E2.02.One Line Diagram.pdf
PDF 193 KB Posted
- Solicitation number
- RFP GMAA 2019000145 3
- Issued by
- Denver County, Denver City, Colorado
About this file
This is an Electrical One-Line Diagram for the Auraria Library Renovation project at the Auraria Higher Education Center in Denver, Colorado. The diagram illustrates the electrical distribution system (MDC2) serving the renovated facility, with a primary focus on the redesign and upgrade of electrical infrastructure to support new mechanical equipment installations across multiple floors and basement levels. The project involves replacing existing panels, transformers, and distribution equipment while maintaining connectivity to the existing electrical grid supplied by Xcel Energy. Key work items include providing new 600-ampere mechanical panels on the south basement, first floor south, and second floor south mechanical rooms; replacing existing transformers with new units of specified capacities (ranging from 30 kVA to 75 kVA); upgrading conduit sizes from 2.5 inches to 3 inches in specified locations; relocating existing panels with associated extensions; and conducting infrared scans and maintenance on existing distribution gear. The electrical design accommodates a total connected load of 848,770 volt-amperes across multiple distribution panels with demand factors applied per National Electrical Code requirements.
The one-line diagram specifies conductor sizing, conduit types, and overcurrent protection settings in accordance with the 2011 National Electrical Code. The system operates at 480-volt three-phase primary service with secondary voltages of 208Y/120 volts three-phase four-wire. All conductors are copper with magnetic conduit systems. The project document includes coordination requirements with the building owner for all equipment shutdowns and specifies that existing circuit configurations must be field-verified during installation. Engineering services were provided by BCER, structural engineering by Martin & Martin, and the project is owned by the Auraria Higher Education Center. The addendum dated February 9, 2015, updates the electrical design specifications for the phased renovation project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
#842 50(3#10 & 1#10G)3/4"C. (4#6 & 1#8G)1"C.1815 25T1
GROUNDING ELECTRODE CONDUCTOR SIZED PER TABLE 250.66 OF 2011 N.E.C.
EQUIPMENT GROUNDING CONDUCTOR SIZED PER TABLE 250.122 OF 2011 N.E.C.
SUPPLY SIDE BONDING JUMPER SIZED PER 250.102 OF THE 2011 N.E.C.
b.
c.
a.NOTES:
T4
T3
T2
KEY KVA AMPS
(4#500KCMIL & 1#1/0G)3-1/2"C.
208Y/120 VOLT, 3 PHASE, 4W - SECONDARY
(4#3 & 1#8G)1-1/4"C.
(4#1/0 & 1#6G)2"C.
DRY TYPE TRANSFORMER SCHEDULE
(3#1 & 1#6G)1-1/4"C.
(3#6 & 1#10G)1"C.
(3#4 & 1#8G)1"C.
480 VOLT, 3 PHASE - PRIMARY
PFEEDER
AMPS
#1/0
#6
#8
FEEDER S G
(3#2/0 & 1#6G)2"C.112.5T5 135 175
(4#4/0 & 1#2G)3"C.200 225 #2
2[(4#4/0 & 1#1/0G)3"C.]450415 #1/0(3#4/0 & 1#4G)2-1/2"C.150T6 180 225
2[(4#500KCMIL & 1#2/0G)3-1/2"C.]700625 #2/0(3#500KCMIL & 1#3G)3"C.225T7 270 350
3[(4#350KCMIL & 1#3/0G)3-1/2"C.]900831 #3/02[(3#4/0 & 1#2G)2"C.]300T8 360 450
5[(4#400KCMIL & 1#250KCMIL-G)4"C.]16001385 #3/02[(3#500KCMIL & 1#1/0G)3"C.]500T9 600 750
O.C.
PROTECTION
GRD.
ELECTRODE
O.C.
PROTECTION
CONDUCTOR SIZES BASED ON COPPER.d.
FAULT CURRENT SCHEDULE - MDC2
Node ID
Node Description
Xcel Energy
Utility Xfmr
MDC2
PANEL MPBS
PANEL MPGW
PANEL MP2W
45K-PRIM RGW2/RGW3
45K-SEC RGW2/RGW3
PANEL LBS1
PANEL LGW1
45KVA-PRIM RGW1
45KVA-SEC RGW1
PANEL L2W1
NodeType
Utility
Xfmr
Panel
Panel
Panel
Panel
Panel
Xfmr
Panel
Panel
Panel
Xfmr
Panel
Line Voltage
From
To
Utility Avail MVA Xfrmr Size
1,500
45.0
45.0
Feeder Information
Runs
Size
#500KCMIL
#350KCMIL
#350KCMIL
#350KCMIL
#4
#350KCMIL
#500KCMIL
#4
#500KCMIL
Length
ConductorType
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Conduit Type
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Sym.RMS Fault Current
33,914
32,612
15,850
10,267
10,091
9,510
2,955
10,574
9,080
8,529
2,924
8,838
Per Unit R Value
0.00860
0.00978
0.04787
0.08659
0.08849
0.10677
1.14344
0.08341
0.08530
0.10548
1.14215
Per Unit jX Value
0.05250
0.05445
0.10328
0.15292
0.15536
0.15683
0.82350
0.14885
0.17945
0.18336
0.85003
X/R Ratio
6.10
5.57
2.16
1.77
1.76
1.47
0.72
1.78
2.10
1.74
0.74
2.09
''MDC2'' LOAD SUMMARY
277/480V, 3P, 4W
Panel
DPS1
MPBS
MPGW
MP2W
RGW2
RGW3(REMOVED)
LGS1
RGS3
RGS2
RGS1
LBS1
RBS1/RBS2
CBLSA/CBLSB
LGW1
RGW1
L2W1
R2W1
C2W1
CGW1
DPS2*
RGC4A/RGC4B
S2
TOTAL CONNECTED VA
DEMAND FACTORS PER NEC
TOTAL DEMAND LOAD (VA)
* DIST PANEL ONLY - NO LOAD EXCEPT FOR SUB PANELS
Sub-Feed Panel
NEC - DERATED DEMAND LOAD IN VA
Lighting
37,774
17,500
17,500
1,350
19,212
1,150
95,966
1.25
119,958
Recepts
3,420
19,620
9,720
14,760
3,600
4,860
4,200
13,260
2,520
75,960
NEC 220.44
42,980
Largest Motor
79,444
47,367
84,762
1,130
84,762
1.25
105,953
TOTAL DEMAND LOAD
SPARE CAPACITY
TOTAL
Remaining Motors
47,888
24,930
19,612
4,308
1,600
227,229
1.00
227,229
Equipment
13,400
10,481
8,500
14,530
9,390
24,800
12,550
3,500
97,651
1.00
97,651
Panel(s)
125,000
20,000
70,000
40,000
255,000
1.00
255,000
36%
Kitchen
0.65
1,021
1,600
Total
848,770
A
A
A
R G S
(N)
M P B S
(N) L B S
(N)
P P
T
P
P
G
R G C A
(R)
R G C B
(R)
S
L G W
(N)
M P G W (N)
R G W
(N)
T P
S
G
T G
P
R G W
(N)
L W
(N)
M P W (N)
P
T G
R W
(N)
S
P
L G S
(E)
R G S
(E)
T
T
R G S
(E)
T
R G S S A
(E)
R G S S B
(E)
R B L S C
(E)
R B L S B
(E)
R B L S B
(E)
T
C B L S A
(E)
C B L S B
(E)
T
J
R B S
(E)
R B S
(E)
D P S
(E)
S
(E)
T
T
R G W
(E)
T
C W
(E)
C G W
(E)
ELECTRICAL ONE-LINE DIAGRAM - MDC2
(E)SWITCHBOARD "MDC2"
1600A, 480Y/277V, 3PH, 4W
50,000AIC
(E)SWITCHBOARD "DPS1"
800A, 208Y/120V, 3PH, 4W
50,000AIC
400/3
400A
400/3
300A
400/3
400A
400/3
400A
45KVA
K-13
45KVA
SPD
600/3
600A
600/3
600A
800/3
225KVA
800/3
(MAIN)
800A
400/3
DIM #1
100/3
DIM #2
100/3
200/3 200/3 200/3 200/3
FOUR WIRE + GROUND
COPPER CONDUCTORS
INSULATION PER SPECIFICATIONS
FEEDER
IDENTIFIER
FEEDER TABLE
THREE WIRE + GROUND
INSULATION PER SPECIFICATIONS
COPPER CONDUCTORS
IDENTIFIER
FEEDER
DEVICE SETTINGS
OVERCURRENT
8[(4#500KCMIL + 1#400KCMILG)3-1/2"C]
7[(4#500KCMIL + 1#350KCMILG)3-1/2"C]
6[(4#500KCMIL + 1#250KCMILG)3-1/2"C]
5[(4#400KCMIL + 1#4/0G)3-1/2"C]
4[(4#350KCMIL + 1#3/0G)3"C]
3[(4#400KCMIL + 1#2/0G)3"C]
2[(4#500KCMIL + 1#1/0G)3-1/2"C]
2[(4#350KCMIL + 1#1G)3"C]
2[(4#250KCMIL + 1#2G)3"C]
(4#500KCMIL + 1#3G)3-1/2"C
(4#350KCMIL + 1#3G)3-1/2"C
(4#350KCMIL + 1#4G)3-1/2"C
(4#250KCMIL + 1#4G)3"C
(4#4/0 + 1#4G)2-1/2"C
(4#3/0 + 1#6G)2-1/2"C
(4#2/0 + 1#6G)2"C
(4#1/0 + 1#6G)2"C
(4#1 + 1#6G)1-1/2"C
(4#2 + 1#8G)1-1/4"C
(4#4 + 1#8G)1"C
(4#6 + 1#10G)1"C
(4#6 + 1#10G)1"C
(4#8 + 1#10G)3/4"C
(4#10 + 1#10G)3/4"C
(4#12 + 1#12G)3/4"C
4WG3000
4WG2500
4WG2000
4WG1600
4WG1200
4WG1000
4WG800
4WG600
4WG500
4WG400
4WG350
4WG300
4WG250
4WG225
4WG200
4WG175
4WG150
4WG125
4WG100
4WG70
4WG60
4WG50
4WG40
4WG30
4WG20
8[(3#500KCMIL + 1#400KCMILG)3"C]
7[(3#500KCMIL + 1#350KCMILG)3"C]
6[(3#500KCMIL + 1#250KCMILG)3"C]
5[(3#400KCMIL + 1#4/0G)3-1/2"C]
4[(3#350KCMIL + 1#3/0G)2-1/2"C]
4[(3#250KCMIL + 1#2/0G)2-1/2"C]
2[(3#500KCMIL + 1#1/0G)3"C]
2[(3#350KCMIL + 1#1G)2-1/2"C]
2[(3#250KCMIL + 1#2G)2-1/2"C]
(3#500KCMIL + 1#3G)3"C
(3#500KCMIL + 1#3G)3"C
(3#350KCMIL + 1#4G)2-1/2"C
(3#250KCMIL + 1#4G)2-1/2"C
(3#4/0 + 1#4G)2"C
(3#3/0 + 1#6G)2"C
(3#2/0 + 1#6G)2"C
(3#1/0 + 1#6G)2"C
(3#1 + 1#6G)1-1/4"C
(3#2 + 1#8G)1-1/4"C
(3#4 + 1#8G)1"C
(3#6 + 1#10G)1"C
(3#6 + 1#10G)1"C
(3#8 + 1#10G)3/4"C
(3#10 + 1#10G)3/4"C
(3#12 + 1#12G)3/4"C
3WG3000
3WG2500
3WG2000
3WG1600
3WG1200
3WG1000
3WG800
3WG600
3WG500
3WG400
3WG350
3WG300
3WG250
3WG225
3WG200
3WG175
3WG150
3WG125
3WG100
3WG70
3WG60
3WG50
3WG40
3WG30
3WG20
45KVA
200/3
SPD SPD
400/3
75KVA
75KVA
(R)
100/3 w/90A FUSES (R)
SPD
30KVA
(R)
2A
2A
45KVA(N)
45KVA
45KVA(N)
2B
2B
45KVA
K-13
SPD
45KVA(N)
SPD
Isc=32,612A
Isc=15,850A
Isc=10,267A
Isc=10,267A
Isc=2,955A
Isc=9,510A Isc=2,955A
Isc=9,510A
(E)(4#350KCMIL)3"C
Isc=10,5754A
Isc=3,000A (at 5%Z)
(E)(4#500KCMIL)3-1/2"C
Isc=9,080A Isc=8,529A
Isc=2,924A
Isc=8,838A
(E)(4#500KCMIL)3-1/2"C
Isc=4,500A (at 5%Z)
W
G
W G
W
G
SCALE: NO SCALE
WORK NOTES:
PROVIDE NEW PANEL TO REPLACE EXISTING PANEL. CONNECT ALL EXISTING MAIN PANEL
FEEDS AND BRANCH CIRCUITS TO THE SAME CIRCUIT NUMBERS IN THE NEW PANEL. FIELD
VERIFY EXISTING CIRCUIT CONFIGURATIONS. COORDINATE ALL SHUTDOWNS WITH OWNER
PRIOR TO START OF WORK.
PROVIDE NEW 600A MECHANICAL PANEL TO FEED NEW MECHANICAL EQUIPMENT IN THE SOUTH
BASEMENT MECHANICAL ROOM. REPLACE EXISTING (2)2-1/2" WITH (2) 3" CONDUITS AND PULL
NEW CONDUCTORS TO PANEL. COORDINATE ALL SHUTDOWNS WITH OWNER PRIOR TO START
OF WORK.
PROVIDE NEW 600A MECHANICAL PANEL TO FEED NEW MECHANICAL EQUIPMENT IN THE FIRST
FLOOR SOUTH MECHANICAL ROOM. REPLACE EXISTING (2)2-1/2" WITH (2) 3" CONDUITS AND
PULL NEW CONDUCTORS TO PANEL. COORDINATE ALL SHUTDOWNS WITH OWNER PRIOR TO
START OF WORK.
PROVIDE NEW 600A MECHANICAL PANEL TO FEED NEW MECHANICAL EQUIPMENT IN THE
SECOND FLOOR SOUTH MECHANICAL ROOM. REPLACE EXISTING (2)2-1/2" WITH (2) 3"
CONDUITS AND PULL NEW CONDUCTORS TO PANEL. COORDINATE ALL SHUTDOWNS WITH
OWNER PRIOR TO START OF WORK.
RELOCATE EXISTING PANEL AND ALL ASSOCIATED ELECTRICAL EQUIPMENT. EXTEND EXISTING
PANEL FEEDS TO NEW LOCATION. ALSO, EXTEND BRANCH CIRCUITS TO THE NEW PANEL
LOCATION. FIELD VERIFY EXISTING CIRCUIT CONFIGURATIONS. COORDINATE ALL SHUTDOWNS
WITH OWNER PRIOR TO START OF WORK.
REPLACE EXISTING TRANSFORMER WITH NEW TRANSFORMER OF SIZE INDICATED.
REPLACE EXISTING 30KVA TRAPEZE MOUNTED TRANSFORMER WITH NEW 45KVA TRAPEZE
MOUNTED TRANSFORMER. PROVIDE ADDITIONAL STRUCTURAL SUPPORTS IN ORDER TO
SUPPORT THE WEIGHT OF THE NEW TRANSFORMER AS REQUIRED. REMOVE THE EXISTING
100A/3P DISCONNECT AND ASSOCIATED CONDUIT AND WIRING FEEDING EXISTING PANEL "RGW1"
AND PROVIDE ALL NEW AS INDICATED.
REPLACE EXISTING 75KVA TRAPEZE MOUNTED TRANSFORMER WITH NEW 75KVA TRAPEZE
MOUNTED TRANSFORMER. PROVIDE ADDITIONAL STRUCTURAL SUPPORTS IN ORDER TO
SUPPORT THE WEIGHT OF THE NEW TRANSFORMER AS REQUIRED. REMOVE THE EXISTING
400A/3P DISCONNECT AND ASSOCIATED CONDUIT AND WIRING FEEDING EXISTING PANEL(S)
"RGE1" AND "RGE2" AND PROVIDE ALL NEW AS INDICATED.
EXISTING DISTRIBUTION GEAR IS TO BE INSPECTED, CLEANED ON THE INTERIOR AND PROVIDED
WITH AN INFRARED SCAN TO INSURE PROPER WORKING ORDER. ALL EXISTING CONNECTIONS
TO BE TORQUED PER MANUFACTURER'S RECOMMENDATIONS. COORDINATE SHUTDOWN OF
GEAR WITH OWNER PRIOR TO PERFORMING WORK.
OWNERSHIP OF DOCUMENTS:
ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE ENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
PROJECT NO:P
R
O J E
C T
C 2013 STUDIOTROPE, LLC
OWNER
STRUCTURAL ENGINEER
Martin & Martin 12499 W Colfax Ave
Lakewood, CO 80215
(303) 431-6100
MECHANICAL ENGINEER
BCER
5420 Ward Rd
Arvada, CO 80002
(303) 422-7400
ELECTRICAL ENGINEER
BCER
5420 Ward Rd
Arvada, CO 80002
(303) 422-7400
TECHNOLOGY
SSR Inc.
7995 E PRENTICE AVE #104E
GREENWOOD VILLAGE, CO 80111
(303) 779-1222
ACOUSTICS/AUDIO VISUAL
K2 Audio 4900 Pearl E Cir
Boulder, CO 80301
(303) 865-5500
AURARIA HIGHER
EDUCATION CENTER
1156 7th Street, Development
& Planning Annex
Denver, CO 80204 P:(303) 556-3236 auraria.edu
A u ra ri a
L ib ra r y
R e n o v a ti o n
S ta te P h a s e
I I th
S tr e e t D e n v e r, C
O
CIVIL
LANDSCAPE ARCHITECT
Mundus Bishop 2601 Blake Street
Denver, CO 80205
(303) 477-5744
BOWMAN - VISION LAND
603 Park Point Drive
Golden, CO 80401
(303) 674-7355
/9
/2
:2
:5
A
M
E2.02
ELECTRICAL ONE-LINE
DIAGRAM - MDC2
Date Issued Phase
01.19.2015 ADDENDUM NO. 1
02.09.2015 ADDENDUM NO. 2
File details come from the government source that posted it. Updated .