ELECTRICAL PANEL SCHEDULE U18L.xlsx

XLSX spreadsheet 25 KB Posted

Attached to
WWYK250063 - INSTALL REACT VII FACILITY, B9001, POST V19
Solicitation number
FA813727R0002
Issued by

About this file

This is an electrical panel schedule document for two 480V and 208V three-phase electrical distribution panels designated U18H and U18L, respectively. Panel U18H operates at 480 volts with a 200-amp main disconnect and 250-amp power capacity, featuring a 22K AIC rating and Square D NF or equivalent main breaker. The panel distributes power to VAV (Variable Air Volume) units for HVAC zones 101-104, an Energy Recovery Ventilator (ERV-V19), and a Transient Voltage Surge Suppressor (TVSS) rated at 50KA. The total connected load is approximately 98.93 KVA with an estimated demand load of 79.14 KVA requiring 95.19 amps. The TVSS installation specifies an Eaton #SP1-480D (Grainger #787R41) or equal connected to a 3-pole, 30-amp breaker with short, straight leads and no sharp bends.

Panel U18L operates at 208 volts with a 225-amp main disconnect and NEMA 1 enclosure, featuring a 10K AIC rating and Square D NQ panel. This panel serves lighting loads for rooms 101-105, receptacles, office furniture feeds, an electric hot water heater (7,280VA on a 2-pole 50-amp breaker), overhead doors, AHU-1 control panel, and a supply fan (SFV-19-01). The total connected load is 33.0 KVA with an estimated demand load of 26.4 KVA requiring 73.3 amps. The TVSS installation requires a Mersen unit rated for 208/120V, 50KAV connected to a 3-pole, 30-amp breaker with leads kept short, straight, and without sharp bends. Both panels include spare circuit capacity for future expansion.

View the file

Other files

File Type Posted
250063_ATT 13_Prebid RFI Responses Round 1.pdf PDF
250063_ATT 8_Liquidated Damages.pdf PDF
250063_ATT 4_ODS.pdf PDF
2026 TAFB Mechanical Standard_signed.pdf PDF
2026 TAFB FIRE PROTECTION STANDARD.pdf PDF
SOW Att 04_Automated Casting Cell.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
250063_ATT 10_Submittal Register.pdf PDF
23 00 00.pdf PDF
08 11 13.pdf PDF
08 33 23.pdf PDF
10 22 13.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 71 00.pdf PDF
01 33 00.pdf PDF
01 50 00.pdf PDF
ufc_3_260_01_2019_c1.pdf PDF
EM_385-1-1.pdf PDF
dafi21-101_afmcsup_afmcgm2023-01.pdf PDF
ufc_3_601_02_2021.pdf PDF
tinkerafbi13-204.pdf PDF
afman32-7003.pdf PDF
afman91-203_oc-alcsup.pdf PDF
afi48-104.pdf PDF
dodio-2000.16v1_afi10-245-o.pdf PDF
007200_Attch7b_Monthly Hazardous Usage Report.pdf PDF
007200_Attch9_EMS Awareness Training.pdf PDF
JOIST SPECIAL INSPECTIONS.xlsx XLSX spreadsheet
250063_ Redline A-502.pdf PDF
HE05IN_Dimension_Drawing.pdf PDF
lrad331965pd_spec.pdf PDF
ELECTRICAL COMBINED.pdf PDF
4500-MUG.pdf PDF
220042 As Built Drawings.pdf PDF
Solicitation - FA813727R0002.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
250063_ATT 3_RMDF.pdf PDF
23 05 15.pdf PDF
23 09 13.pdf PDF
09 90 00.pdf PDF
26 20 00.pdf PDF
08 51 23.pdf PDF
07 92 00.pdf PDF
07 14 00.pdf PDF
08 71 00.pdf PDF
23 05 93.pdf PDF
07 84 00.pdf PDF
03 01 00.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

PANEL U18H SCHEDULE
VOLTS (L-l) 480PHASE 3WIRE 4S/N BUSS 100%EG BUS 100%MOUNT SURFACEENCLOSURE NEMA 1
DISCONNECT Main BreakerDISCONNECT AMPS 200POWER AMPS 250PANEL AIC 22K MINUM
COMMENTS SQ D NF OR EQUAL WITH MAIN BREAKER
Load /Phase (VA)
Circuit No.Trip AmpNo. PolesLoad TypeLoad ServedABCLoad ServedLoad TypeNo. PolesTrip AmpCircuit No.
1153MVAV - 101< 926Air Handling Unit (AHU-1)M3202
2106 >
3< 9264
2106 >
5< 9266
2106 >
7153MVAV - 102< 1109VAV - 103M3158
926 >
9< 1109SPAREF12010
926 >
11< 1109SPAREF12012
926 >
13203F< 1801VAV - 104M31514
F1109 >
15201ERV-V19< 1801SPAREF12016
F1109 >
171< 1801SPAREF12018
F1109 >
19201SPARE<SPAREF12020
F>
21201SPARE<SPAREF12022
F>
231<SPAREF12024
F>
251<SPAREF12026
F>
271<SPAREF12028
F>
291<SPAREF12030
F>
311<F132
F>
331<F134
F>
351<F136
F>
37303OTVSS< 075KVAT312538
25000 >
39< 040
25000 >
41< 042
25000 >
TOTAL329773297732977
TOTAL CONNECTED LOAD 98.93 KVA
ESTIMATED DEMAND LOAD 79.14 KVADEMAND LINE AMPS 95.19 AMPS
INSTALL TVSS EATON #SP1-480D (GRAINGER #787R41) OR EQUAL 480V, 50KA CONNECT TO 3P30A BREAKER IN PANEL AND KEEP LEADS AS SHORT AND STRAIGHT AS POSSIBLE WITH NO SHARP BENDS ALLOWED.
PANEL U18L SCHEDULE
VOLTS (L-l) 208PHASE 3WIRE 4S/N BUSS 100%EG BUS 100%MOUNT SURFACEENCLOSURE NEMA 1
DISCONNECT Main BreakerDISCONNECT AMPS 225POWER AMPS 225PANEL AIC 10K MINUM
COMMENTS SQ DNQ PANEL
Load /Phase (VA)
Circuit No.Trip AmpNo. PolesLoad TypeLoad ServedABCLoad ServedLoad TypeNo. PolesTrip AmpCircuit No.
1201LROOM LIGHTS 101 & 102<536ROOM 101 SW OFFICER1202
540>
3201LROOM LIGHTS 104<380ROOM 101 SW OFFICER1204
360>
5201LROOM LIGHTS 103<766ROOM 101 SW OFFICER1206
360>
7201RROOM 102 PRINTER AND RECPT<720ROOM 104 NORTH RECPTR1208
1080>
9201FROOM 102 EASTCOUNTERTOP<1500ROOM 104 L6-30 RECPTR23010
2400>
11201RROOM 102 CENTER COUNTERTOP<150012
2400>
13201RROOM 102 WEST COUNTERTOP<1920ROOM 104 RECPTR12014
540>
15201RROOM 102 OFFICE FURNITURE FEED<720ROOM 104 RECPTR12016
720>
17201RROOM 102 OFFICE FURNITURE FEED<720ROOM 104 RECPTR12018
540>
19201RROOM 103 WEST RECPT<540ROOM 102 NE RECPTR12020
1080>
21201RROOM 103 N CENTER CORD REEL<540ROOM 103 S CENTER CORD REELR12022
540>
23201RROOM 103 NE CENTER CORD REEL<540ROOM 103 SE CENTER CORD REELR12024
>
25201OSPARE<ELECTRIC HOT WATER HEATERO25026
7280>
27201OROOM 103 OVERHEAD DOOR<75028
7280>
29201MAHU-1 CONTROL PANEL<1200SPARES12030
732>
31201SSPARE<SUPPLY FAN SFV-19-01S12032
>
33201OROOM 105

OVERHEAD

DOOR100SPARES12034
>
35100SPARES12036
>
37151ODOORBELL<500SPARE2038
>
3920SPARE<SPARE2040
>
4120SPARE<SPARE2042
>
43<44
>
45<46
>
47<48
>
49303OTVSS< 050
>
51052
>
53< 054
>
TOTAL147361577014106
TOTAL CONNECTED LOAD 33.0 KVA
ESTIMATED DEMAND LOAD 26.4 KVADEMAND LINE AMPS 73.3 AMPS
INSTALL TVSS MERSEN FOR 201/120V, 50KAV, CONNECT TO 3P, 30A BREAKER IN PANEL AND KEEP LEADS AS SHORT AND STRAIGHT AS POSSIBLE WITH NOT SHARP BENDS.

File details come from the government source that posted it. Updated .