This is an electrical panel schedule document for two 480V and 208V three-phase electrical distribution panels designated U18H and U18L, respectively. Panel U18H operates at 480 volts with a 200-amp main disconnect and 250-amp power capacity, featuring a 22K AIC rating and Square D NF or equivalent main breaker. The panel distributes power to VAV (Variable Air Volume) units for HVAC zones 101-104, an Energy Recovery Ventilator (ERV-V19), and a Transient Voltage Surge Suppressor (TVSS) rated at 50KA. The total connected load is approximately 98.93 KVA with an estimated demand load of 79.14 KVA requiring 95.19 amps. The TVSS installation specifies an Eaton #SP1-480D (Grainger #787R41) or equal connected to a 3-pole, 30-amp breaker with short, straight leads and no sharp bends.
Panel U18L operates at 208 volts with a 225-amp main disconnect and NEMA 1 enclosure, featuring a 10K AIC rating and Square D NQ panel. This panel serves lighting loads for rooms 101-105, receptacles, office furniture feeds, an electric hot water heater (7,280VA on a 2-pole 50-amp breaker), overhead doors, AHU-1 control panel, and a supply fan (SFV-19-01). The total connected load is 33.0 KVA with an estimated demand load of 26.4 KVA requiring 73.3 amps. The TVSS installation requires a Mersen unit rated for 208/120V, 50KAV connected to a 3-pole, 30-amp breaker with leads kept short, straight, and without sharp bends. Both panels include spare circuit capacity for future expansion.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| PANEL U18H SCHEDULE | |||||||||||||||
| VOLTS (L-l) 480 | PHASE 3 | WIRE 4 | S/N BUSS 100% | EG BUS 100% | MOUNT SURFACE | ENCLOSURE NEMA 1 | |||||||||
| DISCONNECT Main Breaker | DISCONNECT AMPS 200 | POWER AMPS 250 | PANEL AIC 22K MINUM | ||||||||||||
| COMMENTS SQ D NF OR EQUAL WITH MAIN BREAKER | |||||||||||||||
| Load /Phase (VA) | |||||||||||||||
| Circuit No. | Trip Amp | No. Poles | Load Type | Load Served | A | B | C | Load Served | Load Type | No. Poles | Trip Amp | Circuit No. | |||
| 1 | 15 | 3 | M | VAV - 101 | < 926 | Air Handling Unit (AHU-1) | M | 3 | 20 | 2 | |||||
| 2106 > | |||||||||||||||
| 3 | < 926 | 4 | |||||||||||||
| 2106 > | |||||||||||||||
| 5 | < 926 | 6 | |||||||||||||
| 2106 > | |||||||||||||||
| 7 | 15 | 3 | M | VAV - 102 | < 1109 | VAV - 103 | M | 3 | 15 | 8 | |||||
| 926 > | |||||||||||||||
| 9 | < 1109 | SPARE | F | 1 | 20 | 10 | |||||||||
| 926 > | |||||||||||||||
| 11 | < 1109 | SPARE | F | 1 | 20 | 12 | |||||||||
| 926 > | |||||||||||||||
| 13 | 20 | 3 | F | < 1801 | VAV - 104 | M | 3 | 15 | 14 | ||||||
| F | 1109 > | ||||||||||||||
| 15 | 20 | 1 | ERV-V19 | < 1801 | SPARE | F | 1 | 20 | 16 | ||||||
| F | 1109 > | ||||||||||||||
| 17 | 1 | < 1801 | SPARE | F | 1 | 20 | 18 | ||||||||
| F | 1109 > | ||||||||||||||
| 19 | 20 | 1 | SPARE | < | SPARE | F | 1 | 20 | 20 | ||||||
| F | > | ||||||||||||||
| 21 | 20 | 1 | SPARE | < | SPARE | F | 1 | 20 | 22 | ||||||
| F | > | ||||||||||||||
| 23 | 1 | < | SPARE | F | 1 | 20 | 24 | ||||||||
| F | > | ||||||||||||||
| 25 | 1 | < | SPARE | F | 1 | 20 | 26 | ||||||||
| F | > | ||||||||||||||
| 27 | 1 | < | SPARE | F | 1 | 20 | 28 | ||||||||
| F | > | ||||||||||||||
| 29 | 1 | < | SPARE | F | 1 | 20 | 30 | ||||||||
| F | > | ||||||||||||||
| 31 | 1 | < | F | 1 | 32 | ||||||||||
| F | > | ||||||||||||||
| 33 | 1 | < | F | 1 | 34 | ||||||||||
| F | > | ||||||||||||||
| 35 | 1 | < | F | 1 | 36 | ||||||||||
| F | > | ||||||||||||||
| 37 | 30 | 3 | O | TVSS | < 0 | 75KVA | T | 3 | 125 | 38 | |||||
| 25000 > | |||||||||||||||
| 39 | < 0 | 40 | |||||||||||||
| 25000 > | |||||||||||||||
| 41 | < 0 | 42 | |||||||||||||
| 25000 > | |||||||||||||||
| TOTAL | 32977 | 32977 | 32977 | ||||||||||||
| TOTAL CONNECTED LOAD 98.93 KVA | |||||||||||||||
| ESTIMATED DEMAND LOAD 79.14 KVA | DEMAND LINE AMPS 95.19 AMPS | ||||||||||||||
| INSTALL TVSS EATON #SP1-480D (GRAINGER #787R41) OR EQUAL 480V, 50KA CONNECT TO 3P30A BREAKER IN PANEL AND KEEP LEADS AS SHORT AND STRAIGHT AS POSSIBLE WITH NO SHARP BENDS ALLOWED. |
| PANEL U18L SCHEDULE | |||||||||||||||
| VOLTS (L-l) 208 | PHASE 3 | WIRE 4 | S/N BUSS 100% | EG BUS 100% | MOUNT SURFACE | ENCLOSURE NEMA 1 | |||||||||
| DISCONNECT Main Breaker | DISCONNECT AMPS 225 | POWER AMPS 225 | PANEL AIC 10K MINUM | ||||||||||||
| COMMENTS SQ D | NQ PANEL | ||||||||||||||
| Load /Phase (VA) | |||||||||||||||
| Circuit No. | Trip Amp | No. Poles | Load Type | Load Served | A | B | C | Load Served | Load Type | No. Poles | Trip Amp | Circuit No. | |||
| 1 | 20 | 1 | L | ROOM LIGHTS 101 & 102 | <536 | ROOM 101 SW OFFICE | R | 1 | 20 | 2 | |||||
| 540> | |||||||||||||||
| 3 | 20 | 1 | L | ROOM LIGHTS 104 | <380 | ROOM 101 SW OFFICE | R | 1 | 20 | 4 | |||||
| 360> | |||||||||||||||
| 5 | 20 | 1 | L | ROOM LIGHTS 103 | <766 | ROOM 101 SW OFFICE | R | 1 | 20 | 6 | |||||
| 360> | |||||||||||||||
| 7 | 20 | 1 | R | ROOM 102 PRINTER AND RECPT | <720 | ROOM 104 NORTH RECPT | R | 1 | 20 | 8 | |||||
| 1080> | |||||||||||||||
| 9 | 20 | 1 | F | ROOM 102 EASTCOUNTERTOP | <1500 | ROOM 104 L6-30 RECPT | R | 2 | 30 | 10 | |||||
| 2400> | |||||||||||||||
| 11 | 20 | 1 | R | ROOM 102 CENTER COUNTERTOP | <1500 | 12 | |||||||||
| 2400> | |||||||||||||||
| 13 | 20 | 1 | R | ROOM 102 WEST COUNTERTOP | <1920 | ROOM 104 RECPT | R | 1 | 20 | 14 | |||||
| 540> | |||||||||||||||
| 15 | 20 | 1 | R | ROOM 102 OFFICE FURNITURE FEED | <720 | ROOM 104 RECPT | R | 1 | 20 | 16 | |||||
| 720> | |||||||||||||||
| 17 | 20 | 1 | R | ROOM 102 OFFICE FURNITURE FEED | <720 | ROOM 104 RECPT | R | 1 | 20 | 18 | |||||
| 540> | |||||||||||||||
| 19 | 20 | 1 | R | ROOM 103 WEST RECPT | <540 | ROOM 102 NE RECPT | R | 1 | 20 | 20 | |||||
| 1080> | |||||||||||||||
| 21 | 20 | 1 | R | ROOM 103 N CENTER CORD REEL | <540 | ROOM 103 S CENTER CORD REEL | R | 1 | 20 | 22 | |||||
| 540> | |||||||||||||||
| 23 | 20 | 1 | R | ROOM 103 NE CENTER CORD REEL | <540 | ROOM 103 SE CENTER CORD REEL | R | 1 | 20 | 24 | |||||
| > | |||||||||||||||
| 25 | 20 | 1 | O | SPARE | < | ELECTRIC HOT WATER HEATER | O | 2 | 50 | 26 | |||||
| 7280> | |||||||||||||||
| 27 | 20 | 1 | O | ROOM 103 OVERHEAD DOOR | <750 | 28 | |||||||||
| 7280> | |||||||||||||||
| 29 | 20 | 1 | M | AHU-1 CONTROL PANEL | <1200 | SPARE | S | 1 | 20 | 30 | |||||
| 732> | |||||||||||||||
| 31 | 20 | 1 | S | SPARE | < | SUPPLY FAN SFV-19-01 | S | 1 | 20 | 32 | |||||
| > | |||||||||||||||
| 33 | 20 | 1 | O | ROOM 105 |
OVERHEAD
| DOOR | 100 | SPARE | S | 1 | 20 | 34 | ||||||||||
| > | ||||||||||||||||
| 35 | 100 | SPARE | S | 1 | 20 | 36 | ||||||||||
| > | ||||||||||||||||
| 37 | 15 | 1 | O | DOORBELL | <500 | SPARE | 20 | 38 | ||||||||
| > | ||||||||||||||||
| 39 | 20 | SPARE | < | SPARE | 20 | 40 | ||||||||||
| > | ||||||||||||||||
| 41 | 20 | SPARE | < | SPARE | 20 | 42 | ||||||||||
| > | ||||||||||||||||
| 43 | < | 44 | ||||||||||||||
| > | ||||||||||||||||
| 45 | < | 46 | ||||||||||||||
| > | ||||||||||||||||
| 47 | < | 48 | ||||||||||||||
| > | ||||||||||||||||
| 49 | 30 | 3 | O | TVSS | < 0 | 50 | ||||||||||
| > | ||||||||||||||||
| 51 | 0 | 52 | ||||||||||||||
| > | ||||||||||||||||
| 53 | < 0 | 54 | ||||||||||||||
| > |
| TOTAL | 14736 | 15770 | 14106 | |||
| TOTAL CONNECTED LOAD 33.0 KVA | ||||||
| ESTIMATED DEMAND LOAD 26.4 KVA | DEMAND LINE AMPS 73.3 AMPS | |||||
| INSTALL TVSS MERSEN FOR 201/120V, 50KAV, CONNECT TO 3P, 30A BREAKER IN PANEL AND KEEP LEADS AS SHORT AND STRAIGHT AS POSSIBLE WITH NOT SHARP BENDS. |