E2.01.One Line Diagram.pdf
PDF 190 KB Posted
- Solicitation number
- RFP GMAA 2019000145 3
- Issued by
- Denver County, Denver City, Colorado
About this file
This is an electrical one-line diagram for the Auraria Library Renovation—State Phase II project located at 1155 10th Street, Denver, Colorado, prepared for the Auraria Higher Education Center. The diagram illustrates the electrical distribution system (MDC1) designed to support the library renovation, featuring a 1600-ampere, 480-volt/277-volt, three-phase, four-wire switchboard with a 50,000-ampere interrupting capacity serving as the main distribution center. The system includes three dry-type transformers (45 killovolt-amperes, 75 killovolt-amperes, and 112.5 killovolt-amperes) that step down power from 480 volts primary to 208 volts/120 volts secondary, distributing power to multiple panels and equipment throughout the building. The diagram specifies conductor sizes, conduit types, feeder lengths, fault current calculations, and grounding requirements based on the 2011 National Electrical Code, with detailed load summaries indicating total connected demand of approximately 866 kilowatt-amperes across lighting, receptacles, motors, and equipment loads.
The work notes direct contractors to provide new panels to replace existing panels, relocate equipment as required, replace three transformers with new units of specified sizes, upgrade existing two-inch conduits to three-inch conduits, coordinate all shutdowns with the facility owner, inspect and torque existing distribution connections, and perform infrared scans of electrical distribution gear. Engineering design services were provided by BCER (mechanical and electrical engineer) located in Arvada, Colorado, with structural engineering by Martin & Martin in Lakewood, Colorado. The diagram was issued on January 19, 2015, with addendum revisions dated February 9, 2015, indicating an active design and construction planning phase for the electrical infrastructure upgrade.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
#842 50(3#10 & 1#10G)3/4"C. (4#6 & 1#8G)1"C.1815 25T1
GROUNDING ELECTRODE CONDUCTOR SIZED PER TABLE 250.66 OF 2011 N.E.C.
EQUIPMENT GROUNDING CONDUCTOR SIZED PER TABLE 250.122 OF 2011 N.E.C.
SUPPLY SIDE BONDING JUMPER SIZED PER 250.102 OF THE 2011 N.E.C.
b.
c.
a.NOTES:
T4
T3
T2
KEY KVA AMPS
(4#500KCMIL & 1#1/0G)3-1/2"C.
208Y/120 VOLT, 3 PHASE, 4W - SECONDARY
(4#3 & 1#8G)1-1/4"C.
(4#1/0 & 1#6G)2"C.
DRY TYPE TRANSFORMER SCHEDULE
(3#1 & 1#6G)1-1/4"C.
(3#6 & 1#10G)1"C.
(3#4 & 1#8G)1"C.
480 VOLT, 3 PHASE - PRIMARY
PFEEDER
AMPS
#1/0
#6
#8
FEEDER S G
(3#2/0 & 1#6G)2"C.112.5T5 135 175
(4#4/0 & 1#2G)3"C.200 225 #2
2[(4#4/0 & 1#1/0G)3"C.]450415 #1/0(3#4/0 & 1#4G)2-1/2"C.150T6 180 225
2[(4#500KCMIL & 1#2/0G)3-1/2"C.]700625 #2/0(3#500KCMIL & 1#3G)3"C.225T7 270 350
3[(4#350KCMIL & 1#3/0G)3-1/2"C.]900831 #3/02[(3#4/0 & 1#2G)2"C.]300T8 360 450
5[(4#400KCMIL & 1#250KCMIL-G)4"C.]16001385 #3/02[(3#500KCMIL & 1#1/0G)3"C.]500T9 600 750
O.C.
PROTECTION
GRD.
ELECTRODE
O.C.
PROTECTION
CONDUCTOR SIZES BASED ON COPPER.d.
FAULT CURRENT SCHEDULE - MDC1
Node ID
Node Description
Xcel Energy
Utility Xfmr
MDC1
PANEL LGN1
45KVA-PRIM RGN1
45KVA-SEC RGN1
PANEL L2N1
45K-PRIM R2N1/CGN1
45K-SEC R2N1/C2N1
PANEL LGE1
PANEL L2E1
75KVA-PRIM RGE1
75KVA-SEC RGE1
PANEL MPBE
PANEL MP2E
PANEL LBE1
112KVA-PRIM RBE1
112KVA-SEC RBE1
NodeType
Utility
Xfmr
Panel
Panel
Panel
Xfmr
Panel
Panel
Xfmr
Panel
Panel
Panel
Xfmr
Panel
Panel
Panel
Panel
Xfmr
Line Voltage
From
To
Utility Avail MVA Xfrmr Size
1,500
45.0
45.0
75.0
112.5
Feeder Information
Runs
Size
1600A Busduct
#500KCMIL
#4
#500KCMIL
#4
#500KCMIL
#500KCMIL
#1
#350KCMIL
#350KCMIL
#500KCMIL
#2/0
Length
ConductorType
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Conduit Type
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Mag.
Non-Mag.
Sym.RMS Fault Current
33,914
33,238
11,429
10,580
3,004
11,173
10,359
2,996
17,102
12,125
15,971
4,036
30,146
23,394
19,042
18,097
4,306
Per Unit R Value
0.00860
0.00995
0.06470
0.08489
1.12155
0.06659
0.08677
1.12344
0.03733
0.05998
0.04774
0.55374
Per Unit jX Value
0.05250
0.05336
0.14399
0.14789
0.81456
0.14711
0.15102
0.81769
0.09868
0.13618
0.10239
0.87039
X/R Ratio
6.10
5.36
2.23
1.74
0.73
2.21
1.74
0.73
2.64
2.27
2.14
1.57
4.23
2.89
2.82
2.41
2.61
''MDC1'' LOAD SUMMARY
277/480V, 3P, 4W
Panel
LBE1
RBE1/RBE2
MPBE
MP2E
LGE1
RGE1
RGE2
L2E1
C2E1
CGE1
R2E1
LGN1
RGN3
LCS
L2N1
R2N1
RGN1
RGN2
C2N1
CGN1
TOTAL CONNECTED VA
DEMAND FACTORS PER NEC
TOTAL DEMAND LOAD (VA)
Sub-Feed Panel
NEC - DERATED DEMAND LOAD IN VA
Lighting
30,000
44,020
20,639
26,221
15,292
1,800
139,719
1.25
174,649
Recepts
40,544
13,680
13,680
7,920
10,260
3,060
11,340
10,860
111,884
NEC 220.44
60,942
Largest Motor
28,586
102,213
1,920
102,213
1.25
127,766
TOTAL DEMAND LOAD
SPARE CAPACITY
TOTAL
Remaining Motors
57,029
152,737
1,920
242,742
1.00
242,742
Equipment
10,000
7,500
27,300
8,400
50,500
7,430
8,712
9,000
11,450
6,556
4,200
8,100
1,100
160,248
1.00
160,248
Panel(s)
65,000
18,880
15,000
98,880
1.00
98,880
35%
Kitchen
1.00
1,042
1,600
Total
865,977
A
A
A
L G N
(N)
L N
(N)
R N
(N)
L G E
(N)
T
R G E
(N)
P
G
S
S
T
R G N
(R)
R G N
(N)
T G
P
R G N
(N)
S
S
P
T G
P
L B E
(N)
P
M P B E
(N)
M P E
(N)
L C S
(R)
JS
ELECTRICAL ONE-LINE DIAGRAMS - MDC1
T
C N
(E)
C G N
(E)
L E
(E) T
C E
(E)
C G E
(E)
T
P
G
R E
(N)
P
J
J
S R G E
(E)
T G
R B E
(E)
R B E
(E)
(E)SWITCHBOARD "MDC1"
1600A, 480Y/277V, 3PH, 4W
50,000AIC
45KVA
K-13
400/3
400A
600/3
600A
400/3
400A
400/3
400A
45KVA
K-13
112.5KVA
(3#1/0, 2#1/0-N & 1#6G)2-1/2"CEXTEND TO
NEW LOCATION
EXTEND TO
NEW LOCATION
(E)(4#500KCMIL)3-1/2"C
(4#500KCMIL & 1#3G)3-1/2"C
PROVIDE NEW (1#3G)
IN EXISTING CONDUIT.
(E)(4#500KCMIL)3-1/2"C
Isc=17,102A
Isc=3,000A (at 5%Z)
Isc=7,000A (at 5%Z)
FOUR WIRE + GROUND
COPPER CONDUCTORS
INSULATION PER SPECIFICATIONS
FEEDER
IDENTIFIER
FEEDER TABLE
THREE WIRE + GROUND
INSULATION PER SPECIFICATIONS
COPPER CONDUCTORS
IDENTIFIER
FEEDER
DEVICE SETTINGS
OVERCURRENT
8[(4#500KCMIL + 1#400KCMILG)3-1/2"C]
7[(4#500KCMIL + 1#350KCMILG)3-1/2"C]
6[(4#500KCMIL + 1#250KCMILG)3-1/2"C]
5[(4#400KCMIL + 1#4/0G)3-1/2"C]
4[(4#350KCMIL + 1#3/0G)3"C]
3[(4#400KCMIL + 1#2/0G)3"C]
2[(4#500KCMIL + 1#1/0G)3-1/2"C]
2[(4#350KCMIL + 1#1G)3"C]
2[(4#250KCMIL + 1#2G)3"C]
(4#500KCMIL + 1#3G)3-1/2"C
(4#350KCMIL + 1#3G)3-1/2"C
(4#350KCMIL + 1#4G)3-1/2"C
(4#250KCMIL + 1#4G)3"C
(4#4/0 + 1#4G)2-1/2"C
(4#3/0 + 1#6G)2-1/2"C
(4#2/0 + 1#6G)2"C
(4#1/0 + 1#6G)2"C
(4#1 + 1#6G)1-1/2"C
(4#2 + 1#8G)1-1/4"C
(4#4 + 1#8G)1"C
(4#6 + 1#10G)1"C
(4#6 + 1#10G)1"C
(4#8 + 1#10G)3/4"C
(4#10 + 1#10G)3/4"C
(4#12 + 1#12G)3/4"C
4WG3000
4WG2500
4WG2000
4WG1600
4WG1200
4WG1000
4WG800
4WG600
4WG500
4WG400
4WG350
4WG300
4WG250
4WG225
4WG200
4WG175
4WG150
4WG125
4WG100
4WG70
4WG60
4WG50
4WG40
4WG30
4WG20
8[(3#500KCMIL + 1#400KCMILG)3"C]
7[(3#500KCMIL + 1#350KCMILG)3"C]
6[(3#500KCMIL + 1#250KCMILG)3"C]
5[(3#400KCMIL + 1#4/0G)3-1/2"C]
4[(3#350KCMIL + 1#3/0G)2-1/2"C]
4[(3#250KCMIL + 1#2/0G)2-1/2"C]
2[(3#500KCMIL + 1#1/0G)3"C]
2[(3#350KCMIL + 1#1G)2-1/2"C]
2[(3#250KCMIL + 1#2G)2-1/2"C]
(3#500KCMIL + 1#3G)3"C
(3#500KCMIL + 1#3G)3"C
(3#350KCMIL + 1#4G)2-1/2"C
(3#250KCMIL + 1#4G)2-1/2"C
(3#4/0 + 1#4G)2"C
(3#3/0 + 1#6G)2"C
(3#2/0 + 1#6G)2"C
(3#1/0 + 1#6G)2"C
(3#1 + 1#6G)1-1/4"C
(3#2 + 1#8G)1-1/4"C
(3#4 + 1#8G)1"C
(3#6 + 1#10G)1"C
(3#6 + 1#10G)1"C
(3#8 + 1#10G)3/4"C
(3#10 + 1#10G)3/4"C
(3#12 + 1#12G)3/4"C
3WG3000
3WG2500
3WG2000
3WG1600
3WG1200
3WG1000
3WG800
3WG600
3WG500
3WG400
3WG350
3WG300
3WG250
3WG225
3WG200
3WG175
3WG150
3WG125
3WG100
3WG70
3WG60
3WG50
3WG40
3WG30
3WG20
2A
75KVA
45KVA
(R)
45KVA(N)
1 1
45KVA(N)5
112.5KVA
400/3
400/3
2A
Isc=33,238A
Isc=11,429A
Isc=10,580A
Isc=3,004A
Isc=11,173A
Isc=10,359A
Isc=10,359A
Isc=2,996A
Isc=2,996A
(E)(4#500KCMIL)3-1/2"C
Isc=12,125A
Isc=15,971A
Isc=4,036A
Isc=30,146A
Isc=23,394A
(E)(4#500KCMIL)3-1/2"C
Isc=19,042A
Isc=18,097A
Isc=4,306A
NEW JUNCTION BOX
EXTEND TO NEW LOCATION
Isc=3,004A
W
G
W G
04WG100
SCALE: NO SCALE
WORK NOTES:
PROVIDE NEW PANEL TO REPLACE EXISTING PANEL. CONNECT ALL EXISTING MAIN PANEL FEEDS AND BRANCH CIRCUITS TO THE SAME CIRCUIT NUMBERS IN THE NEW PANEL. FIELD VERIFY EXISTING CIRCUIT CONFIGURATIONS.
COORDINATE ALL SHUTDOWNS WITH OWNER PRIOR TO START OF WORK.
PROVIDE NEW 600A MECHANICAL PANEL TO FEED NEW MECHANICAL EQUIPMENT IN THE NORTH BASEMENT MECHANICAL ROOM. REPLACE EXISTING (2)2" WITH (2) 3" CONDUITS AND PULL NEW CONDUCTORS TO PANEL.
COORDINATE ALL SHUTDOWNS WITH OWNER PRIOR TO START OF WORK.
PROVIDE NEW 600A MECHANICAL PANEL TO FEED NEW MECHANICAL EQUIPMENT IN THE SECOND FLOOR EAST MECHANICAL ROOM. REPLACE EXISTING (2)2" WITH (2) 3" CONDUITS AND PULL NEW CONDUCTORS TO PANEL.
COORDINATE ALL SHUTDOWNS WITH OWNER PRIOR TO START OF WORK.
RELOCATE EXISTING PANEL AND ALL ASSOCIATED ELECTRICAL EQUIPMENT. EXTEND EXISTING PANEL FEEDS TO NEW LOCATION. ALSO, EXTEND BRANCH CIRCUITS TO THE NEW PANEL LOCATION. FIELD VERIFY EXISTING CIRCUIT
CONFIGURATIONS. COORDINATE ALL SHUTDOWNS WITH OWNER PRIOR TO START OF WORK.
REPLACE EXISTING TRANSFORMER WITH NEW TRANSFORMER OF SIZE INDICATED.
REPLACE EXISTING 30KVA TRAPEZE MOUNTED TRANSFORMER WITH NEW 45KVA TRAPEZE MOUNTED TRANSFORMER. PROVIDE ADDITIONAL STRUCTURAL SUPPORTS IN ORDER TO SUPPORT THE WEIGHT OF THE NEW TRANSFORMER AS REQUIRED. REMOVE THE EXISTING 100A/3P DISCONNECT AND ASSOCIATED CONDUIT AND
WIRING FEEDING EXISTING PANEL "RGN1"("R2N1") AND PROVIDE ALL NEW AS INDICATED.
REPLACE EXISTING 75KVA TRAPEZE MOUNTED TRANSFORMER WITH NEW 75KVA TRAPEZE MOUNTED TRANSFORMER. PROVIDE ADDITIONAL STRUCTURAL SUPPORTS IN ORDER TO SUPPORT THE WEIGHT OF THE NEW TRANSFORMER AS REQUIRED. REMOVE THE EXISTING 400A/3P DISCONNECT AND ASSOCIATED CONDUIT AND WIRING FEEDING EXISTING PANEL(S) "RGE1" AND "RGE2" AND PROVIDE ALL NEW AS INDICATED.
EXISTING DISTRIBUTION GEAR IS TO BE INSPECTED, CLEANED ON THE INTERIOR AND PROVIDED WITH AN INFRARED SCAN TO INSURE PROPER WORKING ORDER. ALL EXISTING CONNECTIONS TO BE TORQUED PER MANUFACTURER'S RECOMMENDATIONS. COORDINATE SHUTDOWN OF GEAR WITH OWNER PRIOR TO PERFORMING
WORK.
OWNERSHIP OF DOCUMENTS:
ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE ENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
PROJECT NO:P
R
O J E
C T
C 2013 STUDIOTROPE, LLC
OWNER
STRUCTURAL ENGINEER
Martin & Martin 12499 W Colfax Ave
Lakewood, CO 80215
(303) 431-6100
MECHANICAL ENGINEER
BCER
5420 Ward Rd
Arvada, CO 80002
(303) 422-7400
ELECTRICAL ENGINEER
BCER
5420 Ward Rd
Arvada, CO 80002
(303) 422-7400
TECHNOLOGY
SSR Inc.
7995 E PRENTICE AVE #104E
GREENWOOD VILLAGE, CO 80111
(303) 779-1222
ACOUSTICS/AUDIO VISUAL
K2 Audio 4900 Pearl E Cir
Boulder, CO 80301
(303) 865-5500
AURARIA HIGHER
EDUCATION CENTER
1156 7th Street, Development
& Planning Annex
Denver, CO 80204 P:(303) 556-3236 auraria.edu
A u ra ri a
L ib ra r y
R e n o v a ti o n
S ta te P h a s e
I I th
S tr e e t D e n v e r, C
O
CIVIL
LANDSCAPE ARCHITECT
Mundus Bishop 2601 Blake Street
Denver, CO 80205
(303) 477-5744
BOWMAN - VISION LAND
603 Park Point Drive
Golden, CO 80401
(303) 674-7355
/9
/2
:2
:5
A
M
E2.01
ELECTRICAL ONE-LINE
DIAGRAM - MDC1
Date Issued Phase
01.19.2015 ADDENDUM NO. 1
02.09.2015 ADDENDUM NO. 2
File details come from the government source that posted it. Updated .