ex. f - Comm center - control drawings.PDF
PDF 1 MB Posted
- Attached to
- 2025 BAS Upgrades
- Solicitation number
- PW-2025115-0-2025/JH
- Issued by
- Waukesha County, Wisconsin
About this file
This document is a detailed set of control system and mechanical drawings for the Waukesha County Communication Center project, prepared by Johnson Controls, Inc. The comprehensive drawings cover the building's environmental control systems, including heating, ventilation, air conditioning (HVAC), and building automation systems (BAS) for a facility located at 1621 Woodburn Road in Waukesha, Wisconsin. The project involves installing multiple rooftop units (RTU-1 and RTU-2), VAV terminal units, hot water heating systems, CRAC units for data and radio rooms, and a network of sensors and controllers to manage environmental conditions across different zones and spaces.
The technical drawings provide extensive details on system configurations, including specific equipment like Liebert CRAC units, ceiling exhaust fans, humidifiers, and various valve and damper schedules. The control system will integrate multiple subsystems using BACnet MS/TP communication protocols, with a network of field controllers, network sensors, and a supervisory controller (JACE). The system is designed to provide precise temperature and humidity control, with features like variable air volume (VAV) terminal units, hot water reheat capabilities, occupancy mode controls, and comprehensive monitoring of environmental conditions across approximately 22 different zones in the facility. The project appears to be a complete building automation and environmental control system upgrade, with careful attention to zonal temperature management, energy efficiency, and flexible operational modes.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Creating a better climate for business.
Environmental Control System
Air Conditioning Heating Diagnostic Services Coil Cleaning Refrigeration Automatic Temperature Controls Facility Management Systems Fire Management Security Management Building Operations and Management Water Treatment Electrical Equipment Emergency Generator / Lighting Equipment Industrial Controls / Recording / Indication Equipment
Facility Management System Air and Water System Balancing Fire Management System Security System Lighting Services Instrumentation System Installation Building Operations Management Energy Conservation Control Training Programs Performance Contracting Planned Service Agreements
Waukesha County Communication Center 7N03-0223
LEGEND
2/183
Wire Symbol indicating:
Cable Destination (DA-T), Cable number (3), Number of wires and size (E.G. 2 #18 wires)
S
Main Air Supply Tube at 20 PSIG
D-N 15-20
Dual Air Supply Tube at
15/20 PSIG
Day=15, Night=20
S
High Pressure Air Supply Tube at 80 PSIG
Air line or Electrical Wire
Connected Lines or Wires
Crossing Lines or Wires, Not Connected
Pneumatic Tube indicating Tube Number
2/18 Wire Symbol indicating:
number of wires and size (E.G. 2 #18 wires)
Electrical Wire Terminal with Appropriate Number
Item Located on Panel Face
In-Line Restrictor
Opposed Blade Damper
Parallel Blade Damper
Air Flow Measuring Station
Filter
Humidifier
Fan
Pump
Heating or Cooling Coil
Ductwork or Piping with Flow Direction Shown
Drawing Revision Symbol with Appropriate Number
Gage
Current Sensing Switch or Combination Current Sensing switch & Command Relay
Duct Detector (Smoke, CO, CO2)
2-Way Valve with Actuator
N C
3-Way Valve with Actuator
N 0
C N C
Vapor Tension Temperature Sensing Element (Low Limit)
Vapor Tension Temperature Sensing Element (Hi Limit)
Paddle Type Flow Switch
Pressure Sensing Device
Bulb Type Temperature Sensing Element Located inside Separable Socket/Well
Strap-on Bulb Type Temperature Sensing Element
Combination Bulb Type Temperature Sensing Element and Humidity Sensor (Duct Mount)
Bulb Type Temperature Sensing Element
Humidity Sensing Element Located under Shield in Outside air
Bulb Type Temperature Sensing Element Located under Shield in Outside air
Device H
C N O
N O
IN CONSIDERATION OF THE RECEIPT OF
THIS DOCUMENT, THE RECIPIENT AGREES
NOT TO REPRODUCE, COPY, USE OR
TRANSMIT THIS DOCUMENT AND/OR THE
INFORMATION THEREIN CONTAINED, IN
WHOLE OR IN PART, OR TO SUFFER SUCH
ACTION BY OTHERS, FOR ANY PURPOSE,
EXCEPT WITH THE ADVANCE WRITTEN
PERMISSION OF JOHNSON CONTROLS,
INC. AND FURTHER AGREES TO
SURRENDER SAME TO JOHNSON
CONTROLS, INC. UPON DEMAND.
COPYRIGHT JOHNSON CONTROLS, INC. 2017
NUMBER
number
Title.vsd
REVISION
INFORMATION
04/02/18
09:53 AM
extra
DATE
TIME
FILE NAME
Waukesha County Communication Center
PROJECT TITLE
ARCHITECT
Kueny Architects, LLC 10505 Corporate Drive Suite #100 Pleasant Prairie, WI 53158 Phone: 262-857-8101
ENGINEER
Southport Engineered Systems 1343 South 27th Street Caledonia, WI 53108 Phone: 262-818-4409
MECHANICAL CONTRACTOR
Butters Fetting Co Inc 1669 S. 1st St.
Milwaukee, WI 53204-2999 Phone: 414-645-1535
ELECTRICAL CONTRACTOR
7N03-0223
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
DATE
Branch Information
CONTRACT NUMBER
CoEE
APPLICATION ENGINEER
06/19/2017
PROJECT MANAGERSALES ENGINEER
REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY
MPKJW
1621 Woodburn Road Waukesha WI, 53188
REV. DWG NUMBER DWG TITLE
1.1-1.3 LEGEND
2.1-2.4 NET REFERENCE
1 2.5 COMMUNICATION BUS
3.1-3.3 HWS
3.1 HWS FLOW
3.2 PANEL P-1
3.3 PANEL P-1 WIRING
NAE-01-PS-1 POINT SCHEDULE
1 4.1-4.3 RTU
4.1 RTU-1 FLOW
1 4.2 RTU-2 FLOW
1 4.3 RTU-1 & RTU-2 SEQUENCE
1 5.1-5.5 ROOM SCHEDULE DETAILS
5.1 DETAIL A: VAV W/ REHEAT
5.2 DETAIL B: VAV W/ REHEAT & FTR
5.3 DETAIL C: UNIT HEATER
5.4 DETAIL D: FTR
1 5.5 DETAIL E: VAV W/ IT/RADIO ROOM MONITORING
REV DWG NUMBER DWG TITLE
6.1-6.4 MISCELLANEOUS DETAIL
6.1 DETAIL A: POWER DETAIL
1 6.2 DETAIL B: LIEBERT UNIT
6.3 DETAIL C: EXHAUST FAN CEF-1
6.4 DETAIL D: HUMIDIFIER H-1
WD-1 WIRING DETAIL
1 DS-1 DAMPER SCHEDULE
1 RS-1 ROOM SCHEDULE
VS-1 VALVE SCHEDULE
WS-1 WELL SCHEDULE
WD-2 WELL DETAILS
1 Revision as per CB 7N03-0223-001 9/12/2017 CoEE
2 Record Drawing 4/2/2018 CoEE
TABLE 1
USAGE ANIXTER DESCRIPTION ANIXTER DESCRIPTION BLACK WHITE
JACKET
COLOR RED ANIXTER DESCRIPTION ANIXTER DESCRIPTION BLACK WHITE
JACKET
COLOR RED DRAIN COMMENTS
AI CBL-18/2YEL-PLN 18/2 Shld Yellow CBL-18/2YEL-PVC 18/2 Shld Yellow AI Com — AI — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld AI Com AI — — TABLE 2
AI CBL-18/3YEL-PLN 18/3 Shld Yellow CBL-18/3YEL-PVC 18/3 Shld Yellow AI Com Pow er AI — CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld AI Com Pow er — AI TABLE 2
AO CBL-18/2TAN-PLN 18/2 Shld Tan CBL-18/2TAN-PVC 18/2 Shld Tan AO Com — AO — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld AO Com AO — — TABLE 2
AO CBL-18/3TAN-PLN 18/3 Shld Tan CBL-18/3TAN-PVC 18/3 Shld Tan AO Com Pow er AO — CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld AO Com Pow er — AO TABLE 2
BI CBL-18/2ORG-PLN 18/2 Shld Orange CBL-18/2ORG-PVC 18/2 Shld Orange BI 24V — BI — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld BI 24V BI — — TABLE 2
BO CBL-18/2VLT-PLN 18/2 Shld Violet CBL-18/2VLT-PVC 18/2 Shld Violet BO Com — BO — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld BO Com BO — — TABLE 2
BO CBL-18/3VLT-PLN 18/3 Shld Violet CBL-18/3VLT-PVC 18/3 Shld Violet BO Com BO BO — CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld BO Com BO — BO TABLE 2
GENERAL PURPOSE CBL-18/2NAT-PLN 18/2 Shld Natural CBL-18/2NAT-PVC 18/2 Shld Natural Common Pow er — — CBL-18/2NAT-PLN 18/2 Shld CBL-18/2NAT-PVC 18/2 Shld Common Pow er — — —
GENERAL PURPOSE CBL-18/3NAT-PLN 18/3 Shld Natural CBL-18/3NAT-PVC 18/3 Shld Natural Common Pow er — Signal CBL-18/3NAT-PLN 18/3 Shld CBL-18/3NAT-PVC 18/3 Shld Common Pow er — Signal —
GENERAL PURPOSE CBL-18/2WHTNS-PLN 18/2 Non-Shld White — — Common Pow er — — CBL-18/2WHTNS-PLN 18/2 Non-Shld White — — Common Pow er — — —
GENERAL PURPOSE CBL-18/3WHTNS-PLN 18/3 Non-Shld White — — Common Pow er — Signal CBL-18/3WHTNS-PLN 18/3 Non-Shld White — — Common Pow er — Signal —
METASTAT CBL-24/8NAT-PLN 24/8 Natural CBL-24/8NAT-PVC 24/8 Natural — — — — CM-00424BBG-3 24/8 Natural CM-00424BBG-3 24/8 Natural — — — — — SEE TABLES 4, 5, & 6
METASTAT PHONE JACK CBL-STATxxx Pre-Term'd Blue CBL-STATxxx Pre-Term'd Blue — — — — CBL-STATxxx Pre-Term'd Blue CBL-STATxxx Pre-Term'd Blue — — — — — SEE TABLES 4, 5, & 6, NOTE #4
24VAC CBL-18/2GRY-PLN 18/2 Shld Gray CBL-18/2GRY-PVC 18/2 Shld Gray 24 V Com — 24 VAC — CBL-18/2GRY-PLN 18/2 Shld Gray CBL-18/2GRY-PVC 18/2 Shld Gray 24 V Com 24 VAC — — —
24VAC POWER BUS AL-1402C-2-2N-01 14/2 Shld White AL-1402C-2-2N-01 14/2 Shld White Common — — 24 VAC AL-1402C-2-2N-01 14/2 Shld White AL-1402C-2-2N-01 14/2 Shld White Common — — 24 VAC —
600 V B8248 18/2 B8248 18/2 — — — — — — — — — — — — —
600 V B83336 18/3 B83336 18/3 — — — — — — — — — — — — —
N2 BUS CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue N2- REF N2+ — CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue N2- REF N2+ — TABLE 3
N1 BUS-ARCNET CBL-RG62PUR-PLN RG62 Purple CBL-RG62PUR-PVC RG62 Purple — — — — CBL-RG62PUR-PLN RG62 Purple CBL-RG62PUR-PVC RG62 Purple — — — — —
N1 BUS-ETHERNET CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — — SEE TABLES 7 & 8, CAT 5E
BACNET IP CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — CBL-CAT52404P-7U 24/8 Purple CM-00424BKTE-5U-10 24/8 Purple — — — — — SEE TABLES 7 & 8, CAT 5E
LON BUS CBL-22/2-NS-PLN 22/2 Non-Shld White CBL-22/2-NS-PVC 22/2 Non-Shld Gray — — — — CBL-22/2-NS-PLN 22/2 Non-Shld White CBL-22/2-NS-PVC 22/2 Non-Shld Gray — — — — —
XT BUS CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue XT- REF XT+ — CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue XT- REF XT+ — —
BACNET MS/TP FC BUS CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue FC- COM FC+ — CBL-22/3-FC-PLN 22/3 Shld Blue CBL-22/3-FC-PVC 22/3 Shld Blue FC- COM FC+ — TABLE 3
BACNET MS/TP SA BUS CBL-22/2P-SA-PLN 22/4 Shld Brow n CBL-22/2P-SA-PVC 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (BRN) PWR (WHITE) CBL-22/2P-SA-PLN 22/4 Shld Brow n CBL-22/2P-SA-PVC 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (BRN) PWR (WHITE) TABLE 3 TERMINAL BLOCK
BACNET MS/TP SA BUS CBL-NETWORKxxx 26/6 Preassembled CBL-NETWORKxxx 26/6 Preassembled — — — — CBL-NETWORKxxx 26/6 Preassembled CBL-NETWORKxxx 26/6 Preassembled — — — — TABLE 3 MODULAR JACK, 26AWG IS ACCEPTABLE, NOTE #4
PLENUM PART NUMBER NON-PLENUM PART NUMBER PLENUM PART NUMBER NON-PLENUM PART NUMBER
COLOR CODED CABLE 18 GAUGE NON-COLOR CODED CABLE 18 GAUGE
CABLE / WIRE SPECIFICATION CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR CABLE / WIRE SPECIFICATION CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR
NUMBER
number legend-a.vsd
REVISION
INFORMATION
04/02/18
02:07 PM
extra
DATE
TIME
FILE NAME
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee
WI 53222
Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
LEGEND
1.1
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NOTE #1: WHEN USING COLOR CODED CABLE, REFERENCE DETAILS
OVERRIDE COLOR CODE IN TABLE 1. WHEN USING NON-COLOR CODED
CABLE, TABLE 1 DETAILS OVERRIDE COLOR CODE IN REFERENCE
DETAILS.
NOTE #2: EXISTING JOB STANDARDS OVERRIDE NOTE #1 AND TABLE1.
NOTE #3: SEE JOHNSON CONTROLS INSTALLATION INFORMATION FOR
CABLE LENGTH LIMITATIONS.
NOTE #4: AVAILABLE IN 25FT, 50FT, 75FT AND 100FT LENGTH.
NOTE #5: USE PLENUM CABLE PER NEC REQUIREMENTS.
NOTE #6: USE SHIELDED CABLE IN “NOISY” ENVIRONMENTS.
NOTE #7: FOR VENDOR DEVICES ON THE N2 OR MS/TP BUS, DO NOT
TERMINATE THE REF / COM WIRE BUT WIRE STRAIGHT THROUGH TO THE
NEXT JCI DEVICE. THIS IS ESPECIALLY IMPORTANT FOR ALL VFD’S,
NUMBER
number legend-b.vsd
REVISION
INFORMATION
04/02/18
02:07 PM
extra
DATE
TIME
FILE NAME
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee
WI 53222
Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
LEGEND
1.2
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
FIGURE B
ASC
REF
N2+
N2 BUS 18/3 Shld Blue
REF
N2- N2+
HRD GRD
HG
ENCLOSURE
SUPERVISORY
CONTROLLER
HG
ASC
ENCLOSURE
HG
DEVICE
TAPE BACK DRAIN WIRE @ DEVICE
(ISOLATE FROM GROUNDING)
GROUND WITHIN 3" OF
ENTERING THE PANEL
TABLE 2
ENCLOSURE NO ENCLOSURE
I/O
HARD GROUND @ EACH
PANEL. TAPE BACK @
EACH DEVICE.
TAPE BACK @ EACH END SEE FIGURE A
BO (NOISY INDUCTIVE
LOADS)
TAPE BACK @ EACH END TAPE BACK @ EACH END
ADD MOV-1 @
CONTROLLER
TERMINALS
BO (GAS IGNITION) TAPE BACK @ EACH END TAPE BACK @ EACH END
ADD FILTER-1 @
CONTROLLER
TERMINALS. HARD
GROUND CASE.
DRAIN CABLE
I/O GROUNDING
TERMINALS COMMENTS
FIGURE A
DRAIN
N2-
18/x Shld
DRAIN
ASC
DEVICE
TAPE BACK DRAIN WIRE @ EACH END
(ISOLATE FROM GROUNDING)
18/x Shld
DRAIN
TABLE 3
ENCLOSURE NO ENCLOSURE
SUPERVISORY CONTROLLER HARD GROUND TO BACK
PLANE.
NA
ASC
STRAIGHT THROUGH TO
NEXT DEVICE
STRAIGHT THROUGH TO
NEXT DEVICE
ASC (EOL) TAPE BACK @ ASC TAPE BACK @ ASC
ASC (NOISY)
SOFT GROUND ONCE PER
ENCLOSURE
TAPE BACK @ ASC
ADD CAP-1 @ ENCLOSURE
SEE FIGURE B
DRAIN CABLE
N2 GROUNDING
TERMINALS COMMENTS
ENCLOSURE
HGHG
ASC
REF
N2+ N2-
DRAINDRAIN
ASC
REF
N2+ N2-
ASC
REF
N2+ N2-
DRAINDRAIN
D R
A
IN
TAPE BACK DRAIN WIRE @ EOL ASC
(ISOLATE FROM GROUNDING)
WIRE NUT DRAIN WIRE THROUGH TO NEXT
DEVICE (TYPICAL)
WIRE NUT DRAIN WIRES
TOGETHER
legend-c.vsd
REVISION
INFORMATION
04/02/18
02:07 PM
extra
DATE
TIME
FILE NAME
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee
WI 53222
Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
LEGEND
1.3
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
8 7 6 5 4 3 2 1
CAT 5 OR
METASTAT
CABLE
END VIEW OF 8-PIN PLUG
TAB DOWN
123456
SA BUS PORT
MODULAR
JACK
TABLE 7 STANDARD EIA/TIA T568B
PIN NO. COLOR
1 WHT / ORN
2 ORN / WHT
3 WHT / GRN
4 BLU / WHT
5 WHT / BLU
6 GRN / WHT
7 WHT / BRN
8 BRN / WHT
ETHERNET PATCH CABLE
NOTE: A PATCH CABLE HAS
BOTH ENDS CONFIGURED AS A
PATCH CABLE.
ETHERNET CROSSOVER CABLE
TABLE 8 STANDARD EIA/TIA T568B
PIN NO. COLOR
1 WHT / GRN
2 GRN / WHT
3 WHT / ORN
4 BLU / WHT
5 WHT / BLU
6 ORN / WHT
7 WHT / BRN
8 BRN / WHT
NOTE: A CROSSOVER CABLE HAS ONE
END CONFIGURED AS A CROSSOVER
CABLE AND THE OPPOSITE END
CONFIGURED AS A PATCH CABLE.
ADDRESS VALUE /
ADDRESS RANGE CLASS EXAMPLES
0 Bus Supervisor NAE on the FC Bus, FEC or VMA on SA Bus
1 Reserved Wireless Commissioning Converter 2 - 3 Reserved Reserved for future use
4 - 127 Master Range FEC, VMA, IOM, TEC26xx on the FC Bus
IOM on the SA Bus
128 - 254 Slave Range Slave devices and NS netw ork sensors on the SA Bus
198 Reserved VAV Balancing Sensor (handheld)
199 Reserved Most NS Series Netw ork Sensor models or
VAV Balancing Sensor (w all-mounted)
200 - 203 Reserved NS Series Netw ork Sensors (specif ied models)
255 Broadcast Do not apply address 255 to any device.
MS/TP BUS ADDRESS VALUES AND ADDRESS RANGES
TABLE 4 PHONE JACK PIN DESIGNATIONS
PHONE JACK
PIN NO. SIGNAL DESIGNATION COLOR
1 SA BUS (+) WHT / GRN
2 SA BUS (-) WHT / ORG
3 SA BUS COMMON (POWER FROM SENSOR TO
TOOL)
BLU / WHT
4 SA POWER (POWER TO SENSOR FROM TOOL) WHT / BLU
5 SA BUS COMMON (POWER FROM BUS TO
NETWORK SENSOR)
ORG / WHT
6 SA POWER (POWER FROM BUS TO NETWORK
SENSOR)
GRN / WHT
TABLE 5 TERMINAL BLOCK WIRING
TERMINAL NO. SIGNAL DESIGNATION COLOR
1 SA BUS (+) BLACK
2 SA BUS (-) WHITE
3 SA BUS COMMON BLUE
4 SA BUS POWER RED
NS SERIES SENSOR
NOTE:
DO NOT USE A CROSSOVER CABLES ON THE SA BUS
ON
EOL SWITCH = ON
EOL TERMINATION FOR THE MS/TP BUS
NOTE:
END-OF-LINE TERMINATION IS REQUIRED ON ALL FC
AND SA BUSES
NOTE:
REFER TO THE MS/TP COMMUNICATIONS BUS TECHNICAL
BULLETIN (LIT-12011034) FOR EOL TERMINATION GUIDELINES
ADDRESS SWITCH 2 SWITCH 1
199 N/A N/A
200 OFF OFF
201 OFF ON
202 ON OFF
203 ON ON
NS SERIES SENSOR DEVICE ADDRESS
(DIP SWITCH SHOWN IN
DEFAULT POSITION)
NS-xTN7003-0 SERIES
ON
1 2
NOTE:
NON-ADDRESSABLE NS SERIES SENSORS
HAVE A FIXED ADDRESS OF 199
KEY:
SWITCH IS IN THE UP
POSTION (ON)
SWITCH IS IN THE
DOWN POSTION (OFF)
END OF THE LINE SWITCHING AND
REPEATER GUIDELINES
METASYS MSTP NETWORK INSTALLATION DETAILS
Category Rules / Maximums Allowed
General Typically daisy-chained; branch or star configuration acceptable when repeaters are used. See End of Line Switching and Repeater Guideline graphic.
Number of Devices
When all of the devices connected on the FC Bus are Metasys FECs, VMAs, and/or IOMs, the device and bus segment limits are:
100 devices total per FC Bus (maximum) 3 bus segments per FC Bus (maximum) 50 devices per bus segment (maximum, not to exceed 100 devices per FC Bus) When one or more TEC26xx Series thermostat or third-party MS/TP device is connected on the FC Bus, the device and bus segment limits are:
64 devices total per FC Bus (maximum) 3 bus segments per FC Bus (maximum) 32 devices per bus segment (maximum, not to exceed 64 devices per FC Bus) Note: Metasys MS/TP devices generate less data traffic than third-party MS/TP devices and TEC26xx thermostats. Connecting third-party devices or TEC26xx thermostats to the FC Bus increases data traffic, reduces bus performance, and reduces the number of devices that can be connected to the bus.
Bus segments on an FC Bus are connected with repeaters (only). Up to two cascaded repeaters may be applied to an FC Bus (to connect three bus segments).
Line Length and Type
Cable 22 AWG stranded, 3-wire, twisted shielded cable
EOL Termination
End-of-Line (EOL) termination is required on the FC Bus to reduce signal reflection when data transmissions reach the end of a bus segment and bounce back. EOL termination is built into some Metasys FC devices and is enabled with a switch or jumper on the device.
EOL Termination on NAEs An EOL switch on an NAE enables EOL termination. For those NAEs with two FC Bus connections, two EOL double-pole switches are provided. Set the EOL switch to the ON (up) position to set the controller as an EOL termination device.
EOL Termination on Switch-Terminating Devices Some field controllers have an EOL switch or jumper. Such devices include FECs, IOMs, VMAs, ZFR1810s, and repeaters. Set the EOL termination to On for any of these devices when it is the last device on a bus segment.
EOL Termination on Devices Without EOL Provision For the devices such as TECs and third-party controllers in which no EOL provision is provided, install the MS-BACEOL-0 RS485 End-of-Line Terminator at the device if at the end of the bus segment.
EOL Termination Across the FC Bus The FC Bus may consist of up to three bus segments. Each bus segment on an FC Bus requires two EOL termination devices, one at each end of the bus segment. All other devices on the FC Bus should have their EOL termination disabled (EOL switches Off) . If only one device on an FC segment has an EOL termination, it must be set to On.
EOL on FC Bus Repeaters When using repeaters in the FC Bus, set the EOL jumpers based on the position of the repeater in the run.
When all of the devices connected on the FC Bus are Metasys FECs, VMAs, and/or IOMs, the cable length limits are:
Each bus segment can be up to 1520 m (5000 ft) in length (using 22 AWG 3-wire twisted, shielded cable).
Each FC Bus can be up to 4750 m (15,000 ft) in length (using 22 AWG 3-wire twisted, shielded cable).
When one or more TEC26xx Series thermostat or third-party MS/TP device is connected on the FC Bus, the device and bus segment limits are:
Each bus segment can be up to 1220 m (4000 ft) in length (using 22 AWG 3-wire twisted, shielded cable) Each FC Bus can be up to 3660 m (12,000 ft) in length (using 22 AWG 3-wire twisted, shielded cable).
When using fiber-optic connections: 2,010 m (6,600 ft.) between two fiber modems 22 AWG Stranded, 3-Wire Twisted, Shielded Cable
Open Plenum Installations. 38400+ Baud RS-485 Communication.
Typical Usage Anixter # Belden # AreapF/ftType
22/2pr Shielded Plenum
CBL-22/2P-SA-PVC
6541FE 33 0.033
31 0.0345541FE
CBL-22/2P-SA-PLN
EMT (Raceway) Installations. 38400+ Baud RS- 485 Communication.
22/2pr Shielded
PVC
RECOMMENDED MSTP SENSOR ACTUATOR BUS CABLE
Open Plenum Installations. 38400+ Baud RS-485 Communication.
Typical Usage Anixter # Belden # AreapF/ftType
22/3c Shielded Plenum
CBL-22/3-FC-PVC
6501FE 25 0.014
31 0.0155501FE
CBL-22/3-FC-PLN
EMT (Raceway) Installations. 38400+ Baud RS- 485 Communication.
22/3c Shielded
PVC
RECOMMENDED MSTP FIELD CONTROLLER BUS CABLE
+–S H
LD
R E
F A
Earth Ground
The shield should be earth grounded at one and only one point for the entire bus segment. (Preferably in the NAE Panel.) The shield screws on the controllers are simply a convenient way to continue the daisy chain of the bus. They are not attached to earth ground. You can use the shield terminal or twist together the shield and tape back at each controller.
SHIELD GROUNDING
The information in this document is not intended to replace the published Technical Product Literature for the Johnson Controls systems and products presented. The Installation Instructions that are packed with products, and the Technical Bulletins and Product Bulletins released with Johnson Controls systems and products supersede the information on this page. It is the responsibility of the product installer and product user to obtain and follow the product installation, operation, and safety procedures provided with the products or project specific information required by specification or local codes.
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
NET REFERENCE
2.1
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NUMBER
number
NET Ref1.vsd
REVISION
INFORMATION
04/02/18
02:08 PM
extra
DATE
TIME
FILE NAME
NET REF2
Bus and Cable Type Part Number O.D. Part Number O.D.
FC Bus: 22 AWG Stranded, Anixter: CBL-22/3-FC-PVC 0.138 in. Anixter: CBL-22/3-FC-PLN 0.140 in.
3-Wire Twisted Shielded Cable1 Belden®: B5501FE Belden: B6501FE
SA Bus (Terminal Block): Anixter: 0.209 in. Anixter: CBL-22/2P-SA-PLN 0.206 in.
22 AWG Stranded, 4-Wire, CBL-22/2P-SA-PVC Belden: B6541FE
2 Twisted-Pair Shielded Cable1 Belden: B5541FE SA Bus (Modular Jack)2: Anixter, Inc. preassembled: 0.15 in.
26 AWG Solid 6-Wire, CBL-NETWORK25 3 Twisted-Pair Cable CBL-NETWORK50
CBL-NETWORK75
CBL-NETWORK100
1 A 3-wire (for FC Bus) and 4-wire, 2 twisted-pair (for SA Bus), 22 AWG stranded, shielded cable is strongly recommended. 22 gauge cable offers the best performance for various baud rates, cable distances and number of trunk devices primarily due to lower conductor-to-conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable. Observe the shield grounding requirements.
2 26 AWG solid, 6-wire, (3 twisted pairs) cable is recommended as the best fit for fabricating modular cables with the modular jack housing assembly. Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire.
Non-Plenum Applications Plenum Applications Recommended Cable for FC Buses and SA Buses
SHIELD GROUNDING
Soft Ground Connection on FC Bus (Best)
Hard Ground - Shield
Isolate Shield Connections from Ground
Single Hard Ground Connection on FC Bus (Good)
F C B u s
Important: Only one hard ground point per bus segment
Address Value/ Address Range
Class Devices
0 Bus Supervisor FC Bus: NAE or NCE SA Bus: FECs and VMAs
1 Reserved Wireless Commissioning Converter
2 Reserved Reserved for future use.
3 Reserved DIS1710 Local Controller Display 4 - 127 Master Range FC Bus: FECs, VMAs, IOMs, and TEC26xx
SA Bus: IOMs Note: On applications using an NCE, the address value 4 is reserved for the NCE’s integral field controller.
128 - 254 Slave Range Slave devices, VSDs, and NS network sensors on the SA Bus
198 Reserved VAV Balancing Sensor (handheld) 199 Reserved Most NS Series Network Sensor models or VAV
Balancing Sensor (wall-mounted)
200 - 203 Reserved NS Series Network Sensors (specified models) 255 Broadcast Do not apply address 255 to any device.
MS/TP BUS ADDRESSING VALUES AND RANGES
NAE
Bus Segment 1520 m (5,000 ft) Maximum
50 Metasys Device Connections
T T T T T T
RR
R Repeater
T EOL Termination switch ON
Bus Segment 1520 m (5,000 ft) Maximum
50 Metasys Device Connections
Bus Segment 1520 m (5,000 ft) Maximum
50 Metasys Device Connections
Note: When TEC26xx Series thermostats or third-party MS/TP devices are connected to an FC Bus, a bus segment supports only up to 32 devices and the FC Bus supports only up to 64 devices.
4570 m (15,000 ft) Maximum 100 Total Metasys Device Connections (Maximum)
T
EOL switch set to ON BEST but Optional
10 Device Connections (Maximum) (No more than four can be NS Sensors)NCE, FEC, or VMA
(SA Bus Supervisor)
Side Jumper Instructions If at end-of-line, install both jumpers over Pins 1 and 2 (EOL In). Side A J1 and J2
If not at end-of-line, install both jumpers over Pins 2 and 3 (EOL Out).
If at end-of-line, install both jumpers over Pins 1 and 2 (EOL In). Side B J3 and J4
If not at end-of-line, install both jumpers over Pins 2 and 3 (EOL Out).
RECOMMENDED BUS CABLING
5 6 0 p F C a p a c i t o r 1000v Disc Type SF Electronics Part# 90156
MS/TP BUS ARCHITECTURE
NAE
VMA
FEC
IOM
FC FC FC
5 6 7
Network Sensor
Network Sensor
Network Sensor
SA Bus Connections and Addresses
FC Bus Connections and Addresses
Ethernet Network
Network Sensor
Network Sensor
FC Bus (Supervisor) Connection and Address
FC Bus Connections and Addresses
FC/SA BUS SPECIFICATIONS
Data Transmission Standard: RS-485 Signaling Method: BACnet MS/TP Signaling Rate: 38,400 baud (recommended)
FC BUS REPEATERFC BUS MAXIMUMS
SA BUS MAXIMUMS
6-PIN MODULAR RJ-12 PINOUT
SA+
SA-
SA Bus Com
SA Pwr (Tool)
SA Bus Com
SA Pwr (Sensor)
RJ-12
Modular
Plug
SA+
SA-
SA Bus Common
SA Power (Power to Tool*)
SA Bus Common
SA Power (Power to Network Sensor)
P in
N u m b e r
A ss ig n m e n t fo r
S tr a ig h t-th o u g h C a b le
RJ-12
Modular
Jack
P ri n te r C ir cu it B o a rd1
* Provides power from the Network Sensor SA Bus terminal block to a Wireless Commissioning Converter (MS-BTCVT-0) or handheld VAV balancing sensor connected to the modular jack.
EOL SWITCH
Only devices at the end of the line should have the EOL switch in the ON position.
Address 21 shown above
ADDRESS SWITCH
RS-485 SIDE A
AC INPUT
TX A
B
TX B
A
FA
UL
T B
S-
-3
-6
-1
-2
-4
-9
-1 9.
2K
-3 8.
4K
BA
UD
RA
TE
RS-485 SIDE B
TB1
TB2
TB3
FA
UL
T A
PO
W
ER
Wire Purpose Standard Color Application N2 or FC Bus Blue All Installations SA Bus Brow n All Installations
Analog Input Cable Yellow When Required
Analog Output Cable Tan When Required
Binary Input Cable Orange When Required
Binary Output Cable Violet When Required N1 Bus. Ethernet - Cat 5 or Coax Purple When Required 24VAC Cable Gray When Required
Spare White When Required Lon Pink When Required
METASYS CABLE JACKET COLOR STANDARDS
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
NET REFERENCE
2.2
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NET REF3
A-306
EXTERIOR WALL
L H
DPT
SD-01
INTERIOR WALL
RPS
DETAIL I100 BUILDING PRESSURE
INSTALLATION DETAIL
ROOM STATIC PRESSURE SENSORS: (RPS)
MODEL RPS IS A STAINLESS STEEL ROOM STATIC PRESSURE
SENSOR. IT MOUNTS DIRECTLY TO THE WALL OR TO A CEILING USING
A STANDARD ELECTRICAL BOX.
SURGE DAMPENER: (SD-01)
SURGE DAMPENERS ABSORB RAPID PRESSURE FLUCTUATIONS IN
ORDER TO STEADY A PRESSURE SIGNAL. EACH SURGE DAMPENER
HAS TWO INDEPENDENT CHANNELS – ONE FOR THE LOW-PRESSURE
TUBING AND ONE FOR THE HIGH-PRESSURE TUBING.
OUTDOOR STATIC PRESSURE SENSOR: (A-306)
THE A-306 OUTDOOR STATIC PRESSURE SENSOR PROVIDES AN
OUTDOOR PRESSURE SIGNAL FOR REFERENCE IN BUILDING
PRESSURIZATION APPLICATIONS. THE A-306 INCLUDES THE SENSOR,
50' (15.24M) OF VINYL TUBING, MOUNTING BRACKET, AND HARDWARE.
DIFFERENTIAL PRESSURE TRANSMITTER: (DPT)
PRESSURE TRANSDUCERS SENSE DIFFERENTIAL OR GAUGE (STATIC)
PRESSURE AND CONVERT THIS PRESSURE DIFFERENCE TO A
PROPORTIONAL ELECTRICAL OUTPUT FOR EITHER UNIDIRECTIONAL
OR BIDIRECTIONAL PRESSURE RANGES.
1. ROTATE THE DAMPER BLADE(S) TO THE DESIRED
POSITION IF THE POWER IS LOST. TO ENSURE A TIGHT SEAL,
INSERT THE MANUAL OVERRIDE CRANK AND TURN IT IN THE
DIRECTION INDICATED BY THE ARROW ON THE LABEL 5
TURNS; THE POSITION INDICATOR SHOULD BE NEAR THE 0°
POSITION ON THE SCALE. QUICKLY ROTATE THE MANUAL
OVERRIDE CRANK A HALF TURN IN THE OPPOSITE
DIRECTION TO TEMPORARILY LOCK THE ACTUATOR HUB IN
PLACE.
2. EVENLY HAND TIGHTEN EACH CLAMP NUT ONTO THE
U-BOLT, KEEPING THE ACTUATOR FLAT. SECURE THE U-
BOLT TO THE DAMPER SHAFT AND TIGHTEN TO A TORQUE
OF 100 TO 125 LB⋅IN (11 TO 14 N⋅M).
3. TO RELEASE THE SPRING, TURN THE MANUAL OVERRIDE
CRANK IN THE DIRECTION INDICATED ON THE LABEL; THE
ACTUATOR SPRING RETURNS TO ITS STARTING POSITION. IF
THIS STEP IS OMITTED, THE SPRING RELEASES
AUTOMATICALLY WHEN POWER IS APPLIED TO THE
ACTUATOR.
4. REMOVE THE MANUAL OVERRIDE CRANK AND STORE IT IN
AN UNUSED MOUNTING HOLE.
5. APPLY POWER LONG ENOUGH FOR THE ACTUATOR TO
TRAVEL A FULL STROKE, AND VERIFY THAT THE ACTUATOR
ROTATES FREELY THROUGHOUT THE RANGE.
NOTE: IF ELECTRIC POWER IS NOT AVAILABLE, COMPLETE
THIS VERIFICATION BY REINSERTING THE MANUAL
OVERRIDE CRANK AND TURNING IT IN THE DIRECTION
INDICATED TO ROTATE THE COUPLER TO THE FULLY OPEN
POSITION.
DETAIL I101 DAMPER PRE-LOADING
INSTRUCTIONS
DETAIL I102 LOW LIMIT INSTALLATION
A70
DUCT CROSS-SECTION
LOCATE THE LOW LIMIT DEVICE AT
THE HIGHEST POINT
(1 SENSOR PER 20 SQ.FT COIL AREA)
USE CAPILLARY
MOUNTING CLIPS AS
NEEDED; DO NOT KINK
CAPILLARY.
ELEMENT MUST BE
MOUNTED WITH A
CONTINUOUS DECLINE
SLEEVE PENETRATIONS
WITH ¼” POLY OR
BUSHING
FINAL PASS MUST BE
WITHIN 6" OF COIL
BOTTOM.
IMPORTANT
EACH TURN MUST
BE WITHIN 6" OF
COIL EDGE. 12" - 16"
SECURE ELEMENT
AT END AND EVERY
2' - 3' ALONG
ELEMENT WITH ¼”
POLY AND TIE WRAP.
MOUNTING MATERIAL (KELE)
M-648 CAP. MTG. CLIP 1/8" MAX
CC-1G CAP. MTG. CLIP 3/8" MAX
M-633 MID DUCT SUPPORT MTG.
DETAIL I103 FILTER DP MOUNTING DETAIL
AIR
FLOW
HIGH LOW
PRESSURE
SENSOR OR
SWITCH
FILTER
AIR
FLOW
MOUNTING PROBES (JCI)
FTG18A-600R REMOTE MTD PROBE (1 PER SWITCH)
21118 6IN STATIC PRESS PROBE (2 PER SENSOR)
PROBE
DETAIL I104 AVERAGING ELEMENT
INSTALLATION
DUCT CROSS-SECTION
USE AVERAGING
ELEMENT HOLDERS AT
ALL END TURNS
(KELE CC-1G OR
JCI TE-6008-1)
SECURE ELEMENT AT END AND EVERY 2' - 3'
ALONG ELEMENT WITH ¼” POLY AND TIE WRAP.
TE
SA+
SA-
SA Bus Common
SA Power (Power to Tool*)
SA Bus Common
SA Power (Power to Network Sensor)
Pin Number Assignment for Straight-though Cable
RJ-12
Modular
Jack
P ri n te r C ir cu it B o a rd
(Power to Tool*) - Provides power from the Network Sensor SA Bus to a Wireless Commissioning Converter (MS-BTCVT-0) or VAV balancing sensor connected to the modular jack.
DETAIL I108 6-PIN MODULAR RJ-12 PINOUT
DETAIL I106A FC/SA BUS TERMINAL BLOCK
WIRING INSTALLATION DETAIL
MATERIAL (ANIXTER)
CBL-22/3-FC-PVC – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, NON-PLENUM
CBL-22/3-FC-PLN – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, PLENUM
FC BUS WITH HARD GROUND AT NAE, SHIELD TO ISOLATED TB
FC BUS WITH SOFT GROUND, SHIELD TO CAPACITOR
MATERIAL (ANIXTER)
CBL-22/3-FC-PVC – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, NON-PLENUM
CBL-22/3-FC-PLN – 22 AWG STRANDED, 3-WIRE, TWISTED SHIELDED CABLE, PLENUM
MATERIAL (SF ELECTRONICS)
90156 – 1000V, DISK TYPE, 560PF CAPACITOR
SA BUS WITH HARD GROUND AT FEC/NCE, SHIELD
ISOLATED TO WIRE NUT
NAE
FEC
VMA
IOM
TEC
NAE
FEC
VMA
IOM
TEC
NCE
FEC
VMA
IOM
MATERIAL (ANIXTER)
CBL-22/2P-SA-PVC – 22 AWG STRANDED, 4-WIRE, 2 TWISTED-PAIR SHIELDED CABLE, NON-PLENUM CBL-22/2P-SA-PLN – 22 AWG STRANDED, 4-WIRE, 2 TWISTED PAIR SHIELDED CABLE, PLENUM
TO NEXT
DEVICE
FROM LAST
DEVICE
FC
FC
F C
B U
S
SHLD
COM
SHD
SHD
WHT
BLK
BLU
BLU
BLU
BLU
WHT
BLK
TO NEXT
DEVICE
FROM LAST
DEVICE
FC
FC
F C
B U
S
SHLD
COM
BLK
BLK
WHT
WHT
BLU
BLU
BLU
BLU
TO NEXT
DEVICE
FROM LAST
DEVICE
BRN
SA
SA
SA PWR
COM
BRN
S A
B U
S
RED
WHT
BLK
BLU
RED
WHT
BLK
BLU
Anixter
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
NET REFERENCE
2.3
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NUMBER
number
NET Ref3.vsd
REVISION
INFORMATION
04/02/18
02:08 PM
extra
DATE
TIME
TABLE 1
USAGE ANIXTER DESCRIPTION BLACK WHITE
JACKET
COLOR RED ANIXTER DESCRIPTION BLACK WHITE
JACKET
COLOR RED DRAIN COMMENTS
AI CBL-18/2YEL-PLN 18/2 Shld Yellow AI Com ---------- AI ---------- CBL-22/2-NS-PVC 22/2 Non-Shld AI Com AI ---------- ---------- TABLE 2
AI CBL-18/3YEL-PLN 18/3 Shld Yellow AI Com Pow er AI ---------- CBL-22/3-NS-PVC 22/3 Non-Shld AI Com Pow er ---------- AI TABLE 2
AO CBL-18/2TAN-PLN 18/2 Shld Tan AO Com ---------- AO ---------- CBL-22/2-NS-PVC 22/2 Non-Shld AO Com AO ---------- ---------- TABLE 2
AO CBL-18/3TAN-PLN 18/3 Shld Tan AO Com Pow er AO ---------- CBL-22/3-NS-PVC 22/3 Non-Shld AO Com Pow er ---------- AO TABLE 2
BI CBL-18/2ORG-PLN 18/2 Shld Orange BI 24V ---------- BI ---------- CBL-22/2-NS-PVC 22/2 Non-Shld BI 24V BI ---------- ---------- TABLE 2
BO CBL-18/2VLT-PLN 18/2 Shld Violet BO Com ---------- BO ---------- CBL-22/2-NS-PVC 22/2 Non-Shld BO Com BO ---------- ---------- TABLE 2
BO CBL-18/3VLT-PLN 18/3 Shld Violet BO Com BO BO ---------- CBL-22/3-NS-PVC 22/3 Non-Shld BO Com BO ---------- BO TABLE 2
GENERAL PURPOSE CBL-18/2NAT-PLN 18/2 Shld Natural Common Pow er ---------- ---------- CBL-22/2-NS-PVC 22/2 Non-Shld Common Pow er ---------- ---------- ----------
GENERAL PURPOSE CBL-18/3NAT-PLN 18/3 Shld Natural Common Pow er ---------- Signal CBL-22/3-NS-PVC 22/3 Non-Shld Common Pow er ---------- Signal ----------
METASTAT CBL-24/8NAT-PLN 24/8 Natural ---------- ---------- ---------- ---------- CM-00424BBG-3 24/8 Natural ---------- ---------- ---------- ---------- ---------- SEE TABLES 4, 5, & 6
METASTAT PHONE JACK CBL-STAT25 Pre-Term'd Blue ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- SEE TABLES 4, 5, & 6, NOTE #4
24VAC CBL-18/2GRY-PLN 18/2 Shld Gray 24 V Com ---------- 24 VAC ---------- CBL-18/2-NS-PVC 18/2 Non-Shld Gray 24 V Com 24 VAC ---------- ---------- ----------
24VAC POWER BUS AL-1402C-2-2N-01 14/2 Non-Shld White Common ---------- ---------- 24 VAC ---------- ---------- ---------- ---------- ---------- ---------- ----------
600 V B8248 18/2 ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------
600 V B83336 18/3 ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------
N2 BUS CBL-18/3BLU-PLN 18/3 Shld Blue N2- REF N2+ ---------- CBL-22/3BLU-NS-PVC 22/3 Non-Shld Blue N2- REF N2+ ---------- TABLE 3
N1 BUS-ARCNET CBL-RG62PUR-PLN RG62 Purple ---------- ---------- ---------- ---------- CBL-RG62PUR-PVC RG62 Purple ---------- ---------- ---------- ---------- ----------
N1 BUS-ETHERNET CMP-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- CM-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- ---------- SEE TABLES 7 & 8
BACNET BUS CMP-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- CM-00424BEL-5 24/8 Purple ---------- ---------- ---------- ---------- ---------- SEE TABLES 7 & 8
LON BUS 9J2201544 22/2 Shld Blue ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------
NT BUS CBL-PLN2204-91 22/4 Shld White ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ---------- ----------
XT BUS CBL-18/3BLU-PLN 18/3 Shld Blue XT- REF XT+ ---------- CBL-22/3BLU-NS-PVC 22/3 Non-Shld Blue XT- REF XT+ ---------- ----------
BACNET MS/TP FC BUS CBL-22/3-FC-PLN 22/3 Shld Blue FC- COM FC+ ---------- CBL-22/3-FC-PVC 22/3 Shld Blue FC- COM FC+ ---------- TABLE 3
BACNET MS/TP SA BUS CBL-22/2P-SA-PLN 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (RED) PWR (WHITE) CBL-22/2P-SA-PVC 22/4 Shld Brow n SA- (BLUE) COM (BLACK) SA+ (RED) PWR (WHITE) TABLE 3 TERMINAL BLOCK
BACNET MS/TP SA BUS CBL-NETWORKxxx 26/6 Preassembled ---------- ---------- ---------- ---------- CBL-NETWORKxxx 26/6 Preassembled ---------- ---------- ---------- ---------- TABLE 3 MODULAR JACK, 26AWG IS ACCEPTABLE
PLENUM PART NUMBER NON-PLENUM PART NUMBER
COLOR CODED CABLE NON-COLOR CODED CABLE
CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR CABLE / WIRE SPECIFICATION TERMINALS PER CONDUCTOR COLOR
NET REF4
123456
SA BUS PORT
MODULAR
JACK
TABLE 4 PHONE JACK PIN DESIGNATIONS
PHONE JACK
PIN NO. SIGNAL DESIGNATION COLOR
1 SA BUS (+) WHT / GRN
2 SA BUS (-) WHT / ORG
SA BUS COMMON (POWER FROM
SENSOR TO TOOL)
BLU / WHT
SA POWER (POWER TO SENSOR FROM
TOOL)
WHT / BLU
SA BUS COMMON (POWER FROM BUS TO
NETWORK SENSOR)
ORG / WHT
SA POWER (POWER FROM BUS TO
NETWORK SENSOR)
GRN / WHT
TABLE 5 TERMINAL BLOCK WIRING
TERMINAL NO. SIGNAL DESIGNATION COLOR
1 SA BUS (+) BROWN
2 SA BUS (-) BLACK
3 SA BUS COMMON WHITE
4 SA BUS POWER RED
5 15 VDC POWER (VMA) 24 VAC POWER (AHU, UNT, VAV)WHT / GRN
COMMON FOR POWER, ZONE BUS, OR
MANUAL OVERRIDE AND LED
GRN / WHT
NOTE: DO NOT USE CROSSOVER CABLES ON THE SA BUS
NS SERIES SENSOR
(DIP SWITCH SHOWN IN
DEFAULT POSITION)
NS-xTN7003-0 SERIES
ON
1 2
KEY:
SWITCH IS IN THE UP
POSTION (ON)
SWITCH IS IN THE
DOWN POSTION (OFF)
ADDRESS SWITCH 2 SWITCH 1
199 N/A N/A
200 OFF OFF
201 OFF ON
202 ON OFF
203 ON ON
NS SERIES SENSOR DEVICE ADDRESS
NOTE: NON-ADDRESSABLE NS SERIES
SENSORS HAVE A FIXED ADDRESS OF
8 7 6 5 4 3 2 1
CAT 5 OR
METASTAT
CABLE
END VIEW OF 8-PIN PLUG
TAB DOWN
TABLE 7 STANDARD EIA/TIA T568B
PIN NO. COLOR
1 WHT / ORN
2 ORN / WHT
3 WHT / GRN
4 BLU / WHT
5 WHT / BLU
6 GRN / WHT
7 WHT / BRN
8 BRN / WHT
TABLE 8 STANDARD EIA/TIA T568B
PIN NO. COLOR
1 WHT / GRN
2 GRN / WHT
3 WHT / ORN
4 BLU / WHT
5 WHT / BLU
6 ORN / WHT
7 WHT / BRN
8 BRN / WHT
NOTE: A CROSSOVER CABLE HAS ONE
END CONFIGURED AS A CROSSOVER
CABLE AND THE OPPOSITE END
CONFIGURED AS A PATCH CABLE.
NOTE: A PATCH CABLE HAS BOTH
ENDS CONFIGURED AS A PATCH CABLE.
ETHERNET PATCH CABLE
ETHERNET CROSSOVER CABLE
ON
EOL SWITCH = ON
EOL TERMINATION FOR THE MS/TP BUS
NOTE:
END-OF-LINE TERMINATION IS REQUIRED
ON ALL FC AND SA BUSES
NOTE:
REFER TO THE MS/TP COMMUNICATIONS
BUS TECHNICAL BULLETIN (LIT-12011034)
FOR EOL TERMINATION GUIDELINES
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
NET REFERENCE
2.4
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
COMMUNICATION BUS
2.5
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NOTE:
1. NAE-01 WILL BE USED AS BACNET INTEGRATION TO TRIDIUM HEAD END.
2. COMMUNICATION TRUNK IS SHOWN SCHEMATICALLY. ACTUAL RUN WILL VARY, AND JCI INSTALLER TO
DOCUMENT ACTUAL COMMUNICATION BUS INSTALL FOR RECORD PURPOSES
3. COMMUNICATION TRUNK FOR VFD AND THIRD PARTY EQUIPMENT PROVIDED BY OTHERS.
+–S H
LD
R E
F A
Earth Ground
If a shield is used, it should be earth grounded at one and only one point for the entire bus segment.
(Preferably in the NAE Panel.) The shield screws on the controllers are simply a convenient way to continue the daisy chain of the bus. They are not attached to earth ground.
SHIELD GROUNDING
NUMBER
number trunk.vsd
REVISION
INFORMATION
04/02/18
05:37 PM
extra
DATE
TIME
FILE NAME
1ST FLOOR
PANEL: P-1 BOILER ROOM 113
FEC
ADD.034
HWS
IOM2721
ADD.004
HWP-4 & 5 VFD
QTY=2
VFD
ADD.006-007
VMA
ADD.008-021
V-x
QTY=14
VMA
ADD.022,024-033
VAV-xxx
QTY=10
T
SET
EOL ON
FC-1 BUS
MS/TP
3/22 TWS
HUB OR SWITCH
N1 ETHERNET
CAT 5
IP DROP BY
OWNER
FC-1 BUS
MS/TP
3/22 TWS
RTU-2RTU-2
ADD.023
RTU-2 CONTROL PANEL
QTY=1
FC-1 BUS
MS/TP
3/22 TWS
FC-1 BUS
MS/TP
3/22 TWS
FC-1 BUS
MS/TP
3/22 TWS
HWS
FC-1 BUS
MS/TP
3/22 TWS
BOILERBOILER(B-X)
BOILER
CONTROL PANEL
QTY=3
MODBUS
RTU
UPS
QTY=1
UPS
ADD.005
FC-1 BUS
MS/TP
3/22 TWS
NOTE : FACILITY TO PROVIDE DEDICATED DATA DROP TO EACH BAC-IP DEVICE
RTU-1RTU-1
ADD.04
RTU-1 CONTROL PANEL
QTY=1
FC-1 BUS
MS/TP
3/22 TWS
1 Revision as per CB 7N03-0223-001 9/12/2017 CoEE
SUPERVISORY
CONTROLLER (JACE)
PROVIDED BY OTHERS
2 Record Drawing 4/2/2018 CoEE
BLR3-EN
HWS
HWR
SHWR-T
B-1
B-2
B-3
BOILER 1 CONTROL
CABINET
BLR2-EN
BOILER 2 CONTROL
CABINET
BOILER 3 CONTROL
CABINET
P-5
P-4
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
HWS FLOW
3.1
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NUMBER
number hws-f.vsd
REVISION
INFORMATION
04/02/18
09:55 AM
extra
DATE
TIME
FILE NAME
OA-T
TAG: P-1
GPM: 19
HP: 1/6
V/PH: 115/1/60
LOCATED IN HALL 117
NOTE: SEE MANUFACTURER'S WIRING DIAGRAM FOR
COMPLETE WIRING DETAILS. DO NOT TERMINATE
MS/TP REFERENCE TO DRIVE. WIRE NUT REFERENCE
TO CONTINUE TO THE NEXT DEVICE.
PUMP P-4 & P-5 VFD WIRING
TYPICAL OF 2
0-10 VDC+
Px-O
COM
Px-C
N
P
COM
DANFOSS VLT
+24 VDC
X1
GND
DIN
DI1 START/STOP
X2
BYPASS CONTROL BOARD
12 +24 VDC
MS/TP+
MS/TP-
REF
SHLD
FC BUS
CS-x
SYS
RUNNING
Px-S
Px-C
TAG: P-3
GPM: 19
HP: 1/6
V/PH: 115/1/60
TAG: P-4
GPM: 50
HP: 1.5
V/PH: 208/3/60
TAG: P-2
GPM: 19
HP: 1/6
V/PH: 115/1/60
TAG: P-5
GPM: 50
HP: 1.5
V/PH: 208/3/60
VSD
VSD
Hot Water Boiler and Heating Pumps
A. The hot water will maintain the secondary loop temperature at 140°F (adjustable). The boiler con trol will not energize until the outside air temperature is at or below 65°F.
B. New Boiler will be provided with BAS Control interface. Manufacturer internal control will control firing rate and safeties.
Heating Water Pumps:
A. Pump P-4 & P-5 will be interlocked with boiler operation. The pump will very speed to maintain differential pressure between the supply and return piping.
BILL OF MATERIALS
Designation Qty Part Number Description Field Devices:
BLRx-EN 3 RIBU1S SPST,10A,HC=10-30 VAC/DC,W/LED,W/OVRD
HW-DP 1 231G-MS2-5V-D 10-100 PSI W/DISPLAY 5V MANIFOLD
Px-C,-CS-x 2 CSD-CA1G1-1 SPLT/ADJ LED 1.25A W/RLY
SHWR-T 1 TE-6300W-101 T-WELL 6" BRASS DIR MNT
1 TE-631AM-2 WELL TEMP SEN 6" 1K NI
SHWS-T 1 TE-6300W-101 T-WELL 6" BRASS DIR MNT
1 TE-631AM-2 WELL TEMP SEN 6" 1K NI
NOTES:
1. MANUFACTURER INTERNAL CONTROL WILL CONTROL FIRING AND SAFETIES.
2. JCI WILL TIE IN THE FACTORY PACKAGED BOILER CONTROLLER TO DDC SYSTEM.
3. BOILER INLINE PUMPS ARE CONTROLLED BY BOILER INTERNAL CONTROLS.
4. ALL THE BOILER POINTS WILL BE MONITORED THROUGH MODBUS RTU.
B-x CONTOL PANEL
BACNET INTEGRATION
OA-T
W/ UNIT
EXISTING
CONTROL
BLR1-EN
SHWS-T
BOILER PUMP WIRING DIAGRAM
TYPICAL OF 3
120 VAC BOILER PUMP
P-x
BOILER
TERMINALS
L
H
V-1
V-3
V-4
HW-DP
VENT
VENT
PSIG mA 0 4 20 20
HWR
RANGE SELECTION SWITCH SETTING
FOR HW-DP
MS2 100
A
B
C
D
RANGES
A B C D
S.NO POINT NAME
BACnet
OBJECT
TYPE
BACnet
OBJECT ID
1 Boiler Supply Temperature AI 1
2 Firing Rate AV 1
3 Heating Loop Setpoint AV 8
4 Boiler Pump Status BV 2
5 Boiler Pump Control BV 16
6 Outdoor Temperature AI 6
7 Boiler 1 Status MV 19
8 Boiler 2 Status MV 20
9 Boiler 3 Status MV 21
10 Boiler Alarm BV 6
BOILER POINTS THROUGH MODBUS RTU
2 Record Drawing 4/2/2018 CoEE
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
PANEL P-1
3.2
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NUMBER
number p-1.vsd
REVISION
INFORMATION
04/02/18
05:38 PM
extra
DATE
TIME
FILE NAME
BILL OF MATERIALS
Designation Qty Part Number Description Field Devices:
TXP-1 1 PSH300AB10-LVC POWER SUPPLY HILO LVC 100VAx3 120 to 24VAC UPS 1 PSH550-UPS-BC ENCLOSED BACnet 550 VA UPS Panel Devices:
ES-1 1 ESW105 DIN-RAIL ETHERNET SWITCH
FEC-4 1 MS-FEC2621-0 FEC2621-1,FEC 17
IOM 1 MS-IOM2721-0 MS-IOM2721-0, IN/OUTPUT
P-1 1 PAN-ENC2436WDP 24X36X9,PERF-SUB,W/ DOOR,NEMA 1,UL 50
PS-1 1 PSM24A24DAS PWR SPLY ISOL DC,24VAC- 24VDC TRACK
TAG-x 2 NAMETAG-CUSTOM 1" X 3" TAG, 3-LINES MAX CUSTOM PNL FACE
TB-1 2 BAM2 END STOP - KELE
1 FEM6 END SECTION - KELE
7 M4/6 LOW VOLTAGE TERMINAL - KELE
TB-2 2 BAM2 END STOP - KELE
1 BJS6-5 JUMPER BAR FOR M4/6, FIVE POLES PER BAR
1 EV-6 JUMPER BAR HARDWARE
1 FEM6 END SECTION - KELE
6 M4/6 LOW VOLTAGE TERMINAL - KELE
4 SCF6 CIRCUIT SEPARATOR
NAMETAG SCHEDULE
ITEM DESCRIPTION
TAG-1 PANEL P-1
HWS SYSTEM
JCI # 7N03-0223
PANEL INFORMATION
LOCATED: BOILER ROOM 113
POWERED FROM: PANEL ?, CIRCUIT ?
TAG-2 PANEL TXP-1
24VAC POWER
JCI # 7N03-0223
LOCATED: BOILER ROOM 113
POWERED FROM: PANEL ?, CIRCUIT ?
36.00in.
24.00in.
24v ONLY
TXP-1
PSH300AB10-LVC
TAG-2
PANEL P-1
1- 1/
2" W
IR
E
D U
C T
P
N E
U M
A T
IC
H
IG
H V
O
LT
A G
E )Terminal End Stop
Terminal End Stop
Terminal End Stop
SHLD
MS/TP + OUT
MS/TP - OUT
COM OUT
Terminal End Stop
MS/TP + IN
MS/TP - IN
COM IN
FE
C
FEC2621
PS-1
1-1/2" WIRE DUCT
E S
-1
1-1/2" WIRE DUCT
1-1/2" WIRE DUCT
TAG-1
F A U L T
B U S
I O M
C O M
IOM2721
1-1/2" WIRE DUCT
UPS
120 VAC
2 Record Drawing 4/2/2018 CoEE
JACE
PROVIDED BY OTHERS
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
PANEL P-1 WIRING
3.3
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
NUMBER
number p-1 pw.vsd
REVISION
INFORMATION
04/02/18
05:38 PM
extra
DATE
TIME
FILE NAME
Pneumatic Tubing
Cable
Low Voltage Terminal
Wired by JCI
Field Wiring
High Voltage Terminal
Wiring Legend
VAC
Power
INSTALLATION NOTE:
WIRE 120v TO PSH300AB10-LVC TRANSFORMER(TXP-1). NO 120v
POWER CAN BE PRESENT INSIDE OF P-1
H COM
SW-1
1 3
2 4
CK-1 CK-2 CK-3
120 VAC
PSH300AB10-LVC
IOM-4
HOT COM
2 4
LOW VOLTAGE WIRING DIAGRAM FOR CONTROLLER
PSH300AB10-LVC
(POWERED BY TXP-1 / CK-2 100VA)
FEC-4
HOT COM
PS-1
VOLTAGE INPUT
24VAC
IN#
INCOM#
HW-DP
TB-1
TB-2
FEC-4, UI-1
PS-1
HOT COM
24V COM
PWR-1
24 VAC
ES-1
HOT COM1 3
LOW VOLTAGE WIRING DIAGRAM FOR CONTROLLER
PSH300AB10-LVC
(POWERED BY PSH300AB10-LVC/TXP-1/CK-1 100VA)
HWS
FEC 2621
COM
PWR
SA ADDR. 4
IOM 2721
COM
PWR
COM
SHD
FC +
FC -
R E
D
B
LU
B
LK
W H
T
SA BUS DETAIL
COM
JACE
HOT COM
2 Record Drawing 4/2/2018 CoEE
Site Director ID 4/2/2018Waukesha County Communication Center
Electrician/Fitter Point Information Controller Information Panel Information Intermediate Device Field Device
Tag Point Type System Name Object Name Expanded ID
Controller Details
Trunk Type
Trunk Nbr Trunk Addr.
Cable Destination Bay/Terminal
Termination Out Panel Panel Location Reference Drawing
Panel-x-Cable Destination
Bay/Terminal
Wiring /Tubing
Termination In Device Termination Out Wiring /Tubing
Termination In Device Ref Detail
Shape Comment Template
FEC 2621 Power to Controller FEC 2621 MS/TP 1 4 P-1 BOILER ROOM 113 BacNet FC Bus
UI IN-1 HWS HW-DP Hot Water Differential Pressure FEC 2621 MS/TP 1 4 UI IN-1 IN1, +15V P-1 BOILER ROOM 113 1-4-UI IN-1 2/22 -, + DPT2xxx (mA) F106 UI IN-2 HWS SHWR-T Secondary HW Return Temperature FEC 2621 MS/TP 1 4 UI IN-2 IN2, ICOM2 P-1 BOILER ROOM 113 1-4-UI IN-2 2/22 2-Wire TE F131 UI IN-3 HWS SHWS-T Secondary HW Supply Temperature FEC 2621 MS/TP 1 4 UI IN-3 IN3, ICOM3 P-1 BOILER ROOM 113 1-4-UI IN-3 2/22 2-Wire TE F131 UI IN-4 MSDET-D RA-H Return Air Humidity FEC 2621 MS/TP 1 4 UI IN-4 IN4, ICOM4, +15V P-1 BOILER ROOM 113 1-4-UI IN-4 3/22 OUT,GND,PWR HE-6700(Duct Mnt) - HE F153
UI IN-5 FEC 2621 MS/TP 1 4 UI IN-5 P-1 BOILER ROOM 113 1-4-UI IN-5
UI IN-6 FEC 2621 MS/TP 1 4 UI IN-6 P-1 BOILER ROOM 113 1-4-UI IN-6
BI IN-7 HWS P5-S HW Pump 5 Status FEC 2621 MS/TP 1 4 BI IN-7 IN7, ICOM7 P-1 BOILER ROOM 113 1-4-BI IN-7 2/22 OUT, COM Current Relay Motor Lead 2/22 See wiring detail Dry Contact F301 BI IN-8 HWS P4-S HW Pump 4 Status FEC 2621 MS/TP 1 4 BI IN-8 IN8, ICOM8 P-1 BOILER ROOM 113 1-4-BI IN-8 2/22 See wiring detail Dry Contact F301 BO OUT-1 HWS BLR3-EN Boiler 3 Enable FEC 2621 MS/TP 1 4 BO OUT-1 OUT1, 24V COM P-1 BOILER ROOM 113 1-4-BO OUT-1 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501 BO OUT-2 HWS BLR2-EN Boiler 2 Enable FEC 2621 MS/TP 1 4 BO OUT-2 OUT2, 24V COM P-1 BOILER ROOM 113 1-4-BO OUT-2 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501 BO OUT-3 HWS P4-C HW Pump 4 Command FEC 2621 MS/TP 1 4 BO OUT-3 OUT3, 24V COM P-1 BOILER ROOM 113 1-4-BO OUT-3 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F501 CO OUT-4 HWS P5-C HW Pump 5 Command FEC 2621 MS/TP 1 4 CO OUT-4 OUT4, 24V COM P-1 BOILER ROOM 113 1-4-CO OUT-4 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F901 CO OUT-5 HWS BLR1-EN Boiler 1 Enable FEC 2621 MS/TP 1 4 CO OUT-5 OUT5, 24V COM P-1 BOILER ROOM 113 1-4-CO OUT-5 2/22 COIL-,COIL+ Relay COM, NO 2/18 See wiring detail 24VAC OUT (Sw Hi, EXT Source) F901
CO OUT-6 FEC 2621 MS/TP 1 4 CO OUT-6 P-1 BOILER ROOM 113 1-4-CO OUT-6
CO OUT-7 FEC 2621 MS/TP 1 4 CO OUT-7 P-1 BOILER ROOM 113 1-4-CO OUT-7
AO OUT-8 HWS P4-O HW Pump 4 Output FEC 2621 MS/TP 1 4 AO OUT-8 OUT8, OCOM8 P-1 BOILER ROOM 113 1-4-AO OUT-8 2/22 See VFD Detail VFD Speed Control (Vdc) AO OUT-9 HWS P5-O HW Pump 5 Output FEC 2621 MS/TP 1 4 AO OUT-9 OUT9, OCOM9 P-1 BOILER ROOM 113 1-4-AO OUT-9 2/22 See VFD Detail VFD Speed Control (Vdc)
IOM 2721 P-1 BOILER ROOM 113 Power to Controller IOM 2721 SA Bus 1 4 P-1 BOILER ROOM 113 BacNet SA Bus 1,0
UI IN-1 MSDET-D H1-A Humidifier Alarm IOM 2721 SA Bus 1 4 UI IN-1 IN1, ICOM1 P-1 BOILER ROOM 113 4-1-4-UI IN-1 2/22 See wiring detail Dry Contact F301 UI IN-2 HWS P4-A HW Pump 4 VFD Fault IOM 2721 SA Bus 1 4 UI IN-2 IN2, ICOM2 P-1 BOILER ROOM 113 4-1-4-UI IN-2 2/22 See VFD Detail VFD Fault UI IN-3 HWS P5-A HW Pump 5 VFD Fault IOM 2721 SA Bus 1 4 UI IN-3 IN3, ICOM3 P-1 BOILER ROOM 113 4-1-4-UI IN-3 2/22 See VFD Detail VFD Fault UI IN-4 IOM 2721 SA Bus 1 4 UI IN-4 P-1 BOILER ROOM 113 4-1-4-UI IN-4 UI IN-5 IOM 2721 SA Bus 1 4 UI IN-5 P-1 BOILER ROOM 113 4-1-4-UI IN-5 UI IN-6 IOM 2721 SA Bus 1 4 UI IN-6 P-1 BOILER ROOM 113 4-1-4-UI IN-6 UI IN-7 IOM 2721 SA Bus 1 4 UI IN-7 P-1 BOILER ROOM 113 4-1-4-UI IN-7 UI IN-8 IOM 2721 SA Bus 1 4 UI IN-8 P-1 BOILER ROOM 113 4-1-4-UI IN-8 AO OUT-1 IOM 2721 SA Bus 1 4 AO OUT-1 P-1 BOILER ROOM 113 4-1-4-AO OUT-1 AO OUT-2 IOM 2721 SA Bus 1 4 AO OUT-2 P-1 BOILER ROOM 113 4-1-4-AO OUT-2
Rev-2; Record Drawing; CoEE; 4/2/2018
7N03-0223 NAE-01-PS-1HWS Point Schedule
PFILT-DP
EA
DA
RA
VSD
TS-1
NO
D-2
RAD-O
MA-T
7N03-0223
Drawing Title
CoEEMPKJW
Johnson Controls, Inc.
12000 W. Wirth Street Suite 102 Milwaukee, WI 53222 Phone: 414-259-2800 Fax: 414-259-2775
REFERENCE DRAWING
RTU-1 FLOW
4.1
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Waukesha County Communication Center
1621 Woodburn Road Waukesha WI, 53188
RA-SD
SA-F
(WITH AHU)
NUMBER
number rtu-1-f.vsd
REVISION
INFORMATION
04/02/18
09:56 AM
extra
DATE
TIME
FILE NAME
SET @ 32 Deg. F
RA-T
FACM-A
BY OTHERS
OA
N C
D-1
OAD-O
DA-T
N C
D-3
RLFD-O
PH1-C
PH2-C
GAS
C
RA-H
DX
C
CONDESING
UNIT
RS RL
SS-SW
BY OTHERS
SR-SW
BY OTHERS
TS-1
PACKAGED UNIT
NOTES:
1. ALL CONTROLS COMPONENTS WILL BE PROVIDED BY THE…