This document is a set of technology design standards for structured cabling developed by the Office of Technology Services for the Lone Star College System. It outlines the requirements for telecommunications connections, critical technology spaces including Main Distribution Frames (MDF) and Technology Rooms, IP network standards for wired and wireless networks, and cabling specifications. Key details include physical space requirements, power and HVAC needs, cabling access and pathway standards, lighting, and equipment specifications for infrastructure, cables, data systems, voice communications, wireless, and uninterruptible power supply. The standards apply to new construction as well as renovations of existing buildings and classrooms across the college system.

The document provides detailed technical requirements and standards for the design, construction, and equipping of technology spaces and infrastructure to support the Lone Star College System's technology needs. It does not contain information on the procurement process, response dates, funding sources, or contract terms.

View the file

Other files

File Type Posted
ESBD_376393_1726235996169_LSC-HSP PAR FORM SDD2017 7.10.17 .pdf PDF
ESBD_376393_1726236023510_LSC-_Bid_Submission_Guideline.pdf PDF
ESBD_376393_1726235977499_Conflict of Interest Form Rev 09102024 (for vendors).pdf PDF
ESBD_376393_1726235881660_RFP 964 - Voice Data Comm Cabling Services Bid Document.pdf PDF
ESBD_376393_1726235918823_Exhibit A - LSC TechDesignStandardsCabling_8062024.docx DOCX document
ESBD_376393_1726235949744_Exhibit B - LSC Locations.xlsx XLSX spreadsheet
ESBD_376393_1728505015680_RFP 964 Addendum No. 1.pdf PDF
ESBD_376393_1726235881660_RFP 964 - Voice Data Comm Cabling Services Bid Document.pdf PDF
ESBD_376393_1726235949744_Exhibit B - LSC Locations.xlsx XLSX spreadsheet
ESBD_376393_1726235996169_LSC-HSP PAR FORM SDD2017 7.10.17 .pdf PDF
ESBD_376393_1726236023510_LSC-_Bid_Submission_Guideline.pdf PDF
ESBD_376393_1726235977499_Conflict of Interest Form Rev 09102024 (for vendors).pdf PDF
ESBD_376393_1726235918823_Exhibit A - LSC TechDesignStandardsCabling_8062024.docx DOCX document
ESBD_376393_1728505015680_RFP 964 Addendum No. 1.pdf PDF
ESBD_376393_1726235949744_Exhibit B - LSC Locations.xlsx XLSX spreadsheet
ESBD_376393_1726235977499_Conflict of Interest Form Rev 09102024 (for vendors).pdf PDF
ESBD_376393_1726235881660_RFP 964 - Voice Data Comm Cabling Services Bid Document.pdf PDF
ESBD_376393_1726235996169_LSC-HSP PAR FORM SDD2017 7.10.17 .pdf PDF
ESBD_376393_1726236023510_LSC-_Bid_Submission_Guideline.pdf PDF
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNOLOGY DESIGN STANDARDS STRUCTURED CABLING

Prepared by:

Office of Technology Services

Version 14 – Revised August 6, 2024

CONTENTS

INTRODUCTION3
Purpose of This Report3
Technology Spaces4
Main Distribution Frame (MDF)4
Technology Rooms8
Telco Demarcation Room18
Building Pathways and Access for Cabling19
Conduit Requirements (Main Distribution Frame)20
Conduit Requirements (Future Expansion)20
Conduit Requirements (Technology Rooms)20
Conduit Requirements (Wall and Floor Outlets)20
Cabling (Low-Voltage)21
Horizontal Network Cabling21
Vertical Riser Cable (or MDF to Technology Room)21
Inter-Building Connectivity21
Wireless Communications21
802.11 Wireless21
Cable Labeling Standards22
New Center22
New Building (Existing Campus)22
Patch Panel22
Equipment Description and Specifications25
Infrastructure Products25
Cable Products25
WAN Infrastructure Products26
Data Systems Products26
Voice Communications Products26
Wireless Products26
Uninterrupted Power Supply Products26

INTRODUCTION

PURPOSE OF THIS REPORT

This document is intended to be used by those designing, building, and equipping new buildings, as well as renovations associated with existing buildings and classrooms. This document includes design guidelines for:

A. Telecommunications connections to each campus.

B. Critical technology space needs, including Main Distribution Frames and Technology Closets.

C. An IP network standard for both wired and wireless networks in each building.

D. Office of Technology Services Structured Cabling Standard.

This report presents pragmatic, step-by-step technology design elements expressed as Technology Standards. Bond Program architects and engineers should carefully review these standards as designs are developed, ensuring these minimum guidelines are included in the program and budget for each building.

TECHNOLOGY SPACES

1.1 Main Distribution Frame (MDF)

Larger buildings that are designated as an IT distribution point (this will be determined by IT per project) and new campuses will require a separate Main Distribution Frame to house local servers, controllers for digital signage, and telecommunications equipment. The construction must conform to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces.

A. The MDF should be at least 250 sq. ft. in size, as geometrically square as possible, and located toward the center or core of the building structure.

B. The room should be placed on the ground floor whenever possible due to equipment access and floor loading considerations. Avoid placing the Main Distribution Frame next to outside walls, elevator shafts, and/or internal fixed building walls.

C. All perimeter walls shall be full height (deck-to-deck), 1-hour rated construction, fire sealed, and sealed to prevent chemical fire suppression leaks. The ceiling height should be at least 9 feet - 6 inches from finished floor surface.

D. A primary 6 feet - 0 inches wide double door will be required for access to the hallway closest to the loading dock. All other door entrances should be at least 4 feet - 0 inches wide.

E. There should be no water or plumbing distribution piping routed through the ceiling, room, walls, or plenum.

F. There should not be any water related areas (coffee/break rooms, restrooms, etc.) above or adjacent to the MDF footprint.

1.1.1 Power Requirements

A. Estimated power load should be 100KVA/80KW for the entire room. (This figure is based on about 100 watts per square foot to support high density computing.)

B. The power shall be overhead mounted to the ladder rack behind the cabinets and racks.

C. All equipment outlets require “N+1” UPS backup (at least 15 minutes of battery backup).

D. All UPS systems shall connect to the emergency generator system.

E. Grounding and Bonding is required in accordance to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces.

1. This will require a ground bus connection to the main Telecommunications Ground Bus.

2. An eight-lug grounding bar, attached to the main ground bus via a 6- awg copper cable, provided by the General Contractor.

1.1.2 HVAC Requirements

A. 24-hour HVAC at an estimated 25-ton load, delivered via two 15-ton systems at either end of the room.

B. HVAC and power loads should be at least 100 watts per square foot (to support high density computing).

C. HVAC must be connected to the room Emergency Generator System.

1.1.3 Room Safety

A. The Main Distribution Frame should be finished with static dissipative vinyl composition tile (VCT) or sealed concreate.

B. Electronic access control systems shall be employed via access card technology at each entry door for security purposes.

C. An Emergency Power Off (EPO) switch should be installed in the MDF (only if required by code).

1. If required, the EPO should be mounted to the far left of the exit door and shielded by a plastic cover to prevent inadvertent activation.

1.1.4 Cabling Access and Pathways

A. Each MDF will require four (4) four-inch sleeves with collars where needed for horizontal cable distribution. To be specified per project.

B. Each MDF will require at least four (4) four-inch floor cores, with sleeves, for vertical backbone cable distribution to the street easement pull box. To be specified per project.

C. Cable tray shall be provided for at least 20 feet leaving the MDF.

1.1.5 Lighting

A. Required lighting to provide 50-foot candles measured 3 feet from the finished floor surface.

B. An emergency generator should back lighting.

Main Distribution Frame for a Building Location Independent of any Main Campus

IDF/MDF General Notes

· Refer to sheet T0.00 for telecommunications system abbreviations and symbol legend

· Coordinate any structural variances in room layout with General Contractor, communications sub & owner’s representative prior to equipment installation.

· Port count shown for reference. Contractor is responsible for ensuring correct port counts necessary for termination of all communications cable.

· All material shown to be provided by communications sub unless noted otherwise

· General contractor to wrap room with ¾’ plywood painted with fire retardant paint.

Keyed Notes:

· One (1) TIA relay rack for fiber riser, network equipment and horizontal cable terminations. (General contractor furnished/installed – communication sub).

· 16” ladder tray for cable support. Tray shall be installed so that it crosses the room and is plumb and level. The use of cable runway radius drops, junction splice kits and rack to runway support kites are required. (General contractor furnished/installed – communication sub).

· Convenience duplex power outlet as shown at 18” A.F.F. (General contractor furnished/installed – electrical sub).

· Equipment power outlet – 120vac 20 AMP, mounted on ladder tray. (General contractor furnished/installed – electrical sub).

· Equipment power outlet – 208vac 30 AMP, mounted on ladder tray. (General contractor furnished/installed – electrical sub).

· Vertical wire management as indicated (CommScope if going into existing MDF/IDF. Panduit if new MDF/IDF). (General contractor furnished/installed – electrical sub).

· One (1) telecommunications grounding bar (minimum 4”x1/4”x12”). Grounding shall meet ANSI/TIA607-B standard mount at 78” A.F.F. (General contractor furnished/installed – electrical sub).

· Indicated equipment is owner furnished and installed

· 48 Port CAT6 patch panel (Quantity as required for installation). (General contractor furnished/installed – communication sub).

· One (1) 2RU horizontal wire manager. (General contractor furnished/installed – communication sub).

· One (1) 24-port CAT6 panel for voice backbone. (General contractor furnished/installed – communication sub).

· One (1) 1RU rack mount fiber connect panel. Loaded duplex LC connector panel. Blanks and cable fastening hardware required. (General contractor furnished/installed – communication sub).

· APC Smart-UPS outlet to be connected to generator power. (General contractor furnished/installed – communication sub).

· No patch panels, horizontal cable manager may be installed on in the rack below the level of rack mounted UPS

1.2 Technology Rooms

Critical cabling, IP network, and A/V components will be housed in Technology Rooms situated throughout the space. These Technology Rooms will house equipment for voice and data networks, as well as, security, audio/visual systems, overhead paging, and building automation systems. The construction must conform to the current ANSI/TIA 569 Standards for Commercial Building Telecommunications Pathways and Spaces.

1.2.1 Dimensions and Locations

A. Every floor in each campus facility should have at least one Technology Room per 20,000 square feet of useable space.

B. All rooms should stack vertically within the building.

C. Each Technology Room should be centrally located, square.

D. Each Technology Room should be at least 110 sq. ft. in size (10 feet x 11 feet preferable, with the minimum dimension no less than 9 feet).

E. No closet should be more than 260 feet from the most distant cable run assuming corridor cable routing.

F. The doors should be a minimum of 30 inches in width.

G. There should be no water or plumbing distribution piping routed through the ceiling, room, walls, or plenum.

H. There should not be any water related areas (coffee/break rooms, restrooms, etc.) above or adjacent to the MDF footprint.

I. All walls should be covered with ¾-inch plywood and painted with flame retardant paint.

J. Lay in ceiling is neither required, nor recommended in the Technology Rooms.

1.2.2 Power Requirements

A. An estimated power load of 7kVA/5.6kKW per room will be required, however the design teams should carefully monitor systems selected and amend this projection as needed.

B. The power will be divided into circuits that are supported by the UPS/generator, and generator only. When the UPS is under maintenance, equipment will be supported in the Technology Rooms with no interruption.

C. Each Technology Room will require at least (2) 208vac, 30amp circuits above the equipment racks and at least (4) 120vac 20amp ISO circuits on the walls.

D. Grounding and Bonding is required in accordance to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces.

1. This will require a ground bus connection to the main Telecommunications Ground Bus.

2. An eight-lug grounding bar, attached to the main ground bus via a 6-awg copper cable, provided by the General Contractor.

1.2.3 HVAC Requirements

A. Each Technology Room will require a 7x24 HVAC capable of dissipating approximately 24,000 BTU/hour or 2 tons and supply constant air flow.

B. The HVAC systems in the Technology Rooms should be on the emergency generator.

1.2.4 Room Safety

A. The MDF should be finished with static dissipative vinyl composition tile (VCT) or sealed concrete.

B. If code requires fire suppression, the water heads should be high temperature heads, and no water head or pipe should be positioned above the equipment racks.

C. Electronic access control systems are required via access card technology at each entry door for security purposes as well as keyed entry.

D. A surveillance camera is recommended at each entry door.

E. All walls should be painted with flame retardant paint.

1.2.5 Cabling Access and Pathways

A. Each Technology Room will require four (4) four-inch sleeves with collars above the door for horizontal cable distribution.

B. Each Technology Room will require three (3) four-inch floor cores, with sleeves, for vertical backbone cable distribution.

C. Cable tray shall be provided for at least 20 feet leaving the Technology Room.

D. A single four-inch core should also be provided in the mechanical or electrical room on each floor for a secondary fiber route to the Main Distribution Frame.

1.2.6 Lighting

A. Required lighting to provide 50-foot candles measured 3 feet from the finished floor surface.

B. If required, lighting should be backed by an emergency generator.

Typical 2 Rack IDF

Typical TBB Conductor Bar

Typical Wall Phone Placement

1.3 MDF/D-Marc

This room provides for the distribution of networking and telecommunication services throughout each campus. These rooms have similar amenities as a typical Technology Room. Sometimes the D-Marc end room is an adjunct to the MDF or a Technology Room, where a separate room is generally not required. Each D-Marc room should be designed based upon the following criterion:

1.3.1 Dimensions and Locations

A. Room should be located as close to the Main Distribution Frame as possible.

B. Each D-Marc should be at least 200 sq. ft. in size.

C. A primary 6 feet - 0 inches double door will be required for access to the hallway closest to the loading dock.

D. There should be no water or plumbing distribution piping routed through the ceiling, room, walls, or plenum.

E. There should not be any water related areas (coffee/break rooms, restrooms, etc.) above or adjacent to the Main Distribution Frame footprint.

F. All walls should be covered with ¾-inch plywood and painted with flame retardant paint.

G. Lay in ceiling is neither required, nor recommended. All walls should go deck-to- deck.

1.3.2 Power Requirements

A. An estimated power load of 20kVA/16KW per room will be required, however the design teams should carefully monitor systems selected and amend this projection as needed.

B. The power will be supported by the Central UPS system, backed by the Emergency Generator system.

C. Each Technology Room will require multiple 208vac circuits above the equipment racks and at least (4) four 120vac 20amp ISO circuits on the walls.

D. There will need to be at a minimum of one L6-30 power outlet supplied for each UPS installed in room. To be determined by owner.

E. Grounding and bonding are required in accordance to the current ANSI/TIA 569 Standard for Commercial Building Telecommunications Pathways and Spaces.

1. This will require a ground bus connection to the main Telecommunications Ground Bus.

2. An eight-lug grounding bar, attached to the main ground bus via a 6-awg copper cable, provided by the General Contractor.

1.3.3 HVAC Requirements

A. The D-Marc will require a 7x24 HVAC capable of dissipating approximately 36,000 BTU/hour or 3 tons and supply constant airflow.

B. The HVAC systems in the D-Marc should be on the emergency generator.

1.3.4 Room Safety

A. The D-Marc should be finished with static dissipative vinyl composition tile (VCT) or sealed concrete.

B. If code requires fire suppression, the water heads should be high temperature heads, and no water head or pipe should be positioned above the equipment racks.

C. At a minimum, each D-Marc should be secured with a key and electronic access control.

D. Electronic access control systems are required via access card technology at each entry door for security purposes.

E. A surveillance camera is recommended at each entry door.

F. All walls should be painted with flame retardant paint.

1.3.5 Cabling Access and Pathways

A. Each D-Marc will require four (4) four-inch sleeves with collars above the door for horizontal cable distribution.

B. Each D-Marc will require three (3) four-inch floor cores, with sleeves, for vertical backbone cable distribution.

C. Cable tray shall be provided for at least 20 feet leaving the D-Marc.

D. A single four-inch core should also be provided in the mechanical or electrical room on each floor for a secondary fiber route to the D-Marc.

1.3.6 Lighting

A. Required lighting to provide 50-foot candles measured 3 feet from the finished floor surface.

B. If required, provide generator backed lighting.

BUILDING PATHWAYS AND ACCESS FOR CABLING

Building pathways are defined as clear and un-obstructed conduits or cable trays for routing cabling into and within a facility.

1.4 Conduit Requirements (Main Distribution Frame)

A. It is required that each facility have at least one sets of four (4) four-inch conduits routed from the Main Distribution Frame to manholes in the utility easements.

B. Each set of conduits should have at least one four-inch conduit clear for routing large pair counts of copper cable, and the other conduits should have three – 2-inch inter- ducts installed in them for fiber.

C. Each set of conduits should exit the facility at least 100 feet in separation and preferably on opposite sides of the facility.

D. These conduits are primarily for routing telecommunications services into the facility from the Telecommunications providers.

1.5 Conduit Requirements (Future Expansion)

A. Stub additional four-inch conduits out of each campus facility for future buildings and wireless connectivity in open areas of the campus such as parking lots.

1.6 Conduit Requirements (Technology Rooms)

A. Each Technology Room should have one clear paths to the Main Distribution Frame to route redundant fiber risers to each Technology Room.

1.7 Conduit Requirements (Wall and Floor Outlets)

A. Each wall outlet that is accessible by an open ceiling will only require a “ring and string” single-gang opening.

B. All wall outlets that are not accessible by an open ceiling to include all wall phone outlets need to have at least a 2-inch conduit to accessible ceiling with a double- gang back box and a single-gang reducer.

C. All classrooms should have a 2-inch conduit from the Podium to the overhead projector.

D. Floor outlet locations should be capable of supporting four cables.

E. A one-inch conduit from the floor outlet location should be routed to the closest wall then to the plenum space for overhead routing.

F. The most common in-floor outlets used with high-end cable systems are the Walker RC4 Flush Quad poke-thru and the Hubbell PT4XBRS poke-thru.

CABLING (LOW-VOLTAGE)

1.8 Horizontal Network Cabling

A. New IDF/MDF closets will have Panduit VariMaTriX Category 6A family of products (for all new data rooms and to be continued in those rooms).

B. Existing IDF/MDF Closets will have Category 6, CommScope/SYSTIMAX 2091b from the GigaSpeed X10D family of products (for all existing data rooms and to be continued in those rooms).

C. Universal Structured cabling – no distinction between voice, data or video.

D. Horizontal cables per work outlet:

1. Administrative – 2

2. Wall Phone – 1

3. Typical Desk – 2

4. Lab Desk – 2

5. Instructor’s Podium – 2

6. Wireless Access Points – 1

7. Projectors – 2

8. Security Camera – 1

9. Card readers - 1

10. Room Scheduler - 1

1.9 Patch Cord Color

A. Blue - Data B. Yellow - Security, IP Camera’s, Alarm C. Orange - DMarc Extension D. Green - Network Connections (Switch to Switch, and Wireless Access Points) E. Purple - Common Equipment Server F. White - Analog Connections (this should be approved with owner)

1.10 Vertical Riser Cable (or MDF to Technology Room)

A. One 12-strand Single Mode fiber optic cables to connecting IDF from the MDF.

B. Fiber to be terminated with LC Connections.

1.11 Inter-Building Connectivity

A. One 48-strand Single-Mode fiber optic cables between each required building on a campus to the MDF.

B. Fiber to be terminated with LC connections.

WIRELESS COMMUNICATIONS

1.12 802.11 Wireless A. One access point should be placed every 1,000 square feet.

B. One Category 6A cables will be pulled to each Wireless Access Point (WAP) location (color GREEN) C. Each Wireless Access Point (WAP) location shall have one data cable installed and terminated to a single port, surface mount box for each cable.

D. Leave a 20-foot ‘figure-8’ service loop in the plenum for each cable. Cables should be terminated at the access point end with 2 single port surface mount enclosures.

E. All Wireless Access Points (WAP) should be placed in secure wireless enclosures in the ceiling.

1. Enclosures to be verified with owner before order. This will be based on type of wireless access point being installed.

SECURITY CAMERA COMMUNICATIONS

1.13 Security Camera Installation outdoors

A. Installation of security camera’s that reside outside or attached to an outer perimeter of a building must be installed using either Panduit Opti-Core Indoor-Outdoor Riser Hybrid Powered fiber cable that is to be brought to the closest IDF/MDF or B. Panduit PoE power extenders may also be used. This will be determined by the owner based on requirements. This type of installation may call for 1 port or up to 4 port PoE injectors. This installation will also require shelving to be installed in the IDF/MDF where termination is.

CABLE LABELING STANDARDS

1.14 New Center

A. MDF-101 (Should have room number when available) B. IDF-1A (2nd IDF-Should be labeled with room number when available, i.e., the 1A would be the IDF room number, IDF-201) C. IDF-2A (IDF-Should be labeled with room number when available, i.e., the 2A would be the IDF room number, then A designating the 2nd panel in the IDF ex: IDF-201A)

1.15 New Building (Existing Campus)

A. IDF-1A (1st IDF-Should be labeled with room number when available, i.e., the 1A would be the IDF room number, IDF-201) B. IDF-2A (2nd panel in IDF-Should be labeled with room number when available, i.e., the 2A would be the IDF room number, then A designating the 2nd panel in the IDF ex: IDF-201A) C. IDF-2B (3nd panel in IDF-Should be labeled with room number when available, i.e., the 2B would be the IDF room number, then B designating the 3nd panel in the IDF ex: IDF-201B) D.

1.16 Patch Panel

A. IDF label

1. Number start from 001 – 300 (no A’s and B’s)

2. Identify Fire Panels (fire), Elevators (Elv)

B. Faceplate

1. IDF Location upper middle (top)

2. IDF Location lower middle (bottom)

3. Start with 001 – 004 (no A’s and B’s)

EQUIPMENT DESCRIPTION AND SPECIFICATIONS

Based on the current Lone Star College System standards, the following products should be used to provide for technology support in the MDF, closets and D-Marc room (note that these products may change as the manufacturer updates their products. This is a guideline for selection).

1.17 Infrastructure Products

Description
Product
2- Post Racks
Panduit R2P, 19” 7ft.
Ladder Rack
SYSTIMAX CR-SLR-10L12W
Cable Management
Panduit Patchlink Horizontal 1U/2U, Netmanager Horizontal 3/U, Patchrunner Vertical WMPFSE, WMPF1E, NM3, PR2VD06, PR2VD08, PR2VD10, PR2VD12

1.18 Cable Products Existing Closets will use SYSTIMAX/CommScope. All new builds will use Panduit

Description
Product
Category 6 UTP
PUP6004BU-WLP PANDUIT Enhanced CAT6
Category 6 UTP
SYSTIMAX 2071E
Category 6 Patch Panels
PANDUIT DP48688TGY DP6 PLUS 48-PORT CAT6 PUNCH-DOWN PATCH PANEL, 2U

PANDUIT DP24688TGY DP6 PLUS 24-PORT CAT6 PUNCH-DOWN PATCH PANEL, 1U

Category 6 Patch Panels

360-IPR-1100-E-GS3-2U-48 GigaSPEED XL Category 6 U/UTP Patch Panel, 2U, 48 port 360-IPR-1100-E-GS3-1U-24 GigaSPEED XL Category 6 U/UTP Patch Panel, 1U, 24 port

Faceplates
CFPE2IWY PANDUIT 2 Port Mini-com faceplate
Faceplates
SYSTIMAX M12LE White for hard-wall locations and 630B8 Stainless steel for telephone wall phone
Information Outlets
PANDUIT Mini-Com Cat6A UTP Jack, White for voice, orange for data), CJ6X88TGWH (white), CJ6X88TGOR (orange)
Information Outlets
SYSTIMAX Category 6A MGS600 Information Outlets (white for voice, orange for data)
Category 6 Patch Cables
PANDUIT TX6 Plus Cat6 Patch cable (PROVIDE TWO FOR EACH CABLE INSTALLED, VERIFY WITH OWNER FOR SIZE AND QUANTITY). Refer to section 1.9 for patch cord color.

Category 6 Patch Cables

SYSTIMAX GigaSPEED X10D cable (PROVIDE TWO FOR EACH CABLE INSTALLED, VERIFY WITH OWNER FOR SIZE AND QUANTITY). Refer to section 1.9 for patch cord color.

Copper Riser
Plenum 25 pair Category 5E
Fiber Riser
PANDUIT 12 Strand Opti-Core indoor Dist Cable, inter-locking armor, plenum-rated, OM4 (FOPPZ12Y)

PANDUIT 24 Strand Opti-Core indoor Dist Cable, inter-locking armor, plenum-rated, OM4 (FOPPZ24Y)

Fiber Riser
SYSTIMAX LazrSPEED 550 50micron (P-012-DZ-5K-FSUAQ) 12 Strand

SYSTIMAX LazrSPEED 550 50micron (P-024-DZ-5K-FSUAQ) 24 Strand

Fiber Shelves
PANDUIT Opticom 4U fiber enclosure for 12 modules (FRME4 recommend FCE4U)

PANDUIT Opticom 12-port (24 Fiber) module, Duplex LC, OM4 (FAP12WAQCLCZ)

Fiber Shelves
SYSTIMAX SD-4U with PNL-BK-024-MFA-LC02-AQ-NS (IDF’s)

SYSTIMAX SD-4U with PNL-BK-024-MFA-LC02-AQ-NS (MDF’s)

Fiber Patch Cords
PANDUIT 2-F Opti-Core patch cords, LC-LC, OM4 Length TBD (FZ2ERLNLNSNMxxx, xxx=length in meters)
Fiber Patch Cords
SYSTIMAX FEXLCLC42 (quantityand length TBD)
Fiber Connectors
PANDUIT Opti-Cam Simplex LC connector, OM4 (FLCSMCXAQY)
Fiber Connectors
SYSTIMAX BTW LC Connector, Pre-radiused for .9mm buffered fiber approved

1.19 Data Systems Products

Description
Product
Core Switches
Cisco 6XXX or 94XX Catalyst Switches
Access Layer Switches
Cisco 9300X or 94XX 48 port PoE Switches

1.20 Voice Communications Products

Description
Product

Cisco VOIP Unified Communications Suite Copper Tie One (1) 24-Port RJ45 Panel (rack mounted) installed to the voice gateway

1.21 Wireless Products

Description
Product
Wireless Access Points
Catalyst 9166I AP (W6E, tri-band 4x4) w/MERAKI
Wireless LAN access point enclosure
1077-CW9166-Oberon

1.22 Uninterrupted Power Supply Products

Description
Product
UPS for each IDF/MDF Closet
APC Smart UPS 5000VA RM # SRT5KRMXLT

Depending on gear Vertical Rack PDU (AP8641) for 9XXX switch gear (confirm with LSC OTS) image4.png image5.png image6.jpeg image7.png image7.jpeg image8.jpeg image9.png image10.jpeg image11.jpeg image12.png image13.png image14.jpeg image15.jpeg image16.jpeg image17.png image18.png image1.png image2.jpeg image3.jpeg