ex. f - Comm center - control drawings.PDF

PDF 1 MB Posted

Attached to
2025 BAS Upgrades
Solicitation number
PW-2025115-0-2025/JH
Issued by
Waukesha County, Wisconsin

About this file

This document is a detailed set of control system and mechanical drawings for the Waukesha County Communication Center project, prepared by Johnson Controls, Inc. The comprehensive drawings cover the building's environmental control systems, including heating, ventilation, air conditioning (HVAC), and building automation systems (BAS) for a facility located at 1621 Woodburn Road in Waukesha, Wisconsin. The project involves installing multiple rooftop units (RTU-1 and RTU-2), VAV terminal units, hot water heating systems, CRAC units for data and radio rooms, and a network of sensors and controllers to manage environmental conditions across different zones and spaces.

The technical drawings provide extensive details on system configurations, including specific equipment like Liebert CRAC units, ceiling exhaust fans, humidifiers, and various valve and damper schedules. The control system will integrate multiple subsystems using BACnet MS/TP communication protocols, with a network of field controllers, network sensors, and a supervisory controller (JACE). The system is designed to provide precise temperature and humidity control, with features like variable air volume (VAV) terminal units, hot water reheat capabilities, occupancy mode controls, and comprehensive monitoring of environmental conditions across approximately 22 different zones in the facility. The project appears to be a complete building automation and environmental control system upgrade, with careful attention to zonal temperature management, energy efficiency, and flexible operational modes.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Creating a better climate for business.

Environmental Control System

Air Conditioning Heating Diagnostic Services Coil Cleaning Refrigeration Automatic Temperature Controls Facility Management Systems Fire Management Security Management Building Operations and Management Water Treatment Electrical Equipment Emergency Generator / Lighting Equipment Industrial Controls / Recording / Indication Equipment

Facility Management System Air and Water System Balancing Fire Management System Security System Lighting Services Instrumentation System Installation Building Operations Management Energy Conservation Control Training Programs Performance Contracting Planned Service Agreements

Waukesha County Communication Center 7N03-0223

LEGEND

2/183

Wire Symbol indicating:

Cable Destination (DA-T), Cable number (3), Number of wires and size (E.G. 2 #18 wires)

S

Main Air Supply Tube at 20 PSIG

D-N 15-20

Dual Air Supply Tube at

15/20 PSIG

Day=15, Night=20

S

High Pressure Air Supply Tube at 80 PSIG

Air line or Electrical Wire

Connected Lines or Wires

Crossing Lines or Wires, Not Connected

Pneumatic Tube indicating Tube Number

2/18 Wire Symbol indicating:

number of wires and size (E.G. 2 #18 wires)

Electrical Wire Terminal with Appropriate Number

Item Located on Panel Face

In-Line Restrictor

Opposed Blade Damper

Parallel Blade Damper

Air Flow Measuring Station

Filter

Humidifier

Fan

Pump

Heating or Cooling Coil

Ductwork or Piping with Flow Direction Shown

Drawing Revision Symbol with Appropriate Number

Gage

Current Sensing Switch or Combination Current Sensing switch & Command Relay

Duct Detector (Smoke, CO, CO2)

2-Way Valve with Actuator

N C

3-Way Valve with Actuator

N 0

C N C

Vapor Tension Temperature Sensing Element (Low Limit)

Vapor Tension Temperature Sensing Element (Hi Limit)

Paddle Type Flow Switch

Pressure Sensing Device

Bulb Type Temperature Sensing Element Located inside Separable Socket/Well

Strap-on Bulb Type Temperature Sensing Element

Combination Bulb Type Temperature Sensing Element and Humidity Sensor (Duct Mount)

Bulb Type Temperature Sensing Element

Humidity Sensing Element Located under Shield in Outside air

Bulb Type Temperature Sensing Element Located under Shield in Outside air

Device H

C N O

N O

IN CONSIDERATION OF THE RECEIPT OF

THIS DOCUMENT, THE RECIPIENT AGREES

NOT TO REPRODUCE, COPY, USE OR

TRANSMIT THIS DOCUMENT AND/OR THE

INFORMATION THEREIN CONTAINED, IN

WHOLE OR IN PART, OR TO SUFFER SUCH

ACTION BY OTHERS, FOR ANY PURPOSE,

EXCEPT WITH THE ADVANCE WRITTEN

PERMISSION OF JOHNSON CONTROLS,

INC. AND FURTHER AGREES TO

SURRENDER SAME TO JOHNSON

CONTROLS, INC. UPON DEMAND.

COPYRIGHT JOHNSON CONTROLS, INC. 2017

NUMBER

number

Title.vsd

REVISION

INFORMATION

04/02/18

09:53 AM

extra

DATE

TIME

FILE NAME

Waukesha County Communication Center

PROJECT TITLE

ARCHITECT

Kueny Architects, LLC 10505 Corporate Drive Suite #100 Pleasant Prairie, WI 53158 Phone: 262-857-8101

ENGINEER

Southport Engineered Systems 1343 South 27th Street Caledonia, WI 53108 Phone: 262-818-4409

MECHANICAL CONTRACTOR

Butters Fetting Co Inc 1669 S. 1st St.

Milwaukee, WI 53204-2999 Phone: 414-645-1535

ELECTRICAL CONTRACTOR

7N03-0223

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

DATE

Branch Information

CONTRACT NUMBER

CoEE

APPLICATION ENGINEER

06/19/2017

PROJECT MANAGERSALES ENGINEER

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

MPKJW

1621 Woodburn Road Waukesha WI, 53188

REV. DWG NUMBER DWG TITLE

1.1-1.3 LEGEND

2.1-2.4 NET REFERENCE

1 2.5 COMMUNICATION BUS

3.1-3.3 HWS

3.1 HWS FLOW

3.2 PANEL P-1

3.3 PANEL P-1 WIRING

NAE-01-PS-1 POINT SCHEDULE

1 4.1-4.3 RTU

4.1 RTU-1 FLOW

1 4.2 RTU-2 FLOW

1 4.3 RTU-1 & RTU-2 SEQUENCE

1 5.1-5.5 ROOM SCHEDULE DETAILS

5.1 DETAIL A: VAV W/ REHEAT

5.2 DETAIL B: VAV W/ REHEAT & FTR

5.3 DETAIL C: UNIT HEATER

5.4 DETAIL D: FTR

1 5.5 DETAIL E: VAV W/ IT/RADIO ROOM MONITORING

REV DWG NUMBER DWG TITLE

6.1-6.4 MISCELLANEOUS DETAIL

6.1 DETAIL A: POWER DETAIL

1 6.2 DETAIL B: LIEBERT UNIT

6.3 DETAIL C: EXHAUST FAN CEF-1

6.4 DETAIL D: HUMIDIFIER H-1

WD-1 WIRING DETAIL

1 DS-1 DAMPER SCHEDULE

1 RS-1 ROOM SCHEDULE

VS-1 VALVE SCHEDULE

WS-1 WELL SCHEDULE

WD-2 WELL DETAILS

1 Revision as per CB 7N03-0223-001 9/12/2017 CoEE

2 Record Drawing 4/2/2018 CoEE

TABLE 1

USAGE ANIXTER DESCRIPTION ANIXTER DESCRIPTION BLACK WHITE

JACKET

COLOR RED ANIXTER DESCRIPTION ANIXTER DESCRIPTION BLACK WHITE

JACKET

COLOR RED DRAIN COMMENTS

AI CBL-18/2YEL-PLN 18/2 Shld Yellow CBL-18/2YEL-PVC 18/2 Shld Yellow AI Com — AI — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld AI Com AI — — TABLE 2

AI CBL-18/3YEL-PLN 18/3 Shld Yellow CBL-18/3YEL-PVC 18/3 Shld Yellow AI Com Pow er AI — CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld AI Com Pow er — AI TABLE 2

AO CBL-18/2TAN-PLN 18/2 Shld Tan CBL-18/2TAN-PVC 18/2 Shld Tan AO Com — AO — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld AO Com AO — — TABLE 2

AO CBL-18/3TAN-PLN 18/3 Shld Tan CBL-18/3TAN-PVC 18/3 Shld Tan AO Com Pow er AO — CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld AO Com Pow er — AO TABLE 2

BI CBL-18/2ORG-PLN 18/2 Shld Orange CBL-18/2ORG-PVC 18/2 Shld Orange BI 24V — BI — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld BI 24V BI — — TABLE 2

BO CBL-18/2VLT-PLN 18/2 Shld Violet CBL-18/2VLT-PVC 18/2 Shld Violet BO Com — BO — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld BO Com BO — — TABLE 2

BO CBL-18/3VLT-PLN 18/3 Shld Violet CBL-18/3VLT-PVC 18/3 Shld Violet BO Com BO BO — CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld BO Com BO — BO TABLE 2

GENERAL PURPOSE CBL-18/2NAT-PLN 18/2 Shld Natural CBL-18/2NAT-PVC 18/2 Shld Natural Common Pow er — — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld Common Pow er — — —

GENERAL PURPOSE CBL-18/3NAT-PLN 18/3 Shld Natural CBL-18/3NAT-PVC 18/3 Shld Natural Common Pow er — Signal CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld Common Pow er — Signal —

GENERAL PURPOSE CBL-18/2WHTNS-PLN 18/2 Non-Shld White — — Common Pow er — — CBL-18/2WHTNS-PLN 18/2 Non-Shld White — — Common Pow er — — —

GENERAL PURPOSE CBL-18/3WHTNS-PLN 18/3 Non-Shld White — — Common Pow er — Signal CBL-18/3WHTNS-PLN 18/3 Non-Shld White — — Common Pow er — Signal —

METASTAT CBL-24/8NAT-PLN 24/8 Natural CBL-24/8NAT-PVC 24/8 Natural — — — — CM-00424BBG-3 24/8 Natural CM-00424BBG-3 24/8 Natural — — — — — SEE TABLES 4, 5, & 6

METASTAT PHONE JACK CBL-STATxxx Pre-Term'd Blue CBL-STATxxx Pre-Term'd Blue — — — — CBL-STATxxx Pre-Term'd Blue CBL-STATxxx Pre-Term'd Blue — — — — — SEE TABLES 4, 5, & 6, NOTE #4

24VAC CBL-18/2GRY-PLN 18/2 Shld Gray CBL-18/2GRY-PVC 18/2 Shld Gray 24 V Com — 24 VAC — CBL-18/2GRY-PLN 18/2 Shld Gray CBL-18/2GRY-PVC 18/2 Shld Gray 24 V Com 24 VAC — — —

24VAC POWER BUS AL-1402C-2-2N-01 14/2 Shld White AL-1402C-2-2N-01 14/2 Shld White Common — — 24 VAC AL-1402C-2-2N-01 14/2 Shld White AL-1402C-2-2N-01 14/2 Shld White Common — — 24 VAC —

600 V B8248 18/2 B8248 18/2 — — — — — — — — — — — — —

600 V B83336 18/3 B83336 18/3 — — — — — — — — — — — — —

N2 BUS CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue N2- REF N2+ — CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue N2- REF N2+ — TABLE 3

N1 BUS-ARCNET CBL-RG62PUR-PLN RG62 Purple CBL-RG62PUR-PVC RG62 Purple — — — — CBL-RG62PUR-PLN RG62 Purple CBL-RG62PUR-PVC RG62 Purple — — — — —

N1 BUS-ETHERNET CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — — SEE TABLES 7 & 8, CAT 5E

BACNET IP CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — — SEE TABLES 7 & 8, CAT 5E

LON BUS CBL-22/2-NS-PLN 22/2 Non-Shld White CBL-22/2-NS-PVC 22/2 Non-Shld Gray — — — — CBL-22/2-NS-PLN 22/2 Non-Shld White CBL-22/2-NS-PVC 22/2 Non-Shld Gray — — — — —

XT BUS CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue XT- REF XT+ — CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue XT- REF XT+ — —

BACNET MS/TP FC BUS CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue FC- COM FC+ — CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue FC- COM FC+ — TABLE 3

BACNET MS/TP SA BUS CBL-22/2P-SA-PLN 22/4 Shld Brow n CBL-22/2P-SA-PVC 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (BRN) PWR (WHITE) CBL-22/2P-SA-PLN 22/4 Shld Brow n CBL-22/2P-SA-PVC 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (BRN) PWR (WHITE) TABLE 3 TERMINAL BLOCK

BACNET MS/TP SA BUS CBL-NETWORKxxx 26/6 Preassembled CBL-NETWORKxxx 26/6 Preassembled — — — — CBL-NETWORKxxx 26/6 Preassembled CBL-NETWORKxxx 26/6 Preassembled — — — — TABLE 3 MODULAR JACK, 26AWG IS ACCEPTABLE, NOTE #4

PLENUM PART NUMBER NON-PLENUM PART NUMBER PLENUM PART NUMBER NON-PLENUM PART NUMBER

COLOR CODED CABLE 18 GAUGE NON-COLOR CODED CABLE 18 GAUGE

CABLE / WIRE SPECIFICATION CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR CABLE / WIRE SPECIFICATION CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR

NUMBER

number legend-a.vsd

REVISION

INFORMATION

04/02/18

02:07 PM

extra

DATE

TIME

FILE NAME

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee

WI 53222

Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

LEGEND

1.1

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NOTE #1: WHEN USING COLOR CODED CABLE, REFERENCE DETAILS

OVERRIDE COLOR CODE IN TABLE 1. WHEN USING NON-COLOR CODED

CABLE, TABLE 1 DETAILS OVERRIDE COLOR CODE IN REFERENCE

DETAILS.

NOTE #2: EXISTING JOB STANDARDS OVERRIDE NOTE #1 AND TABLE1.

NOTE #3: SEE JOHNSON CONTROLS INSTALLATION INFORMATION FOR

CABLE LENGTH LIMITATIONS.

NOTE #4: AVAILABLE IN 25FT, 50FT, 75FT AND 100FT LENGTH.

NOTE #5: USE PLENUM CABLE PER NEC REQUIREMENTS.

NOTE #6: USE SHIELDED CABLE IN “NOISY” ENVIRONMENTS.

NOTE #7: FOR VENDOR DEVICES ON THE N2 OR MS/TP BUS, DO NOT

TERMINATE THE REF / COM WIRE BUT WIRE STRAIGHT THROUGH TO THE

NEXT JCI DEVICE. THIS IS ESPECIALLY IMPORTANT FOR ALL VFD’S,

NUMBER

number legend-b.vsd

REVISION

INFORMATION

04/02/18

02:07 PM

extra

DATE

TIME

FILE NAME

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee

WI 53222

Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

LEGEND

1.2

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

FIGURE B

ASC

REF

N2+

N2 BUS 18/3 Shld Blue

REF

N2- N2+

HRD GRD

HG

ENCLOSURE

SUPERVISORY

CONTROLLER

HG

ASC

ENCLOSURE

HG

DEVICE

TAPE BACK DRAIN WIRE @ DEVICE

(ISOLATE FROM GROUNDING)

GROUND WITHIN 3" OF

ENTERING THE PANEL

TABLE 2

ENCLOSURE NO ENCLOSURE

I/O

HARD GROUND @ EACH

PANEL. TAPE BACK @

EACH DEVICE.

TAPE BACK @ EACH END SEE FIGURE A

BO (NOISY INDUCTIVE

LOADS)

TAPE BACK @ EACH END TAPE BACK @ EACH END

ADD MOV-1 @

CONTROLLER

TERMINALS

BO (GAS IGNITION) TAPE BACK @ EACH END TAPE BACK @ EACH END

ADD FILTER-1 @

CONTROLLER

TERMINALS. HARD

GROUND CASE.

DRAIN CABLE

I/O GROUNDING

TERMINALS COMMENTS

FIGURE A

DRAIN

N2-

18/x Shld

DRAIN

ASC

DEVICE

TAPE BACK DRAIN WIRE @ EACH END

(ISOLATE FROM GROUNDING)

18/x Shld

DRAIN

TABLE 3

ENCLOSURE NO ENCLOSURE

SUPERVISORY CONTROLLER HARD GROUND TO BACK

PLANE.

NA

ASC

STRAIGHT THROUGH TO

NEXT DEVICE

STRAIGHT THROUGH TO

NEXT DEVICE

ASC (EOL) TAPE BACK @ ASC TAPE BACK @ ASC

ASC (NOISY)

SOFT GROUND ONCE PER

ENCLOSURE

TAPE BACK @ ASC

ADD CAP-1 @ ENCLOSURE

SEE FIGURE B

DRAIN CABLE

N2 GROUNDING

TERMINALS COMMENTS

ENCLOSURE

HGHG

ASC

REF

N2+ N2-

DRAINDRAIN

ASC

REF

N2+ N2-

ASC

REF

N2+ N2-

DRAINDRAIN

D R

A

IN

TAPE BACK DRAIN WIRE @ EOL ASC

(ISOLATE FROM GROUNDING)

WIRE NUT DRAIN WIRE THROUGH TO NEXT

DEVICE (TYPICAL)

WIRE NUT DRAIN WIRES

TOGETHER

legend-c.vsd

REVISION

INFORMATION

04/02/18

02:07 PM

extra

DATE

TIME

FILE NAME

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee

WI 53222

Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

LEGEND

1.3

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

8 7 6 5 4 3 2 1

CAT 5 OR

METASTAT

CABLE

END VIEW OF 8-PIN PLUG

TAB DOWN

123456

SA BUS PORT

MODULAR

JACK

TABLE 7 STANDARD EIA/TIA T568B

PIN NO. COLOR

1 WHT / ORN

2 ORN / WHT

3 WHT / GRN

4 BLU / WHT

5 WHT / BLU

6 GRN / WHT

7 WHT / BRN

8 BRN / WHT

ETHERNET PATCH CABLE

NOTE: A PATCH CABLE HAS

BOTH ENDS CONFIGURED AS A

PATCH CABLE.

ETHERNET CROSSOVER CABLE

TABLE 8 STANDARD EIA/TIA T568B

PIN NO. COLOR

1 WHT / GRN

2 GRN / WHT

3 WHT / ORN

4 BLU / WHT

5 WHT / BLU

6 ORN / WHT

7 WHT / BRN

8 BRN / WHT

NOTE: A CROSSOVER CABLE HAS ONE

END CONFIGURED AS A CROSSOVER

CABLE AND THE OPPOSITE END

CONFIGURED AS A PATCH CABLE.

ADDRESS VALUE /

ADDRESS RANGE CLASS EXAMPLES

0 Bus Supervisor NAE on the FC Bus, FEC or VMA on SA Bus

1 Reserved Wireless Commissioning Converter 2 - 3 Reserved Reserved for future use

4 - 127 Master Range FEC, VMA, IOM, TEC26xx on the FC Bus

IOM on the SA Bus

128 - 254 Slave Range Slave devices and NS netw ork sensors on the SA Bus

198 Reserved VAV Balancing Sensor (handheld)

199 Reserved Most NS Series Netw ork Sensor models or

VAV Balancing Sensor (w all-mounted)

200 - 203 Reserved NS Series Netw ork Sensors (specif ied models)

255 Broadcast Do not apply address 255 to any device.

MS/TP BUS ADDRESS VALUES AND ADDRESS RANGES

TABLE 4 PHONE JACK PIN DESIGNATIONS

PHONE JACK

PIN NO. SIGNAL DESIGNATION COLOR

1 SA BUS (+) WHT / GRN

2 SA BUS (-) WHT / ORG

3 SA BUS COMMON (POWER FROM SENSOR TO

TOOL)

BLU / WHT

4 SA POWER (POWER TO SENSOR FROM TOOL) WHT / BLU

5 SA BUS COMMON (POWER FROM BUS TO

NETWORK SENSOR)

ORG / WHT

6 SA POWER (POWER FROM BUS TO NETWORK

SENSOR)

GRN / WHT

TABLE 5 TERMINAL BLOCK WIRING

TERMINAL NO. SIGNAL DESIGNATION COLOR

1 SA BUS (+) BLACK

2 SA BUS (-) WHITE

3 SA BUS COMMON BLUE

4 SA BUS POWER RED

NS SERIES SENSOR

NOTE:

DO NOT USE A CROSSOVER CABLES ON THE SA BUS

ON

EOL SWITCH = ON

EOL TERMINATION FOR THE MS/TP BUS

NOTE:

END-OF-LINE TERMINATION IS REQUIRED ON ALL FC

AND SA BUSES

NOTE:

REFER TO THE MS/TP COMMUNICATIONS BUS TECHNICAL

BULLETIN (LIT-12011034) FOR EOL TERMINATION GUIDELINES

ADDRESS SWITCH 2 SWITCH 1

199 N/A N/A

200 OFF OFF

201 OFF ON

202 ON OFF

203 ON ON

NS SERIES SENSOR DEVICE ADDRESS

(DIP SWITCH SHOWN IN

DEFAULT POSITION)

NS-xTN7003-0 SERIES

ON

1 2

NOTE:

NON-ADDRESSABLE NS SERIES SENSORS

HAVE A FIXED ADDRESS OF 199

KEY:

SWITCH IS IN THE UP

POSTION (ON)

SWITCH IS IN THE

DOWN POSTION (OFF)

END OF THE LINE SWITCHING AND

REPEATER GUIDELINES

METASYS MSTP NETWORK INSTALLATION DETAILS

Category Rules / Maximums Allowed

General Typically daisy-chained; branch or star configuration acceptable when repeaters are used. See End of Line Switching and Repeater Guideline graphic.

Number of Devices

When all of the devices connected on the FC Bus are Metasys FECs, VMAs, and/or IOMs, the device and bus segment limits are:

100 devices total per FC Bus (maximum) 3 bus segments per FC Bus (maximum) 50 devices per bus segment (maximum, not to exceed 100 devices per FC Bus) When one or more TEC26xx Series thermostat or third-party MS/TP device is connected on the FC Bus, the device and bus segment limits are:

64 devices total per FC Bus (maximum) 3 bus segments per FC Bus (maximum) 32 devices per bus segment (maximum, not to exceed 64 devices per FC Bus) Note: Metasys MS/TP devices generate less data traffic than third-party MS/TP devices and TEC26xx thermostats. Connecting third-party devices or TEC26xx thermostats to the FC Bus increases data traffic, reduces bus performance, and reduces the number of devices that can be connected to the bus.

Bus segments on an FC Bus are connected with repeaters (only). Up to two cascaded repeaters may be applied to an FC Bus (to connect three bus segments).

Line Length and Type

Cable 22 AWG stranded, 3-wire, twisted shielded cable

EOL Termination

End-of-Line (EOL) termination is required on the FC Bus to reduce signal reflection when data transmissions reach the end of a bus segment and bounce back. EOL termination is built into some Metasys FC devices and is enabled with a switch or jumper on the device.

EOL Termination on NAEs An EOL switch on an NAE enables EOL termination. For those NAEs with two FC Bus connections, two EOL double-pole switches are provided. Set the EOL switch to the ON (up) position to set the controller as an EOL termination device.

EOL Termination on Switch-Terminating Devices Some field controllers have an EOL switch or jumper. Such devices include FECs, IOMs, VMAs, ZFR1810s, and repeaters. Set the EOL termination to On for any of these devices when it is the last device on a bus segment.

EOL Termination on Devices Without EOL Provision For the devices such as TECs and third-party controllers in which no EOL provision is provided, install the MS-BACEOL-0 RS485 End-of-Line Terminator at the device if at the end of the bus segment.

EOL Termination Across the FC Bus The FC Bus may consist of up to three bus segments. Each bus segment on an FC Bus requires two EOL termination devices, one at each end of the bus segment. All other devices on the FC Bus should have their EOL termination disabled (EOL switches Off) . If only one device on an FC segment has an EOL termination, it must be set to On.

EOL on FC Bus Repeaters When using repeaters in the FC Bus, set the EOL jumpers based on the position of the repeater in the run.

When all of the devices connected on the FC Bus are Metasys FECs, VMAs, and/or IOMs, the cable length limits are:

Each bus segment can be up to 1520 m (5000 ft) in length (using 22 AWG 3-wire twisted, shielded cable).

Each FC Bus can be up to 4750 m (15,000 ft) in length (using 22 AWG 3-wire twisted, shielded cable).

When one or more TEC26xx Series thermostat or third-party MS/TP device is connected on the FC Bus, the device and bus segment limits are:

Each bus segment can be up to 1220 m (4000 ft) in length (using 22 AWG 3-wire twisted, shielded cable) Each FC Bus can be up to 3660 m (12,000 ft) in length (using 22 AWG 3-wire twisted, shielded cable).

When using fiber-optic connections: 2,010 m (6,600 ft.) between two fiber modems 22 AWG Stranded, 3-Wire Twisted, Shielded Cable

Open Plenum Installations. 38400+ Baud RS-485 Communication.

Typical Usage Anixter # Belden # AreapF/ftType

22/2pr Shielded Plenum

CBL-22/2P-SA-PVC

6541FE 33 0.033

31 0.0345541FE

CBL-22/2P-SA-PLN

EMT (Raceway) Installations. 38400+ Baud RS- 485 Communication.

22/2pr Shielded

PVC

RECOMMENDED MSTP SENSOR ACTUATOR BUS CABLE

Open Plenum Installations. 38400+ Baud RS-485 Communication.

Typical Usage Anixter # Belden # AreapF/ftType

22/3c Shielded Plenum

CBL-22/3-FC-PVC

6501FE 25 0.014

31 0.0155501FE

CBL-22/3-FC-PLN

EMT (Raceway) Installations. 38400+ Baud RS- 485 Communication.

22/3c Shielded

PVC

RECOMMENDED MSTP FIELD CONTROLLER BUS CABLE

+–S H

LD

R E

F A

Earth Ground

The shield should be earth grounded at one and only one point for the entire bus segment. (Preferably in the NAE Panel.) The shield screws on the controllers are simply a convenient way to continue the daisy chain of the bus. They are not attached to earth ground. You can use the shield terminal or twist together the shield and tape back at each controller.

SHIELD GROUNDING

The information in this document is not intended to replace the published Technical Product Literature for the Johnson Controls systems and products presented. The Installation Instructions that are packed with products, and the Technical Bulletins and Product Bulletins released with Johnson Controls systems and products supersede the information on this page. It is the responsibility of the product installer and product user to obtain and follow the product installation, operation, and safety procedures provided with the products or project specific information required by specification or local codes.

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

NET REFERENCE

2.1

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NUMBER

number

NET Ref1.vsd

REVISION

INFORMATION

04/02/18

02:08 PM

extra

DATE

TIME

FILE NAME

NET REF2

Bus and Cable Type Part Number O.D. Part Number O.D.

FC Bus: 22 AWG Stranded, Anixter: CBL-22/3-FC-PVC 0.138 in. Anixter: CBL-22/3-FC-PLN 0.140 in.

3-Wire Twisted Shielded Cable1 Belden®: B5501FE Belden: B6501FE

SA Bus (Terminal Block): Anixter: 0.209 in. Anixter: CBL-22/2P-SA-PLN 0.206 in.

22 AWG Stranded, 4-Wire, CBL-22/2P-SA-PVC Belden: B6541FE

2 Twisted-Pair Shielded Cable1 Belden: B5541FE SA Bus (Modular Jack)2: Anixter, Inc. preassembled: 0.15 in.

26 AWG Solid 6-Wire, CBL-NETWORK25 3 Twisted-Pair Cable CBL-NETWORK50

CBL-NETWORK75

CBL-NETWORK100

1 A 3-wire (for FC Bus) and 4-wire, 2 twisted-pair (for SA Bus), 22 AWG stranded, shielded cable is strongly recommended. 22 gauge cable offers the best performance for various baud rates, cable distances and number of trunk devices primarily due to lower conductor-to-conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable. Observe the shield grounding requirements.

2 26 AWG solid, 6-wire, (3 twisted pairs) cable is recommended as the best fit for fabricating modular cables with the modular jack housing assembly. Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire.

Non-Plenum Applications Plenum Applications Recommended Cable for FC Buses and SA Buses

SHIELD GROUNDING

Soft Ground Connection on FC Bus (Best)

Hard Ground - Shield

Isolate Shield Connections from Ground

Single Hard Ground Connection on FC Bus (Good)

F C B u s

Important: Only one hard ground point per bus segment

Address Value/ Address Range

Class Devices

0 Bus Supervisor FC Bus: NAE or NCE SA Bus: FECs and VMAs

1 Reserved Wireless Commissioning Converter

2 Reserved Reserved for future use.

3 Reserved DIS1710 Local Controller Display 4 - 127 Master Range FC Bus: FECs, VMAs, IOMs, and TEC26xx

SA Bus: IOMs Note: On applications using an NCE, the address value 4 is reserved for the NCE’s integral field controller.

128 - 254 Slave Range Slave devices, VSDs, and NS network sensors on the SA Bus

198 Reserved VAV Balancing Sensor (handheld) 199 Reserved Most NS Series Network Sensor models or VAV

Balancing Sensor (wall-mounted)

200 - 203 Reserved NS Series Network Sensors (specified models) 255 Broadcast Do not apply address 255 to any device.

MS/TP BUS ADDRESSING VALUES AND RANGES

NAE

Bus Segment 1520 m (5,000 ft) Maximum

50 Metasys Device Connections

T T T T T T

RR

R Repeater

T EOL Termination switch ON

Bus Segment 1520 m (5,000 ft) Maximum

50 Metasys Device Connections

Bus Segment 1520 m (5,000 ft) Maximum

50 Metasys Device Connections

Note: When TEC26xx Series thermostats or third-party MS/TP devices are connected to an FC Bus, a bus segment supports only up to 32 devices and the FC Bus supports only up to 64 devices.

4570 m (15,000 ft) Maximum 100 Total Metasys Device Connections (Maximum)

T

EOL switch set to ON BEST but Optional

10 Device Connections (Maximum) (No more than four can be NS Sensors)NCE, FEC, or VMA

(SA Bus Supervisor)

Side Jumper Instructions If at end-of-line, install both jumpers over Pins 1 and 2 (EOL In). Side A J1 and J2

If not at end-of-line, install both jumpers over Pins 2 and 3 (EOL Out).

If at end-of-line, install both jumpers over Pins 1 and 2 (EOL In). Side B J3 and J4

If not at end-of-line, install both jumpers over Pins 2 and 3 (EOL Out).

RECOMMENDED BUS CABLING

5 6 0 p F C a p a c i t o r 1000v Disc Type SF Electronics Part# 90156

MS/TP BUS ARCHITECTURE

NAE

VMA

FEC

IOM

FC FC FC

5 6 7

Network Sensor

Network Sensor

Network Sensor

SA Bus Connections and Addresses

FC Bus Connections and Addresses

Ethernet Network

Network Sensor

Network Sensor

FC Bus (Supervisor) Connection and Address

FC Bus Connections and Addresses

FC/SA BUS SPECIFICATIONS

Data Transmission Standard: RS-485 Signaling Method: BACnet MS/TP Signaling Rate: 38,400 baud (recommended)

FC BUS REPEATERFC BUS MAXIMUMS

SA BUS MAXIMUMS

6-PIN MODULAR RJ-12 PINOUT

SA+

SA-

SA Bus Com

SA Pwr (Tool)

SA Bus Com

SA Pwr (Sensor)

RJ-12

Modular

Plug

SA+

SA-

SA Bus Common

SA Power (Power to Tool*)

SA Bus Common

SA Power (Power to Network Sensor)

P in

N u m b e r

A ss ig n m e n t fo r

S tr a ig h t-th o u g h C a b le

RJ-12

Modular

Jack

P ri n te r C ir cu it B o a rd1

* Provides power from the Network Sensor SA Bus terminal block to a Wireless Commissioning Converter (MS-BTCVT-0) or handheld VAV balancing sensor connected to the modular jack.

EOL SWITCH

Only devices at the end of the line should have the EOL switch in the ON position.

Address 21 shown above

ADDRESS SWITCH

RS-485 SIDE A

AC INPUT

TX A

B

TX B

A

FA

UL

T B

S-

-3

-6

-1

-2

-4

-9

-1 9.

2K

-3 8.

4K

BA

UD

RA

TE

RS-485 SIDE B

TB1

TB2

TB3

FA

UL

T A

PO

W

ER

Wire Purpose Standard Color Application N2 or FC Bus Blue All Installations SA Bus Brow n All Installations

Analog Input Cable Yellow When Required

Analog Output Cable Tan When Required

Binary Input Cable Orange When Required

Binary Output Cable Violet When Required N1 Bus. Ethernet - Cat 5 or Coax Purple When Required 24VAC Cable Gray When Required

Spare White When Required Lon Pink When Required

METASYS CABLE JACKET COLOR STANDARDS

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

NET REFERENCE

2.2

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NET REF3

A-306

EXTERIOR WALL

L H

DPT

SD-01

INTERIOR WALL

RPS

DETAIL I100 BUILDING PRESSURE

INSTALLATION DETAIL

ROOM STATIC PRESSURE SENSORS: (RPS)

MODEL RPS IS A STAINLESS STEEL ROOM STATIC PRESSURE

SENSOR. IT MOUNTS DIRECTLY TO THE WALL OR TO A CEILING USING

A STANDARD ELECTRICAL BOX.

SURGE DAMPENER: (SD-01)

SURGE DAMPENERS ABSORB RAPID PRESSURE FLUCTUATIONS IN

ORDER TO STEADY A PRESSURE SIGNAL. EACH SURGE DAMPENER

HAS TWO INDEPENDENT CHANNELS – ONE FOR THE LOW-PRESSURE

TUBING AND ONE FOR THE HIGH-PRESSURE TUBING.

OUTDOOR STATIC PRESSURE SENSOR: (A-306)

THE A-306 OUTDOOR STATIC PRESSURE SENSOR PROVIDES AN

OUTDOOR PRESSURE SIGNAL FOR REFERENCE IN BUILDING

PRESSURIZATION APPLICATIONS. THE A-306 INCLUDES THE SENSOR,

50' (15.24M) OF VINYL TUBING, MOUNTING BRACKET, AND HARDWARE.

DIFFERENTIAL PRESSURE TRANSMITTER: (DPT)

PRESSURE TRANSDUCERS SENSE DIFFERENTIAL OR GAUGE (STATIC)

PRESSURE AND CONVERT THIS PRESSURE DIFFERENCE TO A

PROPORTIONAL ELECTRICAL OUTPUT FOR EITHER UNIDIRECTIONAL

OR BIDIRECTIONAL PRESSURE RANGES.

1. ROTATE THE DAMPER BLADE(S) TO THE DESIRED

POSITION IF THE POWER IS LOST. TO ENSURE A TIGHT SEAL,

INSERT THE MANUAL OVERRIDE CRANK AND TURN IT IN THE

DIRECTION INDICATED BY THE ARROW ON THE LABEL 5

TURNS; THE POSITION INDICATOR SHOULD BE NEAR THE 0°

POSITION ON THE SCALE. QUICKLY ROTATE THE MANUAL

OVERRIDE CRANK A HALF TURN IN THE OPPOSITE

DIRECTION TO TEMPORARILY LOCK THE ACTUATOR HUB IN

PLACE.

2. EVENLY HAND TIGHTEN EACH CLAMP NUT ONTO THE

U-BOLT, KEEPING THE ACTUATOR FLAT. SECURE THE U-

BOLT TO THE DAMPER SHAFT AND TIGHTEN TO A TORQUE

OF 100 TO 125 LB⋅IN (11 TO 14 N⋅M).

3. TO RELEASE THE SPRING, TURN THE MANUAL OVERRIDE

CRANK IN THE DIRECTION INDICATED ON THE LABEL; THE

ACTUATOR SPRING RETURNS TO ITS STARTING POSITION. IF

THIS STEP IS OMITTED, THE SPRING RELEASES

AUTOMATICALLY WHEN POWER IS APPLIED TO THE

ACTUATOR.

4. REMOVE THE MANUAL OVERRIDE CRANK AND STORE IT IN

AN UNUSED MOUNTING HOLE.

5. APPLY POWER LONG ENOUGH FOR THE ACTUATOR TO

TRAVEL A FULL STROKE, AND VERIFY THAT THE ACTUATOR

ROTATES FREELY THROUGHOUT THE RANGE.

NOTE: IF ELECTRIC POWER IS NOT AVAILABLE, COMPLETE

THIS VERIFICATION BY REINSERTING THE MANUAL

OVERRIDE CRANK AND TURNING IT IN THE DIRECTION

INDICATED TO ROTATE THE COUPLER TO THE FULLY OPEN

POSITION.

DETAIL I101 DAMPER PRE-LOADING

INSTRUCTIONS

DETAIL I102 LOW LIMIT INSTALLATION

A70

DUCT CROSS-SECTION

LOCATE THE LOW LIMIT DEVICE AT

THE HIGHEST POINT

(1 SENSOR PER 20 SQ.FT COIL AREA)

USE CAPILLARY

MOUNTING CLIPS AS

NEEDED; DO NOT KINK

CAPILLARY.

ELEMENT MUST BE

MOUNTED WITH A

CONTINUOUS DECLINE

SLEEVE PENETRATIONS

WITH ¼” POLY OR

BUSHING

FINAL PASS MUST BE

WITHIN 6" OF COIL

BOTTOM.

IMPORTANT

EACH TURN MUST

BE WITHIN 6" OF

COIL EDGE. 12" - 16"

SECURE ELEMENT

AT END AND EVERY

2' - 3' ALONG

ELEMENT WITH ¼”

POLY AND TIE WRAP.

MOUNTING MATERIAL (KELE)

M-648 CAP. MTG. CLIP 1/8" MAX

CC-1G CAP. MTG. CLIP 3/8" MAX

M-633 MID DUCT SUPPORT MTG.

DETAIL I103 FILTER DP MOUNTING DETAIL

AIR

FLOW

HIGH LOW

PRESSURE

SENSOR OR

SWITCH

FILTER

AIR

FLOW

MOUNTING PROBES (JCI)

FTG18A-600R REMOTE MTD PROBE (1 PER SWITCH)

21118 6IN STATIC PRESS PROBE (2 PER SENSOR)

PROBE

DETAIL I104 AVERAGING ELEMENT

INSTALLATION

DUCT CROSS-SECTION

USE AVERAGING

ELEMENT HOLDERS AT

ALL END TURNS

(KELE CC-1G OR

JCI TE-6008-1)

SECURE ELEMENT AT END AND EVERY 2' - 3'

ALONG ELEMENT WITH ¼” POLY AND TIE WRAP.

TE

SA+

SA-

SA Bus Common

SA Power (Power to Tool*)

SA Bus Common

SA Power (Power to Network Sensor)

Pin Number Assignment for Straight-though Cable

RJ-12

Modular

Jack

P ri n te r C ir cu it B o a rd

(Power to Tool*) - Provides power from the Network Sensor SA Bus to a Wireless Commissioning Converter (MS-BTCVT-0) or VAV balancing sensor connected to the modular jack.

DETAIL I108 6-PIN MODULAR RJ-12 PINOUT

DETAIL I106A FC/SA BUS TERMINAL BLOCK

WIRING INSTALLATION DETAIL

MATERIAL (ANIXTER)

CBL-22/3-FC-PVC – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, NON-PLENUM

CBL-22/3-FC-PLN – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, PLENUM

FC BUS WITH HARD GROUND AT NAE, SHIELD TO ISOLATED TB

FC BUS WITH SOFT GROUND, SHIELD TO CAPACITOR

MATERIAL (ANIXTER)

CBL-22/3-FC-PVC – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, NON-PLENUM

CBL-22/3-FC-PLN – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, PLENUM

MATERIAL (SF ELECTRONICS)

90156 – 1000V, DISK TYPE, 560PF CAPACITOR

SA BUS WITH HARD GROUND AT FEC/NCE, SHIELD

ISOLATED TO WIRE NUT

NAE

FEC

VMA

IOM

TEC

NAE

FEC

VMA

IOM

TEC

NCE

FEC

VMA

IOM

MATERIAL (ANIXTER)

CBL-22/2P-SA-PVC – 22 AWG STRANDED, 4-WIRE, 2 TWISTED-PAIR SHIELDED CABLE, NON-PLENUM CBL-22/2P-SA-PLN – 22 AWG STRANDED, 4-WIRE, 2 TWISTED PAIR SHIELDED CABLE, PLENUM

TO NEXT

DEVICE

FROM LAST

DEVICE

FC

FC

F C

B U

S

SHLD

COM

SHD

SHD

WHT

BLK

BLU

BLU

BLU

BLU

WHT

BLK

TO NEXT

DEVICE

FROM LAST

DEVICE

FC

FC

F C

B U

S

SHLD

COM

BLK

BLK

WHT

WHT

BLU

BLU

BLU

BLU

TO NEXT

DEVICE

FROM LAST

DEVICE

BRN

SA

SA

SA PWR

COM

BRN

S A

B U

S

RED

WHT

BLK

BLU

RED

WHT

BLK

BLU

Anixter

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

NET REFERENCE

2.3

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NUMBER

number

NET Ref3.vsd

REVISION

INFORMATION

04/02/18

02:08 PM

extra

DATE

TIME

TABLE 1

USAGE ANIXTER DESCRIPTION BLACK WHITE

JACKET

COLOR RED ANIXTER DESCRIPTION BLACK WHITE

JACKET

COLOR RED DRAIN COMMENTS

AI CBL-18/2YEL-PLN 18/2 Shld Yellow AI Com ---------- AI ---------- CBL-22/2-NS-PVC 22/2 Non-Shld AI Com AI ---------- ---------- TABLE 2

AI CBL-18/3YEL-PLN 18/3 Shld Yellow AI Com Pow er AI ---------- CBL-22/3-NS-PVC 22/3 Non-Shld AI Com Pow er ---------- AI TABLE 2

AO CBL-18/2TAN-PLN 18/2 Shld Tan AO Com ---------- AO ---------- CBL-22/2-NS-PVC 22/2 Non-Shld AO Com AO ---------- ---------- TABLE 2

AO CBL-18/3TAN-PLN 18/3 Shld Tan AO Com Pow er AO ---------- CBL-22/3-NS-PVC 22/3 Non-Shld AO Com Pow er ---------- AO TABLE 2

BI CBL-18/2ORG-PLN 18/2 Shld Orange BI 24V ---------- BI ---------- CBL-22/2-NS-PVC 22/2 Non-Shld BI 24V BI ---------- ---------- TABLE 2

BO CBL-18/2VLT-PLN 18/2 Shld Violet BO Com ---------- BO ---------- CBL-22/2-NS-PVC 22/2 Non-Shld BO Com BO ---------- ---------- TABLE 2

BO CBL-18/3VLT-PLN 18/3 Shld Violet BO Com BO BO ---------- CBL-22/3-NS-PVC 22/3 Non-Shld BO Com BO ---------- BO TABLE 2

GENERAL PURPOSE CBL-18/2NAT-PLN 18/2 Shld Natural Common Pow er ---------- ---------- CBL-22/2-NS-PVC 22/2 Non-Shld Common Pow er ---------- ---------- ----------

GENERAL PURPOSE CBL-18/3NAT-PLN 18/3 Shld Natural Common Pow er ---------- Signal CBL-22/3-NS-PVC 22/3 Non-Shld Common Pow er ---------- Signal ----------

METASTAT CBL-24/8NAT-PLN 24/8 Natural ---------- ---------- ---------- ---------- CM-00424BBG-3 24/8 Natural ---------- ---------- ---------- ---------- ---------- SEE TABLES 4, 5, & 6

METASTAT PHONE JACK CBL-STAT25 Pre-Term'd Blue ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- SEE TABLES 4, 5, & 6, NOTE #4

24VAC CBL-18/2GRY-PLN 18/2 Shld Gray 24 V Com ---------- 24 VAC ---------- CBL-18/2-NS-PVC 18/2 Non-Shld Gray 24 V Com 24 VAC ---------- ---------- ----------

24VAC POWER BUS AL-1402C-2-2N-01 14/2 Non-Shld White Common ---------- ---------- 24 VAC ---------- ---------- ---------- ---------- ---------- ---------- ----------

600 V B8248 18/2 ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------

600 V B83336 18/3 ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------

N2 BUS CBL-18/3BLU-PLN 18/3 Shld Blue N2- REF N2+ ---------- CBL-22/3BLU-NS-PVC 22/3 Non-Shld Blue N2- REF N2+ ---------- TABLE 3

N1 BUS-ARCNET CBL-RG62PUR-PLN RG62 Purple ---------- ---------- ---------- ---------- CBL-RG62PUR-PVC RG62 Purple ---------- ---------- ---------- ---------- ----------

N1 BUS-ETHERNET CMP-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- CM-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- ---------- SEE TABLES 7 & 8

BACNET BUS CMP-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- CM-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- ---------- SEE TABLES 7 & 8

LON BUS 9J2201544 22/2 Shld Blue ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------

NT BUS CBL-PLN2204-91 22/4 Shld White ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------

XT BUS CBL-18/3BLU-PLN 18/3 Shld Blue XT- REF XT+ ---------- CBL-22/3BLU-NS-PVC 22/3 Non-Shld Blue XT- REF XT+ ---------- ----------

BACNET MS/TP FC BUS CBL-22/3-FC-PLN 22/3 Shld Blue FC- COM FC+ ---------- CBL-22/3-FC-PVC 22/3 Shld Blue FC- COM FC+ ---------- TABLE 3

BACNET MS/TP SA BUS CBL-22/2P-SA-PLN 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (RED) PWR (WHITE) CBL-22/2P-SA-PVC 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (RED) PWR (WHITE) TABLE 3 TERMINAL BLOCK

BACNET MS/TP SA BUS CBL-NETWORKxxx 26/6 Preassembled ---------- ---------- ---------- ---------- CBL-NETWORKxxx 26/6 Preassembled ---------- ---------- ---------- ---------- TABLE 3 MODULAR JACK, 26AWG IS ACCEPTABLE

PLENUM PART NUMBER NON-PLENUM PART NUMBER

COLOR CODED CABLE NON-COLOR CODED CABLE

CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR

NET REF4

123456

SA BUS PORT

MODULAR

JACK

TABLE 4 PHONE JACK PIN DESIGNATIONS

PHONE JACK

PIN NO. SIGNAL DESIGNATION COLOR

1 SA BUS (+) WHT / GRN

2 SA BUS (-) WHT / ORG

SA BUS COMMON (POWER FROM

SENSOR TO TOOL)

BLU / WHT

SA POWER (POWER TO SENSOR FROM

TOOL)

WHT / BLU

SA BUS COMMON (POWER FROM BUS TO

NETWORK SENSOR)

ORG / WHT

SA POWER (POWER FROM BUS TO

NETWORK SENSOR)

GRN / WHT

TABLE 5 TERMINAL BLOCK WIRING

TERMINAL NO. SIGNAL DESIGNATION COLOR

1 SA BUS (+) BROWN

2 SA BUS (-) BLACK

3 SA BUS COMMON WHITE

4 SA BUS POWER RED

5 15 VDC POWER (VMA) 24 VAC POWER (AHU, UNT, VAV)WHT / GRN

COMMON FOR POWER, ZONE BUS, OR

MANUAL OVERRIDE AND LED

GRN / WHT

NOTE: DO NOT USE CROSSOVER CABLES ON THE SA BUS

NS SERIES SENSOR

(DIP SWITCH SHOWN IN

DEFAULT POSITION)

NS-xTN7003-0 SERIES

ON

1 2

KEY:

SWITCH IS IN THE UP

POSTION (ON)

SWITCH IS IN THE

DOWN POSTION (OFF)

ADDRESS SWITCH 2 SWITCH 1

199 N/A N/A

200 OFF OFF

201 OFF ON

202 ON OFF

203 ON ON

NS SERIES SENSOR DEVICE ADDRESS

NOTE: NON-ADDRESSABLE NS SERIES

SENSORS HAVE A FIXED ADDRESS OF

8 7 6 5 4 3 2 1

CAT 5 OR

METASTAT

CABLE

END VIEW OF 8-PIN PLUG

TAB DOWN

TABLE 7 STANDARD EIA/TIA T568B

PIN NO. COLOR

1 WHT / ORN

2 ORN / WHT

3 WHT / GRN

4 BLU / WHT

5 WHT / BLU

6 GRN / WHT

7 WHT / BRN

8 BRN / WHT

TABLE 8 STANDARD EIA/TIA T568B

PIN NO. COLOR

1 WHT / GRN

2 GRN / WHT

3 WHT / ORN

4 BLU / WHT

5 WHT / BLU

6 ORN / WHT

7 WHT / BRN

8 BRN / WHT

NOTE: A CROSSOVER CABLE HAS ONE

END CONFIGURED AS A CROSSOVER

CABLE AND THE OPPOSITE END

CONFIGURED AS A PATCH CABLE.

NOTE: A PATCH CABLE HAS BOTH

ENDS CONFIGURED AS A PATCH CABLE.

ETHERNET PATCH CABLE

ETHERNET CROSSOVER CABLE

ON

EOL SWITCH = ON

EOL TERMINATION FOR THE MS/TP BUS

NOTE:

END-OF-LINE TERMINATION IS REQUIRED

ON ALL FC AND SA BUSES

NOTE:

REFER TO THE MS/TP COMMUNICATIONS

BUS TECHNICAL BULLETIN (LIT-12011034)

FOR EOL TERMINATION GUIDELINES

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

NET REFERENCE

2.4

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

COMMUNICATION BUS

2.5

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NOTE:

1. NAE-01 WILL BE USED AS BACNET INTEGRATION TO TRIDIUM HEAD END.

2. COMMUNICATION TRUNK IS SHOWN SCHEMATICALLY. ACTUAL RUN WILL VARY, AND JCI INSTALLER TO

DOCUMENT ACTUAL COMMUNICATION BUS INSTALL FOR RECORD PURPOSES

3. COMMUNICATION TRUNK FOR VFD AND THIRD PARTY EQUIPMENT PROVIDED BY OTHERS.

+–S H

LD

R E

F A

Earth Ground

If a shield is used, it should be earth grounded at one and only one point for the entire bus segment.

(Preferably in the NAE Panel.) The shield screws on the controllers are simply a convenient way to continue the daisy chain of the bus. They are not attached to earth ground.

SHIELD GROUNDING

NUMBER

number trunk.vsd

REVISION

INFORMATION

04/02/18

05:37 PM

extra

DATE

TIME

FILE NAME

1ST FLOOR

PANEL: P-1 BOILER ROOM 113

FEC

ADD.034

HWS

IOM2721

ADD.004

HWP-4 & 5 VFD

QTY=2

VFD

ADD.006-007

VMA

ADD.008-021

V-x

QTY=14

VMA

ADD.022,024-033

VAV-xxx

QTY=10

T

SET

EOL ON

FC-1 BUS

MS/TP

3/22 TWS

HUB OR SWITCH

N1 ETHERNET

CAT 5

IP DROP BY

OWNER

FC-1 BUS

MS/TP

3/22 TWS

RTU-2RTU-2

ADD.023

RTU-2 CONTROL PANEL

QTY=1

FC-1 BUS

MS/TP

3/22 TWS

FC-1 BUS

MS/TP

3/22 TWS

FC-1 BUS

MS/TP

3/22 TWS

HWS

FC-1 BUS

MS/TP

3/22 TWS

BOILERBOILER(B-X)

BOILER

CONTROL PANEL

QTY=3

MODBUS

RTU

UPS

QTY=1

UPS

ADD.005

FC-1 BUS

MS/TP

3/22 TWS

NOTE : FACILITY TO PROVIDE DEDICATED DATA DROP TO EACH BAC-IP DEVICE

RTU-1RTU-1

ADD.04

RTU-1 CONTROL PANEL

QTY=1

FC-1 BUS

MS/TP

3/22 TWS

1 Revision as per CB 7N03-0223-001 9/12/2017 CoEE

SUPERVISORY

CONTROLLER (JACE)

PROVIDED BY OTHERS

2 Record Drawing 4/2/2018 CoEE

BLR3-EN

HWS

HWR

SHWR-T

B-1

B-2

B-3

BOILER 1 CONTROL

CABINET

BLR2-EN

BOILER 2 CONTROL

CABINET

BOILER 3 CONTROL

CABINET

P-5

P-4

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

HWS FLOW

3.1

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NUMBER

number hws-f.vsd

REVISION

INFORMATION

04/02/18

09:55 AM

extra

DATE

TIME

FILE NAME

OA-T

TAG: P-1

GPM: 19

HP: 1/6

V/PH: 115/1/60

LOCATED IN HALL 117

NOTE: SEE MANUFACTURER'S WIRING DIAGRAM FOR

COMPLETE WIRING DETAILS. DO NOT TERMINATE

MS/TP REFERENCE TO DRIVE. WIRE NUT REFERENCE

TO CONTINUE TO THE NEXT DEVICE.

PUMP P-4 & P-5 VFD WIRING

TYPICAL OF 2

0-10 VDC+

Px-O

COM

Px-C

N

P

COM

DANFOSS VLT

+24 VDC

X1

GND

DIN

DI1 START/STOP

X2

BYPASS CONTROL BOARD

12 +24 VDC

MS/TP+

MS/TP-

REF

SHLD

FC BUS

CS-x

SYS

RUNNING

Px-S

Px-C

TAG: P-3

GPM: 19

HP: 1/6

V/PH: 115/1/60

TAG: P-4

GPM: 50

HP: 1.5

V/PH: 208/3/60

TAG: P-2

GPM: 19

HP: 1/6

V/PH: 115/1/60

TAG: P-5

GPM: 50

HP: 1.5

V/PH: 208/3/60

VSD

VSD

Hot Water Boiler and Heating Pumps

A. The hot water will maintain the secondary loop temperature at 140°F (adjustable). The boiler con trol will not energize until the outside air temperature is at or below 65°F.

B. New Boiler will be provided with BAS Control interface. Manufacturer internal control will control firing rate and safeties.

Heating Water Pumps:

A. Pump P-4 & P-5 will be interlocked with boiler operation. The pump will very speed to maintain differential pressure between the supply and return piping.

BILL OF MATERIALS

Designation Qty Part Number Description Field Devices:

BLRx-EN 3 RIBU1S SPST,10A,HC=10-30 VAC/DC,W/LED,W/OVRD

HW-DP 1 231G-MS2-5V-D 10-100 PSI W/DISPLAY 5V MANIFOLD

Px-C,-CS-x 2 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY

SHWR-T 1 TE-6300W-101 T-WELL 6" BRASS DIR MNT

1 TE-631AM-2 WELL TEMP SEN 6" 1K NI

SHWS-T 1 TE-6300W-101 T-WELL 6" BRASS DIR MNT

1 TE-631AM-2 WELL TEMP SEN 6" 1K NI

NOTES:

1. MANUFACTURER INTERNAL CONTROL WILL CONTROL FIRING AND SAFETIES.

2. JCI WILL TIE IN THE FACTORY PACKAGED BOILER CONTROLLER TO DDC SYSTEM.

3. BOILER INLINE PUMPS ARE CONTROLLED BY BOILER INTERNAL CONTROLS.

4. ALL THE BOILER POINTS WILL BE MONITORED THROUGH MODBUS RTU.

B-x CONTOL PANEL

BACNET INTEGRATION

OA-T

W/ UNIT

EXISTING

CONTROL

BLR1-EN

SHWS-T

BOILER PUMP WIRING DIAGRAM

TYPICAL OF 3

120 VAC BOILER PUMP

P-x

BOILER

TERMINALS

L

H

V-1

V-3

V-4

HW-DP

VENT

VENT

PSIG mA 0 4 20 20

HWR

RANGE SELECTION SWITCH SETTING

FOR HW-DP

MS2 100

A

B

C

D

RANGES

A B C D

S.NO POINT NAME

BACnet

OBJECT

TYPE

BACnet

OBJECT ID

1 Boiler Supply Temperature AI 1

2 Firing Rate AV 1

3 Heating Loop Setpoint AV 8

4 Boiler Pump Status BV 2

5 Boiler Pump Control BV 16

6 Outdoor Temperature AI 6

7 Boiler 1 Status MV 19

8 Boiler 2 Status MV 20

9 Boiler 3 Status MV 21

10 Boiler Alarm BV 6

BOILER POINTS THROUGH MODBUS RTU

2 Record Drawing 4/2/2018 CoEE

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

PANEL P-1

3.2

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NUMBER

number p-1.vsd

REVISION

INFORMATION

04/02/18

05:38 PM

extra

DATE

TIME

FILE NAME

BILL OF MATERIALS

Designation Qty Part Number Description Field Devices:

TXP-1 1 PSH300AB10-LVC POWER SUPPLY HILO LVC 100VAx3 120 to 24VAC UPS 1 PSH550-UPS-BC ENCLOSED BACnet 550 VA UPS Panel Devices:

ES-1 1 ESW105 DIN-RAIL ETHERNET SWITCH

FEC-4 1 MS-FEC2621-0 FEC2621-1,FEC 17

IOM 1 MS-IOM2721-0 MS-IOM2721-0, IN/OUTPUT

P-1 1 PAN-ENC2436WDP 24X36X9,PERF-SUB,W/ DOOR,NEMA 1,UL 50

PS-1 1 PSM24A24DAS PWR SPLY ISOL DC,24VAC- 24VDC TRACK

TAG-x 2 NAMETAG-CUSTOM 1" X 3" TAG, 3-LINES MAX CUSTOM PNL FACE

TB-1 2 BAM2 END STOP - KELE

1 FEM6 END SECTION - KELE

7 M4/6 LOW VOLTAGE TERMINAL - KELE

TB-2 2 BAM2 END STOP - KELE

1 BJS6-5 JUMPER BAR FOR M4/6, FIVE POLES PER BAR

1 EV-6 JUMPER BAR HARDWARE

1 FEM6 END SECTION - KELE

6 M4/6 LOW VOLTAGE TERMINAL - KELE

4 SCF6 CIRCUIT SEPARATOR

NAMETAG SCHEDULE

ITEM DESCRIPTION

TAG-1 PANEL P-1

HWS SYSTEM

JCI # 7N03-0223

PANEL INFORMATION

LOCATED: BOILER ROOM 113

POWERED FROM: PANEL ?, CIRCUIT ?

TAG-2 PANEL TXP-1

24VAC POWER

JCI # 7N03-0223

LOCATED: BOILER ROOM 113

POWERED FROM: PANEL ?, CIRCUIT ?

36.00in.

24.00in.

24v ONLY

TXP-1

PSH300AB10-LVC

TAG-2

PANEL P-1

1- 1/

2" W

IR

E

D U

C T

P

N E

U M

A T

IC

H

IG

H V

O

LT

A G

E )Terminal End Stop

Terminal End Stop

Terminal End Stop

SHLD

MS/TP + OUT

MS/TP - OUT

COM OUT

Terminal End Stop

MS/TP + IN

MS/TP - IN

COM IN

FE

C

FEC2621

PS-1

1-1/2" WIRE DUCT

E S

-1

1-1/2" WIRE DUCT

1-1/2" WIRE DUCT

TAG-1

F A U L T

B U S

I O M

C O M

IOM2721

1-1/2" WIRE DUCT

UPS

120 VAC

2 Record Drawing 4/2/2018 CoEE

JACE

PROVIDED BY OTHERS

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

PANEL P-1 WIRING

3.3

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

NUMBER

number p-1 pw.vsd

REVISION

INFORMATION

04/02/18

05:38 PM

extra

DATE

TIME

FILE NAME

Pneumatic Tubing

Cable

Low Voltage Terminal

Wired by JCI

Field Wiring

High Voltage Terminal

Wiring Legend

VAC

Power

INSTALLATION NOTE:

WIRE 120v TO PSH300AB10-LVC TRANSFORMER(TXP-1). NO 120v

POWER CAN BE PRESENT INSIDE OF P-1

H COM

SW-1

1 3

2 4

CK-1 CK-2 CK-3

120 VAC

PSH300AB10-LVC

IOM-4

HOT COM

2 4

LOW VOLTAGE WIRING DIAGRAM FOR CONTROLLER

PSH300AB10-LVC

(POWERED BY TXP-1 / CK-2 100VA)

FEC-4

HOT COM

PS-1

VOLTAGE INPUT

24VAC

IN#

INCOM#

HW-DP

TB-1

TB-2

FEC-4, UI-1

PS-1

HOT COM

24V COM

PWR-1

24 VAC

ES-1

HOT COM1 3

LOW VOLTAGE WIRING DIAGRAM FOR CONTROLLER

PSH300AB10-LVC

(POWERED BY PSH300AB10-LVC/TXP-1/CK-1 100VA)

HWS

FEC 2621

COM

PWR

SA ADDR. 4

IOM 2721

COM

PWR

COM

SHD

FC +

FC -

R E

D

B

LU

B

LK

W H

T

SA BUS DETAIL

COM

JACE

HOT COM

2 Record Drawing 4/2/2018 CoEE

Site Director ID 4/2/2018Waukesha County Communication Center

Electrician/Fitter Point Information Controller Information Panel Information Intermediate Device Field Device

Tag Point Type System Name Object Name Expanded ID

Controller Details

Trunk Type

Trunk Nbr Trunk Addr.

Cable Destination Bay/Terminal

Termination Out Panel Panel Location Reference Drawing

Panel-x-Cable Destination

Bay/Terminal

Wiring /Tubing

Termination In Device Termination Out Wiring /Tubing

Termination In Device Ref Detail

Shape Comment Template

FEC 2621 Power to Controller FEC 2621 MS/TP 1 4 P-1 BOILER ROOM 113 BacNet FC Bus

UI IN-1 HWS HW-DP Hot Water Differential Pressure FEC 2621 MS/TP 1 4 UI IN-1 IN1, +15V P-1 BOILER ROOM 113 1-4-UI IN-1 2/22 -, + DPT2xxx (mA) F106 UI IN-2 HWS SHWR-T Secondary HW Return Temperature FEC 2621 MS/TP 1 4 UI IN-2 IN2, ICOM2 P-1 BOILER ROOM 113 1-4-UI IN-2 2/22 2-Wire TE F131 UI IN-3 HWS SHWS-T Secondary HW Supply Temperature FEC 2621 MS/TP 1 4 UI IN-3 IN3, ICOM3 P-1 BOILER ROOM 113 1-4-UI IN-3 2/22 2-Wire TE F131 UI IN-4 MSDET-D RA-H Return Air Humidity FEC 2621 MS/TP 1 4 UI IN-4 IN4, ICOM4, +15V P-1 BOILER ROOM 113 1-4-UI IN-4 3/22 OUT,GND,PWR HE-6700(Duct Mnt) - HE F153

UI IN-5 FEC 2621 MS/TP 1 4 UI IN-5 P-1 BOILER ROOM 113 1-4-UI IN-5

UI IN-6 FEC 2621 MS/TP 1 4 UI IN-6 P-1 BOILER ROOM 113 1-4-UI IN-6

BI IN-7 HWS P5-S HW Pump 5 Status FEC 2621 MS/TP 1 4 BI IN-7 IN7, ICOM7 P-1 BOILER ROOM 113 1-4-BI IN-7 2/22 OUT, COM Current Relay Motor Lead 2/22 See wiring detail Dry Contact F301 BI IN-8 HWS P4-S HW Pump 4 Status FEC 2621 MS/TP 1 4 BI IN-8 IN8, ICOM8 P-1 BOILER ROOM 113 1-4-BI IN-8 2/22 See wiring detail Dry Contact F301 BO OUT-1 HWS BLR3-EN Boiler 3 Enable FEC 2621 MS/TP 1 4 BO OUT-1 OUT1, 24V COM P-1 BOILER ROOM 113 1-4-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501 BO OUT-2 HWS BLR2-EN Boiler 2 Enable FEC 2621 MS/TP 1 4 BO OUT-2 OUT2, 24V COM P-1 BOILER ROOM 113 1-4-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501 BO OUT-3 HWS P4-C HW Pump 4 Command FEC 2621 MS/TP 1 4 BO OUT-3 OUT3, 24V COM P-1 BOILER ROOM 113 1-4-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501 CO OUT-4 HWS P5-C HW Pump 5 Command FEC 2621 MS/TP 1 4 CO OUT-4 OUT4, 24V COM P-1 BOILER ROOM 113 1-4-CO OUT-4 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F901 CO OUT-5 HWS BLR1-EN Boiler 1 Enable FEC 2621 MS/TP 1 4 CO OUT-5 OUT5, 24V COM P-1 BOILER ROOM 113 1-4-CO OUT-5 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F901

CO OUT-6 FEC 2621 MS/TP 1 4 CO OUT-6 P-1 BOILER ROOM 113 1-4-CO OUT-6

CO OUT-7 FEC 2621 MS/TP 1 4 CO OUT-7 P-1 BOILER ROOM 113 1-4-CO OUT-7

AO OUT-8 HWS P4-O HW Pump 4 Output FEC 2621 MS/TP 1 4 AO OUT-8 OUT8, OCOM8 P-1 BOILER ROOM 113 1-4-AO OUT-8 2/22 See VFD Detail VFD Speed Control (Vdc) AO OUT-9 HWS P5-O HW Pump 5 Output FEC 2621 MS/TP 1 4 AO OUT-9 OUT9, OCOM9 P-1 BOILER ROOM 113 1-4-AO OUT-9 2/22 See VFD Detail VFD Speed Control (Vdc)

IOM 2721 P-1 BOILER ROOM 113 Power to Controller IOM 2721 SA Bus 1 4 P-1 BOILER ROOM 113 BacNet SA Bus 1,0

UI IN-1 MSDET-D H1-A Humidifier Alarm IOM 2721 SA Bus 1 4 UI IN-1 IN1, ICOM1 P-1 BOILER ROOM 113 4-1-4-UI IN-1 2/22 See wiring detail Dry Contact F301 UI IN-2 HWS P4-A HW Pump 4 VFD Fault IOM 2721 SA Bus 1 4 UI IN-2 IN2, ICOM2 P-1 BOILER ROOM 113 4-1-4-UI IN-2 2/22 See VFD Detail VFD Fault UI IN-3 HWS P5-A HW Pump 5 VFD Fault IOM 2721 SA Bus 1 4 UI IN-3 IN3, ICOM3 P-1 BOILER ROOM 113 4-1-4-UI IN-3 2/22 See VFD Detail VFD Fault UI IN-4 IOM 2721 SA Bus 1 4 UI IN-4 P-1 BOILER ROOM 113 4-1-4-UI IN-4 UI IN-5 IOM 2721 SA Bus 1 4 UI IN-5 P-1 BOILER ROOM 113 4-1-4-UI IN-5 UI IN-6 IOM 2721 SA Bus 1 4 UI IN-6 P-1 BOILER ROOM 113 4-1-4-UI IN-6 UI IN-7 IOM 2721 SA Bus 1 4 UI IN-7 P-1 BOILER ROOM 113 4-1-4-UI IN-7 UI IN-8 IOM 2721 SA Bus 1 4 UI IN-8 P-1 BOILER ROOM 113 4-1-4-UI IN-8 AO OUT-1 IOM 2721 SA Bus 1 4 AO OUT-1 P-1 BOILER ROOM 113 4-1-4-AO OUT-1 AO OUT-2 IOM 2721 SA Bus 1 4 AO OUT-2 P-1 BOILER ROOM 113 4-1-4-AO OUT-2

Rev-2; Record Drawing; CoEE; 4/2/2018

7N03-0223 NAE-01-PS-1HWS Point Schedule

PFILT-DP

EA

DA

RA

VSD

TS-1

NO

D-2

RAD-O

MA-T

7N03-0223

Drawing Title

CoEEMPKJW

Johnson Controls, Inc.

12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775

REFERENCE DRAWING

RTU-1 FLOW

4.1

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Waukesha County Communication Center

1621 Woodburn Road Waukesha WI, 53188

RA-SD

SA-F

(WITH AHU)

NUMBER

number rtu-1-f.vsd

REVISION

INFORMATION

04/02/18

09:56 AM

extra

DATE

TIME

FILE NAME

SET @ 32 Deg. F

RA-T

FACM-A

BY OTHERS

OA

N C

D-1

OAD-O

DA-T

N C

D-3

RLFD-O

PH1-C

PH2-C

GAS

C

RA-H

DX

C

CONDESING

UNIT

RS RL

SS-SW

BY OTHERS

SR-SW

BY OTHERS

TS-1

PACKAGED UNIT

NOTES:

1. ALL CONTROLS COMPONENTS WILL BE PROVIDED BY THE…