ESBD_358125_1714683788600_381859-25-24-05-plans.pdf
PDF 3 MB Posted
- Attached to
- RFC 381859-25-24-05 Fire Repairs, Childress DHQ
- Solicitation number
- 381859-25-24-05
- Issued by
- Cherokee County, Texas
About this file
This government file contains a set of construction documents for a fire repair project at the Childress District Headquarters (DHQ) for the Texas Department of Transportation (TxDOT). The project scope includes the restoration of a pre-engineered metal building to its pre-fire condition, with work involving the replacement of metal siding, overhead doors, electrical components, and other damaged items, as well as cleaning and minor repairs. The estimated cost of the work is $300,000.00, with a bid guaranty or bid bond of $6,000.00 required. The contract time for completion is 270 calendar days. A mandatory pre-bid conference will be held on-site on June 5, 2024, and bids must be submitted electronically by July 3, 2024. The Request for Proposal (RFP) specifies that a Historically Underutilized Business (HUB) Subcontracting Plan (HSP) is required to be submitted with the proposal. The contract will be awarded on a Lump Sum Total cost basis, and the successful bidder will receive their bid guaranty check with the executed contract. The project is subject to TxDOT's Uniform General Conditions for Construction Contracts.
No incumbent vendors or budget ranges are provided in the information given. The RFP does not mention any set-aside requirements or funding sources, but it is likely that the project is funded through state and/or local government resources.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. WORK SHALL CONFORM TO THE CONSTRUCTION DOCUMENTS &
APPLICABLE BUILDING CODES (INCLUDING FEDERAL & STATE CODES,
ORDINANCES, REGULATIONS, ETC.) CONSTRUCTION DOCUMENTS
INCLUDE DRAWINGS & SPECIFICATIONS PLUS ANY ADDENDA TO THE
AFOREMENTIONED.
2. CONSTRUCTION DOCUMENTS ARE INTENDED TO INCLUDE ITEMS
NECESSARY TO CONVEY DESIGN INTENT OF THE WORK.
MANUFACTURERS' INSTRUCTIONS SHALL BE CONSIDERED AS PART OF
THE SPECIFICATIONS WHETHER INCLUDED OR NOT IN THE
SPECIFICATION MANUAL.
3. PERIODIC SITE VISITS BY OWNER'S REPRESENTATIVE SHALL NOT BE
CONSTRUED AS SUPERVISION OF MEANS, METHODS, TECHNIQUES,
SEQUENCES OR PROCEDURES FOR CONSTRUCTION, NOR IMPLY
RESPONSIBILITY FOR PROVIDING A SAFE PLACE FOR PERFORMANCE
OF WORK BY CONTRACTOR OR CONTRACTOR'S EMPLOYEES, OR
EMPLOYEES OF SUPPLIERS, OR FOR ACCESS, VISITS, USE, WORK,
TRAVEL, OR OCCUPANCY BY ANY PERSON.
4. CONTRACTOR IS RESPONSIBLE FOR CONTINUOUS SECURITY AT
AFFECTED OPENINGS FOR THE DURATION OF THE COSNTRUCTION
CONTRACT. COORDINATE SECURITY STATUS CHANGES W/ DISTRICT
REPRESENTATIVE PRIOR TO IMPLEMENTING CHANGES.
5. CONTRACTOR SHALL:
- VERIFY DIMENSIONS & FIELD CONDITIONS BEFORE PROCEEDING.
- NOTIFY ARCHITECT OF FIELD CONDITIONS REQUIRING DEVIATIONS
FROM CONSTRUCTION DOCUMENTS BEFORE THE CONSTRUCTION
OF ANY MODIFICATION.
- PROVIDE ADEQUATE BRACING & SHORING AS NECESSARY UNTIL
PERMANENT SUPPORTS & STIFFENERS ARE INSTALLED.
- IMMEDIATELY REPAIR OR REPLACE DAMAGED OR DEFECTIVE
WORK TO THE APPROVAL OF (AND AT NO ADDITIONAL COST TO)
THE OWNER
- NOTIFY ARCHITECT & APPROPRIATE INSPECTORS AT CRITICAL
CONSTRUCTION MILESTONES IN ORDER TO OBTAIN NECESSARY
APPROVALS & INSPECTIONS PRIOR TO COMMENCEMENT OF
SUBSEQUENT WORK.
- TAKE REASONABLE PRECAUTIONS FOR THE SAFETY OF, AND
PROVIDE REASONABLE PROTECTION TO PREVENT DAMAGE,
INJURY OR LOSS TO:
a) EMPLOYEES & ALL OTHER AFFECTED PERSONS
b) ALL WORK, MATERIALS & EQUIPMENT
c) OTHER PROPERTY AT SITE OR ADJACENT THERETO.
- UPON COMPLETION OF THE WORK, REMOVE MATERIALS, TOOLS &
EQUIPMENT AND LEAVE SITE IN A CONDITION ACCEPTABLE TO
OWNER.
PROJECT
LOCATION
NORTH
THIS PROJECT INCLUDES RESTORATION OF A PRE-ENGINEEERED METAL BUILDING TO PRE-FIRE CONDITION. SCOPE INCLUDES REPLACEMENT OF METAL SIDING, OVERHEAD DOORS, ELECTRICAL CONDUIT AND WIRING, LIGHTS AND OTHER DAMAGED APPURTENANCES. SCOPE INCLUDES
CLEANING OF FIRE STAINING. SCOPE INCLUDES MINOR REPAIRS TO CONCRETE AND CMU.
COVERED ENTRY PORCH: ### SQFT.
OFFICE: #,### SQFT.
SHOP / STORAGE: #,### SQFT.
TRUCK WASH / EQUIP. ROOM: #,### SQFT.
MATERIAL SHED: #,### SQFT.
TOTAL SCOPE: NOT APPLICABLE.
TOTAL STAFF: ## FTEs
SCOPE OF WORK:
BUILDING SUMMARY: TDLR REGISTRATION:
EABPRJ NOT APPLICABLE TO REPAIR
BUILDING CODES:
INTERNATIONAL BUILDING CODE IBC - 2021
AMERICANS W/ DISABILITIES ACT ADAAG - 2010
TEXAS ACCESSIBILITY STANDARDS TAS - 2012
INTERNATIONAL ENERGY CODE IECC - 2018
INTERNATIONAL MECHANICAL CODE IMC - 2021
ASHRAE 62.1 - 2016
INTERNATIONAL PLUMBING CODE IPC - 2021
INTERNATIONAL FUEL AND GAS CODE IFGC- 2021
NATIONAL ELECTRIC CODE NEC - 2023
NATIONAL FIRE CODE NFPA 1 - 2021
NATIONAL LIFE SAFETY CODE NFPA 101 - 2021
TxDOT STANDARD SPECS FOR ... STREETS - 2014
WICHITA
FALLS
BEAUMONT
PARIS
ATLANTA
BRYAN
BROWNWOOD
AMARILLO
ABILENE
CHILDRESS
FORT
WORTH
CORPUS
CHRISTI
DALLAS
EL PASO
HOUSTON
LAREDO
LUBBOCK
LUFKIN
ODESSA
SAN
ANGELO
SAN
ANTONIO
YOAKUM
WACO
TYLER
PHARR
CHILDRESS COUNTY, TX
CHILDRESS DISTRICT (25)
Support Services Division / Facilities Planning & Management
COPYRIGHT 2022 TEXAS DEPTARTMENT OF TRANSPORTATION
6230 E. Stassney LN Austin, Texas 78744-3147 c
VICINITY MAP
INDEX OF DRAWINGS
PROJECT:
Project Manager:
STRUCTURE:
G E
N E
R A
T E
D O
N
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
SUBMITTAL
/2
/2
:5 :1
A
M C
U s e rs
\A S
T O
N E
\D o w n lo a d s \c h ild re s s C
H S
\C H
S D
H Q f ir e r e p a ir .r v t
C H
IL
D
R E
S S
D H
Q
F
IR
E R
E P
A
IR
P R
O J E
C T
N U
M B
E R
-1
-2
-2
-0
PROJECT NUMBER: 38-1859-25-24-05
SITE # 259036
BUILDING # 258063
CHRISTOPHER BECK
806-224-6737
CHRISTOPHER.BECK@TXDOT.GOV
CHILDRESS DHQ - FIRE REPAIR
NAME
Phone: (###) ###-#### E-mail: EMAIL@TXDOT.GOV
7599 US 287, CHILDRESS, TEXAS, 79201
_GENERAL
G2.01 REPAIR FLOOR PLAN
G3.01 LIGHTING REPAIR PLAN
G4.01 POWER REPAIR PLAN
G5.01 BUILDING REPAIR ELEVATIONS
_EXISTING CONSTRUCTION
D-N/a SELECTED EXISTING
CONSTRUCTION SHEETS
04/29/2024
REPAIR KEYED NOTES
1. REMOVE, AND REPLACE WITH NEW, EXTERIOR METAL WALL PANELS
FROM END OF BUILDING TO RIGHT HAND SIDE OF SECOND DOOR.
REPLACE FROM TOP OF CMU WALL TO EAVE. MATCH EXISTING IN KIND.
2. REMOVE, AND REPLACE WITH NEW, SPLIT FACE CMU FROM RIGHT
HAND EDGE OF FIRST DOOR TO 7 BLOCKS TO THE RIGHT. REPLACE WITH
FACTORY EDGE PIECES AND COMPLETE BLOCK ONLY. MATCH EXISTING.
3. REMOVE, AND REPLACE WITH NEW, EXHAUST FANS IN KIND.
4. REMOVE, AND REPLACE WITH NEW, LOUVERS, FRAMING AND ALL
ACCESSORIES ASSOCIATED WITH EXHAUST FANS IN KIND.
5. REMOVE, AND REPLACE WITH NEW, FLASHING ABOVE CANOPY FROM
END OF BUILDING TO RIGHT HAND SIDE OF SECOND DOOR. MATCH OR
EXCEED EXISTING.
6. REMOVE, AND REPLACE WITH NEW, INTERIOR METAL PANELS FROM
END OF BUILDING TO CMU WALL LABELED 6A.. SEE FLOOR PLAN.
7. REMOVE, AND REPLACE WITH NEW, WARPED GIRTS FROM EDGE OF
FIRST DOOR TO PEMB FRAMELINE. SEE FLOOR PLAN. .
8. CLEAN AND REPAINT BOLLARD TO MATCH EXISTING.
9. CLEAN AND REPAINT PILASTER TO MATCH EXISTING.
10. REMOVE, AND REPLACE WITH NEW, OVERHEAD COILING DOOR,
OPENING MECHANISM, WIRING, FRAMING AND ALL ACCESSORIES
ASSOCIATED WITH OVERHEAD DOOR. MATCH OR EXCEED EXISTING.
11. REMOVE, AND REPLACE WITH NEW, OVERHEAD DOOR, OPENING
MECHANISM WIRING AND CIRCUT, AND OTHER ACCESSORIES. MATCH OR
EXCEED EXISTING.
12 REMOVE SPALLED CONCRETE AND PATCH WITH PORTLAND CEMENT
BASED PATCHING MATERIAL SUCH AS SIKASET MORTAR OR OTHER
APPROVED MATERIAL.
13. CLEAN REMAINDER OF UNDERSIDE OF SOFFIT TO CORNER OF
BUILDING
14.CLEAN REMAINDER OF FACE OF CANOPY, AND CLEARANCE SIGNS TO
CORNER OF BUILDING.
15. REMOVE, AND REPLACE WITH NEW, SOFFIT METAL PANELS AND FACE
OF CANOPY FOR THREE BAYS. MATCH EXISTING.
ELECTRICAL KEYED NOTES
A. REMOVE, AND REPLACE WITH NEW, LIGHT FIXTURES, WIRING,
CONDUIT AND CIRCUIT UNDER FIRST THREE BAYS OF CANOPY. SEE
INFORMATIONAL SPECIFICATIONS.
B. REMOVE, AND REPLACE WITH NEW, FIRST THREE EXTERIOR WALL
PACK LIGHTS, WIRING, CONDUIT AND CIRCUIT. SEE INFORMATIONAL
SPECIFICATIONS.
C. REMOVE, AND REPLACE WITH NEW, ELECTRICAL CIRCUIT, WIRING AND
CONDUITS FOR EXHAUST FANS.
D. REMOVE, AND REPLACE WITH NEW, ELECTRICAL CIRCUIT, WIRING AND
CONDUITS FOR FIRST TWO OVERHEAD DOORS.
E. REMOVE, AND REPLACE WITH NEW, DAMAGED ELECTRICAL CIRCUIT,
WIRING AND CONDUITS FOR OVERHEAD SHOP CRANE.
F. CLEAN REMAINDER OF WALL PACK LIGHTS TO CORNER OF BUILDING.
G. REPLACE WIRING AND LIGHT FIXTURES UNDER CANOPY, FIVE BAYS.
F
6A
G
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
G E
N E
R A
T E
D O
N
REVISIONS:
COPYRIGHT 2021c
Texas of Transportation Department
R
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
SUBMITTAL
/2
/2
:1 :4
P
M C
U s e rs
\A S
T O
N E
\D o w n lo a d s \c h ild re s s C
H S
\C H
S D
H Q f ir e r e p a ir .r v t
G2.01
C H
IL
D
R E
S S
D H
Q
F
IR
E R
E P
A
IR
U S
C H
IL
D
R E
S S
T
E X
A S
P R
O J E
C T
N O
-1
-2
-2
-0
DRAWN BY: Author
ISSUED: 11/22/2019
C H
IL
D
R E
S S
C H
IL
D
R E
S S
C O
U N
T Y
REPAIR FLOOR PLAN
CHECKED BY: Checker
FLOOR PLAN NOTES
1. CONTRACTOR IS RESPONSIBLE FOR CONTINUOUS SECURITY AT
AFFECTED OPENINGS FOR THE DURATION OF THE COSNTRUCTION
CONTRACT. COORDINATE SECURITY STATUS CHANGES W/ DISTRICT
REPRESENTATIVE PRIOR TO IMPLEMENTING CHANGES.
2. INFORMATION CONCERNING EXISTING CONDITIONS IS SUITABLE FOR
PREPARATION OF THE DRAWINGS & GIVEN FOR THE CONTRACTOR'S
CONVENIENCE.
3. ENGINEER DOES NOT GUARANTEE ACCURACY OF SUCH
INFORMATION. IT IS CONTRACTOR'S RESPONSIBILITY TO INFORM
HIMSELF & NECESSARY OFFICIALS AS TO THE CONDITIONS AFFECTING
THE WORK.
4. WHERE CONSTRUCTION FEATURES EXIST, VERIFY DIMENSIONS WITH
FIELD CONDITIONS
5. COORDINATE ALL TRADES TO ENSURE COMPLETE & WORKING
INSTALLATIONS.
6. NOTIFY ENGINEER OF ANY DISCREPANCIES.
AIR QUALITY / ENERGY NOTES
1. LIMIT AIR INFILTRATION INTO CONDITIONED AND/OR OCCUPIED SPACES
BY SEALING, CAULKING, GASKETING, AND/OR WEATHER-STRIPPING
THE FOLLOWING:
- EXTERIOR JOINTS AROUND WINDOWS & DOOR FRAMES
- OPENINGS BETWEEN EXTERIOR WALLS & FOUNDATIONS
- OPENINGS BETWEEN EXTERIOR WALLS & ROOF
- OPENINGS AT PENETRATIONS OF UTILITIES THROUGH EXTERIOR
FLOORS, WALLS AND/OR ROOFS
- ALL OTHER SUCH OPENINGS IN THE BUILDING ENVELOPE.
2. PROVIDE IC-RATED RECESSED LIGHTING FIXTURES WHERE ADJACENT
TO INSULATION OTHER THAN CLOSED-CELL SPRAY FOAM.
G5.01
B
A
G
ELECTRICAL KEYED NOTES
A. REMOVE, AND REPLACE WITH NEW, LIGHT FIXTURES, WIRING,
CONDUIT AND CIRCUIT UNDER FIRST THREE BAYS OF CANOPY. SEE
INFORMATIONAL SPECIFICATIONS.
B. REMOVE, AND REPLACE WITH NEW, FIRST THREE EXTERIOR WALL
PACK LIGHTS, WIRING, CONDUIT AND CIRCUIT. SEE INFORMATIONAL
SPECIFICATIONS.
C. REMOVE, AND REPLACE WITH NEW, ELECTRICAL CIRCUIT, WIRING AND
CONDUITS FOR EXHAUST FANS.
D. REMOVE, AND REPLACE WITH NEW, ELECTRICAL CIRCUIT, WIRING AND
CONDUITS FOR FIRST TWO OVERHEAD DOORS.
E. REMOVE, AND REPLACE WITH NEW, DAMAGED ELECTRICAL CIRCUIT,
WIRING AND CONDUITS FOR OVERHEAD SHOP CRANE.
F. CLEAN REMAINDER OF WALL PACK LIGHTS TO CORNER OF BUILDING.
G. REPLACE WIRING AND LIGHT FIXTURES UNDER CANOPY, FIVE BAYS.
REPAIR KEYED NOTES
1. REMOVE, AND REPLACE WITH NEW, EXTERIOR METAL WALL PANELS
FROM END OF BUILDING TO RIGHT HAND SIDE OF SECOND DOOR.
REPLACE FROM TOP OF CMU WALL TO EAVE. MATCH EXISTING IN KIND.
2. REMOVE, AND REPLACE WITH NEW, SPLIT FACE CMU FROM RIGHT
HAND EDGE OF FIRST DOOR TO 7 BLOCKS TO THE RIGHT. REPLACE WITH
FACTORY EDGE PIECES AND COMPLETE BLOCK ONLY. MATCH EXISTING.
3. REMOVE, AND REPLACE WITH NEW, EXHAUST FANS IN KIND.
4. REMOVE, AND REPLACE WITH NEW, LOUVERS, FRAMING AND ALL
ACCESSORIES ASSOCIATED WITH EXHAUST FANS IN KIND.
5. REMOVE, AND REPLACE WITH NEW, FLASHING ABOVE CANOPY FROM
END OF BUILDING TO RIGHT HAND SIDE OF SECOND DOOR. MATCH OR
EXCEED EXISTING.
6. REMOVE, AND REPLACE WITH NEW, INTERIOR METAL PANELS FROM
END OF BUILDING TO CMU WALL LABELED 6A.. SEE FLOOR PLAN.
7. REMOVE, AND REPLACE WITH NEW, WARPED GIRTS FROM EDGE OF
FIRST DOOR TO PEMB FRAMELINE. SEE FLOOR PLAN. .
8. CLEAN AND REPAINT BOLLARD TO MATCH EXISTING.
9. CLEAN AND REPAINT PILASTER TO MATCH EXISTING.
10. REMOVE, AND REPLACE WITH NEW, OVERHEAD COILING DOOR,
OPENING MECHANISM, WIRING, FRAMING AND ALL ACCESSORIES
ASSOCIATED WITH OVERHEAD DOOR. MATCH OR EXCEED EXISTING.
11. REMOVE, AND REPLACE WITH NEW, OVERHEAD DOOR, OPENING
MECHANISM WIRING AND CIRCUT, AND OTHER ACCESSORIES. MATCH OR
EXCEED EXISTING.
12 REMOVE SPALLED CONCRETE AND PATCH WITH PORTLAND CEMENT
BASED PATCHING MATERIAL SUCH AS SIKASET MORTAR OR OTHER
APPROVED MATERIAL.
13. CLEAN REMAINDER OF UNDERSIDE OF SOFFIT TO CORNER OF
BUILDING
14.CLEAN REMAINDER OF FACE OF CANOPY, AND CLEARANCE SIGNS TO
CORNER OF BUILDING.
15. REMOVE, AND REPLACE WITH NEW, SOFFIT METAL PANELS AND FACE
OF CANOPY FOR THREE BAYS. MATCH EXISTING.
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
G E
N E
R A
T E
D O
N
REVISIONS:
COPYRIGHT 2021c
Texas of Transportation Department
R
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
SUBMITTAL
/2
/2
:1 :4
P
M C
U s e rs
\A S
T O
N E
\D o w n lo a d s \c h ild re s s C
H S
\C H
S D
H Q f ir e r e p a ir .r v t
G3.01
C H
IL
D
R E
S S
D H
Q
F
IR
E R
E P
A
IR
U S
C H
IL
D
R E
S S
T
E X
A S
P R
O J E
C T
N
-1
-2
-2
-0
DRAWN BY: DRAFTER
ISSUED: 11/22/2019
C H
IL
D
R E
S S
C H
IL
D
R E
S S
C O
U N
T Y
LIGHTING REPAIR PLAN
CHECKED BY: Checker
1/4" = 1'-0"
LIGHTING PLAN
D
C
C
D
E
ELECTRICAL KEYED NOTES
A. REMOVE, AND REPLACE WITH NEW, LIGHT FIXTURES, WIRING,
CONDUIT AND CIRCUIT UNDER FIRST THREE BAYS OF CANOPY. SEE
INFORMATIONAL SPECIFICATIONS.
B. REMOVE, AND REPLACE WITH NEW, FIRST THREE EXTERIOR WALL
PACK LIGHTS, WIRING, CONDUIT AND CIRCUIT. SEE INFORMATIONAL
SPECIFICATIONS.
C. REMOVE, AND REPLACE WITH NEW, ELECTRICAL CIRCUIT, WIRING AND
CONDUITS FOR EXHAUST FANS.
D. REMOVE, AND REPLACE WITH NEW, ELECTRICAL CIRCUIT, WIRING AND
CONDUITS FOR FIRST TWO OVERHEAD DOORS.
E. REMOVE, AND REPLACE WITH NEW, DAMAGED ELECTRICAL CIRCUIT,
WIRING AND CONDUITS FOR OVERHEAD SHOP CRANE.
F. CLEAN REMAINDER OF WALL PACK LIGHTS TO CORNER OF BUILDING.
G. REPLACE WIRING AND LIGHT FIXTURES UNDER CANOPY, FIVE BAYS.
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
G E
N E
R A
T E
D O
N
REVISIONS:
COPYRIGHT 2021c
Texas of Transportation Department
R
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
SUBMITTAL
/2
/2
:1 :4
P
M C
U s e rs
\A S
T O
N E
\D o w n lo a d s \c h ild re s s C
H S
\C H
S D
H Q f ir e r e p a ir .r v t
G4.01
C H
IL
D
R E
S S
D H
Q
F
IR
E R
E P
A
IR
U S
C H
IL
D
R E
S S
T
E X
A S
P R
O J E
C T
N
-1
-2
-2
-0
DRAWN BY: Author
ISSUED: 11/22/2019
C H
IL
D
R E
S S
C H
IL
D
R E
S S
C O
U N
T Y
POWER REPAIR PLAN
CHECKED BY: Checker
EXTERIOR ELEVATION NOTES
1. DIMENSIONS GIVEN ARE TO FACE OF FRAMING, UNLESS INDICATED
OTHERWISE.
2. WHERE CONSTRUCTION FEATURES EXIST, VERIFY DIMENSIONS WITH
FIELD CONDITIONS & NOTIFY ARCHITECT OF DISCREPANCIES.
3. INFORMATION CONCERNING EXISTING CONDITIONS IS SUITABLE FOR
THE PREPARATION OF THE DRAWINGS & GIVEN FOR THE
CONTRACTOR'S CONVENIENCE. ARCHITECT DOES NOT GUARANTEE
ACCURACY OF SUCH INFORMATION. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO INFORM HIMSELF & NECESSARY OFFICIALS AS TO
THE CONDITIONS AFFECTING THE WORK.
10 2
3 34 4
REPAIR KEYED NOTES
1. REMOVE, AND REPLACE WITH NEW, EXTERIOR METAL WALL PANELS
FROM END OF BUILDING TO RIGHT HAND SIDE OF SECOND DOOR.
REPLACE FROM TOP OF CMU WALL TO EAVE. MATCH EXISTING IN KIND.
2. REMOVE, AND REPLACE WITH NEW, SPLIT FACE CMU FROM RIGHT
HAND EDGE OF FIRST DOOR TO 7 BLOCKS TO THE RIGHT. REPLACE WITH
FACTORY EDGE PIECES AND COMPLETE BLOCK ONLY. MATCH EXISTING.
3. REMOVE, AND REPLACE WITH NEW, EXHAUST FANS IN KIND.
4. REMOVE, AND REPLACE WITH NEW, LOUVERS, FRAMING AND ALL
ACCESSORIES ASSOCIATED WITH EXHAUST FANS IN KIND.
5. REMOVE, AND REPLACE WITH NEW, FLASHING ABOVE CANOPY FROM
END OF BUILDING TO RIGHT HAND SIDE OF SECOND DOOR. MATCH OR
EXCEED EXISTING.
6. REMOVE, AND REPLACE WITH NEW, INTERIOR METAL PANELS FROM
END OF BUILDING TO CMU WALL LABELED 6A.. SEE FLOOR PLAN.
7. REMOVE, AND REPLACE WITH NEW, WARPED GIRTS FROM EDGE OF
FIRST DOOR TO PEMB FRAMELINE. SEE FLOOR PLAN. .
8. CLEAN AND REPAINT BOLLARD TO MATCH EXISTING.
9. CLEAN AND REPAINT PILASTER TO MATCH EXISTING.
10. REMOVE, AND REPLACE WITH NEW, OVERHEAD COILING DOOR,
OPENING MECHANISM, WIRING, FRAMING AND ALL ACCESSORIES
ASSOCIATED WITH OVERHEAD DOOR. MATCH OR EXCEED EXISTING.
11. REMOVE, AND REPLACE WITH NEW, OVERHEAD DOOR, OPENING
MECHANISM WIRING AND CIRCUT, AND OTHER ACCESSORIES. MATCH OR
EXCEED EXISTING.
12 REMOVE SPALLED CONCRETE AND PATCH WITH PORTLAND CEMENT
BASED PATCHING MATERIAL SUCH AS SIKASET MORTAR OR OTHER
APPROVED MATERIAL.
13. CLEAN REMAINDER OF UNDERSIDE OF SOFFIT TO CORNER OF
BUILDING
14.CLEAN REMAINDER OF FACE OF CANOPY, AND CLEARANCE SIGNS TO
CORNER OF BUILDING.
15. REMOVE, AND REPLACE WITH NEW, SOFFIT METAL PANELS AND FACE
OF CANOPY FOR THREE BAYS. MATCH EXISTING.
AIR QUALITY / ENERGY NOTES
1. LIMIT AIR INFILTRATION INTO CONDITIONED AND/OR OCCUPIED SPACES
BY SEALING, CAULKING, GASKETING, AND/OR WEATHER-STRIPPING
THE FOLLOWING:
- EXTERIOR JOINTS AROUND WINDOWS & DOOR FRAMES
- OPENINGS BETWEEN EXTERIOR WALLS & FOUNDATIONS
- OPENINGS BETWEEN EXTERIOR WALLS & ROOF
- OPENINGS AT PENETRATIONS OF UTILITIES THROUGH EXTERIOR
FLOORS, WALLS AND/OR ROOFS
- ALL OTHER SUCH OPENINGS IN THE BUILDING ENVELOPE.
2. PROVIDE IC-RATED RECESSED LIGHTING FIXTURES WHERE ADJACENT
TO INSULATION OTHER THAN CLOSED-CELL SPRAY FOAM.
THIS DRAWING CREATED FOR PRODUCTION ON 22"x34" SHEET SIZE. DO NOT SCALE PRINTS.
G E
N E
R A
T E
D O
N
REVISIONS:
COPYRIGHT 2021c
Texas of Transportation Department
R
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
SUBMITTAL
/2
/2
:1 :4
P
M
1 Date 1 Initials1
C U s e rs
\A S
T O
N E
\D o w n lo a d s \c h ild re s s C
H S
\C H
S D
H Q f ir e r e p a ir .r v t
G5.01
C H
IL
D
R E
S S
D H
Q
F
IR
E R
E P
A
IR
U S
C H
IL
D
R E
S S
T
E X
A S
P R
O J E
C T
N
-1
-2
-2
-0
DRAWN BY: Author
ISSUED: 11/22/2019
C H
IL
D
R E
S S
C H
IL
D
R E
S S
C O
U N
T Y
BUILDING REPAIR ELEVATIONS
CHECKED BY: Checker
For information only
Amy Stone Checker Line
Amy Stone Checker Line
| Sheets |
| G0.0 - COVER SHEET |
File details come from the government source that posted it. Updated .