This document is a set of construction drawings for the Connecticut Valley Hospital (CVH) Old Power Plant Renovations project located at Holmes Drive in Middletown, Connecticut, prepared by the State of Connecticut Department of Administrative Services in coordination with the Department of Mental Health and Addiction Services. The project, identified as BI-MH-134, encompasses the renovation of an existing power plant building and includes comprehensive structural, architectural, and site work. The drawings, prepared by Macchi Engineers, LLC and dated June 2026, detail existing conditions, demolition requirements, foundation work, roof framing, and site logistics. Key work includes removal of an existing 9-inch reinforced concrete roof slab, concrete encasement from steel beams and girders, masonry penthouse and associated equipment, and existing roofing membrane; retention of existing steel beams, girders, and columns; installation of 12-inch precast concrete roof planks with 2-inch concrete topping slabs; application of 75-mil reinforced EPDM roofing; placement of 3-inch concrete topping slabs over existing basement slabs; and installation of sump pump systems with appropriate drainage. The project requires temporary weather protection throughout demolition and construction phases, coordination with the owner to maintain facility operations, field verification of all existing conditions and utilities prior to construction commencement, and submission of a proposed demolition sequence for approval.
The drawings establish design parameters based on the 2022 Connecticut Building Code, American Concrete Institute standards, and AISC guidelines, with concrete specified at 4,500 PSI for structural elements and 4,000 PSI for topping slabs. Wind load analysis reflects a design wind speed of 120 miles per hour for Middletown with ultimate component and cladding pressures coordinated to FM requirements across three pressure zones. Snow load design is based on 30 PSF ground snow load with a minimum roof design live load of 200 PSF. Reinforcing steel conforms to ASTM A-615 Grade 60, and all concrete work must follow ACI 318-14 standards with specified cover requirements. The contractor is responsible for field verification of existing site conditions, protection of existing equipment, temporary support of mechanical systems and utilities during demolition, coordination of site logistics and laydown areas, maintenance of existing floor drains, repair of all site damage upon completion, and adherence to all hazardous material removal protocols as specified in available hazmat reports. The project maintains the operational status of the existing plant throughout construction with all contractor activities requiring coordination with the facility owner.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00 40 15 DAS Prequal Cert Reqts 20251001.docx | DOCX document | |
| 2625BIMH134_Nov_2_26_solicitation_doc.pdf | ||
| 00 43 16 BidBond 20240924.docx | DOCX document | |
| 00 40 14 CertOfAuthority 20231001.docx | DOCX document | |
| 2625BIMH134_Oct_29_26_solicitation_doc.pdf | ||
| 2625BIMH134_Oct_30_26_solicitation_doc.pdf | ||
| 00 41 00 DAS-CS Bid Proposal Form LOCKED 07.01.2026.docx | DOCX document | |
| 00 11 16 DAS-CS Invitation to Bid.pdf | ||
| 00 45 20 Named Sub Signature Page 20251001.docx | DOCX document | |
| 00 45 14 GC Bidder Qual Statement 20251001.docx | DOCX document | |
| 00 40 16 DAS Update Stmt Reqts 20251001.docx | DOCX document | |
| Specifications.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE
LOCATION
DEPARTMENT OF ADMINISTRATIVE SERVICES
MICHELLE HALLORAN GILMAN
COMMISSIONER
DEPARTMENT OF MENTAL HEALTH
AND ADDICTION SERVICES
NANCY NAVARRETTA, MA, LPC, NCC
COMMISSIONER
CD SUBMISSION
LOCATION PLAN
SITE PLAN
CONTRACT DRAWINGS:
D.C.S BUILDING NUMBER 00000
EXISTING CONDITION - SITE PLAN
S101 FOUNDATION PLAN
S102 EXISTING FRAMING AND ROOF DEMOLITION PLAN
S103 ROOF FRAMING PLAN
S104 FRAMING SECTIONS
GOVERNOR NED LAMONT
JUNE 2026
STATE OF CONNECTICUT
CVH - OLD POWER PLANT RENOVATIONS
HOLMES DRIVE
MIDDLETOWN, CONNECTICUT 06457
S105 SITE PHOTOS
S106 GENERAL NOTES
S100
S107 SITE LOGISTICS PLAN
PROJECT
LOCATION
TITLE COVER SHEET
SITE
LOCATION
PROJECT NO. BI-MH-134
Macchi Engineers, LLC 44 Gillett Street Hartford, Connecticut 06105 860 549-6190 www.macchiengineers.com
S108 CODE INFORMATION
mike plickys
CROPPED PE
X X X X X X X X X X
X X X X X X X X X X
X X
X X
X
O O O O O O O O O O O O O O
X
X
N
GRASS AREA EXISTING
STAIRWELL
EAST CORRIDOR
WEST CORRIDOR BELOW (N I C )
EXISTING CHILLER
EXISTING
EXHAUST
FAN
OUTSIDE FACE OF
EXISTING MASONRY
FOUNDATION WALL
E X
IS
T
IN
G
E L E
C R
IC
A
L P
A N
E L
EXISTING FENCING TO BE REMOVED AND REPLACED
EXISTING FENCING TO BE REMOVED AND REPLACED
E X
IS
T
IN
G
F E
N C
IN
G
T O
B
R
E M
O V
E D
A N
D R
E
IN
S T
A L L
E D
EXISTING RAISED WOOD
FRAMED PLATFORM
EXISTING PENTHOUSE
EXISTING PORTION OF CHAIN LINK FENCE TO REMAIN
VAULT ACCESS POINT
APPROXIMATE CONTRACT LIMIT LINE
COORDINATE WITH SITE LOGISTICS PLAN
CONTRACT LIMIT LINE
C O
N T
R A
C
IM
IT
L
IN
E
X
X
EXISTING GATE
TEMPORARY CONSTRUCTION FENCE
TEMPORARY CONSTRUCTION FENCE
TEMPORARY CONSTRUCTION
FENCE. LOCATION TO BE
COORDINATED WITH CVH.
A P
P R
O X
IM
A
N
T R
A C
T
L
IM
IT
L
IN
E
APPROXIMATE CONTRACT LIMIT LINE
A P
P R
O X
IM
A
N
T R
A C
T
L
IM
IT
L
IN
E
EXISTING PRESSURE
RELIEF VENTS
PROVIDE TEMPORARY
PROTECTION BARRIER
E X I S T I N G R O O F
VAULT ACCESS BELOW
V A
U L T
A C
C E
S S
EXISTING GENERATOR
EXISTING HANDRAIL
EXISTING RAISED WOOD
FRAMED PLATFORM
30'-0" VIF
V
IF
CONSTRUCTION
ACCESS
X
E X
IS
T
IN
G
F E
N C
IN
G
T O
B E
R E
M O
V E
D A
N D
R E
P L
A C
E D
N
PROJECT
LOCATION
LOCKABLE GATE
TO MATCH EXISTING
GENERAL NOTES:
1. EXISTING CONDITIONS SHOWN ARE FOR INFORMATION
ONLY. CONTRACTOR TO FIELD VERIFY ALL EXISTING
CONDITIONS AND ELEVATIONS PRIOR TO STARTING
WORK. ALL DISCREPANCIES SHALL BE BROUGHT TO
THE ATTENTION OF THE ENGINEER.
2. FINAL LOCATION OF TEMPORARY CONSTRUCTION FENCING
AND PROJECT LAYDOWN AREAS ARE TO BE COORDINATED
WITH THE OWNER.
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
JNZ
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
EXISTING CONDITIONS - SITE PLAN
S100
1/4" = 1'-0"S100
EXISTING CONDITIONS - SITE
PLAN
CD SUBMISSION
KEY PLAN
N
EAST CORRIDOR (NIC)
WEST CORRIDOR (NIC)
APPROXIMATE LOCATION OF
EXISTING UTILITY TUNNEL
EXISTING CONCRETE
HOUSE KEEPING
PADS TO REMAIN
EXISTING FLOOR DRAIN
TO REMAIN
EXISTING EQUIPMENT
BELOW
EXISTING MEP HOUSE KEEPING
SLABS TO REMAIN
APPROXIMATE LOCATION
OF EXISTING BELOW
GRADE UTILITY TUNNEL
P14
S105
P13
S105
P11
S105
P15
S105
P12
S105
EXISTING CISTERN BELOW
TO BE INFILLED WITH CONCRETE
3" TOPPING SLAB
OVER EXISTING SLAB
SEE DETAIL 4/S1.01.
SUMP PUMP SEE DETAIL 3/S101
RAMP DN.
RAMP DN.
EXISTING INTERIOR BRICK
MASONRY VENEER
VERTICAL DISCHARGE PIPE
PROVIDE SLEEVE THROUGH
NEW CONCRETE CAP
EXISTING SHORING TOWERS
TO BE REMOVED AND STORED
AFTER COMPLETION OF THE
WORK. COORDINATE WITH OWNER.
EXISTING SHORING TOWERS
TO BE REMOVED AND STORED
AFTER COMPLETION OF THE
WORK. COORDINATE WITH OWNER.
OUTSIDE FACE
OF EXISTING VAULT
WALLS
2" PVC PIPING SECURED
TO WALL ABOVE GRADE
DISCHARGE
STONE SPLASH
PAD
SEE 5/S101 (TYP OF 3)
EXISTING MASONRY
VENEER
N
PROJECT
LOCATION
2. EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY.
FIELD VERIFY ALL LOCATIONS AND ELEVATIONS
EXISTING UTILITIES ARE TO BE SHORED AS REQUIRED.
GENERAL NOTES:
1. INDICATES LOCATION OF PHOTO
SEE DRAWING S105.
3. TOPPING SLABS ARE TO BE 3" THICK AND
REINFORCED WITH 6X6 10/10 WWF.
4. ALL DIMENSIONS ARE TO BE FIELD VERIFIED.
3" CONCRETE
TOPPING SLAB
EXISTING CONC SLAB
REMOVABLE 1 1/2"
STEEL GRATING
STEEL BASIN COVER
2" DIA. PVC DISCHARGE PIPE
ASTM-D 2665 SCHEDULE 40
SECURE TO FACE OF EXISTING WALL
18" X 30" PREMOLDED
PERFORATED
FIBERGLASS SUMP
PUMP BASIN
3/4" CRUSHED STONE
M
IN
#4 BARS CONT.
AROUND OPENING
SAWCUT AND REMOVE
EXISTING SLAB AT NEW
SUMP LOCATION
FLUSH
SUMP PUMP 2 HP WITH
20 FT MIN HEAD CAPACITY
AND FLOAT SWITCH.
WIRE TO EXISTING BRANCH
CIRCUIT
1'-4"
DO NOT UNDERMINE
EXISTING SLAB
CHECK VALVE
SURGE PROTECTION TO TIE INTO
EXISTING CAMPUS CIRCUITRY
LOCATED WITHIN VAULT.
COORDINATE WITH OWNER.
CONTRACTOR TO VERIFY EXISTANCE OF EXISTING
BELOW SLAB UTILITIES PRIOR TO EXCAVATION
EXISTING SLAB
ON GRADE
3" TOPPING SLABEXISITING SLAB
TO BE THROUGHLY
CLEANED AN
ROUGHENED
BONDING AGENT
6X6 10/10 WWF
EXISTING SLAB
ON GRADE
NEW TOPPING SLAB
4"
3/4 CHAMFER ALL SIDES
EXISTING COLUMN
(2) #4 HOOPS
TYP.
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
JNZ
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
FOUNDATION PLAN
S101
1/4" = 1'-0"S101
1 FOUNDATION PLAN
1" = 1'-0"S101
3 SUMP BASIN DETAIL
CD SUBMISSION
1" = 1'-0"S101
4 BASEMENT SLAB DETAIL
1" = 1'-0"S101
5 COLUMN BASE DETAIL
FEATHER TOPPING
SLAB INTO RAMP
EXISTING MASONRY
VENEER
KEY PLAN
EAST CORRIDOR (NIC)
WEST CORRIDOR (NIC)
EXISTING RAISED WOODEN
ROOF PLATFORM WITH
PLYWOOD SHEATHING AND
CONCRETE SLAB BELOW
TO BE REMOVED (TYP.)
EXISTING CONCRETE
WALL TO REMAIN
EXISTING CONCRETE ROOF
SLAB TO BE REMOVED
EXISTING MASONRY
PENTHOUSE, FAN, AND ASSOCIATED
WIRING TO BE REMOVED IN
THEIR ENTIRETY.
EXISTING METAL ROOF
DECK TO BE REMOVED NOTE: REMOVE CONCRETE
ENCASEMENT FROM EXISTING
STEEL BEAMS AND GIRDERS.
RE: SECTION 2/S102.
NOTE: CONTRACTOR TO
CARRY 225 SF OF LEAD PAINT
REMOVAL AND DISPOSAL IN
BID.
EXISTING 9" CONCRETE
ROOF SLAB TO BE REMOVED.
LIMIT OF
EXISTING CONCRETE ROOF
SLAB TO BE REMOVED
EXISTING EXHAUST
FAN TO BE REMOVED
AND REINSTALLED
AFTER ROOF
REPLACEMENT.
EXISTING STEAM PRESSURE RELIEF
VENTS TO BE TEMPORARILY
SUPPORTED, EXTENDED DURING
DEMOLITION WORK. NOTE:
VENTS WILL REMAIN OPERATIONAL
DURING ENTIRE PROJECT. COORDINATE
WORK WITH AGENCY.
EXISTING STEEL
BEAMS (B) AND GIRDERS
(G) TO REMAIN.
EXISTING ROOFING MEMBRANE
AND SUBSTRATE TO BE REMOVED.
VERIFY EXTENTS IN FIELD.
P1
S105
28' -7" VIF
V
IF
EXISTING MECH.
UNIT TO REMAIN
E X
IS
T
IN
G
E L
E C
R
IC
A
P
N E
L T
O R
E M
A
IN
P2
S105
P4
S105
P5
S105
P6
S105
P7
S105
P3
S105
P8
S105
P9
S105
P16
S105
P17
S105
P18
S105
B B
G G
G G
PROTECT EXISTING
SITE EQUIPMENT TYP.
N
PROJECT
LOCATION
E X
IS
T
IN
G
C O
N C
R E
T E
R O
O F
S L
A B
T O
B E
R E
M O
V E
D
B B
B B
B B
B B
B B
B B
B B
B B
B B
B B
WARNING:
EXISTING COLUMNS'
TO REMAIN
1. INDICATES LOCATION OF PHOTO
SEE DRAWING S105.
2. LOCATION AND ELEVATION OF ALL EXISTING
UTILITIES ARE TO BE FIELD VERIFIED.
GENERAL NOTES:
3. SHORE EXISTING UTILITIES AND SYSTEMS TO REMAIN
AS REQUIRED TO COMPLETE DEMOLITION WORK.
4. CONTRACTOR TO PROVIDE TEMPORARY WEATHER
PROTECTION AT ALL TIMES DURING DEMOLITION.
5 THE EXISTING PLANT WILL REMAIN OPERATIONAL
DURING THE ENTIRE PROJECT. THIS INCLUDES
PROVIDING ACCESS TO THE OWNER AT ALL TIMES
FOR SERVICING. THE CONTRACTOR SHALL
COORDINATE ALL ACTIVITIES WITH THE OWNER
AND PROVIDE ALL NECESSARY PROTECTIONS
DURING THE ENTIRE DURATION OF THE
WORK.
6. THE CONTRACTOR SHALL SUBMIT PROPOSED
SEQUENCE OF DEMOLITION FOR REVIEW AND
APPROVAL PRIOR TO BEGINNING DEMOLITION
WORK.
7. COORDINATE CONCRETE REMOVAL WITH
AVAILABLE HAZMAT REPORTS. ALL WORK IS TO BE
CONDUCTED IN STRICT CONFORMANCE WITH
CURRENT STATE AND FEDERAL GUIDELINES.
PROVIDE TEMPORARY PROTECTION
BELOW EXISTING ROOF SLAB. PROTECTION
TO BE INSTALL PRIOR TO BEGINNING DEMOLITION
WORK.
EXISTING 9" REINFORCED
CONCRETE ROOF SLAB
TO BE REMOVED. SEE NOTE 7.
EXISTING STEEL BEAMS (B)
AND GIRDERS (G) TO REMAIN.
FIELD VERIFY BEAM SIZE.
REMOVE CONCRETE ENCASEMENT
FROM BEAMS AND GIRDERS IN
THEIR ENTIRETY. SEE NOTE 7.
REMOVE EXISTING UTILITY
HANGERS AS REQUIRED
TO COMPLETE WORK. RESUPPORT
UTILITIES AS REQUIRED.
EXISTING SUSPENDED
UTILITIES ARE TO BE TEMPORARILY
SHORED AND RESUPPORTED
AFTER COMPLETION OF THE WORK
TEMPORARY WEATHER PROTECTION
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
JNZ
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
3000 CT DAS-CS CAD Title Block Template.dwg
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
EXISTING FRAMING AND
ROOF DEMOLITION PLAN
S102
1/4" = 1'-0"S102
EXISTING FRAMING AND ROOF
DEMOLITION
3/4" = 1'-0"S102
CONCRETE ENCASED STEEL
BEAMS AND GIRDERS
CD SUBMISSION
KEY PLAN
EAST TUNNEL CORRIDOR (NIC)
WEST TUNNEL CORRIDOR (NIC)
S104
S104
EXISTING FAN UNIT TO BE
REMOVED AND REINSTALLED
EXISTING STEAM PRESSURE RELIEF
VENT TO BE TEMPORARILY
REMOVED AND REINSTALLED
RE: SECTION 4/S103
CONTINUOUS CONCRETE
BEARING CAP
CONTINUOUS CONCRETE
BEARING CAP. RE: 3/S104
CONTINUOUS CONCRETE
BEARING CAP. RE: 3/S104
CONTINUOUS CONCRETE
BEARING CAP. RE: 3/S104
S103
E X
IS
T
IN
G
E L E
C T
R
IC
P
N E
L T
O R
E M
A
IN
ROOF HATCH
S103
S103
CONTINUOUS CONCRETE
BEARING CAP. RE: 3/S104
SLOPE ROOF 1/4"/FT.
28' - 7" VIF
V
IF
LOCATE HATCH BETWEEN EXISTING
STEEL FRAMING BELOW. FINAL LOCATION
TO BE COORDINATED WITH OWNER.
2'-0" VIF
EXISTING STEEL FRAMING BELOW
NOT SHOWN FOR CLARITY
12" PRECAST CONCRETE PLANKS
WITH 2" CONCRETE TOPPING SLAB
SLOPE ROOF 1/4"/FT.
SLEEVE IN CAP
FOR SUMP PUMP
DISCHARGE
WALKWAY PADS TYPICAL
D-RING SEE
6/S103
D-RING SEE
6/S103
N
PROJECT
LOCATION
INTEGRAL GUARD RAIL
SYSTEM WITH SPRING
LOADED GATE.
75 MIL REINFORCED EPDM
MEMBRANE
ROOF MATERIAL NOTES:
ROOF INSULATION:
POLYISOSCYANURATE INSULATION. SEE SPECIFICATIONS.
ROOF BOARD:
NON-CONBUSTIBLE, MOSTURE RESISTANT GYPSUM
PANELS. SEE SPECIFICATIONS.
EPDM:
75 MIL REINFORCED EPDM. SEE SPECIFICATIONS.
FLASHING:
STAINLESS STEEL. SEE SPECIFICATIONS.
EXISTING FAN UNIT TO BE
REMOVED AND REINSTALLED
NEW CONTINUOUS CONCRETE
BEARING CAP RE: SECTION 3/S104 FOR
ADDITIONAL DETAILS
PRECAST CONCRETE
ROOF PLANK
2X8 PRESSURE TREATED
WOOD ROOF CURB
CANT STRIP ALL SIDES
STAINLESS STEEL
COUNTER FLASHING MIN
2" OVERLAP
2" TOPPING SLAB
PROVIDE PENETRATION
THRU PRECAST PLANK
COORDINATE SIZE WITH
EXISTING FAN UNIT
75 MIL REINFORCED FULLY
ADHEARED EPDM ROOFING
RIGID GYPSUM ROOF BOARD FASTEN
TO TOPPING SLAB AT 4" o.c. ALONG ALL EDGES AND 6" o.c. IN THE PLANE OF
EACH BOARD.
TAPERED INSULATION ON
INSULATION ADHESIVE
ELEV. VARIES
PAPER DAM
GROUT ENDS OF
PLANK SOLID
6"
CAULK CONTINUOUS
EXTEND ROOF BOARD
5/8" FIRE TREATED PLYWOOD
ALL SIDES
45 MIL VAPOR BARRIER
2' - 0"
VIF
EXISTING FRAMING NOT SHOWN FOR CLARITY
CAULK JOINT CONTINUOUS
MIN 6" LAP TYP.
CAULK CONTINUOUS
SEE 5/S104
(2) 2X10
PRECAST CONCRETE
PLANK
2x8 PRESSURE
TREATED
WOOD CURB
CANT STRIP ALL SIDES
2" TOPPING SLAB
75 MIL REINFORCED
FULLY ADHEARED EPDM ROOFING
ROOF HATCH RE:
SPECIFICATIONS
ROOF HATCH CONNECTION
BY MANUFACTURER
RIGID GYPSUM ROOF BOARD FASTEN TO
TOPPING SLAB. SEE 3/S103
TAPERED INSULATION ON
INSULATION ADHESIVE
ELEV. VARIES
1/4" PER FT.
5/8" FIRE TREATED
PLYWOOD ALL SIDES
EXTEND ROOF BOARD
45 MIL VAPOR BARRIER
REMOVABLE SAFETY NETTING
SECURED TO BLOCKING
INTEGRAL GUARD RAIL SYSTEM
WITH SPRING LOADED
GATE
6" MIN LAP
(2) 2X10
PRECAST CONCRETE
ROOF PLANK
CANT STRIP ALL SIDES
2" TOPPING SLAB ON
INSULATION ADHESIVE
75 MIL REINFORCED
FULLY ADHEARED EPDM ROOFING
STAINLESS STEEL
COUNTER FLASHING
RIGID GYPSUM ROOF BOARD
FASTEN TO TOPPING SLAB.
SEE 3/S103 FOR INFORMATION
TAPERED INSULATION
EXISTING CONCRETE SLAB
TO BE REMOVED
VENT WEATHER CAP
REMOVE AND REINSTALL
VENT PIPE
NOTE: PROVIDE ADDITIONAL VENT
PIPE EXTENSION AS REQUIRED TO
ACCOMODATE NEW ROOF ELEVATION
EXISTING STEEL
FRAMING TO REMAIN
ELEV. VARIES
EXTEND ROOF BOARD
45 MIL VAPOR BARRIER
MIN 6" LAP
(2) 2X8
STAINLESS STEEL
D-RING. MIN CAPACITY
5,000 LBS
FLASH INTO
ROOFING
PRECAST
PLANK
PLATE
WASHER
22 1
ZONE PRESSURE
ZONE - 1
ZONE - 2
ZONE - 3
1 - 105
1 - 135
1 - 165
FM PRESSURES
T
Y P
3'-0" TYP.
INDICATES
ZONE
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
JNZ
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
ROOF FRAMING PLAN
S103
1/4" = 1'-0"S103
1 ROOF FRAMING PLAN
3/4" = 1'-0"S103
3 SECTION AT FAN UNIT
1" = 1'-0"S103
5 SECTION AT ROOF HATCH
3/4" = 1'-0"S103
4 SECTION AT ROOF VENT
CD SUBMISSION
1" = 1'-0"S103
6 D-RING
KEY PLAN
FM WIND PRESSURE DIAGRAM
TOP OF EXISTING CONC.
SLAB ELEV. [61.70' +/-] VIF
CONT. CONCRETE
BEARING CAP
CONTINUOUS CONCRETE CAP
RE: OPP. SIDE SIM.
EXISTING STEEL COLUMNS
TO REMAIN (TYP.)
NOTE: REMOVE CONCRETE
ENCASING FROM EXISTING
STEEL BEAMS
EXISTING STEEL BEAMS
TO REMAIN
12" PRECAST CONCRETE
ROOF PLANK
2" CONC. TOPPING SLAB
EXISTING CONCRETE
SLAB TO BE REMOVED
S104
EXISTING UTILITIES NOT SHOWN FOR CLARITY
GROUT ALL JOINTS
CONTINUOUS
EXISTING RUST AT COLUMNS
TO BE REMOVED, PRIMED
AND PAINTED.
EXISTING CONCRETE
FOUNDATION WALL
EXISTING BRICK
MASONRY VENEER
3" TOPPING SLAB
EXISTING CONCRETE
FOUNDATION WALL
EXISTING BRICK
MASONRY VENEER
EXISTING PIPING SUPPORTS
TO BE REMOVED AND REINSTALLED.
SHORE AS REQUIRED
PROVIDE TEMPORARY PROTECTION TYP.
PROVIDE TEMPORARY
WEATHER PROTECTION
SEE 5/S101
TYP. OF 3
75 MIL FULLY AHDEARED
REINFORCED
EPDM ROOF
NOTE: ANY EQUIPMENT POINT
LOADS TO BE SECURED TO PLANK
SHALL BE LOCATED BETWEEN
PLANK VOIDS. DO NOT DRILL
THROUGH PRECAST STRANDS
LOCATED BETWEEN VOIDS. MAX
POINT LOAD PER HANGER 150 LBS.
EXISTING HAUNCH V.I.F.
TOP OF EXISTING CONC.
SLAB ELEV. [61.70' +/-] VIF
CONT.CONTINUOUS
CONCRETE CAPCONTINUOUS CONCRETE
CAP. RE: OPP. SIDE SIM.
12" PRECAST CONCRETE
ROOF PLANK
2" CONCRETE TOPPING SLAB
EXISTING STEEL COLUMNS
TO REMAIN (TYP.)
EXISTING STEEL BEAMS
TO REMAIN
EXISTING CONCRETE
SLAB TO BE REMOVED
SLOPE 1/4"/FT.
6" GRAVEL WASH PAD
EXISTING CONCRETE
FOUNDATION WALL
S104
EXISTING UTILITIES NOT
SHOWN FOR CLARITY
REMOVED CONCRETE
ENCASEMENT AROUND ALL BEAMS
SEE SPECIFICATIONS FOR AVAILABLE
HAZMAT REPORTS
EXISTING BRICK
MASONRY VENEER
3" TOPPING SLAB
EXISTING CONCRETE
FOUNDATION WALL
EXISTING PIPING SUPPORTS
TO BE REMOVED AND REINSTALLED.
SHORE AS REQUIRED
PROVIDE TEMPORARY PROTECTION TYP.
PROVIDE TEMPORARY
WEATHER PROTECTION
SEE 5/S101
TYP. OF 3
3'-6"
75 MIL REINFORCED
FULLY ADHERED
EPDM ROOFING
PAPER DAM
GROUT ENDS OF PLANK SOLID
2" TOPPING SLAB
6" GRAVEL WASH PAD
OVER GEOTEXTILE
PRECAST CONC.
ROOF PLANK
EXISTING STEEL BEAMS
TO REMAIN. REMOVE CONC.
ENCASEMENT AROUND BEAMS
CONT. CONCRETE CAP.
SEE 4/S104
6"
SLOPE 1/4"/FT.
EXISTING SLAB TO
BE REMOVED
3'-0"
#6 DOWEL BARS AT 24" o.c.
EXISTING CONCRETE
FOUNDATION WALL
RIGID GYPSUM ROOF BOARD
FASTEN TO TOPPING SLAB.
SEE 3/S103.
TAPERED INSULATION ON
INSULATION ADHESIVE
( V I F )
CONTINUOUS BENTONITE WATERSTOP
SEE 5/S104
45 MIL VAPOR BARRIER
PROVIDE GROUT
BED AS REQUIRED
TO LEVEL SURFACE
75 MIL REINFORCED
FULLY ADHERED
EPDM ROOFING
2" TOPPING SLAB
PRECAST CONCRETE
ROOF PLANK
CONTINUOUS CONCRETE CAP.
REINFORCE WITH 8 - #5 BARS
CONT. AND #4 TIES AT 12" o.c.
EXISTING STEEL BEAMS TO
REMAIN. REMOVE CONCRETE
ENCASEMENT AROUND BEAMS
2 - #4 HOOKS EPOXIED 6"
INTO EXISTING WALL AT 12" o.c.
EXISTING SLAB TO
BE REMOVED
GROUT KEY CONT.
EXISTING CONCRETE
FOUNDATION WALL
EXISTING BRICK
MASONRY VENEER
RIGID GYPSUM ROOF BOARD
FASTEN TO TOPPING SLAB
SEE 3/S103.
TAPERED INSULATION ON
INSULATION ADHESIVE
#5 DOWEL BARS AT 24"o.c.
( V I F )
CONTINUOUS BENTONITE
WATERSTOP
EXISTING GRADE
6"
SEE 3/S103
45 MIL VAPOR BARRIER
ELEVATION VARIES
MINIMUM 1/4"/ FT.
45 MIL VAPOR BARRIER
STAINLESS STEEL
FASCIA TRIM
CONT. ROOF BOARD
ROOF INSULATION 2" MIN
ON INSULATION ADHESIVE
RIGID GYPSUM ROOF BOARD
SEE 3/S103 FOR ATTACHMENT
EXTEND EPDM ROOFING
ROOFING SEALING
STRIP MIN 6" OVERLAP
CAULK CONTINUOUS
CONTINUOUS STAINLESS
STEEL COUNTER FLASHING
75 MIL REINFORCED
FULLY ADHERED
EPDM ROOFING
2" TOPPING SLAB
PRECAST PLANK
CONCRETE
CAP
REINFORCING NOT
SHOWN FOR CLARITY
SEE 4/S104.
SLOPE 1/4"/FT.
8" MIN VERTICAL COUNTER
FLASHING OVERLAP
2X4 CONT BLOCKING
PROVIDE GROUT BED AS
REQUIRED TO LEVEL SURFACE
PRESTRESSING
STRANDS
PLANK
VOID
2" TOPPING SLAB
ACCEPTABLE
DRILLED IN ANCHOR
LOAD LOCATION.
MAX 150 LBS PER
HANGER
UNACCEPTABLE DRILLED
IN ANCHOR LOAD
LOCATION
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
JNZ
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
3000 CT DAS-CS CAD Title Block Template.dwg
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
FRAMING SECTIONS
S1.04
3/8" = 1'-0"S104
1 SECTION
3/8" = 1'-0"S104
2 SECTION
3/4" = 1'-0"S104
3 SECTION
3/4" = 1'-0"S104
4 SECTION
CD SUBMISSION
1 1/2" = 1'-0"S104
5 DETAIL
1" = 1'-0"S104
6 PLANK SUPPORTS
PROVIDE GROUT
BED AS REQUIRED
TO LEVEL SURFACE
EXISTING SLAB SURFACE TO
BE THROUGHLY CLEANED PRIOR
TO PLACEMENT OF TOPPING SLAB
PHOTO -P1 PHOTO -P2 PHOTO -P3 PHOTO -P4 PHOTO -P5
PHOTO -P6 PHOTO -P7 PHOTO -P8 PHOTO -P9 PHOTO -P10
PHOTO -P11 PHOTO -P12 PHOTO -P13 PHOTO -P14 PHOTO -P15
PHOTO -P16 PHOTO -P17 PHOTO -P18
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
JNZ
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
3000 CT DAS-CS CAD Title Block Template.dwg
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
SITE PHOTOS
S105
CD SUBMISSION
DESIGN DATA
CODES AND STANDARDS USED:
2022 CONNECTICUT BUILDING CODE
AMERICAN CONCRETE INSTITUTE BUILDING CODE (ACI-318-19)
AMERICAN INSTITUTE OF STEEL CONSTRUCTION "ALLOWABLE STRESS DESIGN"
(AISC-16TH EDITION, ANSI/AISC 360-10)
ALLOWABLE STRESSES: SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION
REINFORCING STEEL - ASTM A-615, GRADE 60 AND ASTM A-185
CONCRETE - f'c AT 28 DAYS
4,500 PSI FOR ALL CONCRETE UNLESS NOTED BELOW:
4,000 PSI FOR ALL TOPPING SLABS AND INTERIOR SLABS ON GRADE
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION
ALLOWABLE SOIL BEARING STRESS:
3,000 PSF ASSUMED
GROUT - F'c AT 28 DAYS = 3,000 PSI
WIND LOAD REQUIREMENTS: (IBC SECTION 1609) WIND BORNE DEBRIS REGION
WIND LOAD ANALYSIS DESIGN PROCEDURE - METHOD 1 SIMPLIFIED PROCEDURE
ULTIMATE DESIGN WIND SPEED Vult = 120 MPH (MIDDLETOWN)
RISK CATEGORY II (IBC 1604.5)
EXPOSURE CATEGORY B (IBC 1609.4)
INTERNAL WIND PRESSURE COEFFICIENT GPCi = 0.18
EARTHQUAKE REQUIREMENTS: (IBC SECTION 1613)
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR, Ie = 1.0
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS
Ss = 0.209 (MIDDLETOWN) S1 = 0.056 (MIDDLETOWN)
SESMIC DESIGN CATEGORY = B
RESPONSE MODIFICATION FACTOR R = 3
EQUIVALENT LATERAL FORCE PROCEDURE
SNOW LOAD: (IBC SECTION 1608)
THERMAL FACTOR Ct = 1.0 EXPOSURE FACTOR Ce = 1.0 IMPORTANCE FACTOR Is = 1.10 ROOF GROUND SNOW LOAD Pg = 30 PSF (MIDDLETOWN)
MINIMUM ROOF DESIGN LIVE LOAD 200 PSF
2021 IBC INTERNATIONAL BUILDING CODE
SUPERIMPOSED DEAD LOAD SCHEDULE:
TYPICAL ROOFS 25 PSF
WIND IMPORTANCE FACTOR, Iw = 1.0
ULTIMATE COMPONENT AND CLADDING WIND PRESSURES.
COORDINATE REQUIRED FM REQUIRED PRESSUES
WITH PRESSURE DIAGRAM ON DRAWINGS S103
2022 CONNECTICUT FIRE SAFETY CODE
2022 CONNECTICUT STATE FIRE PROTECTION CODE
CONSTRUCTION STAGING NOTES:
1. CONTRACTOR SHALL STAGE CONSTRUCTION SO AS TO MAINTAIN
OPERATION OF ALL FACILITIES AND PROTECT EXISTING EQUIPMENT FROM
DAMAGE DUE TO CONSTRUCTION AND EXPOSURE TO THE ELEMENTS
DURING THE LIFE OF CONSTRUCTION SHORE AS REQUIRED.
2. CONTRACTOR SHALL TEMPORARILY SUPPORT ALL HANGING OR GROUND
SUPPORTED MECHANICAL EQUIPMENT AND PIPING PRIOR TO DEMOLITION
DURING ANY STAGE OF CONSTRUCTION.
3. ONCE WORK IS COMPLETE CONTRACTOR SHALL ENSURE THAT ALL
MECHANICAL EQUIPMENT AND PIPING SCHEDULED TO REMAIN IS
PERMANENTLY AND ADEQUATELY SUPPORTED.
ROOFING NOTES:
1. ALL WOOD IN DAMP AREAS IN CONTACT WITH EARTH, CONCRETE OR
ROOFING INCLUDING WOOD BLOCKING AND LUMBER CANT STRIPS SHALL
BE PRESERVATIVE TREATED TO RESIST FUNGUS AND INSECT INFESTATION.
2. PROVIDE WALKWAY PADS TO AND AROUND ROOF-MOUNTED EQUIPMENT
THAT REQUIRES SERVICING. USE PADS APPROVED BY ROOFING MATERIALS
MANUFACTURER.
3. AT THE END OF EACH DAY, CONTRACTOR SHALL ENSURE THAT THE
ROOFING ASSEMBLY INCLUDING INTERIM TERMINATION DETAILS AT EDGES
OF ROOFING AND INSULATION ARE WATER-TIGHT.
1.
CONCRETE – SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION
ALL DETAILING, FABRICATION AND ERECTION OF REINFORCING BARS MUST
FOLLOW ACI 318-14.
2. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60.
3. NO TACK WELDING OF REINFORCING WILL BE PERMITTED.
4. UNLESS NOTED OTHERWISE, ALL LAP SPLICES SHALL BE CLASS B, IN
ACCORDANCE WITH ACI 318-14.
5. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185.
6. WIRE MESH REINFORCEMENT MUST LAP ONE MESH SIZE AT SIDES AND ENDS AND
BE WIRED TOGETHER.
7. WELDED WIRE FABRIC SIDE LAPS SHALL BE STAGGERED TO AVOID FOUR MESH
THICKNESS AT COINCIDING END LAP AND SIDE LAP LOCATION.
8. NO CALCIUM CHLORIDE OR ADMIXTURES CONTAINING CHLORIDES SHALL BE USED
IN THE CONCRETE.
9. ALL HORIZONTAL STEEL SHOWN IN SECTIONS AND DETAILS SHALL BE
CONTINUOUS, UNLESS OTHERWISE NOTED. ALL LAPS SHALL BE CLASS “B”
SPLICES IN ACCORDANCE WITH ACI 318.
10. AT INTERSECTIONS OF REINFORCED CONCRETE WALLS/FOOTINGS, PROVIDE
CORNER DOWELS OF SAME SIZE AND AT THE SAME SPACING AS THE SMALLER
HORIZONTAL REINFORCING. DOWELS SHALL HAVE A CLASS B LAP WITH
HORIZONTAL REINFORCING IN EACH DIRECTION. SEE DETAILS.
11. ALL KEYS IN CONCRETE WALLS SHALL BE 2X4 UNLESS NOTED OTHERWISE.
12. SEE ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL,
SITE, SITE UTILITY AND EQUIPMENT DRAWINGS FOR CONCRETE PADS, SLEEVES,
OPENINGS, RECESSES, AND BUILT-IN WORK IN CONCRETE ELEMENTS.
13. THE CONTRACTOR SHALL FURNISH, LOCATE AND INSTALL ALL ACCESSORIES FOR
PROPER ANCHORAGE OF WOOD AND METAL FRAMING, WOOD BLOCKING, BRICK
WORK AND MASONRY UNITS. HE SHALL BE SOLELY RESPONSIBLE FOR
FURNISHING, LOCATING AND ENSURING PROPER QUANTITY OF ALL FASTENING
DEVICES.
14. CONTRACTOR SHALL FOLLOW ACI REQUIREMENTS FOR ALL REINFORCING
CLEARANCES.
15. REINFORCING STEEL SHOP DRAWINGS SHALL INDICATE THE SEQUENCE IN WHICH
LAYERS OF CROSSING REINFORCING SHOULD BE PLACED, IN ORDER TO PRODUCE
THE CORRECT OUTERMOST LAYER AS INDICATED ON THE DRAWINGS.
16. SHOP DRAWINGS SHALL INDICATE LOCATIONS OF ALL WALL CONTROL AND
CONSTRUCTION JOINTS.
17. ALL REINFORCING, THREADED RODS OR BOLTS INDICATED TO BE DRILLED AND
EPOXIED SHALL UTILIZE HILTI HIT-HY200 ADHESIVE OR APPROVED EQUAL.
18. ALL CONCRETE WALLS ARE TO BE REINFORCED. IF NOT SHOWN PROVIDE 2-#6
CONTINUOUS BARS T&B AND #4 VERTICAL BARS AT 18" O.C.
GENERAL NOTES:
1. CONTRACTOR TO COORDINATE STRUCTURAL DRAWINGS WITH OTHER
DISCIPLINES. CONTRACTOR SHALL BE RESPONSIBLE FOR INCORPORATING ALL
REQUIREMENTS IN THE SHOP DRAWINGS AND WORK.
2. DO NOT CHANGE SIZE OR DIMENSIONS OF STRUCTURAL MEMBERS WITHOUT
APPROVAL OF THE ENGINEER.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR LIMITING THE AMOUNT OF
CONSTRUCTION LOAD IMPOSED UPON STRUCTURAL FRAMING. CONSTRUCTION
LOADS SHALL NOT EXCEED THE DESIGN CAPACITY OF STRUCTURAL MEMBERS AT
THE TIME LOADS ARE IMPOSED.
4. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE
STRUCTURE IS DEPENDENT UPON THE LATERAL FORCE RESISTING SYSTEM
INCLUDING, BUT NOT LIMITED TO, BRACED FRAMES, ANCHORAGES AND
ATTACHMENTS FOR STABILITY AND FOR RESISTANCE TO GRAVITY AND LATERAL
FORCES. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING AND SUPPORT AS
REQUIRED TO ENSURE THE STABILITY OF ALL STRUCTURAL ELEMENTS DURING
CONSTRUCTION UNTIL THE ENTIRE STRUCTURE IS IN PLACE.
5. DO NOT SCALE FROM DRAWINGS. USE DIMENSIONS AS NOTED ON THE DRAWINGS.
6. CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE
AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS
DURING THE CONSTRUCTION PERIOD.
7. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS, ELEVATIONS AND MEMBER SIZES ON
STRUCTURAL DRAWINGS PRIOR TO START OF CONSTRUCTION. CONTRACTOR SHALL
INFORM ENGINEER OF ANY DISCREPANCIES PRIOR TO ORDERING MATERIALS OR
PROCEEDING WITH WORK.
8. REVIEW OF SHOP DRAWINGS BY ENGINEER SHALL NOT RELIEVE THE CONTRACTOR FROM
CONFORMING WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. ANY DEVIATION
IN THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE ENGINEER AT THE TIME OF
SUBMISSION AND MUST BE APPROVED BY THE ENGINEER IN WRITING.
9. CONTRACTOR SHALL REVIEW AND APPROVE SHOP DRAWINGS PRIOR TO SUBMISSION TO
ENGINEER. SHOP DRAWINGS NOT STAMPED “REVIEWED” BY THE CONTRACTOR WILL BE
RETURNED WITHOUT BEING REVIEWED.
10. COORDINATE SITE LAYDOWN AREAS WITH SITE LOGISTICS PLAN S107
11. LOCATION OF EXISTING STRUCTURES AND UTILITIES AND MATERIALS OF CONSTRUCTION
SHALL BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO START OF CONSTRUCTION.
12. CONTRACTOR SHALL NOT DISRUPT THE OWNER'S OPERATIONS OR THE OPERATION OF
ANY ACTIVE EQUIPMENT WITHIN THE VAULT DURING THE ENTIRE DURATION OF CONSTRUCTION.
13. CONTRACTOR SHALL PROVIDE ADEQUATE SHORING AND BRACING TO SUPPORT
AND MAINTAIN UTILITIES DURING CONSTRUCTION.
14. CONTRACTOR SHALL PLACE ALL EQUIPMENT AND MATERIAL AS FAR AWAY AS
POSSIBLE FROM THE EDGE OF TRAVEL AREAS SO AS NOT TO IMPEDE TRAFFIC OR
CAUSE A SAFETY HAZARD.
15. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR FABRICATION AND FIT
OF HIS WORK.
16. PRIOR TO BEGINNING WORK, CONTRACTOR SHALL CLEAN EXISTING FLOOR DRAINS
WITHIN THE WORK AREA AND SHALL MAINTAIN THE DRAINS FOR THE DURATION OF
THE PROJECT.
19. REINFORCING BARS SHALL BE PROTECTED BY THE FOLLOWING THICKNESS
OF CONCRETE COVER:
A. CONCRETE PLACED AGAINST EARTH ....................... 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 BARS AND SMALLER ............................. 1 1/2"
#6 BARS AND LARGER ............................... 2"
C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABS, WALLS AND JOISTS:
#11 BARS AND SMALLER ........................... 3/4"
BEAMS AND COLUMNS:
ALL BARS ..................................................... 1 1/2
D. IN ALL CASES THE THICKNESS OF CONCRETE OVER THE REINFORCEMENT
SHALL BE AT LEAST EQUAL TO THE DIAMETER OF THE REINFORCEMENT.
TYPICAL CONCRETE WALL REINFORCING DETAIL
EXTERIOR FACE INTERIOR FACE
CONTINUOUS REINFORCING
NOT TO SCALE
NOTE LAP DETAILS APPLY TO ALL REINFORCING CALLED OUT AS CONTINUOUS
(CONT.) ON THE PLANS AND DETAILS.
CORNER BARS TO MATCH
DIAMETER OF CONTINUOUS BARS
1 1/2" CLR. TYP.
SEE PLAN FOR WALL
THICKNESS (t)
(t)(t)(t)
1'-6" LAP
1'-6" LAP
L A
P
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
MRP
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
GENERAL NOTES
S106
CD SUBMISSION
mike plickys
CROPPED PE
PROJECT
PARKING
PROJECT SITE
PORTA
POTTI
PROJECT LAYDOWN
AND STORAGE AREA
PROJECT SIGN
SITE ACCESS
N
PROTECT
EXISTING TREES TEMPORARY CONSTRUCTION
FENCE WITH LOCKABLE GATE
CONSTRUCTION
TRAILER SITE
COORDINATE WITH
AGENCY
JERSEY
BARRIER
PROTECTION
APPROXIMATE
CONTRACT
LIMIT LINE
STREET TO
REMAIN OPEN
1. SITE LOGISTICS PLAN IS SHOWN FOR INFORMATION ONLY.
CONTRACTOR SHALL SUBMIT A LOGISTICS PLAN FOR
REVIEW AND APPROVAL.
GENERAL NOTES:
2. CONTRACTOR SHALL COORDINATE ANY REQUIRED ROAD
CLOSURES WITH THE AGENCY.
3. AFTER COMPLETION OF THE WORK CONTRACTOR SHALL
REPAIR ALL SITE DAMAGE AND RE ESTABLISH SITE TO PRE
EXISTING CONDITION.
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
MRP
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
SITE LOGISTICS PLAN
S107
CD SUBMISSION
12" = 1'-0"S107
1 SITE LOGISTICS PLAN
12" = 1'-0"S107
2 PROJECT SIGN
JUNE 2026
RENOVATIONS TO THE
CONNECTICUT VALLEY HOSPITAL
BI-MH-134
STATE OF CONNECTICUT
DEPARTMENT OF ADMINISTRATIVE SERVICES
MIDDLETOWN, CT
OLD POWERHOUSE
MRP
AS NOTED
MRP
CAD no.
drawing prepared by project no.
project drawing no.
approved by drawn by scale date drawing title descriptiondatemark
R E V I S I O N Sprofessional seal
3000 CT DAS-CS CAD Title Block Template.dwg
44 GILLETT STREEET
HARTFORD , CT 06105
MACCHI ENGINEERS
CODE INFORMATION
S108
CD SUBMISSION
| COVER SHEET |
| Sheets |
| COVER SHEET - STATE OF CONNECTICUT |
| S100 |
| Sheets |
| S100 - EXISTING CONDITIONS - SITE PLAN |
| S101 |
| Sheets |
| S101 - FOUNDATION PLAN |
| S102 |
| Sheets |
| S102 - EXISTING FRAMING AND ROOF DEMOLITION |
| S103 |
| Sheets |
| S103 - ROOF FRAMING PLAN |
| S104 |
| Sheets |
| S104 - FRAMING SECTIONS |
| S105 |
| Sheets |
| S105 - SITE PHOTOS |
| S106 |
| Sheets |
| S106 - GENERAL NOTES |
| S107 |
| Sheets |
| S107 - SITE LOGISTICS PLAN |
| S108 |
| Sheets |
| S108 - CODE INFORMATION |