EP2 Building Drawings~2.pdf
PDF 6 MB Posted
- Solicitation number
- 69CRC-S2658
- Issued by
- Clark County, Nevada
About this file
This document appears to be a set of drawings and specifications related to the Boulder Flats Solar Interconnection Project, Contract No. CRCBF-14, which is being procured by the Colorado River Commission of Nevada. The project involves furnishing all labor, equipment, materials, and services required for the transmission line and switchyard construction work. The drawings provide detailed information on the electrical equipment, enclosure, structural framing, and grounding requirements for this project located in Clark County and Henderson City, Nevada. The drawings cover topics such as cable tray layout, wireway layout, electrical isometric views, exterior and interior elevations, liftbase assembly, and general construction details. No specific bid date, award date, or contract term is provided in the document.
The document does not contain information on pricing terms, set asides, incumbents, funding requirements, or other salient commercial details. This appears to be a technical specification package intended to provide bidders with the necessary design information to respond to the solicitation for the Boulder Flats Solar Interconnection Project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2300 S. 51st ST
MILWAUKEE, WI 53219
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
1/1 TYPICAL ELECTRICAL HOUSE ENCLOSURE
EQUIPMENT SHELTER UN-MANNED
NTS
SEE NOTES FOR ON SITE WORK
DRAWINGS PREPARED FOR: EP2
PROJECT NAME: BOULDER FLATS SUBSTATION
LOCATION: LAS VEGAS, NV
GLOBAL POWER COMPONENTS JOB# 45-37439
DESIGN NOTES:
THE WORK SPECIFIED HEREIN HAS BEEN DESIGNED IN ACCORDANCE WITH:
ASCE 7-16
ROOF LIVE LOADS: 30 PSF
ULTIMATE WIND SPEED: 109 MPH, EXPOSURE C
FLOOR LOADING: 250 PSF
BASE DEFLECTION: L/240
BUILDING RISK CATEGORY: IV
BUILDING OCCUPANCY CLASSIFICATION: S2
BUILDING CONSTRUCTION TYPE: V-B
SEISMIC DESIGN CATEGORY: D
SEISMIC SPECTRAL RESPONSE ACCELERATIONS: "Ss": 0.589g "S1": 0.192g
SITE CLASS: D
GROUND SNOW LOAD: 5 PSF
AREA: 512 SQ.FT
HEIGHT: 12'11-7/8"
FIRE SEPARATION DISTANCE: >=10'
NUMBER OF STORIES: 1
DESIGN OCCUPANT LOAD: 1
WEIGHTS:
ENCLOSURE: 13665 LBS
LIFTBASE: 15137 LBS
ELECTRICAL GEAR: 18596 LBS
TOTAL WEIGHT: 47398 LBS
GENERAL NOTES:
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN ACCORDANCE WITH
THE REQUIREMENTS OF THE ASCE 7-16
2. STEEL & ALUMINUM ENCLOSURE SHALL CONFORM TO THE DETAILS SHOWN HEREIN.
ALL OTHER CONNECTIONS AND DETAILS NOT ILLUSTRATED IN THIS DOCUMENT SHALL
CONFORM TO THE TYPICAL ASSEMBLY AS SET FORTH BY MANUFACTURER.
3. THE CONTRACTOR IS RESPONSIBLE TO INSULATE MEMBERS FROM DISSIMILAR MATERIALS
TO PREVENT ELECTROLYSIS.
4. ALL FASTENERS TO BE #14 SAE GRADE 5 CADMIUM PLATED OR GREATER WITH
CORROSION RESISTANT MATERIAL.
5. WALL CONSTRUCTION UTILIZES 12GA STEEL STUDS & 14GA STEEL GIRTS, BOTH S.S. GR 50 STEEL, WITH 26GA GR 50 R-5 PANELS. TYPICAL SEAMS AT 16" OC UNLESS OTHERWISE. A +/-3" ALLOWABLE
TOLERANCE MAY BE USED FOR THE SPACING OF PANEL SEAMS ILLUSTRATED HEREIN FOR
CONSTRUCTABILITY AND INTERIOR OBSTRUCTIONS LOCATED WITHIN THE ENCLOSURE
6. FOR STEEL MEMBERS ALL ANCHORS SHALL BE SPACED WITH 3x DIAMETER MIN. SPACING TO ADJACENT ANCHORS AND 3x DIAMETER MIN. END DISTANCE. FOR ALUMINUM MEMBERS ALL ANCHORS SHALL BE SPACED WITH 2x DIAMETER END DISTANCE AND 2.5x DIAMETER MIN. SPACING TO ADJACENT ANCHORS, UNLESS NOTED OTHERWISE.
7.ALL CONCRETE SUBSTRATES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI
AS VERIFIED BY OTHERS U.N.O.
8. ALL WELDING IS IN CONFORMANCE WITH AWS D1.1 BY QUALIFIED WELDERS. ALL DIMENSIONS
SHOWN HEREIN REPRESENT UNITS IN INCHES, UNLESS OTHERWISE NOTED
9.MINIMUM DESIGNED TEMP OF 75 FOR COOLING. HVAC SYSTEM DESIGNED FOR (2) PRIMARY UNITS
TO PERFORM COOLING REQUIREMENTS.
SPECIAL CONDITIONS AND LIMITATIONS:
1. ACCESSIBILITY TO THIS BUILDING, INCLUDING PARKING IS TO BE PROVIDED BY OTHERS AND
CONSTRUCTED IN ACCORDANCE WITH ALL LOCAL BUILDING CODES.
2. BATTERIES ARE TO BE SUPPLIED AND INSTALLED BY OTHERS ON-SITE AND ARE SUBJECT TO
INSPECTION AND APPROVAL OF THE LOCAL JURISDICTION
ON SITE WORK:
3. HOIST STRUCTURE IS OUTSIDE THE SCOPE OF THIS CERTIFICATION AND SHALL BE DESIGNED BY OTHERS
4. ALL SITE WORK SUCH AS FOUNDATION AND ANCHORAGE, GRADING, ELECTRICAL UTILITY CONNECTION, GROUNDING, HVAC UNIT REINSTALLATION, GUTTERS, ETC. ARE TO BE INSTALLED BY OTHERS IN ACCORDANCE WITH
LOCAL BUILDING CODES AND ARE SUBJECT TO APPROVAL OF LOCAL OFFICIALLIST
SHEET NO.
2-3
8-9
10-11
13-15
17-20
E1
E2
E3-E9
PLAN INDEX:
COVER SHEET-DESIGN NOTES & SPECIFICATIONS
PROJECT BILL OF MATERIALS
ENCLOSURE PLAN VIEW
CABLE TRAY LAYOUT
WIREWAY LAYOUT
ELECTRICAL GEAR ISOMETRIC VIEW
EXTERIOR ELEVATION VIEWS
LIFTBASE ELEVATION VIEWS
SHIPPING DETAIL
INTERIOR ELEVATION VIEWS
GENERAL CONSTRUCTION DETAILS
ENCLOSURE STRUCTURAL FRAMING
GENERAL LIFTBASE WELDMENT
ELECTRICAL PLAN VIEW
GROUNDING DETAIL
ELECTRICAL WIRING DIAGRAM
TEXAS NOTES
SPECIAL CONDITIONS AND LIMITATIONS:
1. PER SECTION 203.5 OF 2012 TAS, THIS BUILDING IS NOT REQUIRED TO MEET TAS OR BE ON AN ACCESSIBLE ROUTE
2. OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE BUILDING OWNER OR DESIGNATED
REPRESENTATIVE WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE
ON SITE WORK:
3. HOIST STRUCTURE IS OUTSIDE THE SCOPE OF THIS CERTIFICATION AND SHALL BE DESIGNED BY OTHERS
4. ALL SITE WORK SUCH AS FOUNDATION AND ANCHORAGE, GRADING, ELECTRICAL UTILITY CONNECTION, GROUNDING, HVAC UNIT REINSTALLATION, GUTTERS, ETC. ARE TO BE INSTALLED BY OTHERS IN ACCORDANCE WITH
LOCAL BUILDING CODES AND ARE SUBJECT TO APPROVAL OF LOCAL OFFICIALLIST
REVISIONS
REV. DESCRIPTION DATE APPROVED
0 INITIAL RELEASE 11/3/2022 YXZ
MINIMUM STEEL PROPERTIES
GRADE SHAPE Fy (KSI) Fu (KSI)
ASTM A992 W-BEAMS 50 65
ASTM A36 C-CHANNEL/PLATE 36 58
ASTM SS GRADE 50 STUD/GIRT/PURLIN/TRUSS 50 65
ASTM A1011 CS TYPE B FLOOR JOIST CROSS MEMBERS 33 52
24GA MCELROY 218 PANEL ROOF 50 65
26GA MCELROY R-PANEL EXTERIOR WALLS 50 65
24GA MCELROY MARQUEE-LOK PANEL INTERIOR WALL/CEILING PANELS 50 65
OF
spelkowski Highlight
109 MPH, EXPOSURE C
spelkowski Highlight
IV
spelkowski Highlight S2 spelkowski Highlight D spelkowski Highlight
250 PSF
spelkowski Highlight
5 PSF
spelkowski Callout Provide additional detail on this, is this 75F minimum cooling temp during the hottest day of the year?
spelkowski Callout Pick and place of the enclosure is by EP2, including procurement of required spreader bar for lift
BILL OF MATERIALS ITEM DESCRIPTION QTY PART NO
CUSTOMER EP2 INTERIOR 3070 PERSONNEL DOOR - (LHR) 1
PROJECT NAME BOULDER FLATS SUBSTATION 16GA GAL PRIMED, WELDED, 3-3/4" RABBIT NO SILL 1 LAFORCE WHMF JOB NO 45-37439 18GA GAL PRIMED, INSULATED, FLUSH, "B" LABELED, 1.5 HR FIRE RATED 1 LAFORCE HMD
STAINLESS STEEL HINGES 3 HAGER BB1191 NRP US32D
BUILDING CONSTRUCTION EXTERIOR FRAME: 12GA STUDS, 14GA TRACKS, 14GA GIRTS S.S. 50KSI POST FRAMING FIRE EXIT DEVICE (UL305) 1 VON DUPRIN 22EO-F-3'-SP28
EXTERIOR SHEETING: 26GA 50KSI R-PANEL AUTO DOOR CLOSER WITH HOLD OPEN 1 NORTON 8301H 689 ROOF PANELS: 24GA ASTM A792 50KSI - 2" MAXIMA 218 DOOR HANDLE 1 VON DUPRIN 230L-06 SP28 (LHR)
INTERIOR & CEILING: 24GA 50KSI MARQUEE-LOK RIM STRIKE 1 VON DUPRIN 299F
LOCK CYLINDER 1 SCHLAGE 20-001 C123 626 114
INSULATION WEATHER STRIP 1 REESE 807A - 36"
CEILING 9.5IN FIBERGLASS BATT W. BACKING + 2IN INSULATION BLANKET R30 + R7 KNAUF + OWENS CORNING DOOR SHOE 1 NGP 313VA - 36" WALLS 3IN FIBERGLASS BATT W. BACKING + 2IN INSULATION BLANKET R15 + R7 KNAUF + OWENS CORNING FLOOR 5IN FOAMSULATE CELL SPRAY APPLIED POLYURETHANE FOAM - UES ER #626 R34 FOAMSULATE CC HVAC BARD - 2 TON WALL MOUNT AC, 11 EER, 230/208-1-60, 5 KW HEAT STRIP, BLANK-OFF PLATE, MERV 8 FILTER, GRAY
CABINETS, LOW AMBIENT CONTROL, HIGH/LOW PRESSURE ALARM CONTACTS, 800 C.F.M 2 W24AB-A05BP4XXJ
EMULSION UNDERCOATING TECTYL TECTYL 351S
BARD - LEAD-LAG CONTROLLER WITH ENHANCED ALARMS 1 MC4002-B
FINISH BARD - 20" X 8" ALUMINUM SUPPLY GRILLE WITH BRUSHED ANODIZED FINISH; FOR BARD 1.5 AND 2 TON; 2" FLANGE 2 SG-2W ENCLOSURE/LIFTBASE EXTERIOR ASH GRAY KYNAR 500 BARD - 20"X 12" ALUMINUM RETURN GRILLE WITH BRUSHED ANODIZED FINISH; FOR BARD 1.5 AND 2 TON; 2" FLANGE 2 RG-2W
ENCLOSURE INTERIOR REGAL WHITE KYNAR 500
LIFTBASE FLOOR COATING GRAY-16050 NON-SKID COATING CHEMLINE-7025 HVAC DISCONNECT SQUARE D - 30 AMP NON-FUSED DISCONNECT - 3-POLE, 600V, HEAVY DUTY, NEMA 3R 2 HU361RB
SQUARE D - 30 AMP NON-FUSED DISCONNECT GROUND KIT 2 GTK03
ITEM DESCRIPTION QTY PART NO. INTERIOR LIGHT HOLOPHANE - HRTC SERIES 4 FT INTERIOR LED LIGHT - 5000 LUMENS, 120V, 0-10V DIMMING, 40K, 80 CRI WHITE
FINISH, 27.4 WATTS 15 HRTCL485000LMMVOLTGZ1040K80CRIWH
DOORS
EXTERIOR 3070 PERSONNEL DOOR - (LHR) 1
16GA GAL PRIMED, WELDED, 3-3/4" RABBIT W/SILL 1 LAFORCE WHMF SWITCHES DIMMING MODULE 2 LUT RMJS-8TN-DV-B 18GA GAL PRIMED, INSULATED, FLUSH, "B" LABELED, 1.5 HR FIRE RATED 1 LAFORCE HMD CEILING MOUNTED OCCUPANCY SENSOR 5 LUT LRF2-OCR2B-P-WH STAINLESS STEEL HINGES 3 HAGER BB1191 NRP US32D DIMMING SWITCH BOX MOUNT BRACKET 3 LUT PICO-WBX-ADAPT FIRE EXIT DEVICE (UL305) 1 VON DUPRIN 22EO-F-3'-SP28 DIMMING SWITCH 3 LUT PJ2-3BRL-WH-L01R AUTO DOOR CLOSER WITH HOLD OPEN 1 NORTON 8301H 689 LUTRON - SCREWLESS WALL PLATE FOR REMOTE DIMMING SWITCH 3 CW-1-WH
DOOR HANDLE 1 VON DUPRIN 230L-06 SP28 (LHR)
ELECTRIC RIM STRIKE 1 HES 9500-12/24D-630 EMERGENCY EXIT SIGN HUBBELL - "CS" SERIES LED EMERGENCY EXIT LIGHT WITH BATTERY BACK UP - 3.5 WATTS 3 CSEUER
LOCK CYLINDER 1 SCHLAGE 20-001 C123 626 114
36" ALUMINUM THRESHOLD 1 REESE S484AV - 36" EXTERIOR LIGHT HOLOPHANE - W4GLED SERIES EXTERIOR LED LIGHT - 30 LED PERFORMANCE PACKAGE, 50K, TYPE III MEDIUM
DISTRIBUTION, MULTIVOLT, SPD, BUTTON STYLE PHOTOCELL, GREY FINISH - 104 WATTS, 8427 LUMENS 6 W4GLED30C100050KT3MMVOLTSPDPCBGYSDP
WEATHER STRIP 1 REESE 807A - 36"
DOOR SHOE 1 NGP 313VA - 36"
SIGN "DANGER ELECTRICAL EQUIPMENT/AUTHORIZED PERSONNEL ONLY" 1 BRADY 84068 RECEPTACLES HUBBELL - INTERIOR DUPLEX RECEPTACLE - 20 AMP WHITE 6 5362W
GEORGE RISK - INTRUSION ALARM DOOR CONTACTS - FORM "C" CONTACTS, SPDT, 175V
DC MAXIMUM SWITCHING VOLTAGE 1 4402-A
STEEL CITY - SINGLE GANG INTERIOR DUPLEX GFCI COVER 6 RSL 12
HUBBELL - EXTERIOR GFCI RECEPTACLE - WEATHER & TAMPER RESISTANT 20 AMP GRAY 2 GFTWRST20GY
RED DOT - SINGLE GANG EXTERIOR GFCI RECEPTACLE BOX - WEATHERPROOF 2 IHD3-1
3070 PERSONNEL DOOR - (RHR) 1 HUBBELL - SINGLE GANG EXTERIOR GFCI IN-USE WEATHER RESISTANT COVER 2 ML500G
16GA GAL PRIMED, WELDED, 3-3/4" RABBIT W/SILL 1 LAFORCE WHMF
12" REMOVABLE TRANSOM W. ASTRAGAL 1 POWER DISTRIBUTION
ENCLOSURE
HOFFMAN - 36" x 36" x 8" ENCLOSURE - NEMA 12 1 A363608LP
18GA GAL PRIMED, INSULATED, FLUSH, "B" LABELED, 1.5 HR FIRE RATED 1 LAFORCE HMD HOFFMAN - ENCLOSURE BACKPLATE 1 A36P36
STAINLESS STEEL HINGES 3 HAGER BB1191 NRP US32D
FIRE EXIT DEVICE (UL305) 1 VON DUPRIN 22EO-F-3'-SP28 HYDROGEN MITIGATION
SYSTEM
MERSEN - 3 POLE DISTRIBUTION BLOCK - (2) 600 KCMIL - #2 PRIMARY (2) 600 KCMIL - #2 SECONDARY 1 MPDB69653
AUTO DOOR CLOSER WITH HOLD OPEN 1 NORTON 8301H 689 MERSEN - DISTRIBUTION BLOCK COVER 3 MPDBC6869 DOOR HANDLE 1 VON DUPRIN 230L-06 SP28(RHR) MERSEN - SINGLE POLE DISTRIBUTION BLOCK - (2) 4/0 - #6 PRIMARY - (6) #2-14 SECONDARY 1 MPDB67541 ELECTRIC RIM STRIKE 1 HES 9500-12/24D-630 HOFFMAN - 24" x 24" x 6" ENCLOSURE - NEMA 12 1 A242406LP LOCK CYLINDER 1 SCHLAGE 20-001 C123 626 114 HOFFMAN - ENCLOSURE BACKPLATE 1 A24P24 36" ALUMINUM THRESHOLD 1 REESE S484AV - 36" INTERMATIC - 24 HOUR DIGITAL TIMER 1 ET1125C
WEATHER STRIP 1 REESE 807A - 36" HYDROGEN DETECTION 1 SBS-H2
DOOR SHOE 1 NGP 313VA - 36"
SIGN "DANGER ELECTRICAL EQUIPMENT/AUTHORIZED PERSONNEL ONLY" 1 BRADY 84068 SMOKE DETECTOR GENTEX - 120V AC SMOKE DETECTOR 1 S1209F
GEORGE RISK - INTRUSION ALARM DOOR CONTACTS - FORM "C" CONTACTS, SPDT, 175V
DC MAXIMUM SWITCHING VOLTAGE 1 4402-A
GROUND LOOP 2" COOPER GROUND LOOP 94 N/A
SEE NOTES
212 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
ENCLOSURE BILL OF MATERIALS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
GLOBAL POWER COMPONENTS. ANY REPRODUCTION IN PART OR WHOLE WITHOUT
THE WRITTEN PERMISSION OF GLOBAL POWER COMPONENTS IS PROHIBITED.
spelkowski Callout Is Ash Gray ANSI 70?
spelkowski Rectangle spelkowski Text Box Appreciate the modern design, however please replace this with just three, three-way switches, Leviton per spec
ITEM DESCRIPTION QTY PART NO
AC PANELBOARD SQUARE D - AC PANELBOARD SURFACE MOUNT ENCLOSURE - NEMA 1 2 MH62BE
SQUARE D - AC PANELBOARD INTERIOR - 120 / 208V AC - SINGLE PHASE, 3 WIRE, 10 KAIC, 42 CIRCUIT, 400 AMP TOP FED MAIN BREAKER 2 NQ-MB
SQUARE D - AC PANELBOARD DOOR / TRIM 2 NC62VS
CABLE TRAY COOPER B-LINE ALUMINUM REDI RAIL CABLE TRAY STRAIGHT SECTION - 24" x 6" x 144" 3 RSI06A09SL-24-144
COOPER B-LINE ALUMINUM REDI RAIL CABLE TRAY HORIZONTAL TEE - 24" x 6" - 12" RADIUS 1 RSI06A09HT-24-R12
COOPER B-LINE ALUMINUM REDI RAIL CABLE TRAY HORIZONTAL CROSS - 24" x 6" - 12" RADIUS 1 RSI06A09HX-24-R12
WIREWAY HOFFMAN - 4" x 4" WIREWAY STRAIGHT SECTION - NEMA 1 10 F44G120
HOFFMAN - 4" x 4" WIREWAY 90 6 F44G90E
HOFFMAN - WIREWAY COUPLING 40 F44GUC
INTAKE DAMPER GREENHECK 12" x 12" DAMPER, REVERSED FLANGE, MOTORIZED 1 VCD-23
BELIMO ACTUATOR 1 TFB120
EXHAUST FAN 1/3HP 115/208-230V AC SHUTTER MOUNTED EXPLOSION PROOF EXHAUST FAN-320 C.F.M 1 SD08-XPF
45 WEATHERHOOD 1 N/A
CARD READER PROVISION BOX RED DOT - SINGLE GANG EXTERIOR CARD READER BOX 2 IHD3-1
RED DOT - SINGLE GANG BOX WEATHERPROOF COVER WITH GASKET 2 CCB
MISC. DOWNSPOUTS 6 N/A
ATS ASCO - 400 AMP AUTOMATIC TRANSFER SWITCH - 120 / 240V AC - SINGLE PHASE 3 WIRE WITH SWITCHED NEUTRAL 1 J03ATSB20400FGXC11BE18RX
213 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
ENCLOSURE BILL OF MATERIALS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
GLOBAL POWER COMPONENTS. ANY REPRODUCTION IN PART OR WHOLE WITHOUT
THE WRITTEN PERMISSION OF GLOBAL POWER COMPONENTS IS PROHIBITED.
XZ (UP)
Y
AA
387.97 32'-4"
24 2'
20 1'-8"
20 1'-8"
5.7
5 3 /4"
TY
P.
26 2'-2"
TYP.
36 3'
.5
3'- 1/
2"28 .75
2'- 4 3
/4"
6.6
6 5 /8"
36 3' 15 1'-3"9.3
9 5 /16
.5
3'- 1/
2"
1'-
9"
SP
ILL
CO
NT
AI
NM
EN
T
TY
P.
3"
1.5 1 1
/2"
88 7'-4" SPILL CONTAINMENT, TYP.
2 2"
TYP.
47 3'-11"
29 2'-5"
1'-
10 10"
137 11'-5" BATTERY ROOM LENGTH
83 6'-11"
BATTERY ROOM WIDTH
7"
T
YP
27 2'-3" TYP.
14.5 1'-2 1/2"
2'-
1"
TY
P.
10.5 10 1/2"
39 3'-3" 20 1'-8"
TYP.
64 5'-4"
100 8'-4" TYP. 18 1'-6"
TYP.
125 10'-5" TYP.
9"
T
YP
152 12'-8"
10.74 10 3/4"
.06
1'- 9 1
/16
2'
88.75 7'-4 3/4"6.63 6 5/8"
4.86 4 7/8"
TYP.
5.9
'-4
3'
D
OO
R
3.9
84 7' BATTERY RACK, TYP.
36 3' DOOR
13.19 1'-1 3/16"
3'
D
OO
R
.99 1'-
4"
9 9"
156 13'
2'-
2"
TY
P.
46.38 3'-10 3/8"
2'-
2"
TY
P.
104 8'-8" 26 2'-2"
TYP.
91 7'-7"
140 11'-8"
90 7'-6"
115 9'-7"
36 3'
.5
3'- 1/
2"
4.4
8'-
8 1 /2"
40.49 3'-4 1/2"
31.99 2'-8" 108 9' 108 9' 108 9' 31.99 2'-8"
N
SIDE A
SIDE C
SIDE B
SIDE D
YARD
TERMINATION
CABINET
1000#
ATS-186#
120/208V AC PANEL #1
150#
120/208V AC PANEL #2
150#
POWER DISTRIBUTION
ENCLOSURE-100#
HVAC #1
2 TON
335#
HVAC #2
2 TON
335#
30A HVAC
DISCONNECT 02
30#
30A HVAC
DISCONNECT 01
30#
125VDC BATTERY RACK W.
SPILL CONTAINMENT #1
2500#EYE WASH
STATION-110#
125VDC
BATTERY
CHARGER 02
750#
125VDC
BATTERY
CHARGER 01
750#
200A FUSED BATTERY
DISCONNECT SWTICH
(2x STACKED-50# EACH)
DC TRANSFER SWTICH
(2x STACKED-50# EACH)
120V DC PANEL #1
200#
120V DC PANEL #2
200#
MC4002-B
HYDROGEN MITIGATION
SYSTEM-35#
DOOR
LHR
DOOR
RHR W.
TRANSOM
3070 INTERIOR
DOOR
LHR
1/4 TYPICAL ENCLOSURE PLAN VIEW
1:35
125VDC BATTERY RACK W.
SPILL CONTAINMENT #2
2500#
BATTERY ROOM
MAIN ROOM
RELAY PANEL #3
BOULDER
FLATS-SOLAR
COLLECTOR
STATION LINE
1000#
RELAY PANEL #5
BKR #182 & #282
PROTECTION
1000#
RELAY PANEL #1
BOULDER
FLATS-MEAD LINE
1000#
RELAY PANEL #4
SPARE PANEL
1000#
RELAY PANEL #2
BOULDER
FLATS-NEWPORT
LINE PROTECTION
1000#
CONCRETE PAD
(BY OTHERS)
125VDC RELAY PANEL FRONT
125VDC RELAY PANEL FRONT
RELAY PANEL #6
BKR #382
PROTECTION
1000#
RELAY PANEL #8
COMMUNICATION
PANEL
1000#
RELAY PANEL #9
SYNCHRONIZATION
PANEL
1000#
RELAY PANEL #7
METERING PANEL
1000#
REACTIONS ARE AT THE BASE OF THE FLOOR STRUCTURE.
WIND AND SEISMIC LOADS ARE REVERSIBLE. VALUES SHOWN ARE FOR THE +X AND +Y DIRECTIONS.
VERTICAL REACTIONS (Z) FOR WIND AND SEISMIC LOADS INCLUDE PORTION FROM THE OTM. (SEE CALCULATIONS)
+X IS IN THE LONGITUDINAL DIRECTION
+Y IS IN THE TRANSVERSE DIRECTION
+Z IS IN THE UPWARD DIRECTION
UNFACTORED LOADS ARE IN LBS AND ARE NOT COMBINED.
LOADS ACT AT THE BASE OF THE FLOOR STRUCTURE.
WIND AND SEISMIC LOADS ARE REVERSABLE.
NOTES:
1. INTERIOR CEILING HEIGHT AT 119".
2. DASHED LINES REPRESENT EQUIPMENT INSTALLED BY OTHERS -------
CONCRETE PIER
MIN LOCATIONS REQUIRED
(BY OTHERS)
214 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
ENCLOSURE PLAN VIEW
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
AA
9"
144 12'
51.5 4'-3 1/2"
.75 3'-
1 3 /4"
131.5 10'-11 1/2"
31.38 2'-7 3/8"
3.08 3 1/16"
6.1 6 1
/8"
4'
61.5 5'-1 1/2"
.9 5'-
7/
8"
1/5 TYPICAL CABLE TRAY LAYOUT
1:35
SIDE A
SIDE C
SIDE B
SIDE D
ATS
120/208V AC PANEL #1
120/208V AC PANEL #2
POWER DISTRIBUTION ENCLOSURE
HVAC #1
2 TON
HVAC #2
2 TON
30A HVAC DISCONNECT 02
30A HVAC DISCONNECT 01
125VDC BATTERY RACK W.
SPILL CONTAINMENT #2
125VDC BATTERY RACK W.
SPILL CONTAINMENT #1EYE WASH
STATION
125VDC
BATTERY
CHARGER 02
125VDC
BATTERY
CHARGER 01
200A FUSED BATTERY
DISCONNECT SWTICH
(2x STACKED)
DC TRANSFER SWTICH
(2x STACKED)
120V DC PANEL #1
120V DC PANEL #2
MC4002-B
HYDROGEN MITIGATION SYSTEM
DOOR
LHR
DOOR
RHR W.
TRANSOM
3070 INTERIOR
DOOR
LHR
BATTERY ROOM
MAIN ROOM
125VDC RELAY PANEL FRONT
125VDC RELAY PANEL FRONT
RELAY PANEL #1
BOULDER
FLATS-MEAD LINE
RELAY PANEL #5
BKR #182 & #282
PROTECTION
RELAY PANEL #4
SPARE PANEL
RELAY PANEL #3
BOULDER FLATS-SOLAR
COLLECTOR STATION LINE
RELAY PANEL #2
BOULDER
FLATS-NEWPORT
LINE PROTECTION
YARD
TERMINATION CABINET
RELAY PANEL #9
SYNCHRONIZATION PANEL
RELAY PANEL #7
METERING PANEL
RELAY PANEL #6
BKR #382 PROTECTION
RELAY PANEL #8
COMMUNICATION
PANEL
NOTES:
1. INTERIOR CEILING HEIGHT AT 119".
2. HEIGHT TO BOTTOM OF CABLE TRAY 102"
CABLE TRAY BILL OF MATERIALS
ITEM NO. DESCRIPTION PART NO. QTY. LENGTH
1 B-LINE REDI-RAIL RSI06A09HT-24-R12 1 N/A
2 B-LINE REDI-RAIL RSI06A09HX-24-R12 1 N/A
3 B-LINE REDI-RAIL RSI06A09SL-24-144 1 144.00
4 B-LINE REDI-RAIL RSI06A09SL-24-144 1 9.00
5 B-LINE REDI-RAIL RSI06A09SL-24-144 1 37.75
6 B-LINE REDI-RAIL RSI06A09SL-24-144 1 51.50
7 B-LINE REDI-RAIL RSI06A09SL-24-144 1 31.38
8 B-LINE REDI-RAIL RSI06A09SL-24-144 1 131.50
215 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
CABLE TRAY LAYOUT
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
AA
120 10'
3'-
120 10'
120 10'
118.75 9'-10 3/4"
.75
6'- 5 3
/4"
120 10'15.13 1'-3 1/8"
.38
6'- 9 3
/8"
95.75 7'-11 3/4"
1.5 1 1
/2"
TY
P.
1.61 1 5/8"
TYP.
1/6 TYPICAL WIREWAY LAYOUT
1:35
SIDE A
SIDE C
SIDE B
SIDE D
ATS
120/208V AC PANEL #1
120/208V AC PANEL #2
POWER DISTRIBUTION ENCLOSURE
HVAC #1
2 TON
HVAC #2
2 TON
30A HVAC DISCONNECT 02
30A HVAC DISCONNECT 01
125VDC BATTERY RACK W.
SPILL CONTAINMENT #2
125VDC BATTERY RACK W.
SPILL CONTAINMENT #1EYE WASH
STATION
125VDC
BATTERY
CHARGER 02
125VDC
BATTERY
CHARGER 01
200A FUSED BATTERY
DISCONNECT SWTICH
(2x STACKED)
DC TRANSFER SWTICH
(2x STACKED)
120V DC PANEL #1
120V DC PANEL #2
MC4002-B
HYDROGEN MITIGATION SYSTEM
DOOR
LHR
DOOR
RHR W.
TRANSOM
3070 INTERIOR
DOOR
LHR
MAIN ROOM
BATTERY ROOM
125VDC RELAY PANEL FRONT
125VDC RELAY PANEL FRONT
RELAY PANEL #5
BKR #182 & #282
PROTECTION
YARD
TERMINATION CABINET
RELAY PANEL #1
BOULDER
FLATS-MEAD LINE
RELAY PANEL #3
BOULDER FLATS-SOLAR
COLLECTOR STATION LINE
RELAY PANEL #2
BOULDER
FLATS-NEWPORT
LINE PROTECTION
RELAY PANEL #4
SPARE PANEL
RELAY PANEL #6
BKR #382
PROTECTION
RELAY PANEL #9
SYNCHRONIZATION
PANEL
RELAY PANEL #7
METERING PANEL
RELAY PANEL #8
COMMUNICATION PANEL
NOTES:
1. INTERIOR CEILING HEIGHT AT 119".
2. HEIGHT TO BOTTOM OF WIREWAY 112"
WIREWAY BILL OF MATERIALS
ITEM NO. DESCRIPTION PART NO. QTY. LENGTH
1 4" X 4" HINGED WIREWAY - 90 ELBOW F44G90 6 N/A
2 4"x4" HINGED WIREWAY F44G120 5 120
3 4"x4" HINGED WIREWAY F44G120 1 118.75
4 4"x4" HINGED WIREWAY F44G120 1 47
5 4"x4" HINGED WIREWAY F44G120 1 77.75
6 4"x4" HINGED WIREWAY F44G120 1 95.75
7 4"x4" HINGED WIREWAY F44G120 1 15.13
8 4"x4" HINGED WIREWAY F44G120 1 81.38
216 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
WIREWAY LAYOUT
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
1/7 ELECTRICAL ISOMETRIC VIEW
NTS
217 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
ELECTRICAL ISOMETRIC VIEW
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
.69
2'- 8 1
1/1 6"
412.85 34'-4 7/8"
384 32'
5.8
'-1 1 7
/8"
388.07 32'-4 1/16"
37.99 3'-2"
8.5
9'- 1/
2"
1/8 SIDE A EXTERIOR ELEVATION
1:47
EXTERIOR LIGHT EXTERIOR LIGHT
DOWNSPOUTS DOWNSPOUTS DOWNSPOUTS
8" EXHAUST FAN
W. 45 WEATHERHOOD
3/8 PLAN VIEW EXTERIOR
1:47
36 3' DOOR142 11'-10"
192 16'
7'
D
OO
R
6.63 6 5/8"26.76 2'-2 3/4"
.69
2'- 8 1
1/1 6"
14.88 1'-2 7/8"
DISCONNECT
60 5'
8.3
'-6 3/
8" 27 2'-3"
OPENING
7"
O
PE
NI
NG
1.5
9'- 3 1
/2"
41.49 3'-5 1/2"
102.5 8'-6 1/2"
226.58 18'-10 9/16"
207.85 17'-3 7/8"
2/8 SIDE D EXTERIOR ELEVATION
1:47
DOOR
LHR
HVAC #2
2 TON
EXTERIOR LIGHT
EXTERIOR RECEPTACLE
PROVISION BOX FOR
CARD READER
30A HVAC
DISCONNECT 02
218 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
EXTERIOR ELEVATION VIEWS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
GLOBAL POWER COMPONENTS. ANY REPRODUCTION IN PART OR WHOLE WITHOUT
THE WRITTEN PERMISSION OF GLOBAL POWER COMPONENTS IS PROHIBITED.
ROOF SLOPE
NTS
2.12"
12"
192 16'
36 3' DOOR142 11'-10"
1'
TR
AN
SO
M
7'
D
OO
R
8.3
'-6 3/
8"
.69
2'- 8 1
1/1 6"
226.58 18'-10 9/16"
207.85 17'-3 7/8"
2/9 SIDE B EXTERIOR ELEVATION
1:47
EXTERIOR LIGHT
DOOR
RHR W.
TRANSOM
PROVISION BOX FOR
CARD READER
EXTERIOR RECEPTACLE
10 10"
TYP.
86.76 7'-2 3/4" 6.63 6 5/8"
384 32'
.69
2'- 8 1
1/1 6"
412.85 34'-4 7/8"
388.05 32'-4 1/16"
5.8
'-1 1 7
/8"
14.88 1'-2 7/8"
DISCONNECT
5'
30 2'-6"
38.5 3'-2 1/2"
138 11'-6"
246 20'-6"
354 29'-6"
1/9 SIDE C EXTERIOR ELEVATION
1:47
30A HVAC DISCONNECT 01
HVAC #1
2 TON
DOWNSPOUTS
DOWNSPOUTS
8x LIFT LUGS
4x GROUND PAD
DOWNSPOUTS
EXTERIOR LIGHT EXTERIOR LIGHT
219 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
EXTERIOR ELEVATION VIEWS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
.3
383.5 FLOOR PLATE CRITICAL
384 LIFTBASE LENGTH
1/10 SIDE A LIFTBASE ELEVATION
1:40
4/10
22x 1
TOP FLANGE ONLY
1.2
TY
P.
1.25
TYP.
0 38
0 6 70
6 70
3/10 PLAN VIEW LIFTBASE
1:40
200.28
192 LIFTBASE WIDTH
191.5 FLOOR PLATE CRITICAL
2/10 SIDE B LIFTBASE ELEVATION
1:40
3.5 TY
P.
10 TYP.
4/10 GROUNDING PAD DETAIL
NTS
1/4" STAINLESS STEEL GROUNDING PLATE
DO NOT PAINT - (4x)
1/4" ASTM A36 (36 KSI)
STEEL FLOOR PLATE, TYP.
C10x25 ASTM
A36 STEEL (36 KSI)
PERIMETER FRAMING, TYP.
1/2-13 TAPPED HOLE
(4x PER PLATE)
NOTES: UNLESS OTHERWISE SPECIFIED
1. SPRAY FOAM UNDERSIDE OF LIFTBASE
2. R34-5" MIN OF SPRAY FOAM
3. APPLY TECTYL EMULSION UNDERCOATING
4. PAINT COLOR: ASH GRAY
5. USE 7/8-9 GRADE 8 HARDWARE FOR LIFTING PLATES
6. APPLY CHEMLINE-7025 NON-SKID COATING TO ENTIRE FLOOR
LIFTBASE WEIGHT: 15137 LBS
NOTES: UNLESS OTHERWISE SPECIFIED
1. APPLY DC-315 INTUMESCENT COATING BEFORE SPRAY FOAM
2. SPRAY FOAM UNDERSIDE OF LIFTBASE W. R34-5" MIN OF SPRAY FOAM
3. APPLY TECTYL EMULSION UNDERCOATING
4. PAINT COLOR: ASH GRAY
5. USE 7/8-9 GRADE 8 HARDWARE FOR LIFTING PLATES
6. APPLY CHEMLINE-7025 NON-SKID COATING TO ENTIRE FLOOR
NOTES: UNLESS OTHERWISE SPECIFIED
1. APPLY STAYCELL ONESTEP INTUMESCENT SPRAY FOAM
2. R34-5" MIN OF SPRAY FOAM
3. APPLY TECTYL EMULSION UNDERCOATING
4. PAINT COLOR: ASH GRAY
5. USE 7/8-9 GRADE 8 HARDWARE FOR LIFTING PLATES
6. APPLY CHEMLINE-7025 NON-SKID COATING TO ENTIRE FLOOR
2110 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
LIFTBASE ASSEMBLY
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
25.02 31.81 31.81 31.81 31.81 31.81 31.81 31.81 31.81 31.81 25.02
1/11 FLOOR FRAMING PLAN VIEW
1:42
2/11 2/11
5X
45X
5X
5 TY
P. 0 30
2/11 FLOOR FRAMING SECTION
1:25 - SECTION
8xTIE DOWN
4/11 3/11
9.
.05
.1
.3
.2
4/11 CROSS MEMBER SECTION
NTS
R34-5" MIN OF SPRAY FOAM
.25
.1
.3
.2
3/11 CROSS MEMBER SECTION
NTS
R34-5" MIN OF SPRAY FOAM
NOTES: UNLESS OTHERWISE SPECIFIED
1. SPRAY FOAM UNDERSIDE OF LIFTBASE
2. R34-5" MIN OF SPRAY FOAM
3. APPLY TECTYL EMULSION UNDERCOATING
4. PAINT COLOR: ASH GRAY
5. USE 7/8-9 GRADE 8 HARDWARE FOR LIFTING PLATES
6. APPLY CHEMLINE-7025 NON-SKID COATING TO ENTIRE FLOOR
LIFTBASE WEIGHT: 15137 LBS
NOTES: UNLESS OTHERWISE SPECIFIED
1. APPLY DC4000-2K NON-INTUMESECENT COATING BEFORE SPRAY FOAM
2. SPRAY FOAM UNDERSIDE OF LIFTBASE
3. R34-5" MIN OF SPRAY FOAM
4. PAINT COLOR: ASH GRAY
5. USE 7/8-9 GRADE 8 HARDWARE FOR LIFTING PLATES
6. APPLY CHEMLINE-7025 NON-SKID COATING TO ENTIRE FLOOR
STRUCTURAL BILL OF MATERIALS
ITEM NO. DESCRIPTION MATERIAL LENGTH QTY.
1 C10x25 ASTM A36 384 1
2 C10x25 ASTM A36 384 1
3 C10x25 ASTM A36 186.22 2
4 W10x12 ASTM A992 186.22 10
5 FLOOR JOIST, 10GA AISI 1011 35.81 45
6 FLOOR JOIST, 10GA AISI 1011 27.02 5
7 FLOOR JOIST, 10GA AISI 1011 27.02 5
2111 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
LIFTBASE ASSEMBLY
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
412.85 34'-4 7/8" SHIPPING LENGTH WITH HVAC
403.49 33'-7 1/2" SHIPPING LENGTH WITHOUT HVAC
188.87 15'-8 7/8" C.O.G
5.8
'-1 1 7
/8" S
HI
PP
IN
G
HE
IG
HT
.45
4'- 1 7
/16
C .O
.G
96.4 8'- 3/8" C.O.G
208.28 17'-4 1/4" OVERALL WIDTH
207.85 17'-3 7/8" SHIPPING WIDTH
1/12 SHIPPING DETAIL
1:50
1. THIS DRAWING IS FOR ILLUSTRATION PURPOSES ONLY
2. SIZING OF SPREADER BAR, CABLES, AND OTHER LIFT HARDWARE
ARE THE RESPONSIBILITIES OF OTHERS
3. SUPPLY OF SPREADER BAR, CABLES, AND OTHER LIFT HARDWARE
ARE THE RESPONSIBILITIES OF OTHERS
4. SLING ARRANGEMENT SHOULD BE ADJUSTED TO ALLOW
FOR A LEVEL LIFT
5. SLING ARRANGEMENT SHOULD BE ADJUSTED SO THE CABLES ARE NOT
LESS THAN 60° TO BASE
6. SHIPPED LOOSE ITEMS: 45 WEATHER HOODS, HVAC SIDE UNIT, HVAC DISCONNECT SIDE UNIT, SIDE UNIT EXTERIOR LIGHTS, & DOWNSPOUTS
LIFTING NOTES:
WEIGHTS:
EMPTY BLDG WT: 28802 LBS
EQUIPMENT WT: 18596 LBS
SHIPPING WT: 30153 LBS
ESTIMATED TOTAL WT: 47398 LBS
PER LOCAL APPROVAL & INSPECTION
2112 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
SHIPPING/LIFTING DETAIL
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
SIDE A
SIDE D
SIDE C
SIDE B
1/13 TYPICAL ENCLOSURE PLAN VIEW
1:48
2/13
3/13
4/13
2/13
3/13
4/13
8'- 6"
C
AB
LE
T
RA
Y
HE
IG
HT
182 15'-2" INSULATED WIDTH
3'
2/13 SIDE D INTERIOR ELEVATION
1:48 - SECTION
FIRE EXTINGUISHER RECEPTACLE
5'-
2" T
YP
24 2' 20 1'-8"
TYP.
239 19'-11"
210 17'-6"
264 22'
6'
T
YP
4'-
8"
9'- 4"
W
IR
EW
AY
H
EI
GH
T
9.1
9'-
3/
C
EI
LIN
G
HE
IG
HT
374 31'-2" INSULATED LENGTH
3'
3/13 SIDE C INTERIOR ELEVATION
1:48 - SECTION
ATS
120/208V
AC PANEL
#1
120/208V
AC PANEL
#2
RECEPTACLE
89 7'-5" BATTERY ROOM WIDTH
4'-
6"
3'
4/13 PARTITION WALL INTERIOR ELEVATION
1:48
DIMMING SWITCH
RECEPTACLE
2113 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
INTERIOR ELEVATION VIEWS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
SIDE B
SIDE D
SIDE A
SIDE C
1/14 TYPICAL ENCLOSURE PLAN VIEW
1:50
2/14
2/14
4/14
3/143/14
4/14
21 1'-9" 36.5 3'- 1/2" 21 1'-9"
182 15'-2" INSULATED WIDTH
9.1
9'-
3/
C
EI
LIN
G
HE
IG
HT
3' 54
4'- 6"
2/14 SIDE B INTERIOR ELEVATION
1:50 - SECTION
DIMMING SWITCH
FIRE EXTINGUISHERRECEPTACLE
125VDC
BATTERY
RACK #1
125VDC
BATTERY
RACK #2
.1
5'- 1/
8"
88 7'-4" SPILL CONTAINMENT, TYP.
84 7' BATTERY RACK, TYP.
29 2'-5"
2'-
6"
TY
P.
3'-
8" T
YP
98 8'-2"
2 2"
TYP.
6'
137 11'-5" BATTERY ROOM 231 19'-3" MAIN ROOM
374 31'-2" INSULATED LENGTH
27 2'-3"
TYP.
189.5 15'-9 1/2"
5'
T
YP
39 3'-3"
6'
T
YP
64 5'-4"20 1'-8"
TYP.
152 12'-8"
6'-
6" T
YP
3'-
6" T
YP
100 8'-4" TYP.
125 10'-5" TYP.18 1'-6"
TYP.
9'- 4"
W
IR
EW
AY
H
EI
GH
T
8'- 6"
C
AB
LE
T
RA
Y
HE
IG
HT
2'-
6"
3' 54
4'- 6"
5'
3/14 SIDE A INTERIOR ELEVATION
1:50 - SECTION
125VDC BATTERY RACK W.
SPILL CONTAINMENT #1
EYE WASH
STATION
125VDC
BATTERY
CHARGER 02
125VDC
BATTERY
CHARGER 01
120V DC
PANEL #1
120V DC
PANEL #2
DC TRANSFER SWTICH #1
DC TRANSFER SWTICH #1
200A FUSED
BATTERY
DISCONNECT
SWTICH #2
200A FUSED BATTERY DISCONNECT SWTICH #1
RECEPTACLE
DIMMING SWITCH
MC4002-B
5'
.25
1'- 2 1
/4"
24 2' 44 3'-8"
2'
89 7'-5" BATTERY ROOM
30.75 2'-6 3/4"
4/14 PARTITION WALL INTERIOR ELEVATION
1:50
HYDROGEN
MITIGATION SYSTEM
12" MOTORIZED DAMPER
2114 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
INTERIOR ELEVATION VIEWS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
SIDE BSIDE D
SIDE A
SIDE C
1/15 TYPICAL ENCLOSURE PLAN VIEW
1:50
3/153/15
2/152/15
7'-
6" T
YP
104 8'-8"
26 2'-2"
TYP.
36 3'
3/15 RELAY PANELS ELEVATION
1:50 - SECTION
RELAY PANEL #6
BKR #382 PROTECTION
RELAY PANEL #7
METERING PANEL
RELAY PANEL #9
SYNCHRONIZATION
PANEL
RELAY PANEL #8
COMMUNICATION
PANEL
156 13'
26 2'-2"
TYP.
36 3'
7'-
6" T
YP
374 31'-2" INSULATED LENGTH
9'- 4"
W
IR
EW
AY
H
EI
GH
T
8'- 6"
C
AB
LE
T
RA
Y
HE
IG
HT
2/15 RELAY PANELS ELEVATION
1:50 - SECTION
RELAY PANEL #1 BOULDER
FLATS-MEAD LINE
RELAY PANEL #4
SPARE PANEL
RELAY PANEL #3
BOULDER FLATS-SOLAR
COLLECTOR STATION LINE
YARD TERMINATION
CABINET
RELAY PANEL #2
BOULDER FLATS-NEWPORT
LINE PROTECTION
RELAY PANEL #5
BKR #182 & #282
PROTECTION
2115 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
INTERIOR ELEVATION VIEWS
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
Y
Y AE
AE
AGAG
AA
AD
SECTION Y-Y
AB
1/16 PERIMETER CHANNEL TO PAD DETAIL
NTS
CONCRETE PAD BY OTHERS
TO SUPPPORT THE REACTIONS
LISTED ON SHEET #3
LIFTBASE PERIMETER
C-CHANNEL
WELD BASE TO STEEL
PLATE EMBEDDED IN PAD
(BY OTHERS)
1/4 6
TYP.
5 5" 4 4" 5 5"
1.5 1 1/2"
1"
1/4-14 x 1 1/4" TEK2 ZAC SELF-DRILLER (4x) PER ROOF PANEL
7/16 ROOF PANEL TO EAVE TRIM FASTENER SCHEDULE
NTS NOTE:
IN ADDITION TO TAPE SEALANT, STANDING SEAMS TO BE MADE
WEATHER TIGHT USING SEAMER (HAND/MECHANICAL)
3/16" x 7/8" DOUBLE BEAD TAPE SEALANT
ON SCULPED EAVE AND STANDING SEAM OF
MAXIMA PANEL
24GA GR50 2" MAXIMA 218
ROOF PANEL
4/16 ENCLOSURE MOUNTING TO BASE FRAME
NTS - SECTION
LIFT GUSSET CONNECTION
BEVELED WASHER
1/2 ASTM A36
(36 KSI) STEEL
MOUNTING PLATE
3/4-10 GRADE 5 BOLT WITH
2" FENDER WASHER
SPACED PER PLAN VIEW
ALONG THE ENCLOSURE LENGTH
1/4 ASTM A36
(36 KSI) STEEL
FLOOR PLATE
34 2'-10" 17 1'-5"
AF
AN
SECTION AE-AE
CEILING INSULATED
W. R30 - 9.5" BATT INSULATION
16GA CEILING SUPPORT CHANNEL
12GA TRUSS SPLICE PLATE
(1x) PER SIDE OF TRUSSES
4MIL VAPOR BARRIER
5/16 FIXED RIDGE CONNECTION DETAIL
NTS
16GA PURLIN
22GA LOW FIXED CLIP
(4x) PER SIDE
FIXED RIDGE TRIM EXTERIOR FRAMING WRAPPED
WITH R7 - 2" INSULATION BLANKET
AH AM
SECTION AG-AG
12 1'
6 6"
24GA GR50 INTERIOR LINER PANEL
1/4-14 x 1" L SELF TAPPERS 16GA HAT & CEILING CHANNEL #10-12 x 1" L PANCAKE
HEAD, SELF TAPPING SCREW
2/16 INTERIOR LINER FASTENER SCHEDULE
NTS
NOTES:
1. WALL FASTENER PATTERN: ON TRACKS AND GIRTS OF STRUCTURAL WALL FRAMING
2. CEILING FASTENER PATTERN: ON CEILING SUPPORT CHANNELS
.15 1/8"
6.8 6 1
3/1 6"
1.2
1 1 /4"
12 1' INTERIOR LINER, TYP.
36 3' COVERAGE
7 7" 5 5"
12 1' TYP. 4 4"
TYP.
3/16 EXTERIOR WALL DETAIL
NTS
EXTERIOR FRAMING WRAPPED
WITH R7-2" INSULATION BLANKET
4MIL VAPOR BARRIER
STUD FRAMING INSULATED W. R15 - 3" BATT INSULATION
24GA GR50 INTERIOR LINER PANEL
26GA GR50 CURRUGATING
R-5 EXTERIOR PANEL
1/4-14 x 7/8" LAP TEK SELF-DRILLER
ON LAPS OF MULTI-RIB
1/4-14 x 1-1/4" TEK2 ZAC SELF-DRILLER
.88 7/8"
6"
7.5 7 1/2"
3.75 3 3/4"
3"
9/16 CLAMP PLATE DETAIL
NTS
TBD
10/16 POST INSTALLED ANCHOR TO PIER DETAIL
NTS NOTE: LOCATION OF ANCHOR TO PIER IS FOR REFERENCE ONLY.
ACTUAL LOCATION TO BE DETERMINED BY OTHERS
3/4"x5"L GALVANNIZED STEEL
WEDGE ANCHORS
6"x7-1/2"x3/4" THK
A36 STEEL CLAMP PLATE
QTY: 8
4x 1.13 1 1/8"
0"
2"
3.6
3 5 /8"
6"
8"
0 0"
2 2"
3.81 3 13/16"
6 6"
8 8"
.5
1/
2"
.75 3/4"
6/16 LIFTING LUG DETAIL
NTS
1/4 1/4
TYP.
6.5 6 1/2"
.38 3/8
8"
3.13 3 1/8"
1/4 1/4
TYP.
AP
4"
6"
12 1' INTERIOR LINER, TYP.
12 1' INTERIOR LINER, TYP.
8/16 BATTERY ROOM WALL CONSTRUCTION DETAIL
NTS
24GA GR50 INTERIOR LINER PANEL
4MIL VAPOR BARRIER
24GA GR50 INTERIOR LINER PANEL
4MIL VAPOR BARRIER
R-5 EXTERIOR PANEL FASTENER SCHEDULE
AT BASE AND EAVE
-1/4-14 x 1-1/4" L SELF TAPPERS
-SPACING 5"-7"-5"
AT LAPS OF SHEETING
-1/4-14 x 7/8" L SELF TAPPERS
-SPACING 1'-8"
AT GIRTS
-1/4-14 x 1-1/4" L SELF TAPPERS
-SPACING 12" ON CENTERS
6"x7-1/2"x3/4" THK
A36 STEEL CLAMP PLATE
QTY: 8
1" OVERLAP OF CLAMP
PLATE AND
CHANNEL FLANGE
3/4"x5"L GALVANNIZED
STEEL WEDGE ANCHORS
2116 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
GENERAL ENCLOSURE CONSTRUCTION
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
1/17 STRUCTURAL FRAMING ISOMETRIC VIEW
NTS - ISOMETRIC VIEW
10 21
ENCLOSURE BILL OF MATERIALS
ITEM NO. DESCRIPTION QTY. MATERIAL MATERIAL THICKNESS
1 C6x8.2 CHANNEL 2 ASTM A36 Steel
2 CEILING CONNECTION ANGLE, 14GA 96 A60 GALVANNEALED 0.07
3 CEILING HAT CHANNEL, 16GA 30 A60 GALVANNEALED 0.06
4 CEILING HAT CHANNEL, 16GA 30 A60 GALVANNEALED 0.06
5 CEILING SUPPORT CHANNEL, 16GA 48 A60 GALVANNEALED 0.06
6 EAVE CONNECTION PLATE 2", 16GA 4 A60 GALVANNEALED 0.06
7 EAVE CONNECTION PLATE 4", 16GA 10 A60 GALVANNEALED 0.06
8 EAVE PLATE, 16GA 24 A60 GALVANNEALED 0.06
9 EAVE STRUT, 16GA 12 A60 GALVANNEALED 0.06
10 ENCLOSURE LIFT PLATE, 1/4" A36 8 ASTM A36 Steel 0.25
11 GIRT, 14GA 40 A60 GALVANNEALED 0.07
12 GIRT, 14GA 2 A60 GALVANNEALED 0.07
13 GIRT, 14GA 2 A60 GALVANNEALED 0.07
14 GIRT, 14GA 2 A60 GALVANNEALED 0.07
15 GIRT, 14GA 2 A60 GALVANNEALED 0.07
16 GIRT, 14GA 4 A60 GALVANNEALED 0.07
17 GIRT, 14GA 4 A60 GALVANNEALED 0.07
18 GIRT, 14GA 2 A60 GALVANNEALED 0.07
19 GIRT, 14GA 2 A60 GALVANNEALED 0.07
20 GIRT, 14GA 2 A60 GALVANNEALED 0.07
21 HOIST MOUNTING PLATE, 1/2" A36 8 ASTM A36 Steel 0.5
22 HVAC MOUNTING ANGLE, 12GA 4 A60 GALVANNEALED 0.1
23 HVAC SILL PLATE, 14GA 2 A60 GALVANNEALED 0.07
24 LOW EAVE PLATE, 16GA 6 A60 GALVANNEALED 0.06
25 LOW EAVE PLATE, 16GA 2 A60 GALVANNEALED 0.06
26 MOUNTING PLATE, 1/2" 22 ASTM A36 Steel 0.5
27 PURLIN CONNECTION ANGLE, 14GA 96 A60 GALVANNEALED 0.07
28 PURLIN, 16GA 48 A60 GALVANNEALED 0.06
29 ROOF TRUSS, 12GA 12 A60 GALVANNEALED 0.1
30 ROOF TRUSS, 12GA 12 A60 GALVANNEALED 0.1
31 STUD WALL BRACE, 16GA 32 A60 GALVANNEALED 0.06
32 STUD, 12GA 40 A60 GALVANNEALED 0.1
33 STUD, 12GA 3 A60 GALVANNEALED 0.1
34 STUD, 14GA 4 A60 GALVANNEALED 0.1
35 TRACK, 14GA 32 A60 GALVANNEALED 0.07
36 TRACK, 14GA 2 A60 GALVANNEALED 0.07
37 TRACK, 14GA 1 A60 GALVANNEALED 0.07
38 TRACK, 14GA 1 A60 GALVANNEALED 0.07
39 TRACK, 14GA 1 A60 GALVANNEALED 0.07
40 TRACK, 14GA 1 A60 GALVANNEALED 0.07
41 TRUSS SPLICE PLATE, 12GA 14 A60 GALVANNEALED 0.1
42 WALL HAT CHANNEL, 16GA 18 A60 GALVANNEALED 0.06
2117 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
STRUCTURAL FRAMING CONSTRUCTION
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
64 64 64 64 64 64
.5
2.8
1/18 SIDE A STRUCTURAL FRAME ELEVATION
1:46 - SIDE C HIDDEN FOR CLARITY
3/183/18
4/18
64 64 4 7.88
.19
O
PE
NI
NG
40.25
OPENING 7.88
.5
6.3
24.25
54.13
68.75
86.5
97.5
C6x8.2 CHANNEL
2/18 SIDE D STRUCTURAL FRAME ELEVATION
1:46 - SIDE B HIDDEN FOR CLARITY
H
9.8
.25
OP
EN
IN
G
.88
OP
EN
IN
G
.88
9.8
CO
RN
ER
A -B
CO
RN
ER
B -C
3/18 STRUCTURAL FRAME PLAN SECTION
1:46
5/18 EAVE PLATE CONNECTION
NTS
16GA EAVE CONNECTION PLATE
1/4-14x1" L SELF TAPPERS
16GA EAVE STRUT
12GA ROOF TRUSS
1 1
4/18 STRUCTURAL FRAME CONNECTION
NTS
1/4-14x1" L SELF TAPPERS
2118 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
STRUCTURAL FRAMING CONSTRUCTION
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
2.8
.13
.75
.5 97
.5
1/19 SIDE C STRUCTURAL FRAME ELEVATION
1:42 - SIDE A HIDDEN FOR CLARITY
64 64 4 7.88
40.25
OPENING
7.88
.19
O
PE
NI
NG
6.3
2/19 SIDE B STRUCTURAL FRAME ELEVATION
1:42 - SIDE D HIDDEN FOR CLARITY
C6x8.2 CHANNEL
2119 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
STRUCTURAL FRAMING CONSTRUCTION
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
0 18
1/20 STRUCTURAL FRAME PLAN VIEW - CEILING HAT CHANNEL LOCATIONS
1:45
16GA CEILLING HAT CHANNEL
SIDE A
SIDE D SIDE B
SIDE C
KK
.86
8.12 24 TYP.
5.
97.43
0 12
16GA EAVE STRUT
2/20 ROOF TRUSS SECTION DETAIL
1:16
1/4-20 STEEL HARDWARE
3/8-16 STEEL HARDWARE
16GA CEILLING
SUPPORT CHANNEL
14GA CEILLING
CONNECTION PLATE
3/8-16 STEEL HARDWARE12GA TRUSS SPLICE PLATE
3/8-16 STEEL HARDWARE
12GA ROOF TRUSS
16GA PURLIN
14GA PURLIN
CONNECTION PLATE
2120 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
STRUCTURAL FRAMING CONSTRUCTION
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
LL
MM
V
1/21 LIFTBASE SECTION ISOMETRIC VIEW
NTS
5/21
NPRT
SECTION M-M
SCALE 1 : 66
2/21 PERIMETER WELDMENT
NTS
1/4 3-12
TYP.
1/4 3-12
TYP.
1/4
TYP.
1/4
TYP.
1/4
G
TYP.
6/21 CROSS MEMBER WELDMENT
NTS
1/4 3-20 G
TYP.
1/4 1/4
TYP.
1/4
TYP.
1/4
TYP.
1/4 3-24
TYP.
1/4 3-20 G
TYP.
3/21 CROSS MEMBER WELDMENT
NTS
1/4 1/4
TYP.
1/4 3-20 G
TYP.
1/4 3-24
TYP.
1/4 3-24
TYP.
7/21 TIE DOWN WELDMENT
NTS
1/4 1/4
TYP.
9.7
9 3 /4"
1"
2.5 2 1/2"
2.5 2 1/2"
1"
8/21 FLOOR JOIST CHANNEL
NTS
5/21 FLOOR JOIST CHANNEL WELDMENT
NTS
1/8 G
TYP.
1/8 G
TYP.
1/4
TYP.
1/4
TYP.
9/21 FLOOR JOIST/W10x25 TO FLOOR
NTS
1/8 2
TYP.
1/4 2
TYP.
W
4/21 PERIMETER CHANNEL WELDMENT
NTS
1/4
45° G
TYP.
1/4
TYP.
NOTES:
1. GRIND WELDS FLAT IF NECESSARY
2. WELDING OF S.S. GROUND PLATES ARE NON-STRUCTURAL
3. FLOOR PLATE PLUG WELDS ARE NON-STRUCTURAL
4. WELDING OF HEX NUTS ARE NON-STRUCTURAL. INTENDED FOR MATERIAL HANDLING ONLY
5. WELDING OF TIE DOWNS ARE NON-STRUCTURAL
LIFTBASE BILL OF MATERIALS
ITEM DESCRIPTION GRADE
1 C10x25 CHANNEL - PERIMETER ASTM A36
2 W10x12 BEAM - CROSS MEMBER ASTM A992
3 10GA FLOOR JOIST ASTM A1011 CS TYPE B, GRADE 33
4 1/4 A36 FLOOR PLATE ASTM A36
5 GRD-110 STAINLESS STEEL GROUND PLATE 316 SS
6 WELD ON TIE DOWN ASTM A36
7 7/8-9 A563 GRADE A HEX NUTS A563 GRADE A
8 7GA FLOOR BOTTOM PLATE ASTM A1011 CS TYPE B, GRADE 33
2121 OFSHEETAPPROVAL DRAWINGS
PH 414.475.3000 FAX 414.475.3441
www.globalpowercomponents.com
± .1 ± .06 ± 2° ± .005
.X
.XX
ONE PLACE
TWO PLACE
ANGLE
HOLE DIA.
THE TOLERANCES ARE:
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
FINISH
MATERIAL
DRAWN BY DATE
YXZ 11/3/2022
SEE NOTES
EP2
BOULDER FLATS SUBSTATION
XX
CUSTOMER I/D:
PROJECT NAME:
DRAWING REF:
GENERAL LIFTBASE WELDMENT
SIZE DWG. NO. REV.
DESCRIPTION
B 45-37439 0
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
SD
SD
SD
LED14 LED15LED13LED12LED11
LED7LED6 LED8 LED9 LED10
LED2LED1 LED3 LED4 LED5
OS
OS
OS
OS
OS
1 1 1 1
11111
1 1 1 1 1
GFI
GFI
SYMBOL LEGEND
DESCRIPTIONITEM QTY:
INTERIOR LED LIGHT
DIMMING SWITCH
INTERIOR DUPLEX GFCI RECEPTACLE
EXTERIOR DUPLEX GFCI RECEPTACLE
LED EMERGENCY LIGHT/EXIT SIGN
GFCI
RECEPTACLE
GFI
LED1
LED
LIGHT
ELECTRIC BILL OF MATERIALS
EXTERIOR LED LIGHT W/PHOTOCELL
2-TON HVAC
MC4002-B TSTAT
S D
DIMMING
SWITCH
OCCUPANCY
SENSOR
OS
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
FAX 414.475.3441
www.globalpowercomponents.com
DESCRIPTIONITEM QTY:
OCCUPANCY SENSOR
BATTERY VENT FAN
MOTORIZED INTAKE LOUVER
TIMER
HYDROGEN MODULE
HYDROGEN SENSOR
30A HVAC DISCONNECTS
DOOR CONTACTS
GROUNDING TO BASE DETAIL
1-5/8 UNISTRUT
3/8-16 STRUT CHANNEL NUT
3/8-16 POINT SET SCREW
1-1/4" LENGTH - 91375A626
nVENT LOW VOLTAGE INSULATOR
ISO2-38-16
2" COPPER GROUND BAR
3/8" BELLEVILLE WASHER
3/8-16 HEX BOLT
ISO VIEW OF GROUND BAR INSTALLATION
0 .75 2.5 4.2
6 7.7
9.5 11 .25
IN
ST
AL
L 1
2 A
BO
VE
F
IN
IS
HE
D
FL
OO
R
1.75 TYP.7x
2 HOLE LONG BARREL LUG
GROUND DROP FROM CEILING
2x nVENT INSULATOR
P/N: ISO2-38-16
HOLE LEFT UNUSED FOR
(2x) 3/8-16 HEX BOLT
W. 3/8" BELLEVILLE WASHER
CUSTOMER OR TESTING PURPOSES
.5
1/4" THK COPPER BAR
2 HOLE LONG BARREL LUG
GROUND DROP FROM BASE
1/4" THK COPPER BAR
12" LENGTH
1/4" FLOOR PLATE
4/0AWG THHN TO BASE
BARE TINNED 4/0AWG
CONTINUOUS ALONG
CABLE TRAY
COMPRESSION
LUG AT END OF
CABLE TRAY
COMPRESSION LUG AT
END OF CABLE TRAY
2AWG THHN
4AWG THHN
2AWG THHN
4/0AWG THHN TO BASE
4AWG THHN
BARE TINNED 4/0AWG
CONTINUOUS ALONG
CABLE TRAY
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
FAX 414.475.3441
www.globalpowercomponents.com
**FINAL BUILDING GROUNDING CONNECTION TO SYSTEM GROUND TO BE INSPECTED AND APPROVED BY LOCAL AHJ
500KCMIL PER PHASE AND NEUTRAL
2AWG GND
3" RIGID
2AWG TO 2"X1/4" GND BAR
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
FAX 414.475.3441
VOLTAGE NEUTRAL MIN A.I.C. RATING
SCHEDULE FOR:
240/120VAC
AC PANEL 1 MEC POWER DISTRIBUTION ENCLOSURELOCATION: FED FROM:
YES 10kAIC
MAIN BUS NUMBER OF POLES COMMENTS400A 42
120/240VAC,1ɸ,3W
MCB RATING
EQUIP. GROUND
BUS
MOUNTING400A YES SURFACE
PHASE A
TOTAL LOAD
PHASE B
TOTAL LOAD
TOTAL
CONNECTED LOAD
0 VA
CONTINUOUS LOAD
TOTAL
NON-CONTINUOUS
LOAD TOTAL
125% OF
CONTINUOUS LOAD
LOAD TOTAL
CALCULATED MINIMUM
FEEDER WIRE SIZE
FEEDER
WIRE SIZE
EX
LTG
REC
MOT
HAC
HNC
CNC
OTH
FUT
LOAD TYPES:
EXISTING
LIGHTING
RECEPTACLE
MOTOR
HVAC
NONCOINCIDENT HEATING
NONCOINCIDENT COOLING
OTHER
FUTURE
XAWG PER PHASE
&NEUTRAL
XAWG GND
500KCMIL PER
PHASE &NEUTRAL
2AWG GND
XXFUT
DESCRIPTION
WIRE
SIZE
VA
LOAD
TYPE
CB
AMPS
CKT
XX
XX
XX
XX
XX
FROM POWER DISTRIBUTION ENCLOSURE
500KCMIL PER PHASE AND NEUTRAL
2AWG GND
3" RIGID
CBXG
GROUND
BAR
XXX 31
XXX 33
XXX 35
XXX 37
XXX 39
XXX 41
19 20
X X FUT
DESCRIPTION
WIRE
SIZE
VA
LOAD
TYPE
CB
AMPS
CKT
X X X
X X
X X
X X
X X
X X X32
X X X34
X X X36
X X X38
X X X40
X X X42
37 38
39 40
41 42
CBXN
SOLID
NEUTRAL
2AWG TO 2"X1/4" GND BAR
PCB 182 ES-4127 182HTR-01 30
MOD 189 ES-4151 MOD189-01 20
MOD 389 ES-4153 MOD389-01 20
MOD 289 ES-5152 MOD289-02 20
PCB282 ES-4130 282REC-01 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
SPARE30
MOD 289 ES-4152 MOD289-0120
MOD 189 ES-4151 MOD189-0220
MOD 389 ES-4153 MOD389-0220
PEB382 ES-4132 382REC-0120
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
PCB 382 ES-4131 382HTR-01
PCB 282 ES-4129 282HTR-01
XX
XX
X X
X X X
XXX X X XSPARE 20 SPARE20
XXX X X XSPARE 20 SPARE20
XXX X X XSPARE 20 SPARE20
XXX X X XSPARE 20 SPARE20
XXX X X XSPARE 20 SPARE20
XXX X X XSPARE 20 SPARE20
XXX X X XSPARE 20 SPARE20
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
FUT
FUT
FUT
FUT
FUT
FUT
FUT
FUT
FUT
FUT
FUT
FUT
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
VOLTAGE NEUTRAL MIN A.I.C. RATING
SCHEDULE FOR:
240/120VAC
AC PANEL 2 MEC POWER DISTRIBUTION ENCLOSURELOCATION: FED FROM:
YES 10kAIC
MAIN BUS NUMBER OF POLES COMMENTS400A 42
120/240VAC,1ɸ,3W
MCB RATING
EQUIP. GROUND
BUS
MOUNTING400A YES SURFACE
PHASE A
TOTAL LOAD
PHASE B
TOTAL LOAD
TOTAL
CONNECTED LOAD
8721 VA
8434 VA
17155 VA
CONTINUOUS LOAD
TOTAL
1065 VA
NON-CONTINUOUS
LOAD TOTAL
16090 VA
125% OF
CONTINUOUS LOAD
1331 VA
LOAD TOTAL 17421 VA
CALCULATED MINIMUM
FEEDER WIRE SIZE
FEEDER
WIRE SIZE
EX
LTG
REC
MOT
HAC
HNC
CNC
OTH
FUT
LOAD TYPES:
EXISTING
LIGHTING
RECEPTACLE
MOTOR
HVAC
NONCOINCIDENT HEATING
NONCOINCIDENT COOLING
OTHER
FUTURE
4AWG PER PHASE
&NEUTRAL
8AWG GND
500KCMIL PER
PHASE &NEUTRAL
2AWG GND
356LTG
DESCRIPTION
WIRE
SIZE
VA
LOAD
TYPE
CB
AMPS
CKT
XXX 3
8AWG3600HAC
XXX
XXX
XXX
FROM POWER DISTRIBUTION ENCLOSURE
500KCMIL PER PHASE AND NEUTRAL
2AWG GND
3" RIGID
GROUND
BAR
XXX 29
XXX 31
XXX 33
XXX 35
XXX 37
XXX 39
XXX 41
19 20
DESCRIPTION
WIRE
SIZE
VA
LOAD
TYPE
CB
AMPS
CKT
X X X4
8AWG 3600 HAC6
X X X
X X X
12AWG 624 LTG14
1080 REC16
36018
X X X20
X X X22
X X X24
X X X26
X X X28
X X X30
X X X32
X X X34
X X X36
X X X38
X X X40
X X X42
37 38
39 40
41 42
SOLID
NEUTRAL
2AWG TO 2"X1/4" GND BAR
BUILDING INTERIOR LED LIGHTS
MAIN ROOM ES-4108
YARD LIGHTS ES-4108 YL-01 20
HVAC-1 ES-4108 30
BATTERY CHARGER 1 ES-4108 20
LIGHTS & PANEL RECP. ES-4108 20
YARD LIGHTS YL-06 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
SPARE 20
BUILDING INTERIOR LED LIGHTS
BATTERY ROOM ES-4108
BUILDING EMER. LIGHTS ES-410820
HVAC-2 ES-410830
BATTERY CHARGER 2 ES-410820
YARD LIGHTS YL-0820
BUILDING EXTERIOR LIGHTS20
BUILDING INTERIOR DUPLEX RECEPTACLES20
BUILDING INTERIOR GFCI RECEPTACLES20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
SPARE20
XXX
XXX SPARE 20
XXX SPARE 20
XXX SPARE 20
XXX SPARE 20
12AWG250OTH VENT FAN & LOUVER 20
12AWG30OTH
FIRE ALARM CIRCUIT (**NOTE 1)
**NOTE 1: CIRCUIT DISCONNECTING MEANS SHALL HAVE RED IDENTIFICATION.
THE RED IDENTIFICATION SHALL NOT DAMAGE THE OVER-CURRENT
PROTECTION DEVICE OR OBSCURE MANUFACTURER MARKINGS.**
12AWG
12AWG
12AWG REC
12AWG LTG
8AWG3600HAC
8AWG 3600 HAC
CB1G CB1N
CB2G CB2N
CB6G CB16N
CB7G CB17N
CB16G CB18N
CB17G CB19N
CB18G
CB16G
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
F1
F2
LEAD-LAG TSTAT MC4002-B TO HVAC
WIRING DIAGRAM
R
G
Y2
Y1
W
C
R
G
Y2
Y1
W
C
R
G
W
C
Y
R
G
Y2
Y1
W
C
Y
AG
CU
COPPER
SILVER
BLK
WHT
YEL
GRN
RED
BLK
WHT
YEL
GRN
RED
FE FE
ECON-1
NO NO NO NO NO NO NOC C C C C C CNC NC NC NC NC NC NC
SMOKE/
FIRE
POWER
LOSS-1
POWER
LOSS-2
LOW
TEMP.
HIGH
TEMP-1
HIGH
TEMP-2
CONTROLLER
32 32
NO
C
NCNO
C
NCNO
C
NC
ECON-2 LOCKOUT-1 LOCKOUT-2
LOCKOUT-1
2ND STAGE
LOCKOUT-2
RT
RT
3C/14AWG 600V TC-ER CABLE
F1
F2
Y2
Y1
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
X
D
U C
T
125V AC/DC RATED CONTACTS TB1
1"X3" DUCT
X
D
U C
T
1"X3" DUCT
1"X3" DUCT
1"X3" DUCT
m a x
A
120VAC TB2
HAR2 PL1 PL2 HTR LTR
FAR
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
XX
ALARM BOX
TERMINAL BLOCK NUMBER
120VAC TB2
FAR
A
FROM AC PANEL 2 CB17-H
FROM AC PANEL 2 CB17-N
G
TO SMOKE DETECTOR-A-BLK
FROM SMOKE DETECTOR-YEL
FROM AC PANEL 2 CB19-H
FROM AC PANEL 2 CB19-N
120V AC
24VDC
L N
FROM AC PANEL 2 CB19-G
G
FROM 120/24VDC P.S-G
G FROM HYDROGEN SENSOR-G-18AWG
1A
B
18AWG
*NOTE:
14AWG MTW FOR CONTROL WIRING
UNLESS SPECIFIED OTHERWISE
TO SMOKE DETECTOR-C-WHT
18AWG
G 20
FROM AC PANEL 2 CB17-G
FAR - FIRE ALARM RELAY
HAR-2 - HYDROGEN DETECTOR RELAY-2%
PL1 - HVAC 1 POWER LOSS
PL2 - HVAC 2 POWER LOSS
HTR - HIGH TEMP RELAY
LTR - LOW TEMP RELAY
TIMER
FAR
SBS-H2
FROM TIMER-G
FROM VENT FAN/LOUVER-G
G
G
9 6
TO SMOKE DETECTOR-B-WHT
TO SMOKE DETECTOR-A-WHT
TO SMOKE DETECTOR-B-BLK
TO SMOKE DETECTOR-C-BLK
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
XX
ALARM BOX
TERMINAL BLOCK NUMBER
14AWG MTW
120V AC
24VDC
L N
PL1
PL2
FAR
24VDC
125V AC/DC RATED CONTACTS TB1
DOOR SIDE TBD
CUSTOMER USE
CUSTOMER USE
POWER LOSS
HVAC-1
POWER LOSS
HVAC-2
CUSTOMER USE
CUSTOMER USE
CUSTOMER USE
CUSTOMER USE
CUSTOMER USE
CUSTOMER USE
HAR-2
CUSTOMER USE
CUSTOMER USE
PL1
CUSTOMER USE
CUSTOMER USE
PL2
CUSTOMER USE
CUSTOMER USE
HTR
CUSTOMER USE
CUSTOMER USE
LTR
CUSTOMER USE
CUSTOMER USE
A B
A B
J3-2%
HAR-2
A B
FAR - FIRE ALARM RELAY
HAR-2 - HYDROGEN DETECTOR RELAY-2%
PL1 - HVAC 1 POWER LOSS
PL2 - HVAC 2 POWER LOSS
HTR - HIGH TEMP RELAY
LTR - LOW TEMP RELAY
HTR
HIGH TEMP
ALARM
A B
LTR
HIGH TEMP
ALARM
A B
DOOR SIDE TBD
2300 S. 51st ST
PH 414.475.3000
MILWAUKEE, WI 53219
| 45-37439 - EP2 Boulder Flats Substation |
| 1 |
| Drawing View97 |
| 2 |
| 3 |
| 4 |
| Drawing View95 |
| Section View A-A |
| 5 |
| Drawing View1 |
| Drawing View2 |
| Section View A-A |
| 6 |
| Drawing View4 |
| Drawing View5 |
| Section View A-A |
| 7 |
| Drawing View7 |
| 8 |
| Drawing View8 |
| Drawing View9 |
| Drawing View10 |
| 9 |
| Drawing View11 |
| Drawing View12 |
| 10 |
| Drawing View13 |
| Drawing View14 |
| Drawing View15 |
| Detail View (1 : 5) |
| 11 |
| Drawing View17 |
| Section View - |
| Detail View (1 : 6) |
| Detail View (1 : 6) |
| 12 |
| Drawing View23 |
| Drawing View24 |
| 13 |
This is the start of the file's text. The full file is on GovTribe.