This document is a detailed electrical system legend, abbreviations guide, and installation specifications for the Beaufort County Courthouse Interior Renovation project in Beaufort, South Carolina. The file establishes comprehensive technical standards for electrical work including power distribution, lighting systems, telecommunications infrastructure, fire alarm systems, and emergency communications. The project encompasses renovations to the atrium and main lobby, restrooms, and two Family Court courtrooms, with work required to be completed within 240 calendar days after the Notice to Proceed. A non-mandatory pre-bid conference is scheduled for June 25, 2026 at 2:00 PM virtually, with sealed bids due July 17, 2026 at 3:00 PM EST. The courthouse operates 9:30 a.m. to 5:00 p.m. EST, permitting only quiet activities during operating hours, and all on-site personnel require background checks and identification badges.

The specifications require contractors to coordinate electrical installations with existing conditions and multiple trades, maintain circuit continuity for remaining equipment, and provide as-built drawings and typewritten panelboard directories detailing actual branch circuit arrangements. Key electrical components include Connectrac Flex MX wireway systems for power and data distribution, NEMA 5-20R duplex receptacles with GFCI protection where indicated, LED lighting fixtures with 0-10V dimming capability, telecommunications outlets, fire alarm audio/visual notification devices, and emergency lighting with battery backup. All demolition work must comply with EPA and OSHA standards, particularly regarding asbestos abatement identified on the first and second floors and in both courtrooms. The contract is a fixed-sum award to the lowest responsible bidder, requiring a 5% bid bond at submission and 100% performance and labor/material payment bonds upon award. Contractors must maintain minimum insurance coverage including Workers' Compensation ($500,000 employers liability), Commercial General Liability ($1,000,000 per occurrence/$2,000,000 aggregate), Comprehensive Automobile Liability ($500,000 combined single limit), and Umbrella Liability ($2,000,000), and demonstrate Small and Minority Business Participation Program compliance through required documentation.

View the file

Other files

File Type Posted
Beaufort_County_Courthouse_Renovation_(Addendum_#4_Revision).pdf PDF
Beaufort_County_Courthouse_Renovation_(Addendum_#3_Revision).pdf PDF
Beaufort_County_Courthouse_Renovation_(Addendum_#2_Revision).pdf PDF
A4-4.dwg DWG drawing
M1-1.dwg DWG drawing
P0-1.dwg DWG drawing
A4-1.dwg DWG drawing
A4-2.dwg DWG drawing
A4-3.dwg DWG drawing
A9-1.dwg DWG drawing
E0-1.dwg DWG drawing
E2-1.dwg DWG drawing
M0-1.dwg DWG drawing
M1-2.dwg DWG drawing
M2-1.dwg DWG drawing
M2-2.dwg DWG drawing
A3-1.dwg DWG drawing
E1-1.dwg DWG drawing
G0-1.dwg DWG drawing
P1-1.dwg DWG drawing
P2-1.dwg DWG drawing
A0-1.dwg DWG drawing
A1-2.dwg DWG drawing
A2-2.dwg DWG drawing
A2-1.dwg DWG drawing
Contract_for_Law_Enforcement_Service.pdf PDF
2026.06.09_-_CD_BID_SET_-_DRAWINGS.pdf PDF
2026.06.09_-_CD_BID_SET_-_PROJECT_MANUAL.pdf PDF
BC_Family_Court_2_ACM_Report.pdf PDF
BC_1st_floor_ACM_Report.pdf PDF
BC_Family_Court_1__ACM_Report.pdf PDF
BC_2nd_floor_ACM_Report.pdf PDF
Exhibit_4_-_Monthly_Compliance_Status_Report.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

.81”

IN-WALL

ENTRANCE

FITTING.

POWERTRAC

(TYPICAL)

POWER HUB

(TYPICAL)

POWER END HUB

TRANSITION RAMPS

(TYPICAL)

END RAMPS

(TYPICAL)

RECEPTACLE/DATA DEVICE.

COORDINATE WITH OWNER

AND PROVIDE LOW

VOLTAGE KEYSTONE

ACTIVATIONS PER OWNER

DIRECTION.

(TYPICAL)

HUB CAP

POWER AND DATA CABLES,

CONCEALED IN WALL TO JUNCTION

BOX ABOVE CEILING.

TOP COVER

(TYPICAL)

THIS DETAIL IS INTENDED TO SHOW THE MAJOR PIECES OF THE CONNECTRAC

FLEX MX WIREWAY SYSTEM INSTALLATION.

SEE PLANS FOR EXTENT OF WIREWAY AND QUANTITY OF BOXES.

COORDINATE WITH MANUFACTURER TO PROVIDE ALL REQUIRED HARDWARE,

CONNECTORS, EXTENSIONS, ETC., FOR A COMPLETE SYSTEM INSTALLATION.

4”

RACEWAY CROSS SECTION

DATA/AV

COMPARTMENTS

POWER COMPARTMENT

SLAB

FINISHED FLOOR

WALL/PARTITION CAVITY

2.5" DEEP 2-GANG OUTLET BOX

WITH SINGLE GANG PLASTER RING

WALL/PARTITION FACE

1.25" CONDUIT MINIMUM

SIZE OR AS INDICATED

TERMINATE CONCEALED 6" ABOVE

ACCESSIBLE CEILING IN SAME ROOM.

PROVIDE NYLON BUSHING.

FINISHED CEILING

CEILING TILE

(TYPICAL)

SUSPENDED

CEILING GRID

(TYPICAL)

TBAR SUPPORT

HANGER WIRE

PROVIDE STEEL SUPPORT HANGER WIRE AT (2)

DIAGONAL CORNERS OF FIXTURE AND SECURE

TO STRUCTURE, INDEPENDANT OF CEILNG

GRID. FIXTURE SUPPORT WIRES SHALL BE

IDENTIFIED WITH ORANGE SPRAY PAINT.

VERIFY ACTUAL BUILDING STRUCTURE AND

PROVIDE SUPPLEMENTAL FRAMING FOR

ATTACHMENT OF HANGER WIRES.

SEE FIRE PROOFING NOTE THIS DETAIL.

FIREPROOFING NOTE:

THIS DETAIL APPLIES TO UNPROTECTED STRUCTURE ONLY. IF THE BUILDING STRUCTURE REQUIRES FIREPROOFING, INSTALL BOXES AND CONDUIT WITH A METHOD THAT MAINTAINS THE INTEGRITY OF THE FIREPROOFING METHOD. COORDINATE

METHOD AND SCHEDULING WITH DIVISION 7.

BRANCH CIRCUIT CONDUIT.

SUPPORT IN ACCORDANCE

WITH SPECIFICATIONS.

JUNCTION BOX WITH COVER AND

IDENTIFICATION. MOUNT TO STRUCTURE.

SEE FIREPROOFING NOTE THIS DETAIL.

RECESSED, LAY-IN LUMINAIRE.

SECURE TO GRID WITH CLIPS

UL LISTED FOR SUCH USE.

MAXIMUM 6'-0" LONG MC CABLE OR FLEXIBLE CONDUIT, AS

INDICATED IN SPECIFICATION 260533 - RACEWAYS AND

BOXES FOR ELECTRICAL SYSTEMS. SUPPORT IN

ACCORDANCE WITH SPECIFICATIONS.

CAROLINA

HTUOS

MOSELEY

INC

No. 3983

CERT IFICATE OF AUTHORI

ZA

TI

ON

CAROLINA

HTUOS PR

OFESSIONAL ENGINEERLIC

EN

SE

D

P E T E R K E EW

06/09/2026 No. 34488

PROJECT NO:

DATE:

A

B

C

D

E

1 2 4 53 6 7 8 9 10

F

G

H

I

J

M O

R R

IS

O

N D

R

IV

E, S

U

IT

E

C

H

AR

LE

ST

O N

, S C

PH

O N

E (8

) 5

-5

M O

SE

LE

YD

ES

IG

N

S.

C

O M

MEP Engineering:

Moseley Inc.

6210 Ardrey Kell Road, Suite 425 Charlotte, NC 28277

7/

/2

9:

:5

AM

LEGENDS,

ABBREVIATIONS,

DETAILS AND GENERAL

NOTES

BE

AU

FO

RT

C

OU

NT

Y

PR

OJ

EC

T A

DD

RE

SS

E0.1

644481

JUNE 09, 2026

BE

AU

FO

RT

CO

UN

TY

CO

UR

TH

OU

SE

IN

TE

RIO

R R

EN

OV

AT

ION

ABBREVIATIONS

1P SINGLE PHASE

3P THREE PHASE

3R WEATHERPROOF (NEMA 3R)

A AMPS

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ATS AUTOMATIC TRANSFER SWITCH

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BKR BREAKER

C CONDUIT

CATV COMMUNITY ANTENNA TELEVISION (CABLE)

CB CIRCUIT BREAKER

CBL CABLE

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CLR CLEAR

CO. COMPANY

COMB COMBINATION

COMM COMMUNICATIONS

CU COPPER

DIA DIAMETER

DISC DISCONNECT

DIV DIVISION

DWG DRAWING

EBH ELECTRIC BASEBOARD HEATER

EC EMPTY CONDUIT

ECS EMERGENCY COMMUNICATIONS STATION

ELEC ELECTRICAL

ELEV ELEVATOR

EPO EMERGENCY POWER OFF

EQ EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EX EXISTING

EXT EXTERIOR

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAGP FIRE ALARM GRAPHIC PANEL

FAXP FIRE ALARM EXTENDER PANEL

FFSCP FIRE FIGHTER'S SMOKE CONTROL PANEL

FLA FULL LOAD AMPS

FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS

FPND FUSE PER NAMEPLATE DATA

G GROUND

GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDE ACCESSORY FOR

INDICATED BREAKER)

GFCI GROUND FAULT CIRCUIT INTERRUPT

GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FOR INDICATED

BREAKER)

HKP HOUSEKEEPING PAD

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

Hz HERTZ

IAW IN ACCORDANCE WITH

IG ISOLATED GROUND

J-BOX JUNCTION BOX

KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM

KHz KILOHERTZ

KVA KILOVOLT AMPS

KW KILOWATTS

KWH KILOWATT HOURS

L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FOR INDICATED BREAKER)

LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE

LED LIGHT EMITTING DIODE

LTG LIGHTING

LTS LIGHTS

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH METAL HALIDE

MHz MEGAHERTZ

MIN MINIMUM

ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)

MLO MAIN LUG ONLY

MNS MASS NOTIFICATION SYSTEM

MOCP MAXIMUM OVER CURRENT PROTECTION.

MTD MOUNTED

N NEUTRAL

N/C NORMALLY CLOSED

N/O NORMALLY OPEN

NO. NUMBER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

P PILOT LIGHT (AT THE SWITCH HANDLE)

PBD PANELBOARD

PD PROTECTIVE DEVICE

RCPT RECEPTACLE

REC RECEPTACLE

SEC SECURITY

SPD SURGE PROTECTIVE DEVICE

SPEC. SPECIFICATION(S)

ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)

SW SWITCH

SWBD SWITCHBOARD

TBB TELECOMMUNICATIONS BONDING BACKBONE

TC TELECOMMUNICATIONS CLOSET

TELECOM TELECOMMUNICATIONS

TGB TELECOMMUNICATIONS GROUNDING BUS BAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

TYP TYPICAL

UNO UNLESS NOTED (INDICATED) OTHERWISE

V VOLTS

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

W WATTS

W/ WITH

WG WIRE GUARD

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

RECEPTACLE DEVICE LEGEND

DUPLEX RECEPTACLE, NEMA 5-20R.

DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.

SYMBOL DESCRIPTION

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

FOLLOWING DEVICES ARE DENOTED AS KEYNOTE ONE IN DETAIL:

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R.

DUPLEX RECEPTACLE, NEMA 5-20R.

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

FOLLOWING DEVICES ARE DENOTED AS KEYNOTE TWO IN DETAIL:

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R.

GFCI DUPLEX RECEPTACLE, NEMA 5-20R.

DUPLEX RECEPTACLE, NEMA 5-20R.

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

FOLLOWING DEVICES ARE DENOTED AS KEYNOTE FOUR IN DETAIL:

GFCI DUPLEX RECEPTACLE, NEMA 5-20R.

NOTE: MOUNT THE FOLLOWING DEVICES AS NOTED:

DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.

NON-METALLIC SURFACE RACEWAY, DEVICES AS INDICATED, MOUNTING HEIGHT INDICATED ON

PLANS.

BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN

BELOW SLAB.

BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED.

PANELBOARD OR SWITCHBOARD, PROVIDE 6 INCH CONCRETE HOUSEKEEPING PAD FOR ALL

GROUND MOUNTED EQUIPMENT UNLESS NOTED OTHERWISE. DENOTED BY

PANELBOARD/SWITCHBOARD TAG PER ONE-LINE DIAGRAM.

JUNCTION BOX, WALL MOUNTED. MOUNTING HEIGHT AS INDICATED ON PLANS.

JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.J

POWER DEVICE / EQUIPMENT LEGEND

EQUIPMENT POWER CONNECTION.EC

J

SYMBOL DESCRIPTION

NOTE: MOUNT THE FOLLOWING DEVICES AS NOTED:

POWER / COMMUNICATION DEVICE LEGEND

POWER AND DATA ACTIVATION FOR CONNECTRAC SYSTEM. SEE DETAIL THIS SHEET.

# POWER/COMMUNICATIONS RECESSED FLOOR BOX. WHERE INDICATED, SUBSCRIPT NUMBER

INDICATES OUTLET TYPE.

CA

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

LIGHTING LEGEND

LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS.

SUBSCRIPT/SUPERSCRIPT LETTERS, NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS

FOLLOWS:

3 INDICATES 3-WAY LIGHT SWITCH

4 INDICATES 4-WAY LIGHT SWITCH

D INDICATES DIMMER SWITCH

D3 INDICATES 3-WAY DIMMER LIGHT SWITCH

D4 INDICATES 4-WAY DIMMER LIGHT SWITCH

K INDICATES KEY OPERATED LIGHT SWITCH

K3 INDICATES KEY OPERATED 3-WAY LIGHT SWITCH

K4 INDICATES KEY OPERATED 4-WAY LIGHT SWITCH

LV INDICATES LOW VOLTAGE LIGHT SWITCH

OS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOR

OD INDICATES DIMMER SWITCH WITH INTEGRAL OCCUPANCY SENSOR

P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ON

T INDICATES TIMER LIGHT SWITCH

VS INDICATES SWITCH WITH INTEGRAL VACANCY SENSOR

VD INDICATES DIMMER SWITCH WITH INTEGRAL VACANCY SENSOR

LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION

LIGHT FIXTURE, CEILING MOUNT.

LIGHT FIXTURE WITH EMERGENCY BATTERY BACKUP, CEILING MOUNT.

LIGHT FIXTURE WITH EMERGENCY BATTERY BACKUP, WALL MOUNT, HEIGHT AS INDICATED.

EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.

OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.

DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, WALL MOUNT AT 6" BELOW FINISHED CEILING.

LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

A123

SPACE NUMBER

BUILDING AREA (WHEN USED)

SPACE IDENTIFICATION TAG

GRAPHICS SYMBOLS LEGEND

E4.1

E3.1

E5.1

DETAIL TITLE

1/4"=1'-0"

E5.1E2.2

SECTION TITLE

1/4"=1'-0"

E4.1

SECTION NUMBER

DRAWING WHERE SECTION IS INDICATED

SECTION WHERE CUT

ENLARGED PLAN NUMBER

DRAWING WHERE ENLARGED PLAN IS INDICATED

ENLARGED PLAN WHERE CUT

DETAIL NUMBER

DRAWING WHERE DETAIL IS INDICATED

DETAIL TAG

DETAIL NUMBER

DRAWING WHERE DETAIL IS INDICATED

DRAWING WHERE DETAIL IS CUT

ADDITIONAL DRAWING REFERENCES

E2.3 E2.4

SECTION NUMBER

DRAWING WHERE SECTION IS INDICATED

DRAWING WHERE SECTION IS CUT

ADDITIONAL DRAWING REFERENCES

E2.2 E2.3 E2.4

EXC EXISTING STRUCTURAL GRID LINE WITH DESIGNATION

C STRUCTURAL GRID LINE WITH DESIGNATION

SYMBOL DESCRIPTION

DEMOLITION LEGEND

REMOVE DEVICES, EQUIPMENT, IN ACCORDANCE

WITH THE GENERAL DEMOLITION NOTES.

DEVICES ARE EXISTING TO REMAIN.

WITHIN HATCHED AREAS, DISCONNECT AND REMOVE ALL ELECTRICAL MATERIALS

INCLUDING BUT NOT LIMITED TO LIGHTS, DEVICES, EQUIPMENT, SPEAKERS, FIRE ALARM,

COMMUNICATIONS, AND CIRCUITRY.

SYMBOL DESCRIPTION

X

COMMUNICATIONS LEGEND

TELECOMMUNICATIONS OUTLET, WHERE INDICATED, SUBSCRIPT NUMBER INDICATES OUTLET TYPE.

REFER TO DETAIL ON E4 SERIES DRAWINGS.

TELECOMMUNICATIONS OUTLET, WHERE INDICATED, SUBSCRIPT NUMBER INDICATES OUTLET TYPE.

REFER TO DETAIL ON E4 SERIES DRAWINGS. X

RECESSED FLOOR MOUNT DEVICE COMPLETE WITH FITTINGS FOR FLOOR COVERING. REFER TO

DETAIL THIS SHEET.

MICROPHONE OUTLET, WALL MOUNT AT +1'-6" AAF. SUBSCRIPT NUMBER INDICATES NUMBER OF

JACKS TO PROVIDE IN OUTLET.

SOUND SYSTEM SPEAKER, RECESS CEILING MOUNT.S

M

WIRELESS ACCESS POINT.W

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

FOLLOWING DEVICES ARE DENOTED AS KEYNOTE ONE IN DETAIL:

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

FOLLOWING DEVICES ARE DENOTED AS KEYNOTE TWO IN DETAIL:

NOTE: MOUNT THE FOLLOWING DEVICES AS NOTED:

MICROPHONE, CEILING MOUNT, W/ PENDANT. SUBSCRIPT NUMBER INDICATES NUMBER OF JACKS TO

PROVIDE IN OUTLET.M

GENERAL DEMOLITION NOTES

A.

B.

C.

D.

E.

F.

G.

H.

PROVIDE ALL ELECTRICAL DEMOLITION WORK REQUIRED TO INSTALL THE WORK INDICATED. REMOVE, REROUTE, AND RECONNECT ALL BRANCH CIRCUITS THAT WILL REMAIN IN USE BUT INTERFERES WITH THE WORK.

REMOVE ALL EXISTING CONDUITS THAT WILL NOT BE REUSED AND WHERE THEY WILL BE EXPOSED AFTER COMPLETION. ABANDON ALL OTHERS IN THE WALLS ONLY. DISCONNECT ALL WIRING INDICATED AND/OR REQUIRED TO BE REMOVED FROM ALL POWER SOURCES. REMOVE ALL WIRING FROM ABANDONED CONDUITS

AND PROVIDE BLANK COVER PLATES FOR BOXES NOT UTILIZED FOR THE WORK.

MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN OR PORTIONS THEREOF AFFECTED BY THE WORK.

BEFORE DEMOLITION, VERIFY WITH THE OWNER ALL EQUIPMENT TO BE SALVAGED TO OWNER AND NOT REMOVED FROM THE SITE. FOR ALL REMAINING EQUIPMENT INDICATED FOR REMOVAL (AND NOT RELOCATED), REMOVE AND DISPOSE IN A LEGAL MANNER.

EXERCISE CARE IN REMOVING DEMOLITION ITEMS. REPAIR OR REPLACE ALL DAMAGE CAUSED TO EXISTING

CONSTRUCTION AND EQUIPMENT TO REMAIN.

DRAWINGS ARE BASED UPON EXISTING PLANS AND FIELD INVESTIGATION WITHOUT DEMOLITION. VISIT THE EXISTING BUILDING AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND EXAMINE ALL DRAWINGS TO

AVOID CONFLICTS.

WHERE DEMOLITION OF TELECOMMUNICATIONS DEVICES OCCUR, REMOVE CABLING NOT INDICATED TO REMAIN

BACK TO POINT OF ORIGIN.

DEMOLITION FLOOR PLANS ARE PROVIDED FOR REFERENCE ONLY TO AID IN DEFINING THE SCOPE OF

DEMOLITION WORK.

GENERAL NOTES

A.

B.

C.

D.

E.

F.

G.

THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY OF

WORK.

FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED, INCLUDING ON ARCHITECTURAL ELEVATIONS. MEASURE ALL MOUNTING HEIGHTS FROM THE DEVICE CENTER

LINE UNLESS OTHERWISE INDICATED.

EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS OF ALL CONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.

PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. HAND WRITTEN SCHEDULES

ARE NOT ACCEPTABLE.

ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER

TRADES.

WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELD

COORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.

WHEN GROUPING MULTIPLE LINE TO NEUTRAL BRANCH CIRCUITS IN A CONDUIT, PROVIDE DEDICATED COLOR CODED NEUTRAL CONDUCTORS FOR EACH CIRCUIT. DO NOT USE BREAKER TIES AND SHARED NEUTRALS EVEN

THOUGH PERMITTED BY NEC.

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER SERIES NO. VOLTAGE WATTAGE FINISH COLOR MOUNTING TYPE LIGHT SOURCE LUMENS CCT CRI DRIVER REFLECTORS, OPTIONS & ACCESSORIES

LABELS &

LISTINGS COMMENTS

EX ALUMINUM EXIT SIGN EXITRONIX

BEGHELLI

400EX

LC1E

UNIVERSAL 4 RED LETTERS ON

WHITE HOUSING

WALL MOUNTED LED NA NA NA

LR6 6'x2" WIDE RECESSSED LINEAR LED FOCAL POINT

PINNACLE

ALW

FSM2L-FL

EV2D

LPX2

UNIVERSAL 4 W/FT WHITE FLANGE RECESSED, GYP LED 500 LM/FT 4000K 90 0-10V DIMMING FLUSH LENS DECLARE

PB 33" DIA. PENDANT BOWL MANNING

CAMMAN

G LIGHTING

DP-296

P355-36

GL-2042

UNIVERSAL 192 TBD SUSPENDED LED 5565D/7696I 4000K 80 0-10V DIMMING

RL 8" DIA. RECESSED DOWNLIGHT RETROFIT HALO

LITHONIA

HCD

LBR8

UNIVERSAL 13 WHITE Ceiling LED 1000 4000K 90 0-10V DIMMING SELECTABLE LUMENS AND CCT 1

T22 2x2 RECESSED FLAT PANEL WITH REGRESS

MOUNT KIT FOR 2" REGRESS

METALUX

HE WILLIAMS

ILP

22CGTS / RMK2-22

BP22 / BP222SL-W

VPAN22 / SLM

UNIVERSAL 19 WHITE RECESSED LED 2800 4000K 80 0-10V DIMMING SELECTABLE LUMENS AND CCT, REGRESS MOUNT KIT DLC 1

T24 2x4 RECESSED FLAT PANEL WITH REGRESS

MOUNT KIT FOR 2" REGRESS

METALUX

HE WILLIAMS

ILP

24CGTS / RMK2-24

BP24 / BP242SL-W

VPAN24 / SLM

UNIVERSAL 30 WHITE RECESSED LED 4400 4000K 80 0-10V DIMMING SELECTABLE LUMENS AND CCT, REGRESS MOUNT KIT DLC 1

T44 4X4 RECESSED TROFFER WITH CONCAVE

AND CONVEX LENSES

VISIONEERING OCRW-4x4 UNIVERSAL 57 WHITE RECESSED LED 8000 4000K 80 0-10V DIMMING 1

W1 4' WALL MOUNT LINEAR, DIRECT/INDIRECT FOCAL POINT

PINNACLE

ALW

FSM2BW

EX2DI

LPX2

UNIVERSAL 31 SILVER WALL LED 500LM/FTD /

500LM/FTI

4000K 90 0-10V DIMMING .5" TOP AND BOTTOM POP-UP LENSES DECLARE

NO SCALE

TELECOMMUNICATIONS OUTLET CONDUIT DETAIL

NO SCALE

TROFFER MOUNTING DETAIL

SYMBOL DESCRIPTION

FIRE ALARM LEGEND

FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE. NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM VISUAL NOTIFICATION DEVICE. NUMBER INDICATES STROBE CANDELA RATING.

FIRE ALARM MANUAL PULL STATION.

FIRE ALARM KEY OPERATED MANUAL PULL STATION.

F

FK

FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT. M

xx

NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.

xx

BLUE LIGHT SECURITY VISUAL NOTIFICATION DEVICE.

NO SCALE

CONNECTRAC FLEX MX SYSTEM DETAIL

1.

COMMENTS:

PROVIDE WITH INTEGRAL EMERGENCY BATTERY BACKUP WHERE INDICATED ON PLANS. SEE LIGHTING PLAN AND LIGHTING LEGEND.

REVISIONS

DATE DESCRIPTION

07-13-2026 AD-02

AD-02