ENERGY QAP C16.38-2 FS2 (AUG 2014).pdf
PDF 594 KB Posted
- Solicitation number
- SPE60525RFI1002
- Issued by
-
Defense Logistics Agency Energy
About this file
This is a quality assurance provision (QAP) document specifying requirements for Fuel Oil, Burner No. 2 (Product Code S5000 FS2) supplied to DLA Energy. The document establishes that supplied fuel must conform to all Federal, State, and local environmental requirements at the delivery location, including Title V Clean Air Act permits. For Italy-specific deliveries, fuel must meet Italy STD UNI CTI 6579 standards.
The technical specifications require conformance to ASTM D 396 with specific modifications, including a maximum sulfur content of 0.50 weight percent (or stricter per local requirements). The fuel must contain red dye Solvent Red 164 at specified concentrations, and blending of compatible grades is permitted through mechanical mixing prior to transport. The document explicitly prohibits the use of used oil in the product. This QAP relates to a broader DLA Energy Alaska 3.9 Fuel Program RFI (SPE60525RFI1002) seeking suppliers for approximately 65 million gallons of various fuel types, including this specific fuel oil grade, with responses due January 25, 2025.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C16.38-2 Fuel Oil, Burner No. 2 S5000 (DLA ENERGY AUG 2014)
Supplies delivered under this contract shall conform to all Federal, State, and local environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. This includes delivery of fuel and documentation in a manner consistent with existing or future Title V (Clean Air Act) Permits. In the event that a Federal, State, or local environmental requirement is more stringent than a similar requirement in a fuel specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent environmental requirement will be considered to be a nonconforming supply. All supplies furnished under this contract shall fully meet the requirements of the applicable specification(s) as cited below. In the event that compliance with the more stringent requirement causes the contractor to incur additional costs, the contractor may request an equitable adjustment.
(a) FUEL OIL, BURNER (ITALY ONLY) – Fuel Oil shall meet Italy STD UNI CTI 6579.
(b) FUEL OIL, BURNER (VIRGIN FUEL OIL). Product shall conform to ASTM D 396, as modified by the requirements of paragraphs (1) through (3) below. Product classification is shown in the table below. PRODUCT CONTAINING USED OIL SHALL
NOT BE SUPPLIED.
NATIONAL STOCK NUMBER PRODUCT NOMENCLATURE
DLA ENERGY PRODUCT
CODE
RED DYE
9140-00-247-4365 Fuel Oil, Burner No. 2 S5000 FS2 Yes
(1) SULFUR REQUIREMENT. The maximum allowable sulfur content for Burner Oil, Grade No. 2 S5000, shall be
0.50 weight percent or per State/local environmental requirements, whichever is more stringent. For domestic and overseas bunkers the maximum sulfur requirement shall be stated as in the Schedule.
(2) Blending of various compatible grades of burner oil to produce an intermediate grade is permitted, however, such blending shall be accomplished by mechanical mixing or agitation in a tank, or by in-line blending, prior to loading the product into transport equipment, and the resultant product must meet all the requirements of the grade produced.
(3) Under United States regulations, fuel oil burner Grade No. 2 is required by 40 CFR Part 80 to contain a sufficient amount of the dye Solvent Red 164 so its presence is visually apparent. At or beyond terminal storage tanks, they are required by CFR Part 48 to contain the dye Solvent Red 164 at a concentration spectrally equivalent to 3.9 pounds per thousand barrels of the solid dye standard Solvent Red 26.
Signature
Prepared by:
Quality / Technical Support Office Approval: Prior approval as contract provision
Contracting Approval: Prior approval as contract provision
Legal Approval:
(Only required for E QAPs)
Source Selection Information –See FAR 2.101 and 3.104
DMM0076
Typewritten Text DISTRIBUTION STATEMENT - A: APPROVED FOR PUBLIC RELEASE. DISTRIBUTION IS UNLIMITED
File details come from the government source that posted it. Updated .