This is a Specifications document (Exhibit 5) for the ESB I-5 Albany Right-of-Way Fencing project issued by the Oregon Department of Transportation (ODOT). The project involves removing and replacing 22,476 linear feet of existing right-of-way fence and installing 850 linear feet of new fence along I-5 in the northbound and southbound directions from mile point 233.20 to 237.66, as well as installing one new single swing gate. The work location extends between I-5 and Century Drive on the east side of the highway and between I-5 and Old Salem Road on the west side. The specifications reference the 2024 Oregon Standard Specifications for Construction and include detailed modifications to multiple sections covering mobilization, traffic accommodations, traffic control, fencing materials, fence construction, posts, fasteners, and protective systems. Site visits are highly advised for prospective bidders to familiarize themselves with working locations, conditions, available workspace, and vegetation removal requirements. The contract documents reference standard drawings RD810 for Type 2 fencing and RD850 for the gate, and a KML file is provided to assist contractors in locating work areas using geospatial software.
Pricing terms and specific bid due dates are not included in this specifications document. The contract requires use of metal posts to match existing conditions, and contractor-provided traffic control plans must be submitted five calendar days before the preconstruction conference if single lane closures on Century Drive or Old Salem Road are anticipated. Although lane closures on I-5 are not expected, the specifications establish allowed closure hours for adjacent roads and include a line item for traffic control on the bid form. The project manager is Cody Stone, PE (Region 2 Maintenance and Operations), and the resident project representative is Cecil Hockema (Albany Section Maintenance Manager). Certification as an Emerging Small Business in Oregon is a mandatory requirement to submit a bid for this project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Exh 6.2_Plan Sheet RD810.pdf | ||
| Exh 6.3_Plan Sheet RD820.pdf | ||
| Att A Form A-2_Bid Pricing Form.xlsx | XLSX spreadsheet | |
| 00018261_RFCQ.docx | DOCX document | |
| Exh 6.1_D4 I5 Albany Refencing location.kml | KML file | |
| 00018261_Att B_Sample Contract.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT 5
SPECIFICATIONS
ESB - I5 Albany ROW Fencing
OREGON STANDARD SPECIFICATIONS FOR CONSTRUCTION. The 2024 Oregon Standard Specifications for Construction (“Standard Specifications”) include detailed specifications in Part 00200 and beyond (“technical specifications”) that apply to this Project. Some sections of the technical specifications may be identified and modified in the Contract Documents. Sections of the technical specifications not identified in the Contract Documents remain applicable to the Contract according to their original terms.
Sections 00120-00199 in Part 00100 of the Standard Specifications are not applicable to the Contract unless they are specifically identified in a Contract Document as being applicable. However, if a section in Part 00100, Section 00120—00199, that has been identified as being applicable references another section in Part 00100, or if a technical specification references a section from Part 00100, that section from Part 00100 applies to the Contract for purposes of supporting and giving full effect to the specification that referenced it. Abbreviations, definitions, and conventions in Part 00100, Section 00110, apply to the ITB and any resulting Contract as required for context within the Contract Document. The Standard Specifications can be accessed online at:
http://www.oregon.gov/ODOT/Business/Pages/Standard_Specifications.aspx
SILENCE OF SPECIFICATIONS. The apparent silence of the specifications as to any detail, or the apparent omission of a detailed description concerning any point, shall be regarded as meaning that only the best commercial practice is to prevail and that only materials and workmanship of first quality are to be used.
PROJECT MANAGER:
Cody Stone, PE Region 2 Maintenance and Operations Project Manager 455 Airport Road SE, Bldg E Salem, OR 97301 Cell: 503-953-6334 Cody.Stone@ODOT.Oregon.gov
RESIDENT PROJECT REPRESENTATIVE:
Cecil Hockema Interim Albany Section Maintenance Manager 1100 Gold Fish Farm Rd Albany OR 97322 Cell: 541-206-3919 cecil.hockema@odot.oregon.gov
LOCATION. The general project location is along I5 in the northbound and southbound directions from mile point 233.20 – 237.66. The ROW fencing is typically found between I5 and Century Dr on the east side of the highway and between I5 and Old Salem Rd on the west side of the highway. Attached to this solicitation is a .KML file that can be uploaded to geospatial software such as Google Earth (phone, desktop, or online versions), ArcGIS, ONX, Backcountry Navigator, etc.. for the contractor’s use in locating the work areas in the field. Note that the specific colors and names of the lines and pins in the .KML might not transfer to your viewing software of choice if not using Google Earth.
DESCRIPTION OF WORK:
The work to be done under this Contract consists of the following:
The contractor is to remove and replace 22,476 linear feet of ROW fence and install 850 linear feet of new ROW fence and install a new single swing gate. See standard drawings RD810 for fencing (Type 2 fence) and RD850 for the gate. Contractor to use metal posts to match existing. Although lane closures are not anticipated, section 00220.40(e)(1) below provides the lane closure hours for Century Dr. and Old Salem Rd., and there is a line item for traffic control on the bid pricing form in case the Offeror thinks traffic control will be necessary.
In the .KML file there is a pinned location for the new 12’ single swing gate. Yellow lines named “NB Section” 1, 2, 5, 6, and “SB Section” 1, 2, and 3 are fence runs to be removed and replaced. Red lines named “NB Section” 3 and 4 are new fence runs to be installed. The exact location of the new fence runs are to be marked in the field by the Resident Project Representative.
It is highly advised that prospective Offerors visit the worksite to become familiar with the working locations, conditions, available workspace, and vegetation to be removed.
PROFESSIONAL OF RECORD CERTIFICATION:
June 30, 2026
I certify the Special Provision Sections listed below are applicable to the design for the subject project and modified Special Provisions were prepared by me or under my supervision.
Sections: All
SPECIAL PROVISIONS
The special provisions below identify and modify certain sections of the Standard Specifications. All number references in the special provisions shall be understood to refer to the sections and subsections of the Standard Specifications bearing like numbers.
The apparent silence of the Specifications (including any supplemental Specifications) as to any detail, or the apparent omission of a detailed description concerning any point, shall be regarded as meaning that Contractor shall meet the highest standards prevalent in the industry or business most closely involved in providing the Goods to be provided under the Contract/Purchase Order.
SECTION 00210 - MOBILIZATION
Comply with Section 00210 of the Standard Specifications.
SECTION 00220 - ACCOMMODATIONS FOR PUBLIC TRAFFIC
Comply with Section 00220 of the Standard Specifications modified as follows:
00220.01(b) Abbreviations - Delete this subsection.
00220.40(e)(1) Closed Lanes - Replace this subsection, except for the subsection number and title, with the following:
Traffic Lanes may be closed on Old Salem Road or Century Drive when allowed, shown, or directed during the following periods of time except as specified in 00220.40(e)(2). No lane or shoulder closures on I5 are anticipated.
Single Lane Closures - One Traffic Lane may be closed during the following times:
Daily, Monday through Friday, between 9:00 a.m. and 4:00 p.m.
Nightly, Sunday through Thursday, between 7:00 p.m. and 6:00 a.m.
00220.40(e)(2) Opened Lanes ‑ Replace the paragraph that begins "Keep all Traffic Lanes and …" with the following paragraph:
Keep all Traffic Lanes and pedestrian facilities open during the following periods. Remove all barricades and objects from the Roadway during the periods that Traffic Lanes are to remain open.
00220.40(e)(2)(a) Holidays ‑ Replace the paragraph that begins "When a holiday falls …" with the following paragraph:
When a holiday falls on Sunday, the following Monday is recognized as a legal holiday. When a holiday falls on Saturday, the preceding Friday is recognized as a legal holiday.
SECTION 00221 - COMMON PROVISIONS FOR WORK ZONE TRAFFIC CONTROL
Comply with Section 00221 of the Standard Specifications modified as follows:
00221.06 Traffic Control Plan ‑ Replace this subsection with the following subsection:
00221.06 Traffic Control Plan and Tourist-Oriented Directional and Business Logo Signs –
(a) Traffic Control Plan – Submit the following, 5 Calendar Days before the preconstruction conference:
(1) Contractor Provided Traffic Control Plan – The Contractor shall submit their proposed single lane closure traffic control plan to the Engineer for approval.
00221.60 Temporary Traffic Control Devices – Replace the paragraph that begins “TCD delivered to the Project Site found…” with the following paragraph:
Repair or replace TCD delivered to the Project Site found to be in “marginal” or “unacceptable” condition, at no additional cost to the Agency.
00221.90(b) Temporary Protection and Direction of Traffic – Replace the bullet that begins “Providing, Surfacing, maintain…” with the following bullet:
Providing, surfacing, maintaining, removing, and restoring the TPAR.
SECTION 00222 - TEMPORARY TRAFFIC CONTROL SIGNS
Comply with Section 00222 of the Standard Specifications modified as follows:
00222.10 Temporary Signs ‑ Replace the paragraph that begins "Furnish temporary signs meeting …" with the following paragraph:
Furnish temporary signs meeting the requirements of the "Acceptable" category shown in the ATSSA Quality Guidelines for Temporary Traffic Control Devices and Features handbook, available from the ATSSA website. Use Materials and fabricate signs according to Section 00940, Section 02910 and the following:
00222.45(b) Portable Changeable Message Signs - Add the following bullets to the end of this subsection:
Do not use messages that scroll horizontally or vertically across the face of the sign.
At least seven Calendar Days before the work begins and a lane closure is required, place one or more PCMS displaying the following message as shown, or as directed:
| Panel 1 | Panel 2 |
| (Name/# of highway) | CLOSURE |
| (Location) | (Time Frame) |
| CLOSURE | (Time Frame) |
SECTION 00290 - ENVIRONMENTAL PROTECTION
Comply with Section 00290 of the Standard Specifications.
SECTION 01050 - FENCES
Comply with Section 01050 of the Standard Specifications modified as follows:
01050.10 Materials ‑ Delete “Protective Fence Materials, On and Off Structures.”
01050.41 Lines, Grades, and Preparation Work - Replace the paragraph that begins "Clear, grub and prepare …" with the following paragraph:
Clear, grub and prepare the Fence line area. Remove all shrubs, brush, snags, downed timber, float Rock, and other obstacles, including trees up to 6 inches in diameter that interfere with Fence construction. If directed, preserve trees and geographic features on Fence lines by varying the Fence alignment to miss them.
Replace the paragraph that begins "Fill or excavate ground …" with the following paragraph:
Fill or excavate ground surface irregularities that interfere with maintaining specified clearance above ground surface of the bottom wire of the Fence. Limit the width as necessary to provide a clear way for the Fence.
01050.43(a) General ‑ Replace the paragraph that begins "Set posts to the depths …" with the following paragraph:
Set posts to the depths shown. Reasonable variation in depths are allowed and posts may be appropriately shortened or left slightly high, as approved by the Engineer, to:
01050.43(a)(3) Concrete Footings - Replace this subsection, except for the subsection number and title, with the following:
Construct footing to dimensions no less than shown. Place the concrete to fill the excavated areas with contact against firm Soil at the sides and bottom and tamp around the posts and brace ends after the posts and braces have been brought to and firmly held in proper position. Strike off, slope or crown and smooth the surface of the concrete at the ground level to shed water. Allow to cure for at least 5 Calendar Days before subjecting the posts and braces to strain.
01050.43(d)(1) Barbed and Woven Wire Fences - Replace this subsection, except for the subsection number and title, with the following:
At angle of deflection exceeding 5 degrees for Fences with steel line posts or 15 degrees for Fences with wood line posts. Changes in line where the angle of deflection does not exceed the above limitations are considered alignment angles. Make the adjacent line posts at alignment angles fast to the angle post by means of diagonal tension wires.
01050.43(g)(1) Metal Braces - Replace the paragraph that begins "Provide corner posts …" with the following paragraph:
Furnish corner posts and intermediate end posts with two braces, one each direction from the post in the main Fence lines. Furnish end posts and Gate posts with one brace in the line of the Fence as shown.
01050.44(a) Placing Fabric and Wire - Replace the paragraph that begins "Place fabric and wire …" with the following paragraph:
Place fabric and wire on the face of the post that is away from the Highway or as shown. On curved alignment, place the fabric and wire on the face of the post where the normal pull of the fabric and wire is exerted.
Attach Fence fabric and barbed wire to each post according to recognized standard practice for Fence construction and as shown or directed.
01050.44(b) Splicing Fabric and Wire - Replace this subsection, except for the subsection number and title, with the following:
Splices of fabric and splices of separate lines of wire between posts are allowed provided that not more than two fabric or separate wire splices, spaced at least 50 feet apart, occur in any one Run of Fence. Use wrap or telephone type splices for the longitudinal woven wire and barbed wire with each end wrapped around the other wire for not less than six complete turns.
01050.44(e) Swinging Panels at Waterway Crossings - Replace this subsection, except for the subsection number and title, with the following:
At waterway crossings subject to floating debris, if directed, construct wood framed swinging Panels of Fence fabric, barbed wire or combinations. Attach the Panels to the lower wires of the Fence to provide fenced closure of the waterway so there is no unfenced side or bottom openings exceeding 6 inches when the waterway is at its lightest flow or is dry.
01050.44(f) Additional Panels at Depressions - Replace this subsection, except for the subsection number and title, with the following:
If depressions in the ground surface leave unfenced openings greater than 12 inches in height beneath the bottom line of the Fence, provide additional Panels of Fence fabric, barbed wire, or combinations between line posts, as approved, across the opening so no side or bottom openings exceeds 6 inches. If the bottom line of the Fence leaves an unfenced opening beneath it of 12 inches or less, pull the fabric and wires down between posts and anchor with pins or posts driven at least 18 inches into the ground so there is no bottom opening at any point along the Fence greater than 6 inches in height.
01050.44(g) Stay Wires and Final Adjustments - Replace this subsection, except for the subsection number and title, with the following:
Free the fabric and barbed wire in final position from warp and sag with stay wires placed approximately vertical to the grade of the Fence. Retighten brace guys and leave the lever restrained against the Fence fabric or Fence wires.
01050.45(b)(1) Rails - Replace this subsection, except for the subsection number and title, with the following:
Attach rails to end, Gate and corner posts by clamps and sockets, and thread through loop caps on the end of line posts. Furnish expansion sleeves or couplings at spacings not exceeding 200 feet in longitudinal top and bottom rails.
01050.45(b)(2) Tension Wire - Replace this subsection, except for the subsection number and title, with the following:
Attach tension wire to end, Gate and corner posts by bands and clamps. Either thread the top tension wire through line post loop caps or hold in open slots in a manner to limit vertical movement. Tie or attach the bottom tension wire to the bottom of line posts by ties or clamps in a manner that prevents vertical movement. Furnish tension wires with one turnbuckle or one ratchet take-up in each Run of Fence.
01050.48(a) Metal Gates - Replace this subsection, except for the subsection number and title, with the following:
Install metal Gates and fittings between Gate posts previously set as specified. Firmly attach the fittings to the posts and Gates. Hinge each Single Gate in a manner that prevents removal of the Gate without tools. Set the Gate in an approximately horizontal plane to swing freely inward and outward, and so it can be fastened securely in its latch holder, or in the case of Double Gates, in its latch holder and gate stops. Set Double Gates on their respective hinge pintles to provide a common horizontal plane where each Single Gate swings.
Install Gates to swing open at least 90 degrees in each direction.
01050.49 Removing and Rebuilding Fence - Replace this subsection, except for the subsection number and title, with the following:
Remove and rebuild existing Fences as shown or directed. Construct Fences to approximately the same condition as the original Fence. Salvage the materials in existing Fences to be removed and rebuilt and incorporate in the rebuilt Fences. Replace Fence materials damaged beyond reuse at no additional cost to the Agency. Firmly reset posts to the staked alignment. Provide the same post spacing and number of wires to be strung and stapled to the posts as the original Fence. Furnish and use new staples or clips to fasten the wires to the posts.
01050.50(b) Line Posts, Braces, End Posts, Corner Posts, and Gate Post - Replace this subsection, except for the subsection number and title, with the following:
Furnish metal post and brace components. Do not use wood posts and braces.
01050.50(e) Jumpouts - Replace this subsection, except for the subsection number and title, with the following:
Construct jumpouts as shown or directed with Borrow Material according to 00330.12 that contains no particles with any dimension greater than 3 inches. Make jumpouts of uniform grade and compact until there is no reaction or yielding under the compactor. Jumpouts are visually accepted by the Engineer.
01050.80(a) Barbed and Woven Wire Fence and Gateways ‑ Replace this subsection, except for the subsection number and title, with the following:
Barbed wire Fence, woven wire Fence, and barbed and woven wire Fence will be measured on the length basis. Measurement will be from center to center of posts, measured along the line and grade of each separate continuous Run of Fence as constructed, exclusive of Gates. Where existing Fences are extended to intersect the new Fence, the length of extension, from point of joining to the center of the new end post, will be measured and included for payment, if similar in design or type to a Pay Item, otherwise this Work will be paid for according to 00195.20.
01050.90(a) Barbed and Woven Wire Fence ‑ Replace the paragraph that begins "In item (a) …" with the following paragraph:
In item (a) the type of Fence is inserted in the blank.
Replace the paragraph that begins "In items (b) and (c) …" with the following paragraph:
In items (b) and (c) the width of the Gate opening is inserted in the blank.
01050.90(b) Chain Link Fence - Replace the paragraph that begins "In item (a) …" with the following paragraph:
In item (a) the type of Fence is inserted in the blank.
Replace the paragraph that begins "In item (b) …" with the following paragraph:
In item (b) the type of Fence is inserted in the first blank and the type of Material or pickets used for screening is inserted in the second blank.
Replace the paragraph that begins "In item (c) …" with the following paragraph:
In items (c) and (d) the width of the Gate opening is inserted in the first blank and the height of Gate is inserted in the second blank.
01050.90(e) Wildlife Fence - Replace the paragraph that begins "In item (c) …" with the following paragraph:
In items (c) and (d) the width of the Gate is inserted in the blank.
Replace the paragraph that begins "Payment will be payment …" with the following paragraph:
Payment will be payment in full for furnishing and placing all Materials, and for providing all Equipment, labor, and Incidentals necessary to complete the Work as specified.
SECTION 02110 – POSTS, BLOCKS, AND BRACES
Comply with Section 02110 of the Standard Specifications modified as follows:
02110.10(a) General - Replace this subsection, except for the subsection number and title, with the following:
Furnish posts for guardrail and median barrier of the size shown, manufactured from Douglas fir, Hem-fir, or Southern Yellow Pine. A minimum extreme fiber bending stress (Fb) of 1,200 psi is required for wood posts. Only treated posts from approved Suppliers that are listed in the Nonfield‑Tested Materials Acceptance Guide are allowed.
02110.10(b) Grading - Replace the paragraph that begins "Grading of posts shall…" with the following paragraph:
Furnish posts with grading meeting the following:
02110.10(c) Certificates - Replace this subsection, except for the subsection number and title, with the following:
Provide certificates of lumber inspection by a recognized inspection agency.
02110.10(f) Seasoning and Checking - Replace this subsection, except for the subsection number and title, with the following:
Furnish preservative treated post that show evidence of reasonable amount of seasoning or conditioning having occurred prior to treatment, so that further shrinkage of treated posts will not create checking that would expose untreated wood.
At the time of inspection at the plant and at the time of installation each treated post is subject to inspection for evidence of seasoning having occurred. The presence of checking on the surface of the post will not be cause for rejection unless the width of the widest check, shake, or split exceeds 1/2 inch (surface measurement).
If an otherwise acceptable treated post has a through check, shake, or end split in the same slope of grain or plane as the bolt hole and extending from the top of the post to within 3 inches of the bolt hole, the post is rejected unless it is provided with a tight fastening across the separation, centered on the post, and 2 inches below the top. Fasten with a 1/2‑inch diameter galvanized bolt and nut with a galvanized washer under the bolt head and under the nut after final curing of post is achieved. Treat holes for fastenings according to 00570.40.
02110.10(g) Inspection, Rejection and Marking at Plant - Replace this subsection, except for the subsection number and title, with the following:
Posts are subject to inspection at the treating plant at any time before, during or after treatment. Normally, inspection of treated posts is made by the Agency's Inspector not later than 10 Calendar Days after treatment, provided the Inspector is notified of the time that treating is to be done.
Inspection of treated posts for compliance with the requirements of 02110.10(e) is according to applicable AWPA standards, except as follows:
The Inspector will choose the number of treated posts from any one charge of the treating cylinder for determining penetration of treatment.
Each post selected for testing is representative as a basis of acceptance or rejection of a pro rata number of posts in the charge.
If 20 percent of the posts randomly selected for testing fail to conform to requirements, all of the posts in the entire charge from where they are selected may be classed as unacceptable.
At the Inspector's discretion, each treated post or a representative random selection of treated posts may be inspected for compliance with the requirements of 02110.10(f) "Seasoning and Checking".
Posts that fail to conform to requirements of this Subsection are subject to rejection at the treating plant singly, by partial lots, or by whole lots. (A "lot" comprises the posts in any charge of the treating cylinder.)
Apply a permanent mark or metal tag to each treated post that identifies the Supplier and year of treatment, placed by the Supplier either:
On the top of the post, or On the back of the post, 8 inches to 10 inches below the bolt hole.
02110.10(h) Field Inspection, Acceptance and Rejection - Replace the paragraph that begins "Posts that show a check …" with the following paragraph:
Posts that show a check, shake, or split exceeding 1/2 inch in width (surface measurement) on any surface are rejected.
Replace the paragraph that begins "Acceptance of Material…" with the following paragraph:
Acceptance of Material is according to 00165.35, 02110.10(g), and the Specifications.
02110.20 Guardrail Blocks - Replace this subsection, except for the subsection number and title, with the following:
(a) General - Furnish wood guardrail blocks of the dimensions shown. Furnish blocks either Douglas fir or Hem-fir meeting the requirements of 02110.10, or pine or Southern Yellow Pine meeting the requirements of 02110.20(b) and 02110.10 except for 02110.10(b). The requirements of marking and branding the treated blocks, according to the last paragraph of 02110.10(g), is waived provided that the Supplier of the treated blocks provides certification with each shipment stating that the blocks conform to Specifications and that the preservative treating was done under the inspection and with the approval of the Engineer.
(b) Grading - Furnish pine guardrail blocks according to the requirements of paragraph 80.11 of the current WWPA Grading Rules. Furnish Southern Yellow Pine guardrail blocks according to the requirements for No. 1 timber as specified in section 402 of the current SPIB Grading Rules.
(c) Recycled Plastic - Recycled plastic guardrail blocks from the QPL may be used.
(d) Acceptance - Acceptance of Material is according to 00165.35 and this Section.
02110.30 Fence Posts and Braces - Replace this subsection, except for the subsection number and title, with the following:
Furnish fence posts and brace rails of the sizes and dimensions shown and of sound Douglas fir, western hemlock, or western pine free from decay, end splits, and multiple crooks. Seasoning checks of not more than 5/16‑inch width (surface measurement) is allowed. Allowable crooks may be in one plane only. Do not allow a line drawn between the centers of the butt and tip of each post and brace rail to fall outside of the actual longitudinal centerline of the post or rail by more than 1.67 percent of its length, with an allowable maximum of 2 inches.
Posts and brace rails may be square, rough, or dressed lumber, or may be peeled round posts, as the Contractor elects. Furnish round members free from bark, protruding knots and irregularities detrimental to a pleasing appearance.
Fabricate posts and brace rails before pressure treatment. Where field boring or field cutting of a treated member is required, field-treat the exposed untreated surface of the member according to 00570.40. Do not allow the size of holes after treatment to exceed the size of the dowels or bolts to be inserted by more than 1/16 inch.
Posts intended to be driven may be machine-pointed on either the small end or the large end, before pressure treatment.
Pressure treat the posts and brace rails according to Section 02190.
Acceptance of Material is according to 00165.35 and the Specifications.
02110.40(a) Grading ‑ Replace the paragraph that begins "Grading requirements…" with the following paragraph:
Furnish wood signposts with grading according to the applicable paragraphs of either the current WCLIB Grading Rules or the current WWPA Grading Rules, as follows:
02110.40(b)(1) Length ‑ Replace the paragraph that begins "The length of the posts…" with the following paragraph:
Furnish posts of the length as shown or, where not shown, a sufficient length to provide proper sign mounting, a proper mounting height and the required foundation depth.
02110.40(b)(4) Cuts and Abrasions ‑ Replace this subsection, except for the subsection number and title, with the following:
Treat cuts, abrasions and bolt-holes, prior to shipping, with the same preservative as originally used to treat the post, except that if the post was originally treated with pentachlorophenol - volatile petroleum solvent (LPG) solution, treat cuts, abrasions and bolt-holes with pentachlorophenol - mineral spirits solvent solution according to AWPA Standard M4.
02110.40(c) Cuts and Abrasions ‑ Replace this subsection, except for the subsection number and title, with the following:
Acceptance of Material is according to 00165.35 and this Section.
SECTION 02560 ‑ FASTENERS
Comply with Section 02560 of the Standard Specifications modified as follows:
02560.05 Geometry ‑ Replace this subsection, except for the subsection number and title, with the following:
Use a bolt or rod length such that the end of the bolt or rod extends beyond or is at least flush with the outer face of the nut when properly installed.
02560.10(a) Bolts - Replace this subsection, except for the subsection number and title, with the following:
Furnish carbon steel bolts meeting the requirements of ASTM A307, Grade A or B.
02560.10(b) Nuts - Replace the paragraph that begins “Nuts for carbon steel bolts…” with the following:
Furnish nuts for carbon steel bolts meeting the requirements of the following, or equivalent:
02560.20(a) Bolts - Replace the paragraph that begins “High-strength bolts used in…” with the following:
Use Type 3 high-strength bolts in noncoated weathering steel connections. Furnish high‑strength bolts meeting the requirements of the following:
02560.20(b) Nuts - Replace the paragraph that begins “Nuts for high-strength bolts…” with the following:
Furnish nuts for high-strength bolts meeting the following requirements, or equivalent:
02560.20(c) Washers - Replace this subsection, except for the subsection number and title, with the following:
Furnish washers for high-strength bolts meeting the requirements of ASTM F436. Use Type 3 washers with Type 3 bolts.
02560.20(d) Direct Tension Indicators - Replace this subsection, except for the subsection number and title, with the following:
Furnish direct tension indicators that are the compressible-washer type, mechanically galvanized, according to ASTM F959. Adjust bolt lengths to accommodate both direct tension indicators and hardened washers.
02560.20(e) Markings - Replace this subsection, except for the subsection number and title, with the following:
Mark all bolts, nuts, washers and direct tension indicators according to the appropriate AASHTO/ASTM specifications and with a symbol identifying the manufacturer.
02560.30(a) Steel Tie Rods, Anchor Bolts, and Anchor Rods - Replace this subsection, except for the subsection number and title, with the following:
Furnish steel tie rods, anchor bolts, and anchor rods meeting the requirements of AASHTO M 314, Grade 36 or 55; ASTM F1554, Grade 36 or 55.
02560.30(b) High-Strength Tie Rods, Anchor Bolts, and Anchor Rods - Replace this subsection, except for the subsection number and title, with the following:
Furnish high-strength tie rods, anchor bolts, and anchor rods meeting the requirements of AASHTO M 314, Grade 105; ASTM F1554, Grade 105; or ASTM A449, Type 1.
End stamp all ASTM F1554, Grade 105 according to ASTM F1554 Supplementary Requirements S2 and S3. If the end of the bolt is to be embedded in concrete, mark the projecting end from the concrete.
02560.30(c) Nuts - Replace the paragraph that begins “Nuts for tie rods…” with the following:
Furnish nuts for tie rods, anchor bolts, and anchor rods meeting the following requirements, or equivalent:
02560.30(d) Washers - Replace this subsection, except for the subsection number and title, with the following:
Furnish washers for anchor bolts meeting the requirements of ASTM F436, Type 1.
02560.60(a) Rotational Capacity Test ‑ Replace the paragraph that begins “Test each combination of bolt…” with the following:
Test each combination of bolt production lot, nut lot and washer lot as an assembly. Assign a rotational capacity lot number to each combination of lots tested. The minimum frequency of testing is two assemblies per rotational capacity lot. Test according to one of the following requirements:
02560.60(a)(1) Method 1 ‑ Replace the paragraph that begins “the above measured torque…” with the following:
Do not allow the above measured torque to exceed the torque value calculated by the following equation:
Replace the paragraph that begins “Continue to tighten the nut until…” with the following:
Continue to tighten the nut until the nut has turned twice the rotation shown in Table 00560‑3 of Section 00560 from its snug-tight position mark for bolt lengths up to 8D ( for greater than 8D up to 12D bolt lengths tighten to 1 1/6 turn from snug-tight).
02560.60(a)(2) Method 2 - Replace this subsection, except for the subsection number and title, with the following:
Test bolts that are too short to be tested in a direct bolt tension indicating device in a steel joint.
Place the lubricated fastener including a washer in one or more flat structural steel plates. The total thickness including the washer is such that three to five full threads of the bolt are located between the bearing surfaces of the bolt head and the nut. Provide the hole in the joint at the same nominal diameter as the hole in the washer. Using a calibrated torque wrench, tighten the nut to a snug-tight condition to produce an initial torque in the bolt equal to approximately 10 percent of the torque calculated using the equation given in Method 1 above where P is the minimum tension in the bolt according to Table 00560-1 of Section 00560. Mark the nut's position relative to the fixed bolt for this snug tight position.
Using the calibrated torque wrench, further tighten the nut until the nut has turned the rotation shown in Table 00560-3 of Section 00560 from its snug-tight position mark. Prevent the bolt head from turning during the tightening process. Record the measured torque with the nut in motion. The measured torque is not to exceed 1.15 times the torque value calculated in the preceding step of Method 2. Reject assemblies with torque values exceeding the calculated value.
Tighten the nut further until the nut has turned twice the rotation shown in Table 00560-3 from its snug-tight position mark. Reject assemblies that fail this rotation either by stripping or fracture.
Loosen and remove the nut. Examine the threads on the nut and bolt. Reject assemblies showing evidence of thread shear failure, stripping or torsional failure of the bolt.
02560.60(b) Other Test Requirements ‑ Replace the paragraph that begins “Provide three high‑strength bolt …” with the following:
Furnish three high‑strength bolt assemblies per size per lot for check testing.
Replace the paragraph that begins “Provide one high‑strength tie rod…” with the following:
Furnish one high‑strength tie rod, one high‑strength anchor bolt, and one high‑strength anchor rod assembly per size per lot for check testing.
02560.70 Lubricating Fasteners - Replace the paragraph that begins “Furnish all galvanized and coated…” with the following:
Furnish all galvanized and coated fasteners with a factory applied commercial water‑soluble wax that contains a visible dye of a color that contrasts with the color of galvanizing or coating. Furnish black fasteners that are "oily" to the touch when installed.
02560.80 Acceptance - Replace this subsection, except for the subsection number and title, with the following:
Acceptance of fasteners are according to 00165.35 and this Section.
SECTION 03010 ‑ FENCING MATERIALS
Replace Section 03010 of the Standard Specifications except for the Section number and title with the following:
Description
03010.00 Scope ‑ This Section includes the requirements for barbed wire, woven wire fabric, chain link fabric, wildlife wire fabric, metal posts, braces, hardware, and gates.
Materials
03010.10 Barbed Wire ‑ Furnish two-strand and either 12 1/2 gauge or 15 1/2 gauge barbed wire with four-point barbs spaced at 5-inch intervals according to the requirements of AASHTOM 280 (ASTM A121) with Class 3 galvanizing.
Install new or like new barbed wire on the Project and use the same diameter unless otherwise approved.
03010.20 Woven Wire Fabric ‑ Furnish 12 1/2-gauge galvanized steel woven wire fabric according to the requirements of AASHTO M 279 (ASTM A116), Class 3 coating or 11 gauge or 12 1/2-gauge aluminum coated steel wire according to the applicable requirements of ASTM A116. Furnish 12 1/2-gauge aluminum coated steel wire having the same coating thickness required for 11-gauge steel wire in Table 2 of ASTM A116.
03010.21 Wildlife Wire Fabric ‑ Furnish 12 1/2-gauge galvanized steel wire for wildlife wire fabric according to the requirements of ASTM A116, Design Number 2096-6-12 1/2.
03010.30 Chain Link Fabric, Ties, and Tension Wire ‑ Furnish chain link fabric, ties, and tension wire according to the requirements of AASHTO M 181 supplemented and modified as follows:
Fabric may be zinc-coated steel meeting Type I, Class D coating requirement, aluminum-coated steel, or aluminum alloy. Use only one type on the Project.
Wire fabric ties, wire ties, and hog rings may be zinc-coated steel wire, aluminum-coated steel, or aluminum alloy as elected, regardless of the type of wire fabric used.
Use ductile, zinc-coated steel meeting the coating requirements of ASTM A641, Class 1 for wire fabric ties, wire ties, and hog rings. Coat aluminum-coated steel wire fabric ties, wire ties and hog rings with at least 0.30 ounce per square foot.
Furnish tension wire with a Class 2 coating.
Furnish 9-gauge wire woven in 3 1/2‑inch by 5 1/2-inch diamond mesh for the fence to be installed with pickets. Knuckled finish top and bottom selvage.
03010.31 Pickets ‑ Furnish pickets that are either standard Grade A redwood or cedar pickets, 3/8-inch x 2 1/2-inch x 6 feet, or industry standard metal, or plastic pickets as shown or approved.
03010.40 Vinyl Clad Fabric ‑ Furnish vinyl clad chain link fabric according to AASHTO M 181, Type IV. The color of the PVC coating is either medium or dark green.
03010.50 Metal Fence Posts, Braces, and Appurtenances ‑ Furnish metal fence posts, braces and appurtenances according to the requirements indicated on the Plans and the following:
(a) Painted Metal Posts ‑ Furnish the same kind and color of all painted metal posts.
(b) Posts, Braces, and Appurtenances for Chain Link Fence ‑ Furnish posts, braces, and appurtenances for chain link fence according to the requirements of AASHTO M 181.
Furnish posts, braces, and appurtenances for bridge protective fence according to the requirements of AASHTO M 181, Grade 1, ASTM F1083 and ASTM F1043, Group IA-2.
(c) Posts, Braces, and Appurtenances for Barbed Wire and Woven Wire Fence:
(1) Tubular Steel Posts ‑ Furnish tubular steel posts, braces and appurtenances according to the requirements of AASHTO M 181. Fit tubular posts with a snug-fitting, galvanized metal cap.
(2) Other Shapes ‑ Furnish metal posts and braces, other than tubular shape, for barbed wire and woven wire fences, according to AASHTO M 281 (ASTM A702), except that galvanizing may conform to the requirements of AASHTO M 111 (ASTM A123). The posts and braces may be either galvanized or painted, as elected. Furnish wire fasteners meeting the coating requirements of ASTM A641, Class 1.
(3) Fence Stays, Brace Guys, and Wire Loops ‑ Furnish metal fence stays, brace guy wires, wire loops for gateways and other miscellaneous wire used in barbed and woven wire fences with Class 1 coating as required by ASTM A641. Either 9 1/2‑gauge or 10-gauge wire is acceptable for fence stays.
(d) Concrete In Footings ‑ Furnish concrete for footings according to Section 00440.
(e) Grounding Rod ‑ 5/8 inch by 8 feet, nonrusting, copper covered steel rod with a bronze grounding wire clamp.
(f) Grounding Wire ‑ AWG 4/0 Solid Copper or No. 6 bare aluminum wire with clamps.
(g) Posts, Braces, and Appurtenances for Wildlife Fence ‑ Furnish posts, braces, and appurtenances for wildlife fence according to the requirements of AASHTO M 181.
03010.60 Fence Gates:
(a) General ‑ Furnish tubular steel gate frames according to AASHTO M 181. For fabric in gates used with chain link fence, use chain link of the same gauge and according to applicable requirements of 03010.30. For fabric in gates used with woven wire fence, furnish woven wire fabric according to 03010.20 or chain link fabric according to the applicable requirements of 03010.30, except that the zinc coating may be either Class C or Class D. Use wildlife fence fabric according to 03010.21 for fabric in gates used with wildlife fence.
(b) Hardware ‑ Furnish all fence and gate hardware according to the requirements of AASHTO M 181, except that the thickness of galvanizing is according to AASHTO M 232 (ASTM A153).
03010.75 Protective Fence Materials, On and Off Structures ‑ Provide certification according to 00165.35 that the anchor system selected conforms to requirements as shown.
Resin Bonded Anchor System ‑ Furnish the resin bonded anchor system used to install the fence post anchor rods in the concrete bridge rail from the QPL and install according to the manufacturer's recommendations.
Posts ‑ Modify posts to attach to the Structure as shown.
Steel Plates, Angles, and Bolts ‑ Furnish steel plates, angles, and bolts meeting the applicable requirements of Section 02530 and galvanized according to 02530.70.
Chain Link Fabric, Ties, and Tension Wire ‑ Furnish chain link fabric, ties, and tension wire according to the requirements of 03010.30.
Pickets ‑ Furnish pickets meeting the requirements of 03010.31.
03010.80 Acceptance ‑ Acceptance of fencing Materials is according to 00165.35 and this Section.