This document is a detailed electrical system legend, abbreviations guide, and installation specifications for the Beaufort County Courthouse Interior Renovation project in Beaufort, South Carolina. The file establishes comprehensive technical standards for electrical work including power distribution, lighting systems, telecommunications infrastructure, fire alarm systems, and emergency communications. The project encompasses renovations to the atrium and main lobby, restrooms, and two Family Court courtrooms, with work required to be completed within 240 calendar days after the Notice to Proceed. A non-mandatory pre-bid conference is scheduled for June 25, 2026 at 2:00 PM virtually, with sealed bids due July 17, 2026 at 3:00 PM EST. The courthouse operates 9:30 a.m. to 5:00 p.m. EST, permitting only quiet activities during operating hours, and all on-site personnel require background checks and identification badges.
The specifications require contractors to coordinate electrical installations with existing conditions and multiple trades, maintain circuit continuity for remaining equipment, and provide as-built drawings and typewritten panelboard directories detailing actual branch circuit arrangements. Key electrical components include Connectrac Flex MX wireway systems for power and data distribution, NEMA 5-20R duplex receptacles with GFCI protection where indicated, LED lighting fixtures with 0-10V dimming capability, telecommunications outlets, fire alarm audio/visual notification devices, and emergency lighting with battery backup. All demolition work must comply with EPA and OSHA standards, particularly regarding asbestos abatement identified on the first and second floors and in both courtrooms. The contract is a fixed-sum award to the lowest responsible bidder, requiring a 5% bid bond at submission and 100% performance and labor/material payment bonds upon award. Contractors must maintain minimum insurance coverage including Workers' Compensation ($500,000 employers liability), Commercial General Liability ($1,000,000 per occurrence/$2,000,000 aggregate), Comprehensive Automobile Liability ($500,000 combined single limit), and Umbrella Liability ($2,000,000), and demonstrate Small and Minority Business Participation Program compliance through required documentation.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
.81”
IN-WALL
ENTRANCE
FITTING.
POWERTRAC
(TYPICAL)
POWER HUB
(TYPICAL)
POWER END HUB
TRANSITION RAMPS
(TYPICAL)
END RAMPS
(TYPICAL)
RECEPTACLE/DATA DEVICE.
COORDINATE WITH OWNER
AND PROVIDE LOW
VOLTAGE KEYSTONE
ACTIVATIONS PER OWNER
DIRECTION.
(TYPICAL)
HUB CAP
POWER AND DATA CABLES,
CONCEALED IN WALL TO JUNCTION
BOX ABOVE CEILING.
TOP COVER
(TYPICAL)
THIS DETAIL IS INTENDED TO SHOW THE MAJOR PIECES OF THE CONNECTRAC
FLEX MX WIREWAY SYSTEM INSTALLATION.
SEE PLANS FOR EXTENT OF WIREWAY AND QUANTITY OF BOXES.
COORDINATE WITH MANUFACTURER TO PROVIDE ALL REQUIRED HARDWARE,
CONNECTORS, EXTENSIONS, ETC., FOR A COMPLETE SYSTEM INSTALLATION.
4”
RACEWAY CROSS SECTION
DATA/AV
COMPARTMENTS
POWER COMPARTMENT
SLAB
FINISHED FLOOR
WALL/PARTITION CAVITY
2.5" DEEP 2-GANG OUTLET BOX
WITH SINGLE GANG PLASTER RING
WALL/PARTITION FACE
1.25" CONDUIT MINIMUM
SIZE OR AS INDICATED
TERMINATE CONCEALED 6" ABOVE
ACCESSIBLE CEILING IN SAME ROOM.
PROVIDE NYLON BUSHING.
FINISHED CEILING
CEILING TILE
(TYPICAL)
SUSPENDED
CEILING GRID
(TYPICAL)
TBAR SUPPORT
HANGER WIRE
PROVIDE STEEL SUPPORT HANGER WIRE AT (2)
DIAGONAL CORNERS OF FIXTURE AND SECURE
TO STRUCTURE, INDEPENDANT OF CEILNG
GRID. FIXTURE SUPPORT WIRES SHALL BE
IDENTIFIED WITH ORANGE SPRAY PAINT.
VERIFY ACTUAL BUILDING STRUCTURE AND
PROVIDE SUPPLEMENTAL FRAMING FOR
ATTACHMENT OF HANGER WIRES.
SEE FIRE PROOFING NOTE THIS DETAIL.
FIREPROOFING NOTE:
THIS DETAIL APPLIES TO UNPROTECTED STRUCTURE ONLY. IF THE BUILDING STRUCTURE REQUIRES FIREPROOFING, INSTALL BOXES AND CONDUIT WITH A METHOD THAT MAINTAINS THE INTEGRITY OF THE FIREPROOFING METHOD. COORDINATE
METHOD AND SCHEDULING WITH DIVISION 7.
BRANCH CIRCUIT CONDUIT.
SUPPORT IN ACCORDANCE
WITH SPECIFICATIONS.
JUNCTION BOX WITH COVER AND
IDENTIFICATION. MOUNT TO STRUCTURE.
SEE FIREPROOFING NOTE THIS DETAIL.
RECESSED, LAY-IN LUMINAIRE.
SECURE TO GRID WITH CLIPS
UL LISTED FOR SUCH USE.
MAXIMUM 6'-0" LONG MC CABLE OR FLEXIBLE CONDUIT, AS
INDICATED IN SPECIFICATION 260533 - RACEWAYS AND
BOXES FOR ELECTRICAL SYSTEMS. SUPPORT IN
ACCORDANCE WITH SPECIFICATIONS.
CAROLINA
HTUOS
MOSELEY
INC
No. 3983
CERT IFICATE OF AUTHORI
ZA
TI
ON
CAROLINA
HTUOS PR
OFESSIONAL ENGINEERLIC
EN
SE
D
P E T E R K E EW
06/09/2026 No. 34488
PROJECT NO:
DATE:
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
M O
R R
IS
O
N D
R
IV
E, S
U
IT
E
C
H
AR
LE
ST
O N
, S C
PH
O N
E (8
) 5
-5
M O
SE
LE
YD
ES
IG
N
S.
C
O M
MEP Engineering:
Moseley Inc.
6210 Ardrey Kell Road, Suite 425 Charlotte, NC 28277
7/
/2
9:
:5
AM
LEGENDS,
ABBREVIATIONS,
DETAILS AND GENERAL
NOTES
BE
AU
FO
RT
C
OU
NT
Y
PR
OJ
EC
T A
DD
RE
SS
E0.1
644481
JUNE 09, 2026
BE
AU
FO
RT
CO
UN
TY
CO
UR
TH
OU
SE
IN
TE
RIO
R R
EN
OV
AT
ION
ABBREVIATIONS
1P SINGLE PHASE
3P THREE PHASE
3R WEATHERPROOF (NEMA 3R)
A AMPS
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BKR BREAKER
C CONDUIT
CATV COMMUNITY ANTENNA TELEVISION (CABLE)
CB CIRCUIT BREAKER
CBL CABLE
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CLR CLEAR
CO. COMPANY
COMB COMBINATION
COMM COMMUNICATIONS
CU COPPER
DIA DIAMETER
DISC DISCONNECT
DIV DIVISION
DWG DRAWING
EBH ELECTRIC BASEBOARD HEATER
EC EMPTY CONDUIT
ECS EMERGENCY COMMUNICATIONS STATION
ELEC ELECTRICAL
ELEV ELEVATOR
EPO EMERGENCY POWER OFF
EQ EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EX EXISTING
EXT EXTERIOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAGP FIRE ALARM GRAPHIC PANEL
FAXP FIRE ALARM EXTENDER PANEL
FFSCP FIRE FIGHTER'S SMOKE CONTROL PANEL
FLA FULL LOAD AMPS
FPMR FUSE PER MANUFACTURERS REQUIREMENTS/RECOMMENDATIONS
FPND FUSE PER NAMEPLATE DATA
G GROUND
GE GROUND FAULT PROTECTION FOR EQUIPMENT, 6-50mA PER NEC 427.22 (PROVIDE ACCESSORY FOR
INDICATED BREAKER)
GFCI GROUND FAULT CIRCUIT INTERRUPT
GFP GROUND FAULT PROTECTION FOR PERSONNEL, 4-6mA (PROVIDE ACCESSORY FOR INDICATED
BREAKER)
HKP HOUSEKEEPING PAD
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
Hz HERTZ
IAW IN ACCORDANCE WITH
IG ISOLATED GROUND
J-BOX JUNCTION BOX
KHFSS KITCHEN HOOD FIRE SUPPRESSION SYSTEM
KHz KILOHERTZ
KVA KILOVOLT AMPS
KW KILOWATTS
KWH KILOWATT HOURS
L LOCKOUT TO PREVENT UNAUTHORIZED SWITCHING (PROVIDE ACCESSORY FOR INDICATED BREAKER)
LC ROUTE CIRCUIT TO LOAD VIA LIGHTING CONTACTOR, REFER TO LC SCHEDULE
LED LIGHT EMITTING DIODE
LTG LIGHTING
LTS LIGHTS
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MH METAL HALIDE
MHz MEGAHERTZ
MIN MINIMUM
ML MAINTENANCE LOCK (PROVIDE ACCESSORY FOR INDICATED BREAKER)
MLO MAIN LUG ONLY
MNS MASS NOTIFICATION SYSTEM
MOCP MAXIMUM OVER CURRENT PROTECTION.
MTD MOUNTED
N NEUTRAL
N/C NORMALLY CLOSED
N/O NORMALLY OPEN
NO. NUMBER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
P PILOT LIGHT (AT THE SWITCH HANDLE)
PBD PANELBOARD
PD PROTECTIVE DEVICE
RCPT RECEPTACLE
REC RECEPTACLE
SEC SECURITY
SPD SURGE PROTECTIVE DEVICE
SPEC. SPECIFICATION(S)
ST SHUNT TRIP, 120V COIL (PROVIDE ACCESSORY FOR INDICATED BREAKER)
SW SWITCH
SWBD SWITCHBOARD
TBB TELECOMMUNICATIONS BONDING BACKBONE
TC TELECOMMUNICATIONS CLOSET
TELECOM TELECOMMUNICATIONS
TGB TELECOMMUNICATIONS GROUNDING BUS BAR
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR
TYP TYPICAL
UNO UNLESS NOTED (INDICATED) OTHERWISE
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
W WATTS
W/ WITH
WG WIRE GUARD
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
RECEPTACLE DEVICE LEGEND
DUPLEX RECEPTACLE, NEMA 5-20R.
DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.
SYMBOL DESCRIPTION
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
FOLLOWING DEVICES ARE DENOTED AS KEYNOTE ONE IN DETAIL:
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R.
DUPLEX RECEPTACLE, NEMA 5-20R.
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
FOLLOWING DEVICES ARE DENOTED AS KEYNOTE TWO IN DETAIL:
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R.
GFCI DUPLEX RECEPTACLE, NEMA 5-20R.
DUPLEX RECEPTACLE, NEMA 5-20R.
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
FOLLOWING DEVICES ARE DENOTED AS KEYNOTE FOUR IN DETAIL:
GFCI DUPLEX RECEPTACLE, NEMA 5-20R.
NOTE: MOUNT THE FOLLOWING DEVICES AS NOTED:
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, RECESS FLOOR MOUNT.
NON-METALLIC SURFACE RACEWAY, DEVICES AS INDICATED, MOUNTING HEIGHT INDICATED ON
PLANS.
BRANCH CIRCUIT RUN CONCEALED, UNO. DASHED INDICATES CIRCUITRY REQUIRED TO BE RUN
BELOW SLAB.
BRANCH CIRCUIT HOME RUN TO PANELBOARD AND CIRCUIT INDICATED.
PANELBOARD OR SWITCHBOARD, PROVIDE 6 INCH CONCRETE HOUSEKEEPING PAD FOR ALL
GROUND MOUNTED EQUIPMENT UNLESS NOTED OTHERWISE. DENOTED BY
PANELBOARD/SWITCHBOARD TAG PER ONE-LINE DIAGRAM.
JUNCTION BOX, WALL MOUNTED. MOUNTING HEIGHT AS INDICATED ON PLANS.
JUNCTION BOX, CONCEALED ABOVE CEILING, UNO.J
POWER DEVICE / EQUIPMENT LEGEND
EQUIPMENT POWER CONNECTION.EC
J
SYMBOL DESCRIPTION
NOTE: MOUNT THE FOLLOWING DEVICES AS NOTED:
POWER / COMMUNICATION DEVICE LEGEND
POWER AND DATA ACTIVATION FOR CONNECTRAC SYSTEM. SEE DETAIL THIS SHEET.
# POWER/COMMUNICATIONS RECESSED FLOOR BOX. WHERE INDICATED, SUBSCRIPT NUMBER
INDICATES OUTLET TYPE.
CA
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
LIGHTING LEGEND
LIGHT SWITCH, RATED 120/277 VOLTS, 20-AMPS.
SUBSCRIPT/SUPERSCRIPT LETTERS, NUMBERS, AND SYMBOLS INDICATES SWITCH TYPE AS
FOLLOWS:
3 INDICATES 3-WAY LIGHT SWITCH
4 INDICATES 4-WAY LIGHT SWITCH
D INDICATES DIMMER SWITCH
D3 INDICATES 3-WAY DIMMER LIGHT SWITCH
D4 INDICATES 4-WAY DIMMER LIGHT SWITCH
K INDICATES KEY OPERATED LIGHT SWITCH
K3 INDICATES KEY OPERATED 3-WAY LIGHT SWITCH
K4 INDICATES KEY OPERATED 4-WAY LIGHT SWITCH
LV INDICATES LOW VOLTAGE LIGHT SWITCH
OS INDICATES SWITCH WITH INTEGRAL OCCUPANCY SENSOR
OD INDICATES DIMMER SWITCH WITH INTEGRAL OCCUPANCY SENSOR
P INDICATES PILOT LIGHT, ON WHEN SWITCH IS ON
T INDICATES TIMER LIGHT SWITCH
VS INDICATES SWITCH WITH INTEGRAL VACANCY SENSOR
VD INDICATES DIMMER SWITCH WITH INTEGRAL VACANCY SENSOR
LOWER CASE LETTER INDICATES LIGHT FIXTURE CONTROL DESIGNATION
LIGHT FIXTURE, CEILING MOUNT.
LIGHT FIXTURE WITH EMERGENCY BATTERY BACKUP, CEILING MOUNT.
LIGHT FIXTURE WITH EMERGENCY BATTERY BACKUP, WALL MOUNT, HEIGHT AS INDICATED.
EXIT SIGN, CEILING MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.
EXIT SIGN, WALL MOUNT. DIRECTIONAL ARROWS AS INDICATED. SHADING INDICATES FACE(S) OF SIGN.
OMNI-DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, CEILING MOUNT.
DIRECTIONAL LIGHTING CONTROL OCCUPANCY DETECTOR, WALL MOUNT AT 6" BELOW FINISHED CEILING.
LIGHT FIXTURE, WALL MOUNT, HEIGHT AS INDICATED.
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
A123
SPACE NUMBER
BUILDING AREA (WHEN USED)
SPACE IDENTIFICATION TAG
GRAPHICS SYMBOLS LEGEND
E4.1
E3.1
E5.1
DETAIL TITLE
1/4"=1'-0"
E5.1E2.2
SECTION TITLE
1/4"=1'-0"
E4.1
SECTION NUMBER
DRAWING WHERE SECTION IS INDICATED
SECTION WHERE CUT
ENLARGED PLAN NUMBER
DRAWING WHERE ENLARGED PLAN IS INDICATED
ENLARGED PLAN WHERE CUT
DETAIL NUMBER
DRAWING WHERE DETAIL IS INDICATED
DETAIL TAG
DETAIL NUMBER
DRAWING WHERE DETAIL IS INDICATED
DRAWING WHERE DETAIL IS CUT
ADDITIONAL DRAWING REFERENCES
E2.3 E2.4
SECTION NUMBER
DRAWING WHERE SECTION IS INDICATED
DRAWING WHERE SECTION IS CUT
ADDITIONAL DRAWING REFERENCES
E2.2 E2.3 E2.4
EXC EXISTING STRUCTURAL GRID LINE WITH DESIGNATION
C STRUCTURAL GRID LINE WITH DESIGNATION
SYMBOL DESCRIPTION
DEMOLITION LEGEND
REMOVE DEVICES, EQUIPMENT, IN ACCORDANCE
WITH THE GENERAL DEMOLITION NOTES.
DEVICES ARE EXISTING TO REMAIN.
WITHIN HATCHED AREAS, DISCONNECT AND REMOVE ALL ELECTRICAL MATERIALS
INCLUDING BUT NOT LIMITED TO LIGHTS, DEVICES, EQUIPMENT, SPEAKERS, FIRE ALARM,
COMMUNICATIONS, AND CIRCUITRY.
SYMBOL DESCRIPTION
X
COMMUNICATIONS LEGEND
TELECOMMUNICATIONS OUTLET, WHERE INDICATED, SUBSCRIPT NUMBER INDICATES OUTLET TYPE.
REFER TO DETAIL ON E4 SERIES DRAWINGS.
TELECOMMUNICATIONS OUTLET, WHERE INDICATED, SUBSCRIPT NUMBER INDICATES OUTLET TYPE.
REFER TO DETAIL ON E4 SERIES DRAWINGS. X
RECESSED FLOOR MOUNT DEVICE COMPLETE WITH FITTINGS FOR FLOOR COVERING. REFER TO
DETAIL THIS SHEET.
MICROPHONE OUTLET, WALL MOUNT AT +1'-6" AAF. SUBSCRIPT NUMBER INDICATES NUMBER OF
JACKS TO PROVIDE IN OUTLET.
SOUND SYSTEM SPEAKER, RECESS CEILING MOUNT.S
M
WIRELESS ACCESS POINT.W
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
FOLLOWING DEVICES ARE DENOTED AS KEYNOTE ONE IN DETAIL:
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
FOLLOWING DEVICES ARE DENOTED AS KEYNOTE TWO IN DETAIL:
NOTE: MOUNT THE FOLLOWING DEVICES AS NOTED:
MICROPHONE, CEILING MOUNT, W/ PENDANT. SUBSCRIPT NUMBER INDICATES NUMBER OF JACKS TO
PROVIDE IN OUTLET.M
GENERAL DEMOLITION NOTES
A.
B.
C.
D.
E.
F.
G.
H.
PROVIDE ALL ELECTRICAL DEMOLITION WORK REQUIRED TO INSTALL THE WORK INDICATED. REMOVE, REROUTE, AND RECONNECT ALL BRANCH CIRCUITS THAT WILL REMAIN IN USE BUT INTERFERES WITH THE WORK.
REMOVE ALL EXISTING CONDUITS THAT WILL NOT BE REUSED AND WHERE THEY WILL BE EXPOSED AFTER COMPLETION. ABANDON ALL OTHERS IN THE WALLS ONLY. DISCONNECT ALL WIRING INDICATED AND/OR REQUIRED TO BE REMOVED FROM ALL POWER SOURCES. REMOVE ALL WIRING FROM ABANDONED CONDUITS
AND PROVIDE BLANK COVER PLATES FOR BOXES NOT UTILIZED FOR THE WORK.
MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO REMAIN OR PORTIONS THEREOF AFFECTED BY THE WORK.
BEFORE DEMOLITION, VERIFY WITH THE OWNER ALL EQUIPMENT TO BE SALVAGED TO OWNER AND NOT REMOVED FROM THE SITE. FOR ALL REMAINING EQUIPMENT INDICATED FOR REMOVAL (AND NOT RELOCATED), REMOVE AND DISPOSE IN A LEGAL MANNER.
EXERCISE CARE IN REMOVING DEMOLITION ITEMS. REPAIR OR REPLACE ALL DAMAGE CAUSED TO EXISTING
CONSTRUCTION AND EQUIPMENT TO REMAIN.
DRAWINGS ARE BASED UPON EXISTING PLANS AND FIELD INVESTIGATION WITHOUT DEMOLITION. VISIT THE EXISTING BUILDING AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND EXAMINE ALL DRAWINGS TO
AVOID CONFLICTS.
WHERE DEMOLITION OF TELECOMMUNICATIONS DEVICES OCCUR, REMOVE CABLING NOT INDICATED TO REMAIN
BACK TO POINT OF ORIGIN.
DEMOLITION FLOOR PLANS ARE PROVIDED FOR REFERENCE ONLY TO AID IN DEFINING THE SCOPE OF
DEMOLITION WORK.
GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE BETTER QUALITY. IN THE CASE OF A CONFLICT, DISAGREEMENT, OR AMBIGUITY, PROVIDE THE GREATER QUANTITY OF
WORK.
FOLLOW MOUNTING HEIGHTS INDICATED IN THE ELECTRICAL LEGEND UNLESS OTHERWISE INDICATED, INCLUDING ON ARCHITECTURAL ELEVATIONS. MEASURE ALL MOUNTING HEIGHTS FROM THE DEVICE CENTER
LINE UNLESS OTHERWISE INDICATED.
EQUIPMENT CONNECTIONS ARE INDICATED IN THEIR APPROXIMATE LOCATIONS. VERIFY EXACT LOCATIONS OF ALL CONNECTIONS WITH OTHER TRADES SUPPLYING EQUIPMENT TO AVOID CONFLICTS AT INSTALLATION.
PROVIDE AS-BUILT DRAWINGS INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES INDICATING ACTUAL BRANCH CIRCUIT ARRANGEMENT. HAND WRITTEN SCHEDULES
ARE NOT ACCEPTABLE.
ALL CONDUIT RUNS INDICATED ARE DIAGRAMMATIC, COORDINATE ROUTING IN ALL SPACES WITH OTHER
TRADES.
WHERE POWER AND COMMUNICATION OUTLETS ARE INDICATED IN CLOSE PROXIMITY ON THE DRAWINGS, FIELD
COORDINATE THE LOCATIONS TO PLACE THE OUTLETS ADJACENT TO EACH OTHER.
WHEN GROUPING MULTIPLE LINE TO NEUTRAL BRANCH CIRCUITS IN A CONDUIT, PROVIDE DEDICATED COLOR CODED NEUTRAL CONDUCTORS FOR EACH CIRCUIT. DO NOT USE BREAKER TIES AND SHARED NEUTRALS EVEN
THOUGH PERMITTED BY NEC.
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER SERIES NO. VOLTAGE WATTAGE FINISH COLOR MOUNTING TYPE LIGHT SOURCE LUMENS CCT CRI DRIVER REFLECTORS, OPTIONS & ACCESSORIES
LABELS &
LISTINGS COMMENTS
EX ALUMINUM EXIT SIGN EXITRONIX
BEGHELLI
400EX
LC1E
UNIVERSAL 4 RED LETTERS ON
WHITE HOUSING
WALL MOUNTED LED NA NA NA
LR6 6'x2" WIDE RECESSSED LINEAR LED FOCAL POINT
PINNACLE
ALW
FSM2L-FL
EV2D
LPX2
UNIVERSAL 4 W/FT WHITE FLANGE RECESSED, GYP LED 500 LM/FT 4000K 90 0-10V DIMMING FLUSH LENS DECLARE
PB 33" DIA. PENDANT BOWL MANNING
CAMMAN
G LIGHTING
DP-296
P355-36
GL-2042
UNIVERSAL 192 TBD SUSPENDED LED 5565D/7696I 4000K 80 0-10V DIMMING
RL 8" DIA. RECESSED DOWNLIGHT RETROFIT HALO
LITHONIA
HCD
LBR8
UNIVERSAL 13 WHITE Ceiling LED 1000 4000K 90 0-10V DIMMING SELECTABLE LUMENS AND CCT 1
T22 2x2 RECESSED FLAT PANEL WITH REGRESS
MOUNT KIT FOR 2" REGRESS
METALUX
HE WILLIAMS
ILP
22CGTS / RMK2-22
BP22 / BP222SL-W
VPAN22 / SLM
UNIVERSAL 19 WHITE RECESSED LED 2800 4000K 80 0-10V DIMMING SELECTABLE LUMENS AND CCT, REGRESS MOUNT KIT DLC 1
T24 2x4 RECESSED FLAT PANEL WITH REGRESS
MOUNT KIT FOR 2" REGRESS
METALUX
HE WILLIAMS
ILP
24CGTS / RMK2-24
BP24 / BP242SL-W
VPAN24 / SLM
UNIVERSAL 30 WHITE RECESSED LED 4400 4000K 80 0-10V DIMMING SELECTABLE LUMENS AND CCT, REGRESS MOUNT KIT DLC 1
T44 4X4 RECESSED TROFFER WITH CONCAVE
AND CONVEX LENSES
VISIONEERING OCRW-4x4 UNIVERSAL 57 WHITE RECESSED LED 8000 4000K 80 0-10V DIMMING 1
W1 4' WALL MOUNT LINEAR, DIRECT/INDIRECT FOCAL POINT
PINNACLE
ALW
FSM2BW
EX2DI
LPX2
UNIVERSAL 31 SILVER WALL LED 500LM/FTD /
500LM/FTI
4000K 90 0-10V DIMMING .5" TOP AND BOTTOM POP-UP LENSES DECLARE
NO SCALE
TELECOMMUNICATIONS OUTLET CONDUIT DETAIL
NO SCALE
TROFFER MOUNTING DETAIL
SYMBOL DESCRIPTION
FIRE ALARM LEGEND
FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE. NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM VISUAL NOTIFICATION DEVICE. NUMBER INDICATES STROBE CANDELA RATING.
FIRE ALARM MANUAL PULL STATION.
FIRE ALARM KEY OPERATED MANUAL PULL STATION.
F
FK
FIRE ALARM MAGNETIC DOOR HOLDER, WALL MOUNT. M
xx
NOTE: REFER TO 'TYPICAL DEVICE ELEVATION DETAIL' FOR DEVICE MOUNTING REQUIREMENTS.
xx
BLUE LIGHT SECURITY VISUAL NOTIFICATION DEVICE.
NO SCALE
CONNECTRAC FLEX MX SYSTEM DETAIL
1.
COMMENTS:
PROVIDE WITH INTEGRAL EMERGENCY BATTERY BACKUP WHERE INDICATED ON PLANS. SEE LIGHTING PLAN AND LIGHTING LEGEND.
REVISIONS
DATE DESCRIPTION
07-13-2026 AD-02