERE IS A POTENTIAL CONFLICT, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY. ANY DAMAGE TO UTILITIES, STRUCTURES AND/OR SERVICES SHALL BE
REPAIRED AT THE CONTRACTOR'S EXPENSE IN A MANNER APPROVE BY AND COORDINATE WITH
THE UTILITY OWNER.
10. FOR CONNECTIONS TO AN EXISTING PIPE, THE CONTRACTOR SHALL EXCAVATE THE CONNECTION SITE TO VERIFY THE PIPE TYPE, ELEVATION, SIZE AND CONDITION, AND CHECK FOR OBSTRUCTIONS AND JOINT LOCATIONS PRIOR TO ORDERING MATERIALS AND INSTALLATION OF THE NEW PIPELINE.
11. THE CONTRACTOR HAS THE OPTION TO MOVE/RELOCATE THE ALIGNMENT (HORIZONTAL OR
VERTICAL) TO AVOID CONFLICT WITH EXISTING UTILITIES OR FOR EASE OF WORK, SUBJECT TO
APPROVAL FROM THE CITY. IF THE CONTRACTOR CHANGES THE VERTICAL ALIGNMENT, THE
CONTRACTOR SHALL INSTALL ALL NECESSARY AIR RELEASE VALVES AND FITTINGS AT HIS
EXPENSE.
12. ALL PRIVATE AND PUBLIC PROPERTY AFFECTED BY THIS WORK SHALL BE RESTORED TO A
CONDITION EQUAL TO OR BETTER THAN THE CONDITION EXISTING BEFORE COMMENCING
CONSTRUCTION WORK.
13. WHEN ENCOUNTERED, UNSUITABLE MATERIALS SHALL BE REMOVED FROM THE EXCAVATED
MATERIALS AND BACKFILLED WITH SUITABLE MATERIALS. UNSUITABLE MATERIALS SHALL BE
REMOVED FROM THE JOB SITE AND DISPOSED OF IN A TIMELY AND LEGAL MANNER AND APPROVED
BY THE CITY.
14. INLETS AND CATCH BASINS SHALL BE PROTECTED FROM SEDIMENT UNTIL THE COMPLETION OF ALL
CONSTRUCTION OPERATIONS. EROSION CONTROL AT ALL INLET DRAINAGE STRUCTURES DURING
CONSTRUCTION SHALL BE DONE IN ACCORDANCE WITH CITY STANDARDS.
15. CONTRACTOR SHALL CLEAN DEBRIS AND SOIL FROM ALL NEW AND EXISTING STORM SEWER PIPES, INLETS, CATCH BASINS, AND STRUCTURES WITHIN THE PROJECT SITE AFTER THE CONSTRUCTION
IS COMPLETE AND FROM ALL EXISTING STORM SEWER PIPES AND STRUCTURES OUTSIDE THE
PROJECT SITE IF THESE MATERIALS ORIGINATED FROM THE PROJECT SITE. THE CONTRACTOR
SHALL REMOVE ANY SOIL DEPOSITS AT OUTFALLS FROM PIPES IN LAKES OR PONDS THAT WERE
CAUSED BY THE CONSTRUCTION. THE CONTRACTOR SHALL REMOVE ALL EROSION CONTROL
EQUIPMENT AFTER THE PROJECT SITE IS STABILIZED AND STORM SYSTEM IS CLEANED.
16. PRIOR TO BEGINNING ANY CLEARING ACTIVITIES ON CITY PROPERTY, THE CONTRACTOR SHALL GET
APPROVAL FROM CITY DEPARTMENT FOR TREE REMOVAL, THEN CLEARLY MARK WITH FLAGGING
TAPE OR OTHER APPROVED METHOD, ALL EXISTING TREES TO REMAIN ON THE PROJECT SITE. ALL
TREES TO BE REMOVED SHALL BE MARKED WITH SPRAY PAINT OR OTHER APPROVED METHOD SO
THAT DURING CLEARING, THERE ARE NO MISUNDERSTANDING AS TO WHICH TREES ARE TO BE
REMOVED AND WHICH ARE TO REMAIN.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TREES NOT TO BE DAMAGED, FOR MAINTENANCE OF NEWLY PLANTED GRASS OR VEGETATION UNTIL THE WORK HAS BEEN ACCEPTED BY THE CITY.
18. DEWATERING SYSTEM SHALL BE UTILIZED BY THE CONTRACTOR IN ACCORDANCE WITH GOOD
STANDARD PRACTICES AND MUST BE SUFFICIENT ENOUGH TO LOWER THE WATER LEVEL IN
ADVANCE OF EXCAVATION TO KEEP THE TRENCH BOTTOM AND SIDES FIRM AND DRY, AT LEAST 3'
MINIMUM BELOW THE TRENCH BOTTOM, ADDITIONAL DEWATERING REQUIREMENTS ARE IN
SPECIFICATION 02140. POLLUTED WATER SHALL NOT BE DISCHARGED INTO SANITARY SEWER,
STORM SYSTEM RETENTION POND, OR BODIES OF WATER. ANY DISCHARGE INTO SANITARY SEWER SYSTEM SHALL BE PRE-APPROVED BY THE WASTEWATER DIVISION. DEWATERED LIQUID MUST BE TESTED FOR CONTAMINANTS PRIOR TO DISCHARGE. IF CITY APPROVES DISCHARGE TO SANITARY
SEWER, CITY HAS RIGHT TO CHARGE WASTEWATER FEES BASED ON CURRENT RATES.
CONTAINMENT TESTING TO BE PAID FOR BY CONTRACTOR.
19. EXCAVATIONS SHALL CONFORM TO THE REQUIREMENTS OF THE OSHA TRENCH SAFETY ACT. THE DISPOSAL OF EXCESS EARTHWORK MATERIALS SHALL BE THE RESPONSIBILITY/PROPERTY OF THE
CONTRACTOR.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE STABILITY OF EMBANKMENTS AND SHALL
REPLACE ANY PORTION WHICH HAS BECOME DISPLACED DUE TO EROSION OR DUE TO
CARELESSNESS OR NEGLIGENCE ON THE PART OF THE CONTRACTOR.
21. TEMPORARY DRAINAGE SHALL BE PROVIDED DURING CONSTRUCTION TO ELIMINATE ANY FLOODING
OF PRIVATE PROPERTY AND EXISTING ROADWAYS CAUSED BY CONSTRUCTION ACTIVITIES.
CONTRACTOR SHALL PROVIDE ADDITIONAL DRAINAGE AT NO EXTRA COST TO THE OWNER.
22. HYDROSTATIC PRESSURE AND LEAKAGE TESTS SHALL BE CONDUCTED ONLY FOR INSTALLED
FACILITIES. ALL TEST SHALL BE ACCEPTED BY THE CITY CONSTRUCTION MANAGER BEFORE ANY
PAVEMENT IS PUT IN PLACE.
23. ALL PIPING SHALL BE CLEAN AND FREE OF ALL DIRT, DEBRIS, AND BIOLOGY BEFORE PRESSURE
TESTING AND SHALL BE INCIDENTAL TO PIPE INSTALLATION COST.
24. FORCE MAIN PRESSURE TESTING SHALL BE CONDUCTED FOR A MINIMUM OF 2 HOURS AT A
MINIMUM PRESSURE OF 100 PSI AND MAINTAIN THIS PRESSURE. A DISCERNIBLE PRESSURE DROP
OVER THE 2 HOUR TEST PERIOD SHALL CONSTITUTE A FAILURE OF THE PRESSURE TEST,
PRESSURE TEST MUST BE WITNESSED BY A CITY OF ORLANDO PROJECT MANAGER OR HIS
APPOINTED REPRESENTATIVE.
25. CONTRACTOR SHALL REFERENCE THE REQUIREMENTS SET FORTH BY THE CITY'S ENGINEERING
STANDARDS MANUAL.
26. IF LEAKAGE IS INDICATED BY ANY DISCERNIBLE PRESSURE DROP OVER THE TWO HOUR TEST PERIOD, THE CONTRACTOR SHALL LOCATE THE CAUSE OF THE LEAKS, REPAIR COMPONENTS AND
REPEAT THE LEAKAGE TEST. ALL LEAKAGE SHALL BE ELIMINATED.
27. ALL HYDROSTATIC TESTING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C600-93 SECTION 4 FOR D.I. PIPE AND ANSI/AWWA C605 SECTION 7 FOR PVC PIPE. TEST PRESSURE SHALL BE 200 PSI FOR
POTABLE AND 150 PSI FOR RECLAIMED PIPING.
28. CONCRETE FORMS SHALL BE CONSTRUCTED FROM SOUND WOOD, METAL OR OTHER APPROVED
MATERIALS. FORMS SHALL BE SUITABLE TO PROVIDE A FLAT, UNIFORM SURFACE AND TO
WITHSTAND CONSTRUCTION LOADS WITHOUT SAGGING OR DEFLECTING. WOOD FORMS IN
CONTACT WITH THE CONCRETE SHALL BE COATED WITH A EFFECTIVE RELEASE AGENT. FORMS
SHALL REMAIN IN PLACE PER ACI 301 AND ACI 347. FORMS SHALL REMAIN STRAIGHT, LEVEL, PLUMB
AND TRUE TO SHAPE TO WITHIN 1/4" PER 10'.
29. MOLDING, BEVELS OR OTHER TYPES OF CHAMFER STRIPS SHALL BE PLACED TO PRODUCE A
3/4-INCH CHAMFER AT ALL HORIZONTAL AND VERTICAL PROJECTION CORNERS AND FOR
BLOCKOUTS.
30. CONCRETE REINFORCEMENT SHALL BE NEW, RUST FREE STEEL BARS THAT CONFORM TO ASTM A615, GRADE 60. TIE WIRE SHALL BE A MINIMUM OF 16-GAUGE, BLACK ANNEALED WIRE. CHAIRS
SHALL BE PROVIDED AS NECESSARY TO PREVENT DISPLACEMENT DURING POUR.
31. MINIMUM REINFORCEMENT STEEL AND CONCRETE COVER SHALL BE IN ACCORDANCE WITH ACI-318.
32. A COMPLETE SET OF AS-BUILT DRAWINGS (34" X 22" HARD COPY & AutoCAD FILE), AND ALL INSPECTION AND TEST RECORDS MUST BE SUBMITTED TO THE CITY OF ORLANDO AND APPROVED BEFORE THE NEW SYSTEM IS ALLOWED TO BE PUT INTO SERVICE. THE DRAWINGS MUST INCLUDE ACCURATE LAYOUT, SIZING, AND STATE PLANE COORDINATES FOR ALL VALVES, PIPING BENDS, BRANCHES, ENDS, OUTLETS, CONNECTION POINTS, METER BOXES AND LOCATOR BALLS, OR ANY ITEM LISTED ABOVE. AS-BUILTS SHALL BE SIGNED AND SEALED BY FLORIDA LICENSED SURVEYOR.
ADDITIONAL REQUIREMENTS AND SUBMITTALS ARE LISTED IN SECTION 01050 SURVEYING AND
FIELD ENGINEERING.
33. ALL WATER, SEWER, AND RECLAIMED WATER PIPE, PIPE FITTINGS AND APPURTENANCES
INSTALLED UNDER THIS PROJECT WILL BE COLOR CODED OR MARKED IN ACCORDANCE WITH
SUBPARAGRAPH 62-555.320 (21) (b) 3, FAC, USING BLUE AS A PREDOMINANT COLOR FOR WATER;
GREEN FOR WASTEWATER; PANTONE PURPLE 522C FOR RECLAIMED WATER.
34. ALL BACKFILL SHALL BE COMPACTED TO NOT LESS THAN 95% OF MAXIMUM DRY DENSITY AS MEASURED BY AASHTO T-180 METHOD "D" TEST (MODIFIED PROCTOR) IN OPEN AREAS AND TO NOT
LESS THAN 98% MAXIMUM DRY DENSITY AS MEASURED BY AASHTO T-180 METHOD "D" TEST
(MODIFIED PROCTOR) UNDER ASPHALT OR CONCRETE PAVEMENT. ALL SOIL TESTING TO BE
CONDUCTED BY THE CITY. THE CONTRACTOR SHALL PROVIDE ALL REASONABLE ASSISTANCE
DURING SOIL TESTING.
35. WHEN USING SCALED DATA CONSIDER THAT THESE PLANS MAY HAVE BEEN ALTERED IN SIZE
DURING REPRODUCTION.
36. PIPE LENGTHS SHOWN ON PLANS ARE APPROXIMATE. ACTUAL LENGTHS ARE TO BE DETERMINED
DURING CONSTRUCTION BY THE CONTRACTOR.
37. SUPPORT & PROTECT ALL EXISTING UTILITIES. CONTRACTOR SHALL CONTACT UTILITY OWNERS
FOR LOCATION OF ALL EXISTING FACILITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATING WITH UTILITY OWNERS AND BE RESPONSIBLE FOR PROVIDING TEMPORARY
SUPPORT FOR UTILITY POLES AND ALL OTHER UTILITIES FACILITIES.
38. IF REQUIRED BY DEWATERING ACTIVITIES CONTRACTOR SHALL APPLY FOR AND OBTAIN A
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) PERMIT FROM THE FLORIDA
DEPARTMENT OF ENVIRONMENTAL PROTECTION (FDEP) AND COMPLY WITH ALL NPDES
REQUIREMENTS DURING CONSTRUCTION OF THE PROJECT.
39. EXERCISE EXTREME CAUTION WHEN EXCAVATING NEAR WASTEWATER FORCE MAINS AND GRAVITY
SEWERS. EXPOSE AND VERIFY LOCATION OF MAINS PRIOR TO EXCAVATION.
40. PROTECT EXISTING IMPROVEMENTS TO THE MAXIMUM EXTENT POSSIBLE. ALL DAMAGED SIDEWALK, ROADWAY PAVEMENT, GRASS LANDSCAPING AND OTHER IMPROVEMENTS SHALL BE RESTORED TO
ORIGINAL CONDITION OR BETTER, AT CONTRACTOR'S EXPENSE.
41. BENCHMARK LOCATIONS AND ELEVATION ARE SHOWN IN THE PLANS AS REPRESENTED BY
SURVEYOR AT THE TIME OF THE SURVEY. CONTRACTOR SHALL VERIFY ITS CORRECTNESS AT THE
TIME OF CONSTRUCTION AND INSTALL HIS OWN TEMPORARY BENCHMARKS. ANY DISCREPANCIES
SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE CITY FIELD REPRESENTATIVE.
42. WHEN WORKING IN CONFINED SPACES AT THE SITE, CONTRACTOR EMPLOYEES SHALL MEET ALL
OSHA CONFINED SPACE ENTRY REQUIREMENTS, INCLUDING BUT NOT LIMITED TO PERMITTING,
ATMOSPHERE TESTING, CHECKLISTS, SEWER ENTRY AND RESCUE TEAMS AS REQUIRED BY OSHA
29 CFR 1910 AND PROVIDE CERTIFICATIONS TO THE CITY.
43. APPROVED HOURS CONTRACTOR MAY WORK ONSITE ARE 7:00 AM TO 3:30 PM, MONDAY THROUGH FRIDAY, EXCLUDING CITY HOLIDAYS. ANY WORK OUTSIDE THE STATED TIME MUST BE APPROVED
BY CITY.
44. CONTRACTOR SHALL AT ALL TIMES MAINTAIN ACCESS WAYS FOR CITY VEHICLES AND PERSONNEL
TO MAINTAIN LIFT STATION FOR MAINTENANCE/EMERGENCY SITUATIONS.
45. CONTRACTOR TO PROVIDE TEMPORARY 6-FT CHAIN LINK SECURITY FENCING TO SAFE/PROTECT
THE AREA AT THE END OF THE DAY.
46. CONTRACTOR TO CONTACT THE CITY SURVEYOR IF SURVEY CONTROLS OR BENCHMARKS ARE TO BE DISTURBED OR THAT HAVE BEEN DAMAGED. IT IS THE RESPONSIBILITY OF THE CONTRACTOR'S SURVEYOR (A FLORIDA LICENSED SURVEYOR AND MAPPER) TO COORDINATE WITH CITY SURVEYOR
AND ENGINEER PRIOR CONSTRUCTION OR PRIOR TO DISTURBING CONTROL DURING
CONSTRUCTION. CONTRACTOR SHALL REPLACE CONTROLS WITH THE DOCUMENTATION AND
DIRECTION PROVIDED BY THE CITY SURVEYOR.
47. SURVEY SHALL BE IN ACCORDANCE TO CITY'S ENGINEERING STANDARDS MANUAL (AS-BUILT DETAILED IN CHAPTER 5). CONTRACTOR SHALL HAVE FLORIDA LICENSED SURVEYOR REFERENCE ALL CONTROL POINTS TO CONSTRUCTION. INCLUDING RIGHT OF WAY, CORNERS, OR ANY CONTROL
POINTS AND PROVIDE INFORMATION TO CITY SURVEYOR. ADDITIONAL REQUIREMENTS AND
SUBMITTALS ARE LISTED IN SECTION 01050 SURVEYING AND FIELD ENGINEERING.
CONSTRUCTION NOTES
EMERGENCY WASTEWATER SPILL, WATER MAIN OR ELECTRICAL BREAK
PROCEDURES:
1. THE CONTRACTOR SHALL EXERCISE EXTREME CAUTION WHEN EXCAVATING IN PROXIMITY OF WATER, WASTEWATER FORCE MAINS AND GRAVITY SEWERS. LOCATIONS SHOWN ON PLANS ARE NOT EXACT OR GUARANTEED. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING EXISTING UTILITY LOCATIONS
WHETHER SHOWN ON THE PLANS OR NOT.
2. THE PLANT SHIFT OPERATOR SHALL BE NOTIFIED IMMEDIATELY IN THE EVENT OF A FORCE MAIN, RECLAIMED WATER MAIN, OR GRAVITY SEWER BREAK OR DAMAGE AT (407-448-1013).
3. OUC DISPATCH OPERATOR SHALL BE NOTIFIED IMMEDIATELY IN THE EVENT OF A WATER OR
ELECTRICAL BREAK OR DAMAGE AT (407-823-9150).
4. ALL DAMAGE TO MAINS SHALL BE REPAIRED IMMEDIATELY BY THE CONTRACTOR AT THE
CONTRACTOR'S EXPENSE. IF THE REPAIR IS NOT MADE IN A TIMELY MANNER, AS DETERMINED BY THE CITY INSPECTOR, THE CITY MAY PERFORM REPAIRS AND THE CONTRACTOR WILL BE CHARGED FOR
REPAIRS.
SEQUENCE OF CONSTRUCTION:
1. CONTRACTOR SHALL SUBMIT SEQUENCE OF CONSTRUCTION PLAN FOR APPROVAL TO CITY 14-DAYS PRIOR TO ONSITE CONSTRUCTION. BYPASS PUMPS SHALL REMAIN IN OPERATION 24-HOURS 7-DAYS PER WEEK. ADDITIONAL SEQUENCE AND BYPASS REQUIREMENTS ARE INCLUDED IN SPECIFICATION
SECTION 01014 CONSTRUCTION SEQUENCING/CONSTRAINTS AND 01525 TEMPORARY PUMPING
SYSTEMS
CITY CONTACT INFORMATION:
1. WASTE WATER DIVISION............................................................................... 407-246-2213
2. TRANSPORTATION ENGINEERING DIVISION..……………………………….. 407.246.2020
3. FOR LANE AND STREET CLOSURES FOR CONSTRUCTION ….......…....... 407.246.2372
4. FIRE DEPARTMENT ….......….......................................................................... 407.246.2390
5. OUC (WATER & ELECTRIC) .......................................................….......…...... 407.823.9150
PL
O
T D
AT
E:
/2
6/
:2
K R
O M
ER
O
Fi le
: C :\U
SE
R
S\
KR
O M
ER
O
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \4
-0
_C O
N
SE
R V
II
W
R F
EQ
P
S
FI
N
AL
D
ES
IG
N
\P R
O
JE
C T
FI
LE
S\
_D
ES
IG
N
\0 1-
H
AZ
EN
\G
EN
ER
AL
\4
-0
-G -0
Sa ve d by J
SC
H
EI
N
BE
R
G S av e da te
: 1 2/
/2
3:
P M
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
JULY 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
G-00-04
GENERAL
ABBREVIATIONS AND SYMBOLSW. MARSHALL
SECTION
SECTION AND DETAIL IDENTIFICATION
NOTES:
IF PLAN AND SECTION (OR DETAIL CALL-OUT AND DETAIL)
ARE SHOWN ON SAME DRAWING, DRAWING NUMBER IS
REPLACE BY A DASH (-).
(1)
IF SECTION IS SHOWN IN TWO OR MORE LOCATIONS, THE
FIRST DRAWING NUMBER WHERE THE SECTION IS SHOWN IS
DISPLAYED IN THE SECTION TITLE.
(2)
(3)
IF THE DETAIL TITLE REFERS TO A STANDARD DETAIL, THE
DRAWING NUMBER IN THE DETAIL TITLE IS REPLACED WITH THE
ABBREVIATION STD.
(4)
IF A DETAIL IS SHOWN IN TWO OR MORE LOCATIONS, THE
DRAWING NUMBER IN THE DETAIL TITLE IS REPLACED WITH
A LINE.
A. SECTION CUT ON DRAWING G-1:
B. ON DRAWING G-2 THIS SECTION IS IDENTIFIED AS:
A. DETAIL CALL-OUT ON DRAWING G-1 AS:
DETAIL IDENTIFICATION
SECTION IDENTIFICATION
B. ON DRAWING G-2 THIS DETAIL IDENTIFIED AS:
* DENOTES DIMENSIONS OR ELEVATIONS
DEPENDENT ON EQUIPMENT SUPPLIED.
SECTION LETTER
DRAWING ON WHICH
SECTION APPEARS. (1)
SECTION LETTER
DRAWING FROM WHICH
SECTION WAS TAKEN. (1)(2)
DETAIL NUMBER
DRAWING ON WHICH
DETAIL APPEARS. (1)
DETAIL NUMBER
DRAWING ON WHICH
DETAIL IS CALLED OUT. (1)(3)
A. STANDARD DETAIL CALL-OUT ON DRAWING G-1 AS:
STANDARD DETAIL IDENTIFICATION
B. STANDARD DETAIL ON DRAWING G-10 THIS DETAIL IDENTIFIED AS:
DETAIL NUMBER
DRAWING ON WHICH
DETAIL APPEARS. (1)
DETAIL NUMBER
STANDARD DETAIL (4)
GENERAL NOTES:
FOR WELDING SYMBOLS USE AMERICAN
WELDING SOCIETY STANDARD SYMBOLS.
ELECTRICAL SYMBOLS SHOWN ON ELECTRICAL SHEETS.
(2) (1)
G-2
DETAIL
G-1
G-10
DETAIL
STD
ARROW INDICATES DIRECTION AND POINT OF
VIEW OF PHOTO
LOCATIONS AND ELEVATIONS ARE AS PER AS-BUILT DRAWINGS.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS.
(3)
LBS/FT POUNDS PER FOOT
FT
GALV
FPL, FP&L FLORIDA POWER AND LIGHT CO.
GALVANIZED
FOOT
RADIUS
REQUIRED
REINFORCING
RAD, R
REINF
REQ'D
R/W, ROW RIGHT OF WAY
SANITARY
SHEET
SECTION
SAN
SHT
SECT
SQUARE
STEEL
SQ
STL
SS
SPEC
STAINLESS STEEL
SPECIFICATION
HIGHH
HP
HR
HDPE
HORIZ
INFL
ID
HANDRAIL
HIGH DENSITY POLYETHYLENE
HIGH POINT
INSIDE DIAMETER
INFLUENT
HORIZONTAL
IF
INSUL
INT
ISO
JOINT
INV
JT
LF LINEAL FEET
INVERT
ISOLATION
INTERIOR
INSULATION
INSIDE FACE
TEMPORARY
SYMM
TEMP
T & B
TO
THICKTHK
TOP AND BOTTOM
THROUGHOUT
TEMPERATURE INDICATOR
SYMMETRICAL
VACUUM
TYPICAL
TOS
VAC
TYP
WWF
W/L
WELDED WIRE FABRIC
WATER LEVEL
TOP OF STEEL/TOP OF SLAB
TOC TOP OF CONCRETE
LP
MH
LWL
MAX
MANUF
MAXIMUM
MANUFACTURER
MANHOLE
LOW WATER LEVEL
LOW POINT
MIN
NIC
NGVD
No
OPNG
OD
OC
NTS
NATIONAL GEODETIC VERTICAL DATUM
OUTSIDE DIAMETER
OPENING
ON CENTER
NUMBER
NOT TO SCALE
NOT IN CONTRACT
MINIMUM
MECHANICALMECH
WITH
PI PRESSURE INDICATOR
LONG
STRUCTURAL
LG
STRUC
CENTER TO CENTER
CENTER LINE
C.C.
BLIND FLANGE
BALL VALVE
AIR RELIEF VALVEARV
BF
BV
VALVES, FITTINGS, ETC.
COLUMN
CLEAR
CLEAN OUT/COMPANY
CONCRETE
CONTRACTOR
CONTINUOUS
CONSTRUCTION
COL
CLR
CO
CONC
CONT
CONST
CONTR
DIAGONAL
DETAIL
DIAMETER
DIMENSION
DOWN
DOWEL
DRAWING(S)
DIAG
DET
DIM
DIA
DN
DWL
DWG(S)
EQUIPMENT DRAIN
EXPANSION JOINT
CHECK VALVE
BUTTERFLY VALVE
FLANGE
FITTING
FIRE HYDRANT
CV
BFV
ED
EXP JT
FTG
FH
FLG
GROOVED COUPLING
MECHANICAL JOINT
GATE VALVE
PLUG VALVE
PLAIN END
GC
GV
NPT
MJ
PV
PE
PRV
NATIONAL PIPE THREAD
PRESSURE RELIEF VALVE
CHECK VALVE (CV)
BALL VALVE (BV)
PLUG VALVE (PV)
GATE VALVE (GV)
THREE WAY VALVE
MECHANICAL COUPLING
HOSE BIBB (ELEVATION)
HOSE BIBB (PLAN)
GROOVED COUPLING
HARNESSED EXPANSION JOINT
HARNESSED MECHANICAL COUPLING
PRESSURE REGULATING VALVE
PRESSURE REDUCING/RELIEF VALVE
BUTTERFLY VALVE / DAMPER
EACH
EACH WAY
EACH FACE
EACH END
EFFLUENT
ELECTRIC
ELEVATION
ECCENTRIC
EA
EE
EW
EF
EFF
EL, ELEV
ELEC
ECC
EXISTING
EDGE OF PAVEMENT
EQUIPMENT
FOUL AIR
EXTERIOR
FINISH
FIRE EXTINGUISHER
EXPANSION
EOP
EXIST
EQUIP
FA
EXT
FIN
FE
EXP
ELECTRICAL MAINTENANCE HOLEEMH
PIPING
DUCTILE IRON PIPE
STAINLESS STEEL PIPE
IRON PIPE SIZE
POLYVINYLCHLORIDE
ERCP
DIP
SSP
IPS
PVC
GENERAL
CATCH BASIN
BOTTOM
BUILDING
CB
BOTT
BLDG
UNION
FIRE HYDRANT
EXPANSION JOINT
MAINTENANCE HOLE
POWER POLE
WELDED JOINT
CATCH BASIN
THREADED JOINT
PUSH-ON JOINT
MECHANICAL JOINT
FLANGED JOINT
SOCKET WELDED JOINT
THREADEDTHD
CIP CAST IRON PIPE
PLAIN ENDPE
FL FLOOR
COUPLINGCPLG
HOSE BIBBHB
MOTOR OPERATED VALVEMOV
PUMP STATIONPS
SOV SOLENOID OPERATED VALVE
CHECKEREDCHK'D
COPPER OR CUBICCU
DISCHARGEDISCH
INJECTIONINJ
LINELN
REDUCERRED
REHAB REHABILITATION
SOLENOID
MOTOR OPERATEDM
S
VENTURI METER
GAUGE
MAGNETIC METER
MM
EXISTING UTILITIES/STRUCTURE
PROPOSED PIPELINE (DOUBLE LINE IF
SCALE OF DRAWING PERMITS)
PROPOSED PIPELINE/STRUCTURE
PROPOSED STRUCTURE OR FACILITY
CONCRETE PIPE SUPPORT
REDUCER (SINGLE LINE)
REDUCER (DOUBLE LINE)
BLK BLOCK
VERTICALVERT
FORCE MAINFM
NORTH AMERICAN VERTICAL DATUM NAVD
POND OVERFLOWPO
CL,
INVERT ELEVATIONIE
PUMP STATIONPS
CHECK BALL VALVE
W/O WITHOUT
FIG FIGURE
CHLORINATED POLYVINYL CHLORIDECPVC
ELECTRICAL LIGHT POLE
NPW NON POTABLE WATER
ALUMINUM
ARCHITECTURAL
APPROXIMATEAPPROX
ARCH
AL, ALUM
DRAINDR
HIGH DENSITY POLYETHYLENE PIPEHDPE
RESTRAINED JOINTRJ
LONG RADIUSLR
PUSH ONPO
RJ RESTRAINED JOINT
CORRUGATED METAL PIPECMP
RCP REINFORCED CONCRETE PIPE
ANGLE
AB ANCHOR BOLT
DIGESTERDIG
GR GRADE
FTG FOOTING
HWL HIGH WATER LEVEL
LBS POUNDS
LAT LATERIAL
LENGTHLGTH
LIGHT POLEL.P.
LOCATIONLOC
OF OUTSIDE FACE
POINT OF CURVATUREP.C.
P.I. POINT OF INTERSECTION
PROPERTY LINEP/L, PL
PROPOSEDPROP
POUNDS PER SQUARE INCHPSI
POINT OF TANGENCYP.T.
PAVEMENTPVT
POTABLE WATERPW
REVISIONREV
RESTRAINEDREST
STANDARDSTD
STATIONSTA
TBD TO BE DETERMINED
WIDE
FLOWSTREAM IDENTIFICATION
SD STORM DRAIN
DWG#PHOTO#
W
GRAVITY MAIN
STORM DRAIN
UNDERGROUND ELECTRICAL
LINE
FENCE LINE
SS
SD
BE
X
R/W
BW
OHE
BFM
RIGHT OF WAY
LINE TYPE
NEW ASPHALT PAVEMENT
NEW CONCRETE PAVEMENT
BURIED WATER LINE
OVERHEAD ELECTRICAL LINE
TO BE DEMOLISHED / REMOVED
ELECTRICAL POWER POLE
ELECTRIC METEREM
WATER METER
SEWER MANHOLE
SURVEY CONTROL POINT
WATER MANHOLE
S
WM
W
STORM MANHOLESD
SURVEY CONTROL POINTIP
VENT
GUY POLE
TRAFFIC ELECTRIC VAULT
HOSE BIBB
ELECTRIC PANELEP
ELLIPTICAL REINFORCED
CONCRETE PIPE
BURIED FORCE MAIN
PL
O
T D
AT
E:
/2
6/
:2
K R
O M
ER
O
Fi le
: C :\U
SE
R
S\
KR
O M
ER
O
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \4
-0
_C O
N
SE
R V
II
W
R F
EQ
P
S
FI
N
AL
D
ES
IG
N
\P R
O
JE
C T
FI
LE
S\
_D
ES
IG
N
\0 1-
H
AZ
EN
\G
EN
ER
AL
\4
-0
-G -0
Sa ve d by J
SC
H
EI
N
BE
R
G S av e da te
: 1 2/
/2
:2
PM
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
JULY 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
RAW SEWAGERS
PL
O
T D
AT
E:
/2
6/
:2
K R
O M
ER
O
Fi le
: C :\U
SE
R
S\
KR
O M
ER
O
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \4
-0
_C O
N
SE
R V
II
W
R F
EQ
P
S
FI
N
AL
D
ES
IG
N
\P R
O
JE
C T
FI
LE
S\
_D
ES
IG
N
\0 1-
H
AZ
EN
\C
IV
IL
\4
-C
-0
Sa ve d by O
SC
AR
S av e da te : 1
2/
/2
5:
P
M
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
JULY 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
1" = 10'
10 0 10'
C-01-00
CIVIL
EXISTING SITE SURVEYW. MARSHALL
SCALE: 1" = 10'-0"
PLAN
LEGEND
EXISTING18
" R
C P
RCP/CCFRPM
8" GV
8" GV
8" FP
8" FP
8" FP
4" RWR
4" D
14" FA
12" FA
14" FA
FIRE HYDRANT
6" GV
3" RPZ BACKFLOW
PREVENTER ASSEMBLY
JUNCTION BOX
JUNCTION BOX
60"/54" RS
60"/54" RS
42" RS
42" RS
EXISTING EQUALIZATION
PUMP STATION
EQUALIZATION TANK
FFE: 98.00
97.95
97.95
97.10
96.95
EXIST.ODOR
CONTROL
TANK
EXIST.
EQUALIZATION
TANK
SW
ALE
21.00'
97.00 97.00
.0
0'
A/C PAD #1 A/C PAD #2
APPROX. LIMITS OF
EXIST. OAK TREE
DRIP LINE FROM
GOOGLE EARTH
AERIAL
97.10
MATCH EXIST. ODOR
CONTROL PAD ELEVATION
4.
97.05 96.80
96.65
SOD ALL DISTURBED UNPAVED
AREAS W/BAHIA (TYP.)
SOD ALL DISTURBED UNPAVED
AREAS W/BAHIA (TYP.)
N: 1515472.69 E: 511289.77
96.95
12.00'
97.25 97.25 96.75
96.25
96.25
97.00
97.15
REMOVE AND RECONSTRUCT
EXISTING ASPHALT PAVEMENT
EXIST.
EQUALIZATION
PUMP STA.
9.
7.80'
9.
7.80'
EXIST. EDGE
OF ASPHALT
PAVEMENT
G R
AD
E BR
EAK
97.40
97.40
SOD ALL DISTURBED UNPAVED
AREAS W/BAHIA (TYP.)
N: 1515516.69 E: 511259.11
96.9596.85
97.1096.90
96.4096.30
96.30 96.40
96.00
96.4096.30
96.1596.23
REMOVE AND RECONSTRUCT
EXISTING ASPHALT PAVEMENT
SAW CUT EXIST. EDGE OF PVM'T
MATCH EXIST. CONDITIONS
96.4096.15
96.20
SOD ALL DISTURBED UNPAVED
AREAS W/BAHIA (TYP.)
EXIST. YARD
HYDRANT/HOSE BIB
SHALL REMAIN
96.65 97.10
96.85
96.7596.95
96.55
96.75 96.75
.4
4'
30'R
30'R
44.60'
.0
0'
10.50'
.5
0'
5.00'5.00'
2.
4.
4.
6.59'
.4
0'
6.67'
96.2596.75
N: 1515472.69 E: 511259.11
NEW ELECTRICAL
DUCTBANK MH (6'x6')
N: 1515516.69 E: 511289.77
5' WIDE SIDEEWALK WITH
INTEGRAL CURB/THICKENED
EDGE (SEE STRUCTURAL
DRAWINGS FOR DETAILS)
97.4597.45
97.85
97.35 97.35
TRANSFORMER
PAD #1 (9.5'x8.0')
TRANSFORMER
PAD #2 (9.5'x8.0')
TREE PROTECTION
BARRICADE
REMOVABLE
BOLLARD (TYP.)
EXIST LIGHT POLE
96.00
95.82
95.63
95.45
95.26
98LF SWALE @ 0.92%
IMPERVIOUS AREA CALCULATIONS:
IMPERVIOUS AREA REMOVED: 427+40 = 467 SF
IMPERVIOUS AREA ADDED: 1,111+76+76 = 1,263 SF
NET IMPERVIOUS AREA ADDED: 1,263-467=796 SF
SW
ALE
APPROX. LOCATION
OF EXIST. SWALE
P
LO
T D
A
TE
: 5 /1
9/
:2
P M
Y : S
S H
E A
Fi le
: C :\U
S E
R S
\S S
H E
A \D
C \A
C C
D O
C S
\H A
ZE
N
A N
D S
A W
Y E
R \4
-0
_C O
N S
E R
V
II
W R
F E
Q P
S F
IN
A
L D
E S
IG
N
\P R
O
JE
C T
FI
LE
S \0
1_ D
E S
IG
N
\0 2-
C S
E I\C
IV
IL
\4
-0
M
S P
S av ed b y S
S H
E A
S av e da te : 5
/1 9/
2:
P
M
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
MARCH 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
SCALE: 1" = 10'
10 0 10'
CIVIL / SITE
ENGINEERING, INC. CS
E I1645 N. MAITLAND AVENUE
MAITLAND, FL 32751
SITE GEOMETRY, GRADING
AND DRAINAGE PLAN
C-01-01
TREE PROTECTION UNDISTURBED AREA SHALL BE PROVIDED BASED UPON TREE DBH.
BARRIER SHALL BE ERECTED PRIOR TO ANY CONSTRUCTION IN GENERAL AREA OF TREES TO BE
PROTECTED.
PROHIBITED WITHIN THIS AREA:
1. PARKING OR USE OF VEHICLES, EQUIPMENT, OR MACHINERY
2. STORAGE OR DUMPING OF ANY MATERIALS OR LIQUID.
3. CONSTRUCTION, EXCAVATION, OR TRENCHING
EXISTING VEGETATION REMAINING AFTER GRUBBING FOR BUILDING PADS, STRUCTURES, RIGHT
OF WAY, PARKING AREAS OR SIGNIFICANT GRADE CHANGES SHALL BE PROTECTED DURING THE
CONSTRUCTION PROCESS.
FOR EACH TREE TO BE PRESERVED, ESTABLISH AN UNDISTURBED AREA/TREE PROTECTION
ZONE (TPZ) MEASURED FROM THE CENTER OF EACH TREE. THE MINIMUM UNDISTURBED AREA IS A RADIUS OF 0.75' FOR EACH INCH OF DBH (DIAMETER AT BREAST HEIGHT, 54” HT ABOVE THE SOIL LINE). TREES OF 6" DBH OR LESS SHALL HAVE A MINIMUM UNDISTURBED RADIUS OF 5 FEET.
BARRIERS TO REMAIN IN PLACE UNTIL ALL PAVING AND CONSTRUCTION IS COMPLETED.
UPRIGHTS - THE EQUIVALENT OF 4 X 4 LUMBER AT 4' MINIMUM HEIGHT ON 5' MAX, CENTERS. ON
AN UPRIGHT IN EACH QUADRANT PLACE A SIGN STATING "TREE PROTECTION ZONE"
HORIZONTALS - THE EQUIVALENT OF TWO COURSES OF 1/2" DIA. ROPE WITH YELLOW TAPE
FLAGGING.
ATTACH "TREE PROTECTION ZONE" SIGNS AT EACH QUADRANT
UNDISTURBED AREA
VARIES (5' MINIMUM)
TYPICAL TREE PROTECTION DETAIL
ASPHALT PAVEMENT SECTION
NOT TO SCALE
1 FRICTION COURSE FC-9.5 (1" LIFT) (PG 76-22)
2 SUPERPAVE ASPHALTIC CONCRETE TYPE SP-12.5
(1.5") (TRAFFIC LEVEL D COARSE MIX (PG 76-22)
3 10" CRUSHED CONCRETE (SEE CITY OF
ORLANDO ENGINEERING STANDARDS MANUAL,
SECTION 6.06)
4 12" TYPE 'B' STABILIZATION MIN LBR 40
1.00'
SECTION A-A
A
2 4
NOTES:
1. 4" I.D. REMOVABLE STEEL BOLLARD
(4 1/2" O.D. 1/4" STEEL PIPE)
2. 4" REMOVABLE BOLLARD RECEIVER
3. KEYED LOCK (NOT REQUIRED)
4. RECEIVER COVER
1/4" STEEL WELDED CAP
4 3/4" I.D. STEEL PIPE
SLEEVE (5 5/8" O.D. 3/8"
THICK STEEL PIPE)
3/4" REBAR REMOVABLE
BOLLARD STOP (MIN. 2"
ABOVE BOTTOM OF SLEEVE)
1.33'
1.
0'
No. 57 GRANITIC STONE
DRAIN WRAPPED IN
FILTER FABIC
2.
0'
4.0' PAINTED BOLLARD
(REMOVABLE) COLOR
TO BE CHOSEN BY
OWNER
A
ISOLATION
JOINT
(TYP.)
REMOVABLE BOLLARD DETAIL
NOT TO SCALE
T D
AT
E:
/2
6/
:2
K R
O M
ER
O
Fi le
: C :\U
SE
R
S\
KR
O M
ER
O
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \4
-0
_C O
N
SE
R V
II
W
R F
EQ
P
S
FI
N
AL
D
ES
IG
N
\P R
O
JE
C T
FI
LE
S\
_D
ES
IG
N
\0 1-
H
AZ
EN
\C
IV
IL
\4
-C
-0
Sa ve d by O
SC
AR
S av e da te : 1
2/
/2
5:
P
M
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
JULY 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
1" = 10'
10 0 10'
C-01-02
CIVIL
EXISTING SITE PLAN AND DEMOLITIONW. MARSHALL
SCALE: 1" = 10'-0"
PLAN
TO BE DEMOLISHED / REMOVED
LEGEND
EXISTING
RCP/CCFRPM
8" GV8" GV
8" FP
8" FP
8" FP
" R
C P
4" RWR
4" D
14" FA
12" FA
14" FA
REMOVE 10" FRP FOUL AIR LINE
F.H.
6" GV
3" RPZ
BACKFLOW
PREVENTER
ASSEMBLY
JUNCTION BOX
JUNCTION BOX
60"/54" RS
60"/54" RS
42" RS
42" RS
EXISTING EQUALIZATION
PUMP STATION
EQUALIZATION TANK
REMOVE 3" ALUM LINE
REMOVE 14" FRP
FOUL AIR LINE
SEE PHOTO 1 FOR
DEMOLITION OF ABOVE
GRADE PIPING.
SCALE: NTS
PHOTO 1 - ODOR CONTROL ABOVE GROUND
BURIED ELECTRIC. SEE
ELECTRICAL SITE PLAN
FOR RELOCATION
SCALE: NTS
PHOTO 2 - ABOVE GROUND PIPING AT EQUALIZATION TANK
SAW OFF EXISTING 14"
FRP PIPE, ENSURING A
CLEAN AND SQUARE
CUT. PREPARE PIPE
ENDS.
SEE PHOTO 2 FOR DEMOLITION
OF ABOVE GROUND PIPING AT
THE EQ TANK
DISCONNECT RW LINE
FROM HOSE BIBB
REMOVE 4" RECLAIMED
WATER LINE (SEE NOTE 2)
NOTES:
1. CONTRACTOR TO FIELD VERIFY
EXACT LINE LOCATION AND DEPTH.
HOSE BIBB TO BE RELOCATED
DURING CONSTRUCTION.
KENNY BLANTON PE. No. 46654
T D
AT
E:
/2
6/
:2
K R
O M
ER
O
Fi le
: C :\U
SE
R
S\
KR
O M
ER
O
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \4
-0
_C O
N
SE
R V
II
W
R F
EQ
P
S
FI
N
AL
D
ES
IG
N
\P R
O
JE
C T
FI
LE
S\
_D
ES
IG
N
\0 1-
H
AZ
EN
\C
IV
IL
\4
-C
-0
Sa ve d by O
SC
AR
S av e da te : 1
2/
/2
:5
AM
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
JULY 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
1" = 10'
10 0 10'
TAN QU
O. CABARCAS
C-01-03
CIVIL
YARD PIPINGW. MARSHALL
SCALE: 1" = 10'-0"
PLAN
RCP/CCFRPM
8" GV8" GV
8" FP
8" FP
8" FP 18
" R
C P
4" RWR
4" D
EXITS. 12" FA
EXIST. 10"
FOUL AIR LINE
6" GV
3" RPZ
BACKFLOW
PREVENTER
ASSEMBLY
JUNCTION BOX
JUNCTION BOX
60"/54" RS
60"/54" RS
42" RS
42" RS
EXISTING EQUALIZATION
PUMP STATION
EQUALIZATION TANK
EXISTING 3"
ALUM LINE
4" RS DI
CONNECT 3" ALUM
PIPING TO EXISTING
ALUM PIPING
INSTALL 3" ALUM
PIPING
PROVIDE 14" FRP 90-DEG
BEND(2) FOR TRANISTION
FROM ABOVE GRADE TO
BELOW GRADE PIPING
PROVIDE 14"
FOUL AIR LINE
14" X 10" REDUCER
14" X 14" TEE
14" 90° BEND
(2)14" 11.25°
BEND
14" 90-DEG BEND
CONNECT14" FRP FOUL
AIR LINE TO EXISTING
PIPING AT EQ TANK
10" 45° BEND
PROVIDE 10" FRP
FITTINGS AS NEEDED
FOR TRANSITION
NOTES:
1. APPROXIMATE LOCATIONS OF NEW YARD
PIPING PROVIDED. CONTRACTOR TO REROUTE
AND SLOPE YARD PIPING AS REQUIRED.
14" 90° BEND x2
PROVIDE 14" FRP WITH
CONNECTION TO
EXISTING FAN
PROVIDE 14" 90-DEG BEND FOR
TRANSITION FROM ABOVE GRADE
TO BELOW GRADE PIPING.
SEE NOTE 1
PROVIDE 10"
FOUL AIR LINE
ODOR CONTROL
SYSTEM TO REMAIN IN
SERVICE AT ALL TIMES
(SEE PHOTO 3)
EDGE OF
PAVEMENT
A/C PAD A/C PADRELOCATE 4"
ODOR CONTROL
DRAIN LINE
SCALE: NTS
PHOTO 3 - ODOR CONTROL ABOVE GROUND
ADD FRP TRANSITION TO TO
EXISITNG ODOR CONTROL VENT
TO BE DIRECTED TO THE WEST.
BURIED
ELECTRIC
NEW ELECTRICAL
DUCTBANK MANHOLE
(SEE ELECTRICAL DWGS)
RELOCATE
RECLAIMED
WATER LINE
KENNY BLANTON PE. No. 46654
FIRE HYDRANT
10" 90° BEND
LO
T D
A
TE
: 5 /1
9/
:2
: S
S H
E A
Fi le
: C :\U
S E
R S
\S S
H E
A \D
C \A
C C
D O
C S
\H A
ZE
N
A N
D S
A W
Y E
R \4
-0
_C O
N S
E R
V
II
W R
F E
Q P
S F
IN
A
L D
E S
IG
N
\P R
O
JE
C T
FI
LE
S \0
1_ D
E S
IG
N
\0 2-
C S
E I\C
IV
IL
\4
-0
M
S P
S av ed b y S
S H
E A
S av e da te : 5
/1 9/
:5
P
M
WATER CONSERV II WRF
EQUALIZATION PUMP STATION
IMPROVEMENTS
44051-001
MARCH 2025K. BLANTON
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT No.:
HAZEN No.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
2420 S. LAKEMONT AVENUE, SUITE 325
ORLANDO, FLORIDA 32814
CIVIL / SITE
ENGINEERING, INC. CS
E I1645 N. MAITLAND AVENUE
MAITLAND, FL 32751
CONTRACTOR CERTIFICATION:
" I CERTIFY UNDER PENALTY OF LAW THAT I UNDERSTAND, AND SHALL COMPLY WITH
THE TERMS AND CONDITIONS OF THE STATE OF FLORIDA GENERIC PERMIT FOR
STORMWATER DISCHARGE FROM LARGE AND SMALL CONSTRUCTION ACTIVITIES AND
THIS STORMWATER POLLUTION PREVENTION PLAN THEREUNDER."
NAME: TITLE: .
CONTRACTING FIRM: ADDRESS: .
TELEPHONE No.: DATE: .
GENERAL NOTES:
1. THE "LIMITS OF WORK" LINE SHOWN ON THE PLANS (SILT FENCE) INDICATES THE POINT BEYOND WHICH
THE EXISTING VEGETATION SHOULD NOT BE IMPACTED.
2. STORMWATER POLLUTION PREVENTION MEASURES SHOWN HEREIN ARE THE MINIMUM REQUIRED.
CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ERECTING AND MAINTAINING AN EROSION AND SEDIMENT CONTROL SYSTEM TO MEET THE CITY OF ORLANDO, SJRWMD, AND FDEP REQUIREMENTS.
3. IN ADDITION TO FDEP NPDES PERMIT, THE CONTRACTOR IS REQUIRED TO OBTAIN A DEWATERING PERMIT FROM THE CITY OF ORLANDO. CONTRACTOR SHALL PROVIDE ADDITIONAL DEWATERING INFORMATION IN ORDER TO RECEIVE THE CITY'S APPROVAL TO DISCHARGE. THE ADDITIONAL INFORMATION INCLUDES THE PROPOSED DEWATERING VOLUME, THE DURATION OF DISCHARGE, THE SPECIFIC DISCHARGE LOCATION (MANHOLE, INLET, ETC.) AND A DESCRIPTION OR DRAWINGS OF THE BEST MANAGEMENT PRACTICES
THAT WILL BE EMPLOYED TO PREVENT TURBID WATER AND DEBRIS FROM BEING DISCHARGED.
4. NO AREA OF THE SITE SHALL BE DISTURBED UNTIL IT IS NECESSARY FOR CONSTRUCTION TO PROCEED.
DISTURBED AREAS SHALL BE COVERED OR STABILIZED AS SOON AS POSSIBLE.
5. EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED UNTIL THE AREA THEY PROTECT HAS BEEN SODDED, PAVEMENT HAS BEEN PLACED, OR THE AREA IS OTHERWISE COMPLETELY STABILIZED.
6. ALL DISTURBED AREAS OF THE SITE SHALL BE INSPECTED BY QUALIFIED PERSONNEL OF THE RESPONSIBLE CONTRACTOR EVERY SEVEN CALENDAR DAYS AND WITHIN 24 HOURS AFTER EVERY RAINFALL EVENT OF
0.50 INCHES OR MORE TO ASSESS THE INTEGRITY OF THE EROSION AND SEDIMENT CONTROLS. THE INSPECTOR SHALL NOTE ANY DAMAGE OR DEFICIENCIES IN THE CONTROL MEASURES IN AN INSPECTION REPORT. PROBLEM AREAS SHALL BE CORRECTED BY THE RESPONSIBLE CONTRACTOR WITHIN THREE
CALENDAR DAYS FOLLOWING THE INSPECTION.
7. THE CONTRACTOR SHALL KEEP A RECORD OF CONSTRUCTION ACTIVITIES INCLUDING DATES WHEN MAJOR GRADING ACTIVITIES OCCUR IN A PARTICULAR AREA, DATES WHEN CONSTRUCTION ACTIVITIES CEASE IN AN AREA, WHETHER TEMPORARILY OR PERMANENTLY, AND DATES WHEN AN AREA IS STABILIZED.
8. IF A CHANGE IN CONSTRUCTION SCHEDULE OCCURS OR THIS PLAN PROVES, THROUGH REGULAR
INSPECTIONS, TO BE LACKING, THE PROJECT ENGINEER SHALL BE NOTIFIED SO THAT PLAN
MODIFICATIONS CAN BE MADE.
9. NO EXCAVATED MATERIAL SHALL BE STOCKPILED IN SUCH A MANNER AS TO ALLOW RAINFALL RUNOFF TO
LEAVE THE PROJECT SITE.
10.