EN6952-WXYZ_DA_B_Released.pdf
PDF 2 MB Posted
- Attached to
- Rack Level Power Distribution Units
- Solicitation number
- UU207787178
- Issued by
- Salt Lake County, Utah
About this file
This is a technical specification document for an enLOGIC Advantage Series Rack Power Distribution Unit (PDU) by nVent, a product designed for metered and switched per-outlet power management. The document provides comprehensive technical details across three engineering drawings, including front, side, rear, and bottom views, with precise dimensional measurements and electrical specifications. The PDU is a vertical, 0U full unit with 21 C13/C15 outlets, supports 200-240VAC three-phase delta input, has a rated power of 17.3 kVA, and can handle a 60A input current (48A derated). Key features include remote outlet switching, per-outlet metering, environmental compliance (RoHS), and operational capabilities in temperatures ranging from -5 to 60°C.
The device is configured with multiple circuit breakers, specifically six 20-amp double-pole breakers, and offers various configuration options including input plug types, chassis colors, cord lengths, and orientations. It includes high-visibility data displays showing phase and circuit breaker levels, digital sensor ports, Ethernet connectivity, and critical alarm alert capabilities. The PDU is certified for US and Canadian markets, with different rating specifications: 200-240VAC at 48A for US/Canada and 200-240VAC at 60A for Japan. The device complies with FCC Part 15 rules and includes features like MAC address labeling, serialization, and comprehensive internal wiring schematics that detail the complex interconnections between various electronic boards and components.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| nVent DATA SOLUTIONS MSPO PDU 0U 60A 48A 208V 3P Delta 6 CB 21 C13 21 4 in 1.pdf | ||
| IFB UU207787178 - Rack Level Power Distribution Units.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ENGINEER:
SIZE:
REV .
DRAWN BY:
THRID ANGLE PROJECTION
LRF
APPROVED BY:
PART NO:
TITLE :
PROJECT :
A3
2022/05/24
EN6952-WXYZ_DA
MAX OPERATING
ELEVATION, ABOVE MSL
HUMIDITY
(OPERATING/STORAGE)
METERING
5-90% RH / 5-95% RH;
NON-CONDENSING
VOLTAGE(V), CURRENT(A), APPARENT
POWER(kVA), REAL POWER(kW), POWER FACTOR, ENERGY(kWh)
NOTES
INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE
1.
AND LOCAL CODES.
PRIMARY DIMENSIONS ARE IN MILLIMETERS. SECONDARY DIMENSIONS
2.
ARE IN [INCHES]
UNIVERSAL MOUNTING BRACKET IS AN ALTERNATIVE MOUNTING
3.
METHOD TO THE TOOLLESS MOUNT FOR 3RD PARTY ENCLOSURES.
BRACKET IS PROVIDED WITH THE UNIT.
DETAILED INSTALLATION INSTRUCTIONS CAN BE FOUND IN THE QUICK
4.
START GUIDE
CONNECT EXTERNAL EARTH GROUND TO THE 10-32 SIZE THREADED NUT
5.
SEE PRODUCT DOCUMENTATION FOR FURTHER INFORMATION
6.
INPUT PLUG CONFIGURATION (SEE IDENTIFICATION TABLE) FOR DUAL-
7.
RATED UNITS, NEMA PLUGS ARE NAM RATED ONLY AND CAPTIVE AUS/NZ
PLUGS ARE EMEA RATED ONLY
OPTIONS LISTED ON THIS ROW ARE NON STANDARD,
CONTACT SALES FOR ADDITIONAL INFORMATION
(DEFAULT) TOP FEED = 0
BOTTOM FEED = 2
(DEFAULT) 1.8m [6'] = 0
1m [3.2'] = 1
2m [6.6'] = 2
(DEFAULT) BLACK = 0
RED = R
GREEN = G
MODEL IS SHOWN IN DEFAULT CONFIGURATION. FOR
OPTIONAL CONFIGURATIONS, USE ITEM IDENTIFIER
CODE IN PLACE OF EACH ASTERISK. ORDERABLE
BASED ON FORMAT: EN6952- * * * *
EN6952-
0.5m [1.6'] = A
1.5m [4.9'] = B
2.5m [8.2'] = C
1.2m [4'] = G
1.8m [6'] = F
BLUE = B
WHITE = W
YELLOW = Y
ECN/ECO REV. DESCRIPTION DATE APPROVED
REVISIONS
E1 INITIAL DRAFT REVIEW 2022/05/24 LRF
3000M(9840FT)
RoHS COMPLIANT
COMPLIANCE
SAFETY&ENVIRONMENTAL
FEATURES
INPUT POWER CORD:
METERED COMPONENTS
REMOTE OUTLET SWITCHING
ENVIRONMENTAL CONDITIONS
OPERATING TEMPERATURE
STORAGE TEMPERATURE
INPUT PLUG:
RATED POWER:
INPUT PHASE:
BREAKER QTY & TYPE:
INPUT CURRENT:
INPUT VOLTAGE:
OUTLET QTY & TYPE:
ORIENTATION:
UNIT TYPE:
TECHNICAL SPECIFICATIONS
VERTICAL, 0U FULL
(21)C13/C15,(21)C13/C15/C19
200-240VAC
60A (48A DERATED)
(6)20AMP, DOUBLE-POLE
THREE-PHASE,DELTA
17.3 kVA
SEE NOTE 7
SEE IDENTIFICATION TABLE
+-1% TO ISO/ IEC 62052-21
YES
-5 TO 60 C (23 TO 140 F)
-20 TO 60 C (-4 TO 140 F)
IDENTIFICATION TABLE
THIS DRAWING AND SPECIFICATIONS HEREIN ARE THE PROPERTY OF CIS
GLOBAL AND SHALL NOT BE COPIED, REPRODUCED OR USED IN WHOLE OR IN
PART, AS THE BASIS FOR THE MANUFACTURE OR SALE OF ITEMS WITHOUT
WRITTEN PERMISSION FROM CIS GLOBAL. THIS DRAWING IS BASED UPON
LATEST AVAILABLE INFORMATION AND IS SUBJECT TO CHANGE WITHOUT NOTICE
INTERPRET PER ASME Y14.5M-1994
INPUT PLUG
CHASSIS COLOR
CORD OPTION
ORIENTATION
ORANGE = A
UNLESS NOTED, DIMENSIONS ARE IN
MILLIMETERS & TOLERANCES ARE:
Ø X.X
Ø X.XX
0.3 MM
0.10 MM
X° ±1°
BRACKETED DIMENSIONS ARE IN
INCHES FOR REFERENCE ONLY
X.X ±0.5 MM
X ±1 MM
X ±0.20 MM
X.X° ± 0.5°
SHEET
3m [10'] = 3
SCALE :N/A
(DEFAULT) 460P9 (IP44) =0
(OPTIONAL)460P9W(IP67) =Z
10 10 e n
L O
G I C
Re se t
Se ns or
Se ns or
LJB
Hanson
Advantage Series
Metered & Switched per outlet
MONITORED & SWITCHED PER OUTLET
1780.0
[70.08"]
B1 B2 B3
FRONT VIEW
B4 B5 B6
B1
[WHITE]
B2
[LIGHT GRAY]
B3
[DARK GRAY]
B2
[LIGHT GRAY]
B3
[DARK GRAY]
B1
[WHITE]
B4
[WHITE]
B5
[LIGHT GRAY]
B6
[DARK GRAY]
B4
[WHITE]
B5
[LIGHT GRAY]
B6
[DARK GRAY]
BOTTOM VIEW
75.0
[2.95"]
56.0
[2.20"]
SIDE VIEW
40.5
[1.59"]
2X 24.0
[.94"]
1555.0
[61.22"]
2X 24.0
[.94"]
(4) PL 48.0
[1.89"]
75.0
[2.95"]
INPUT CORD
LENGTH SEE
IDENTIFICATION
TABLE
REAR VIEW
40.5
[1.59"]
24.0
[.94"]
1555.0
[61.22"]
(2) PL Ø18.4
[Ø.72"]
24.0
[.94"] enLOGIC
INPUT(PHASE),CIRCUIT BREAKERS,OUTLETS
E2 2022/10/08
Leo Liu
ECN-2210-0226
ATTRIBUTES
METERING ACCURACY
REVISE METER ACCURACY AND ATTRIBUTES CONTENT
E3 2023/02/09
LRF ECN-2302-0023
ADD MAC LABEL
E N 6 9 5 2 - W X Y Z
X X X X X X X X
MAC 0 A d d r e s s : X X - X X - X X - X X - X X - X X
MAC 1 A d d r e s s : X X - X X - X X - X X - X X - X X
SKU#:
Serial Number
LAYOUT DETAILS
SEE SHEET 2 FOR ADDITIONAL
A
ECN-2310-0251
UPDATE LABEL RATING ,ADD JAPAN RATING 60A TO AVOID PSE
2023/10/10
LRF
B 2023/10/27
LRF ECN-2310-0266
CORRECT LABEL ,DELETE SE ADRRESS
B
2023/10/27
2023/10/27
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text J
AutoCAD SHX Text K
AutoCAD SHX Text L
AutoCAD SHX Text M
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text J
AutoCAD SHX Text K
AutoCAD SHX Text L
AutoCAD SHX Text M
AutoCAD SHX Text H
RECEPTACLE
Advantage Series Metered & Switched per outlet
EXTERNAL GROUND
20 AMP, DOUBLE-POLE ELECTRO
MECHANICAL SWITCH / BREAKER
(6) PLACES
NMC SHOWN IN
DEFAULT ORIENTATION
e n
L O
G I C
Re se t
Se ns or
Se ns or
LRF 2022/05/24
EN6952-WXYZ_DA
LJB
Hanson enLOGIC
E N 6 9 5 2 - W X Y Z
X X X X X X X X
MAC 0 A d d r e s s : X X - X X - X X - X X - X X - X X
MAC 1 A d d r e s s : X X - X X - X X - X X - X X - X X
SKU#:
Serial Number
MAC1 ADDRESS
LABEL DETAIL
SKU#
SERIAL NUMBER
MAC0 ADDRESS
E N 6 9 5 2 - W X Y Z
X X X X X X X X
MAC 0 A d d r e s s : X X - X X - X X - X X - X X - X X
MAC 1 A d d r e s s : X X - X X - X X - X X - X X - X X
SKU#:
Serial Number
B
2023/10/27
NOTES:
1.. INTERNAL WIRI
WIRE TYPE:
LINE 1/R/X COLOR:
LINE 2/S/Y COLOR:
UL AWM 101
Black
Orange
LINE 3/T/Z COLOR: Red EARTH GROUND COLOR: Green/Yellow
2.. FOR FINISHED GOOD PART NUMBER SEE IDENTIFICATI
Advantage Series Metered & Switched per outlet
LRF
EN6952-WXYZ_DA
LJB
Hanson enLOGIC
Metered &Switched per outlet
Power Supply
L N
CN1
CN2
NMC Display
CN1
CN3
NMC Core Board
CN3
CN3
Back Board
CN2 CN4
AWM 1015, 18AWG
AWM 1015, 18AWG
J4 J5 J6J3J1 J2
CB1
LLLN N N
CB2 CB3
VT Board
1 3
J3 4*C13+4*C13/4*C19
J2 4*C13+4*C13/4*C19
1 in 1 out
2 in 2 out
B1
2-Pole-20A
1 in 1 out
2 in 2 out
B2
2-Pole-20A
1 in 1 out
2 in 2 out
B4
2-Pole-20A
1 in 1 out
2 in 2 out
B5
2-Pole-20A
1 in 1 out
2 in 2 out
B3
2-Pole-20A
1 in 1 out
2 in 2 out
B6
2-Pole-20A
Line1/R/X: Black Line2/S/Y: Orange Line3/T/Z: Red Earth ground: Green
J0
IEC 60309 9H 60A
J4 J5 J6J3J1 J2
CB1
LLLN N N
CB2 CB3
VT Board
J1 4*C13+4*C13/4*C19
J4 3*C13+3*C13/3*C19
J5 3*C13+3*C13/3*C19
J6 3*C13+3*C13/3*C19
Control Board
Meter Board
CN3
CN9 CN10
Control Board
Meter Board
CN3
CN9 CN10
Control Board
Meter Board
CN3
CN9 CN10
Relay Board
Meter Board
CN3
CN10CN9
Relay Board
Meter Board
CN3
CN10CN9
Relay Board
Meter Board
CN3
CN10CN9
Control Board
Relay Board
Control Board
Relay Board
Control Board
Relay Board
Control Board
Relay Board
Control Board
Relay Board
Control Board
Relay Board
F1 F2
Ferrite Beads(Black)
2022/05/24
Made In XXXXX
EN6952-WXYZ
Serial Number
SKU #: EN6952-WXYZ
Model #: EP164048-0061-C
RACK Power Distribution Unit
Max load per C13/C15;200-240VAC,10A
Max load per IEC 60309 3P+E 9H:60A
Max load per MCB:20A
Max load per C19;200-240VAC,16A
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE,
AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
CAN ICES-3(A)/NMB-3(A)
C US
300805
RATING FOR US AND CANADA:
MAXIMUM INPUT CIRCUIT RATING:
200-240VAC(50/60Hz),48A
RATING FOR JAPAN:
MAXIMUM INPUT CIRCUIT RATING:
200-240VAC(50/60Hz),60A
X X X X X X X X X
B
| RP6952WXYZ_DA_A-模型 |
| 图纸和视图 |
| 模型 |
RP6952WXYZ_DA_E1
File details come from the government source that posted it. Updated .