FIREX, INC. 1650 West Main Rd. Portsmouth, RI 02871 401.683.5200 fax
401.683.5205 Janicefirex@gmail.com ABS NO. B984499
YEAR
MONTH
APRIL
DAY
NAME
T/S STATE OF MAINE
IMO NO.
CERTIFICATE NO.
F041013ME
TYPE: Halon 1301 PROTECTING: Main Machinery Room CONSISTING OF: 12 ea. cylinders CAPACITY OF EACH: 550 lb AND PILOT CYLINDER 2 EA. CAPACITY 50 lb.
LOCATION CYLINDERS : Cylinder storage room, 2 deck TYPE & LOCATION OF RELEASE: Remote manual; Two stations. Station #1 – Fire Control Room 1 Deck. Station #2 – Inside Engine Operation Station.
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE cylinder release & stop valve X X Two stations
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY 60 second X X 69 sec. final
11 PRESSURE OPERATED SIREN X X
12 ALARM(S) AUDIBLE X X
13 ALARM(S) VISUAL X X
14 PRESSURE SWITCH(S) 2 ea. X X See note
15 VENTILATION SHUTDOWN X X See note
16 MACHINERY SHUTDOWN X X See note
17 OTHER – PNEUMATIC ACTUATORS FOR HALON CYL 12 X X
18 DIRECTIONAL VALVES X
19 STOP VALVES via manual pull stations X X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
ORDER WITH INSPECTION LABELS ATTACHED.
X
NOTE: All pressure switches tested and mechanically proved with test gas. Electrical function to be inspected independent of this test.
Firex Representative Date
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Halon 1301 PROTECTING: Auxiliary Machinery Room CONSISTING OF: 1 ea. cylinders CAPACITY OF EACH: 550 lb AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Cylinder storage room, 2 deck TYPE & LOCATION OF RELEASE: Remote manual; Two stations. Station #1 – Fire Control Room 1 Deck. Station #2 – At entrance to AMR
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE cylinder release & stop valve X X Two stations
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY 30 second X X 31 sec. final
11 PRESSURE OPERATED SIREN X X
12 ALARM(S) AUDIBLE X X
13 ALARM(S) VISUAL X X
14 PRESSURE SWITCH(S) 1 ea. X X See note
15 VENTILATION SHUTDOWN X X See note
16 MACHINERY SHUTDOWN X X See note
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES via manual pull and pneumatic post time delay X X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
ORDER WITH INSPECTION LABELS ATTACHED.
X
NOTE: Pressure switch tested and mechanically proved with test gas. Electrical function to be inspected independent of this test.
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Halon 1301 PROTECTING: Paint Locker CONSISTING OF: 1 ea. cylinders CAPACITY OF EACH: 60 lb AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Main deck passage, port.
TYPE & LOCATION OF RELEASE: Remote manual at entrance to paint locker, main deck, port.
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE cylinder release & stop valve X X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY X
11 PRESSURE OPERATED SIREN X X
12 ALARM(S) AUDIBLE X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) 1 ea. X X
15 VENTILATION SHUTDOWN X X
16 MACHINERY SHUTDOWN X
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES via manual pull X X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
ORDER WITH INSPECTION LABELS ATTACHED.
X
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Halon 1301 PROTECTING: Flamable Locker Deck 2, aft CONSISTING OF: 1 ea. cylinders CAPACITY OF EACH: 55 lb. AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Outside space protected, 2 Deck, aft. TYPE & LOCATION OF RELEASE: Remote manual located next to cylinder.
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE X X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY X
11 PRESSURE OPERATED SIREN X X
12 ALARM(S) AUDIBLE X X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) 1 ea. X X
15 VENTILATION SHUTDOWN X X
16 MACHINERY SHUTDOWN X
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Co2 Fire Suppression PROTECTING: Flammable Stores 2 deck, aft CONSISTING OF: 1 ea. cylinders CAPACITY OF EACH: 100 lb AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Outside space protected, 2 Deck,aft.
TYPE & LOCATION OF RELEASE: Remote manual, outside of entrance to flammable stores room.
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE X X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY 30 second X X 30.1 sec. final
11 PRESSURE OPERATED SIREN X X
12 ALARM(S) AUDIBLE X X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) 1 ea. X X
15 VENTILATION SHUTDOWN X X
16 MACHINERY SHUTDOWN X
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES Pneumatically operated post time delay X X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Halon 1301 PROTECTING: Emergency Generator Room 03 Deck CONSISTING OF: 1 ea.
Cylinders CAPACITY OF EACH: AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Outside space protected, 03 Deck Fan Room TYPE & LOCATION OF RELEASE: Remote manual at entrance to EDG
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE cylinder release & stop valve X X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY 30 second X X 33 sec., final
11 PRESSURE OPERATED SIREN X X
12 ALARM(S) AUDIBLE X X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) 1 ea. X X
15 VENTILATION SHUTDOWN X X note
16 MACHINERY SHUTDOWN X X note
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES via manual pull & Pneumatically operated post time delay X X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
ORDER WITH INSPECTION LABELS ATTACHED.
X
Pressure switch tested and mechanically proved with test gas. Electrical function to be tested independent of this test.
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Co2 Fire Suppression PROTECTING: Main Machinery CONSISTING OF: 2 ea. cylinders CAPACITY OF EACH: 50 lb. AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Semi‐portable, hose reel; 50’ w/ shutoff control.
TYPE & LOCATION OF RELEASE: Local Manual
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED hose pressurized X X
8 REMOTE MANUAL RELEASE X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY X
11 PRESSURE OPERATED SIREN X
12 ALARM(S) AUDIBLE X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) X
15 VENTILATION SHUTDOWN X
16 MACHINERY SHUTDOWN X
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Co2 Fire Suppression PROTECTING: Electric Propulsion Motor Flat 12 MMR CONSISTING OF: 1 ea.
cylinders CAPACITY OF EACH: 50 lb. AND PILOT CYLINDER EA. CAPACITY N/A LOCATION CYLINDERS : Flat 12 MMR, Electric Propulsion TYPE & LOCATION OF RELEASE: Local Manual.
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY X
11 PRESSURE OPERATED SIREN X
12 ALARM(S) AUDIBLE X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) X
15 VENTILATION SHUTDOWN X
16 MACHINERY SHUTDOWN X
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
YEAR
MONTH
APRIL
DAY
NAME
TYPE: H20/N2 Propelled (Hi‐Fog) PROTECTING: Storage Locker, 2 Deck, aft. CONSISTING OF: 2 ea. cylinders
CAPACITY OF EACH: N2 @ 2000 PSI; H20 AND PILOT CYLINDER EA. CAPACITY N/A
LOCATION CYLINDERS : Outside space protected. TYPE & LOCATION OF RELEASE: Local Manual.
REF DESCRIPTION OF INSPECTION INSPECTD TESTED NOT
APPLICABLE
COMMENTS
1 COMPLETE INSPECTION X X
2 CONTENTS CHECKED BY WEIGHING X
3 CONTENTS CHECKED BY LIQUID LEVEL INDICATOR X
4 CYLINDER VALVES VISUALLY INSPECTED X X
5 CYLINDER INTEGRITY X
6 LOCAL MANUAL ACTUATORS X X
7 HOSES/PIPE/MANIFOLD INSPECTED X X
8 REMOTE MANUAL RELEASE X
9 AUTOMATIC RELEASE – TYPE: X
10 TIME DELAY X
11 PRESSURE OPERATED SIREN X
12 ALARM(S) AUDIBLE X
13 ALARM(S) VISUAL X
14 PRESSURE SWITCH(S) X
15 VENTILATION SHUTDOWN X
16 MACHINERY SHUTDOWN X
17 OTHER X
18 DIRECTIONAL VALVES X
19 STOP VALVES X
20 SYSTEM RECONNECTED, SEALED AND LEFT IN OPERATIONAL
YEAR
MONTH
APRIL
DAY
NAME
FIXED FIRE SUPPRESSION CYLINDER RECORD
Description/Serial Number Tare Gross Net Hydro/Mfg Weighed
1 MMR Fixed Halon 45112 326 870 550 2009 Weighed
2 MMR Fixed Halon 57224 318 754 431 2009 Weighed
3 MMR Fixed Halon 50179 336 770 434 1988 Weighed
4 MMR Fixed Halon 57225 334 763 429 1988 Weighed
5 MMR Fixed Halon 57257 335 684 349 1988 Weighed
6 MMR Fixed Halon 57169 335 684 349 1988 Weighed
7 MMR Room Fixed Halon 50188 336 684 348 1988 Weighed
8 MMR Room Fixed Halon 57170 334 665 331 1988 Weighed
9 MMR Room Fixed Halon 57241 332 666 334 1988 Weighed
10 MMR Room Fixed Halon 50183 333 843 510 1988 Weighed
11 MMR Room Fixed Halon 57176 335 834 479 1988 Weighed
12 MMR Fixed Halon 57137 334 635 300 1988 Weighed
13 Co2 actuator 64085 119 169 50 2003 Weighed
14 Co2 actuator 64047 121 171 50 2003 Weighed
15 Spare Co2 40141 110 160 50 Hydro 2009 Hydro 2009
16 AMR Halon 57124 332 784 452 1988 Weighed
17 Paint locker Halon 33321 56 88 32 1986 Weighed
18 Flam Liq. Halon 8077 78 133 55 1988 Weighed
19 Flam liq. Co2 17726 188 288 100 2003 Weighed
20 E. Room Hose Reel 33484 105 155 50 2002 Weighed
21 E. Room Hose Reel 14509 116 166 50 Hydro 2009 Hydro 2009
22 Electric Propulsion 18042 113 163 50 Hydro 2003 Weighed
23 EDGR F6442 Halon 117 171 54 1988 Weighed
YEAR
MONTH
APRIL
DAY
NAME
Fixed Fire Suppression – Pressure Switch
Switch # Main Machinery Space Switch Location
1 Power ventilation 33, 34, 36, 37, 38, 39, 40, 41 Halon room
2 SSDG 1, 2, 2, and SSDG FM Pump 1, 2, 3, Main Engines, F/O Purifiers.
Halon Room
Switch # Auxiliary Machinery Space Location
1 Vent fans 20, 22, DFM Transfer pumps, HFO Transfer Pump
Halon Room
Switch # Paint Locker, Deck 2 aft Location
1 Ventilation Outside paint locker
Switch # Flammable Liquid locker, Deck 2 aft Location
1 Ventilation Outside Flammable Liquid locker
Switch # Paint Locker, Main Deck port Location
1 Ventilation Main deck passage, port
Switch # Emergency Diesel Generator Room Location
1 Ventilation, Machinery Fan Room 03 Deck
Switch # Aft Paint Locker Location
1 Ventilation Shutdown Outside locker in passage
YEAR
MONTH
APRIL
DAY
NAME
TYPE: Ansul Auto Pulse Fire Detection CONSISTING OF: 256 End of Line Devices, 26 Modules Main Panel located at Bridge. Auxiliary Panel located Quarter Deck.
ZONE DESCRIPTION LOCATION TYPE REMARKS
Module 1 04 level forward house
Passageway 04-59-2 ionization 04-60-2 pull Module 2 03 level forward house
Passageway 03-68-2 pull 03-66-2 ionization
03-69-1 Pull 03-67-1 ionization 03-56-0 ionization 03-60-1 pull 03-60-1 ionization 03-60-2 ionization
Stair Tower #1 03-63-0 ionization Module 3 03 level after house
Stair Tower #3 03-105-0 ionization Passageway 03-103-2 ionization
03-112-2 ionization 03-121-2 ionization 03-129-2 ionization 03-136-2 pull
Stair Tower #4 03-137-0 ionization Passageway 03-139-2 ionization
03-147-2 pull 03-143-0 ionization 03-147-1 pull 03-141-1 ionization 03-136-1 pull 03-129-1 ionization 03-121-1 ionization 03-111-1 ionization 03-107-1 pull 03-100-1 ionization 03-97-1 pull Module 4 02 level forward house
Passageway 02-56-2 ionization
YEAR
MONTH
APRIL
DAY
NAME
02-59-2 pull 02-66-0 ionization 02-73-2 ionization 02-76-2 pull
Stair Tower #2 02-76-4 ionization Passageway 02-78-0 pull
02-79-0 ionization 02-74-1 ionization
Stair Tower #1 02-61-0 ionization Passageway 02-57-1 ionization
02-53-1 pull Module 5 02 level after house
Stair Tower #3 02-109-0 ionization Passageway 02-96-2 pull
02-104-2 ionization 02-108-1 ionization 02-117-1 ionization 02-130-1 ionization 02-132-3 pull 02-133-3 ionization 02-138-0 pull 02-139-0 ionization 02-145-1 ionization
Crew Lounge 02-147-0 ionization 02-155-0 ionization
Passageway 02-158-1 ionization 02-164-1 pull 02-159-0 ionization 02-164-2 pull 02-158-2 ionization 02-145-2 ionization 02-136-2 pull
Stair Tower #4 02-137-2 ionization Passageway 02-133-4 pull
02-132-4 ionization 02-131-2 ionization
02-121-2 ionization 02-113-2 ionization 02-108-2 pull
YEAR
MONTH
APRIL
DAY
NAME
Module 6 01 level forward house Passageway 01-77-2 Fire Pull
01-77-2 ionization Stair Tower #2 01-76-2 ionization Passageway 01-68-2 ionization
01-61-2 pull 01-59-2 ionization
01-53-4 pull 01-53-4 ionization 01-54-0 ionization
Stairway 01-46-1 ionization 01-46-1 pull
Passageway 01-53-1 ionization 01-52-1 pull 01-56-1 pull 01-60-1 ionization
Stair Tower #1 01-61-0 ionization Passageway 01-67-1 ionization
01-75-1 ionization 01-79-1 pull Module 7 01 level after house
Stair Tower #3 01-107-0 ionization Passageway 01-106-2 pull
01-98-2 pull 01-106-2 ionization 01-112-2 ionization 01-117-2 ionization 01-128-1 pull 01-130-2 ionization 01-133-4 ionization 01-133-4 pull 01-137-2 pull
Stair Tower #4 01-137-0 ionization Passageway 01-145-2 ionization
01-159-2 ionization 01-164-2 pull 01-164-1 pull 01-159-1 ionization
Lounge 01-156-0 ionization
YEAR
MONTH
APRIL
DAY
NAME
01-151-0 ionization Passageway 01-144-1 ionization
01-146-0 ionization 01-138-0 ionization 01-137-1 ionization 01-132-3 ionization 01-132-3 ionization 01-131-1 ionization 01-119-1 ionization 01-104-1 ionization 01-98-1 ionization Module 8 Main deck (1 deck)
Passageway 1-44-2 pull 1-49-2 ionization 1-56-2 pull
Stair Tower #1 1-56-0 ionization Passageway 1-59-2 ionization
1-64-0 ionization Galley 1-70-0 ionization
Watch Mess 1-70-2 ionization 1-71-2 ionization 1-76-2 pull 1-78-2 ionization 1-83-2 ionization
Stair Tower #2 1-77-2 ionization Crew Mess 1-82-4 ionization
1-90-4 ionization Passageway 1-90-2 ionization
1-96-4 pull 1-96-2 ionization 1-96-0 ionization
Stores Area 1-86-1 ionization Passageway 1-83-1 ionization
1-84-1 pull 1-97-1 ionization 1-98-1 pull 1-100-1 ionization 1-111-1 ionization 1-122-1 ionization
YEAR
MONTH
APRIL
DAY
NAME
1-130-1 ionization 1-138-1 pull 1-137-1 ionization
Stair Tower #4 1-136-2 ionization Passageway 1-136-2 pull
1-132-2 ionization 1-118-2 ionization 1-109-2 pull 1-105-2 ionization
Fwd Mess 1-54-2 ionization 1-65-2 ionization
Stair Tower #3 1-108-0 ionization Passageway 1-137-2 ionization
1-138-4 pull 1-141-2 ionization 1-151-2 ionization 1-158-2 ionization 1-165-2 pull Module 9 2 deck (berthing) Passageway 2-92-2 ionization 2-85-2 ionization 2-78-2 ionization 2-81-0 ionization 2-88-1 ionization 2-95-3 ionization 2-94-1 pull 2-95-1 ionization 2-99-2 ionization Module 10oom 3 deck (classroom/office) 3-96-1 ionization 3-95-1 pull 3-96-2 ionization 3-89-0 ionization 3-82-0 ionization Module 11 4 deck 4-88-4 ionization 4-88-1 ionization 4-80-2 ionization 4-80-1 ionization
YEAR
MONTH
APRIL
DAY
NAME
4-79-2 pull 4-98-2 ionization 4-98-4 ionization 4-95-1 pull 4-95-3 ionization 4-85-3 ionization 4-89-0 pull 4-87-2 ionization 4-81-2 ionization 4-98-1 ionization 4-95-0 ionization Module 12 Wheelhouse pull station
Bridge 04-60-2 Module 13 Emergency Diesel Generator Room 03-70-0 combo 03-70-0 thermal Module 14 Paint Locker 01-76-2 thermal Module 15
Flammable Liquid locker 2-166-2 thermal Aft Paint Locker 2-169-1 thermal
Module 16 Engine Room Pull Stations
Outside ER hatches 1-125-2 1-125-1 01-129-1 02-129-1 Module 17 Main Engine Room Enclosure Module 18 EOS
Outside EOS hatches 2-137-1 2-134-2 Module 19 32' Flat (2nd deck) 2-134-1 thermal 2-128-1 ionization 2-132-2 thermal Machine Shop (2nd deck) 2-118-1 thermal
2-119-0 ionization Engineer's Store Room 2-116-2 ionization
Elect. Work Shop 2-118-2 thermal
YEAR
MONTH
APRIL
DAY
NAME
2-114-4 ionization Module 20 23' Flat (3rd deck) 3-116-1 thermal 3-124-1 ionization Non-operational 3/12/13 3-133-1 thermal 3-130-1 thermal 3-140-1 thermal 3-136-0 ionization 3-133-1 combo 3-138-0 thermal 3-139-2 thermal 3-134-2 thermal 3-134-4 thermal 3-127-2 ionization 3-131-2 ionization 3-124-2 ionization 3-124-2 thermal 3-116-2 thermal 3-117-0 ionization 3-119-0 combo 3-119-1 thermal 3-128-1 combo Module 21 SSDG #1 3-130-1 thermal 3-128-1 combo Module 22 22 SSDG #2 3-124-2 thermal 3-127-2 combo Module 23 23 SSDG #3 3-134-2 thermal 3-131-2 combo Module 24 12' Flat (4th deck) 4-139-2 combo 4-138-2 thermal Module 24 4-129-2 ionization 4-119-2 thermal 4-116-0 ionization 4-118-1 thermal 4-128-1 ionization
YEAR
MONTH
APRIL
DAY
NAME
4-142-1 thermal 4-140-1 thermal Module 25 Machinery Space (Tank Top) Under deck plates 5-140-1 thermal Under deck plates 5-131-1 thermal Under deck plates 5-123-1 ionization Non-operational 3/12/13 Under deck plates 5-118-1 thermal Under deck plates 5-119-2 thermal Under deck plates 5-124-2 ionization Under deck plates 5-133-2 thermal Under deck plates 5-141-2 thermal Module 26 Aux. Machine Rm.
Under deck plates 5-147-0 combo Under deck plates 4-149-1 thermal Under deck plates 4-150-2 ionization Non-operational 3/12/13 Under deck plates 5-149-2 thermal
The above listed End of Line Devices were individually tested and confirmed properly operational, with the exception of three (3) noted. Testing was completed March 12, 2013.
YEAR
MONTH
APRIL
DAY
NAME
PORTABLE FIRE EXTINGUISHER RECORD
NO. LOCATION/DESCRIPTION TYPE SERIAL STATUS
111 04‐54‐0 wheelhouse 10#DC 385109 6yr 09
131 04‐59‐1 chartroom 15#Co2 88175 Hydro 12
112 04‐59‐2 chartroom 15#Co2 414733 Hydro 12
1 03‐55‐2 passageway fwd 10#DC 841489 6yr 09
45 03‐69‐1 cadet navigation lab 15#Co2 379836 Hydro 12
119 03‐72‐2 @ emergency gen room 20#DC 4827 Mfg 12
2 03‐71‐1 passageway forward 10#DC 841430 6yr 09
4 03‐112‐1 passageway aft 10#DC 841488 6yr 09
5 03‐142‐1 passageway aft 10#DC 841506 6yr 09
3 03‐112‐2 passageway aft 10#DC 841423 Hydro 12
82 03‐142‐2 passageway aft 10#DC 841539 6yr 09
6 02‐69‐2 passageway fwd 10#DC 841531 6yr 09
7 02‐69‐1 passageway fwd 10#DC 841411 6yr 09
9 02‐112‐1 passageway aft 10#DC 841502 6yr 09
10 02‐146‐2 passageway aft 10#DC 841537 Hydro 12/rch 13
11 02‐146‐1 passageway aft 10#DC 273885 6yr 13
8 02‐113‐2 passageway aft 10#DC 849499 6yr 09
12 01‐60‐1 passageway fwd 10#DC 385172 6yr 09
13 01‐55‐2 passageway fwd 10#DC 841432 6yr 08
14 01‐81‐2 paint locker 20#DC D249200 Mfg 09
15 01‐109‐2 passageway aft 10#DC 841435 6yr 09
16 01‐109‐1 passageway aft 10#DC 841511 6yr 09
18 01‐143‐1 passageway aft 10#DC 385155 6yr 09
17 01‐143‐2 passageway aft 10#DC 841407 6yr 09
19 1‐15‐2 passageway 10#DC 841521 6yr 09
20 1‐23‐1 passageway 10#DC 385104 6yr 09
21 1‐26‐1 misc. steward stowage 10#DC 841516 6yr 09
22 1‐28‐2 passageway 10#DC 841524 6yr 09
23 1‐37‐1 misc. safety storeroom 10#DC 841538 6yr 09
24 1‐36‐2 passageway 10#DC 841507 Hydro 12
25 1‐52‐2 passageway 10#DC 385164 6yr 09
40 1‐65‐2 forward mess 10#DC 841415 6yr 09
41 1‐48‐0 4/C lounge 10#DC 841417 6yr 09
27 1‐63‐1 dry provision storeroom 15#Co2 86464 Hydro 12
26 1‐69‐1 galley 15#Co2 01484 Hydro 12
29 1‐76‐2 servicing annex 15#Co2 02566 Hydro 12
YEAR
MONTH
APRIL
DAY
NAME
28 1‐76‐1scullery 15#Co2 01486 Hydro 12
30 1‐86‐1 commercial laundry 10#DC 841491 6yr 09
36 1‐129‐1 passageway 10#DC 841418 6yr 09
34 1‐127‐1 stewards store room 10#DC 385159 6yr 09
35 1‐128‐2 passageway 10#DC 385099 6yr 09
135 1‐105‐1 passageway 10#DC 841412 6yr 09
32 1‐90‐1 passageway 10#DC 385106 6yr 09
38 1‐165‐0 Stock room 10#DC 385145 6yr 10
31 1‐96‐2 passageway 10#DC 299543 6yr 12
33 1‐98‐2 Server room 10#DC 841397 6yr 09
39 1‐143‐2 passageway 10#DC 385138 6yr 09
83 1‐78‐2 passageway 10#DC 35453 6yr 09
84 1‐161‐2 passageway 10#DC 385147 6yr 08
FW 1‐140‐1 Fire watch 15#Co2 101720 Hydro 09
43 1‐140‐1 store room 10#DC 385165 6yr 09
46 2‐98‐0 passageway 10#DC 385097 6yr 09
42 2‐83‐2 passageway 10#DC 299530 6yr 12
120 2‐81‐0 passageway 10#DC 385167 6yr 09
44 2‐96‐1 passageway 10#DC 385160 6yr 09
47 2‐108‐2 halon room 10#DC 841503 6yr 09
59 2‐123‐2 electrical workshop 15#Co2 88253 Hydro 12
61 2‐124‐1 engine machine shop 20#DC 714095 6yr 09
FW Engine machine shop Fire Watch 15#C02 114434 Hydro 10
FW Engine machine shop Fire Watch 15#Co2 S9C379249F1 Hydro 09
67 Engine machine shop Fire Watch 15#Co2 01810 Hydro 10
FW Engine machine shop Fire Watch 15# Co2 864561 Hydro 13
FW Engine room Fire Watch 15#Co2 142771 Hydro 10
FW Engine room Fire Watch 15#Co2 S9C379125 Hydro 08
87 2‐121‐0 engineer storeroom 20#DC 714266 6yr 09
124 2‐134‐2 engine operating station 15#Co2 87566 Hydro 12
125 2‐134‐2 engine operating station 20#DC 714275 Hydro 12
129 2‐137‐1 32 flat 15#Co2 01168 Hydro 12
130 2‐132‐2 32 flat 15#Co2 01959 Hydro 12
55 2‐162‐2 marine spikes lab 10#DC 841413 6yr 09
54 2‐167‐2 bosun storeroom 3 10#DC 841492 6yr 09
58 2‐169‐1 engine lab 15#Co2 02232 Hydro 12
60 2‐160‐3 paint locker 15#Co2 00268 Hydro 12
56 2‐162‐1 engine lab 10#DC 841505 6yr 09
51 2‐158‐1 engine lab 10#DC 841529 6yr 09
YEAR
MONTH
APRIL
DAY
NAME
52 2‐160‐1 engine lab 10#DC 385137 6yr 09
57 2‐167‐2 flammable liquid stores 15#Co2 02233 Hydro 12
53 2‐165‐2 passageway 10#DC 841509 6yr 09
50 20158‐2 marine spikes lab 10#DC 841532 6yr 09
128 2‐192‐2 steering gear 10#DC 385169 6yr 09
127 2‐190‐2 steering gear 15#Co2 01359 Hydro 12
121 3‐83‐0 passageway 10#DC 841512 6yr 09
68 3‐86‐2 classroom multi media 10#DC 385143 6yr 09
69 3‐96‐2 passageway 10#DC 385100 6yr 09
65 3‐96‐2 classroom 15#Co2 00160 Hydro 07
126 3‐99‐1 passageway 10#DC 385139 6yr 09
70 3‐88‐1 lecture hall 10#DC 841419 6yr 09
62 3‐119‐0 23 flat 15#Co2 86457 Hydro 10
64 3‐124‐1 23 flat 20#DC 714164 6yr 09
66 3‐128‐2 23 flat 20#DC 714251 6yr 09
63 3‐139‐2 23 flat 15#Co2 87543 Hydro 10
115 3‐134‐1 23 flat 20#DC 714265 6yr 09
116 3‐141‐1 23 flat 15#Co2 86477 Hydro 12
72 4‐78‐2 4th deck/hold 10#DC 841527 6yr 09
73 4‐78‐2 gray water transfer 15#Co2 00523 Hydro 12
81 4‐87‐1 10#DC 841494 6yr 09
80 4‐88‐2 10#DC 385163 6yr 09
79 4‐92‐0 4th deck/hold 15#Co2 02546 Hydro 12
97 4‐92‐2 weight room 10#DC 841501 6yr 09
91 4‐95‐1 weight room 10#DC 841517 6yr 09
104 4‐118‐1 machinery room 15#Co2 86682 Hydro 12
103 4‐119‐2 machinery room 15#Co2 02573 Hydro 12
102 4‐135‐2machinery room 15#Co2 87568 Hydro 12
132 4‐139‐1 machinery room 20#DC 714281 6yr 09
136 4‐146‐2 aux machinery room 20#DC 714283 6yr 09
Auxiliary machinery room 15#Co2 01878 Hydro 10
133 4‐153‐1 aux machinery room 20#DC 714097 6yr 09
71 3‐139‐1 machinery (2) 50#Co2 Hose reel Hydro 03
DC1 01‐75‐1 DC1 15#Co2 85807 Hydro 12
DC2 1‐158‐2 DC2 15#Co2 87556 Hydro 12
DC2 1‐158‐2 DC2 10#DC 385144 6yr 08
DC3 1‐138‐3 DC3 10#DC 841422 6yr 09
SPARES
1 Spare 15#Co2 01493 Hydro 12
YEAR
MONTH
APRIL
DAY
NAME
2 Spare 15#Co2 01350 Hydro 09
3 Spare 15#Co2 00314 Hydro 12
4 Spare 15#Co2 01054 Hydro 12
5 Spare 15#Co2 01902 Hydro 12
6 Spare 15#Co2 87530 Hydro 12
7 Spare 15#Co2 00150 Hydro 12
8 Spare 15#Co2 00125 Hydro 12
9 Spare 15#Co2 00561 Hydro 12
10 Spare 15#Co2 87539 Hydro 12
11 Spare 15#Co2 V377642 Hydro 12
12 Spare 15#Co2 V601637 Hydro 10
13 Spare 15#Co2 85829 Hydro 12
14 Spare 15#Co2 86691 Hydro 12
15 Spare 15#Co2 162568 Hydro 09
16 Spare 15#Co2 01042 Hydro 12
17 Spare 20#DC 638165 6yr 09
18 Spare 20#DC 638128 6yr 09
19 Spare 20#DC 638119 6yr 09
20 Spare 20#DC 00714257 6yr 09
21 Spare 20#DC 644731 6yr 09
22 Spare 20#DC 550804 6yr 13
23 Spare 20#DC 714100 6yr 09/rch 10
24 Spare 20#DC 714091 6yr 09
25 Spare 10#DC 385108 6yr 09/rch 10
26 Spare 10#DC 299556 6yr 12
27 Spare 10#DC 697090 6yr 11/rch 12
28 Spare 10#DC 385102 6yr 08
29 Spare 10#DC 385161 6yr 09/rch 11
30 Spare 10#DC 726186 6yr 09
31 Spare 10#DC 299550 6yr 12
32 Spare 10#DC 385175 6yr 09
33 Spare 10#DC 299545 6yr 12
34 Spare 10#DC 299557 6yr 12
35 Spare 10#DC 299547 6yr 12
36 Spare 10#DC 299542 6yr 12
37 Spare 10#DC 299546 6yr 12
38 Spare 10#DC 299548 6yr 12
39 Spare 10#DC 299537 6yr 12
40 Spare 10#DC 841510 6yr 09
YEAR
MONTH
APRIL
DAY
NAME
The above listed fire extinguishers have been inspected and re‐certified according to NFPA standards.
April 10, 2013
41 Spare 10#DC 385173 6yr 09
42 Spare 10#DC 385168 6yr 09
43 Spare 10#DC 385149 6yr 09
44 Spare 10#DC 385105 6yr 09
45 Spare 10#DC 385150 6yr 09
46 Spare 10#DC 385140 6yr 09
47 Spare 10#DC 385152 6yr 09
48 Spare 10#DC 385171 6yr 09
49 Spare 10#DC 385162 6yr 09
50 Spare 10#DC 841533 6yr 09
51 Spare 10#DC 601118 Hydro 13
52 Spare 10#DC 841420 6yr 09
53 Spare 10#DC 841434 6yr 09
54 Spare 10#DC 299549 6yr 12
55 Spare 10#DC 841526 6yr 09
56 Spare 10#DC 299544 6yr 13
57 Spare 10#DC 385157 6yr 11
58 Spare 10#DC 841498 6yr 09
59 Spare 10#DC 841530 6yr 09
60 Spare 2.5#DC 101403 6yr 11
61 Spare 2.5#DC 109959 6yr 11
62 Spare 2.5#DC 114280 6yr 11
63 Spare 2.5#DC 340886 6yr 13
64 Spare 2.5#DC 341219 6yr 13
65 Spare 2.5#DC 325039 Mfg 09
66 Spare 2.5#DC 325050 Mfg 09
67 Spare 2.5#DC 238388 Mfg 09
68 Spare 2.5#DC 325038 Mfg 09
LIFE BOATS
1 Life Boat 2#DC 206530 Mfg 10
2 Life Boat 2#DC 206525 Mfg 10
3 Life Boat 2#DC 206526 Mfg 10
4 Life Boat 2#DC 206524 Mfg 10
5 Life Boat 2#DC 206529 Mfg 10
6 Life Boat 2#DC 206528 Mfg 10
7 Life Boat 2#DC 118321 Mfg 10
8 Life Boat 2#DC 118324 Mfg 10