FAA Response to Honeywell RFI #3.
1. There is no power shown for the VESDA system in room B101C. Please provide the circuit location for powering this panel.
EPP-1, breaker #17. EEP-1 is located in the Control Wing Basement Equipment Room B120
2. Please provide the model number of the desired VESDA system.
Vesda VLP LaserPlus
3. 28 31 00 – Page 6 – 1.6 System Description Item K.
a. Alarm Silencing – When the alarm silence button is activated at the FACP, the audible notification appliance shall stop, while the visible device continue. If a subsequent alarm occurs, the audible device shall re-activate.
b. The Honeywell existing system does not currently have this functionality.
c. We will need to add a power supply and additional wire to all horn/strobes in the basement of Admin Wing and Control Wing.
d. This will require a rewiring of all the horn/strobes in the basement B120 N/S, B134, Host Room, B101C and all the administration basement wing and the device replacement.
e. Please confirm this is desired.
Currently the existing system in the CWB has a combined silence feature for the Horn and Strobe. This feature will remain the same as existing conditions for the new work in B101 and other applicable areas in the CWB.