Drawings-Renovate Swing Space Bldg 143.pdf

PDF 7 MB Posted

Attached to
Z1DA--RENOVATE SHELL SPACE (658-22-104)
Solicitation number
36C24626B0015
Issued by

About this file

These construction documents detail a renovation project for a shell space at the Salem VA Medical Center located at 1970 Roanoke Blvd in Salem, VA. The project involves renovating an open workspace area, including the installation of 17 workstations, electrical and mechanical systems upgrades, and minimal architectural modifications. The project includes new pendant light fixtures suspended from existing structural steel, electrical infrastructure for modular furniture (power and data connections), and maintaining existing mechanical systems such as air handling and ventilation. The renovation will be fully sprinklered and must comply with multiple codes including NFPA 101 Life Safety Code, National Electrical Code, and VA design standards. The construction documents are dated 03 April 2024 and prepared by Above Group for the VA Office of Construction and Facilities Management, with a project number of 658-22-104.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSTRUCTION

SUBSYSTEM

BUILDING WALL

SECTION

ELEVATION

INTERIOR

ELEVATION

DOORS

ROOM NUMBER

EXTERIOR AND

INTERIOR WINDOWS

PLAN & SECTION

DETAIL REFERENCE

REFERS TO A TYPICAL

ASSEMBLY

LOCATION ON DRAWING

SHEET

SHEET DETAIL IS

LOCATED

REFERS TO NUMBER ON DOOR

SCHEDULE, SEE SHEET A401

REFERS TO NUMBER ON

FLOOR PLAN

REFERS TO FRAME TYPE, SEE

ENLARGED ELEVATIONS ON SHEET A402

LOCATION ON

DRAWING SHEET

ARROW INDICATES DIRECTION OF

ELEVATION

SHEET LOCATION WHERE

ELEVATION IS LOCATED

Room name

A101

SIM

NUMBER INDICATES ELEVATION

ON SHEET

LOCATION ON

DRAWING SHEET

101A

A101

A101

PARTITION

TYPES

REFERS TO INTERIOR PARTITIONS,

SEE SHEET G004

REVISION

REVISIONS ARE SHOWN WITHIN

"CLOUDED" AREA REVISION

NUMBER & DATE WILL APPEAR IN

TITLE BLOCK SPACE SO LABELED

SHEET LOCATION WHERE

ELEVATION IS LOCATED

A101

DEMOLITION NOTE

REFERS TO DEMOLITION

NOTES ON THAT SHEET

X

CONSTRUCTION NOTE REFERS TO CONSTRUCTION

NOTES ON THAT SHEET

X

EXTERIOR AND

INTERIOR STOREFRONT

REFERS TO FRAME TYPE, SEE

ENLARGED ELEVATIONS ON SHEET A40200

SF

REFERS TO EXISTING GRID

LINES IN PROJECT

REFERS TO NEW GRID LINES

EXISTING GRID LINE

NEW GRID LINE

DRAWING LIST

SHEET # SHEET TITLE

GENERAL

G001 COVER SHEET

G002 LIFESAFETY, ABBREVIATIONS & CODE NOTES

ARCHITECTURAL

A101 FIRST FLOOR DEMO , NEW WORK AND REFLECTED CEILING PLAN

MECHANICAL

M-001 MECHANICAL NOTES. LEGEND, & SYMBOLS

M-101 FLOOR PLAN - MECHANICAL - NEW WORK

ELECTRICAL

E-001 ELECTRICAL LEGENDS & SYMBOLS

E-002 ELECTRICAL GENERAL NOTED

E-100 FIRST FLOOR PARTIAL OVERALL

ED101 FLOOR PLAN - LIGHTING DEMO

ED102 FLOOR PLAN - ELECTRICAL EQUIPMENT - DEMO

EL101 FLOOR PLAN - LIGHTING - NEW WORK

EP101 FLOOR PLAN - ELECTRICAL EQUIPMENT - NEW WORK

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL DIAGRAMS

SITE MAP SYMBOLS

IMAGE: GOOGLE EARTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll S p a c e

/2

V

A S a le m R e n o v a te

S h e ll

S p a c e

.r v t

/3

/2

:2

:0

P

M

G001

COVER SHEET Renovate Shell Space

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TB JC

CONSTRUCTION

DOCUMENTS

1970 ROANOKE BLVD

SALEM, VA 24153

Revisions: Date:

Salem VA Medical Center Renovate Shell Space

LaShaun Key Stamp

UP

ABBREVIATIONS:

A LABEL CLASS A DOOR

A/C AIR CONDITION

A/E ARCHITECT/ENGINEER

ABV ABOVE

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADH ADHESIVE

ADJ ADJACENT

ADMIN ADMINISTRATION

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECT

ASB ASBESTOS

ASPH ASPHALT

ASSN ASSOCIATION

AUTO AUTOMATIC

AUX AUXILIARY

BAT BATTEN

BD BOARD

BEV BEVEL

BKG BACKING

BLDG BUILDING

BOT BOTTOM

BTWN BETWEEN

C TO C CENTER TO CENTER

CAB CABINET

CONC CONCRETE

CIR CIRCLE

CL CENTER LINE

CLDG CLADDING

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

COL COLUMN

CONC FLR CONCRETE FLOOR

CONSTR CONSTRUCTION

CONT CONTINUE

COORD COORDINATE

CPT CARPET OR CARPET TILE

CSWK CASEWORK

CT CERAMIC TILE

CTRL CONTROL

DAT DATUM

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DTL DETAIL

DIFF DIFFERENCE

DIM DIMENSION

DIR DIRECTION

DR DOOR, OR DRAIN

DR OPNG DOOR OPENING

MAINT MAINTENANCE

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMO MEMORANDUM

MEZZ MEZZANINE

MID MIDDLE

MIRR MIRROR

MISC MISCELLANEOUS

MLDG MOLDING (MOULDING)

MLWK MILLWORK

MO MASONRY OPENING

MTL METAL

MULL MULLION

NA NOT APPLICABLE

NAT NATURAL

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NUM NUMERAL

OC ON CENTER

OCC OCCUPY

OFF OFFICE

OPNG OPENING

OPP OPPOSITE

OSHA OCCUPATIONAL SAFETY

AND HEALTH ADMINSTRATION

OZ OUNCE

PART PARTIAL

PAT PATTERN

PEN PENETRATE

PERF PERFORATED

PERP PERPENDICULAR

PLAS PLASTER OR PLASTIC

PLBG PLUMBING

PLYWD PLYWOOD

PNL PANEL

PRB PROFILE BASE

PRCST PRECAST

PREFAB PREFABRICATE

PRELIM PRELIMINARY

PREP PREPARATION

PREV PREVIOUS

PROP PROPERTY

PTD PAINTED

PVC POLYVINYL CHLORIDE (PLASTIC)

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QT QUARRY TILE

QTB QUARRY TILE BASE

QTR QUARTER

QTY QUANTITY

R RADIUS OR RISER

RAD RADIATOR

RB RESILIENT BASE OR RUBBER BASE

RBR RUBBER

RCP REFLECTED CEILING PLAN

RCVR RECEIVER

RD ROAD OR ROOF DRAIN

REC RECESSED

RECT RECTANGLE

REF REFERENCE OR REFRIGERATOR

E.J. EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC

ELEV ELEVATOR

EMER EMERGENCY

ENGR ENGINEER

EQ EQUAL

EQUIP EQUIPMENT

EQUIV EQUIVALENT

ESP ESPECIALLY

EXIST EXISTING

FA FIRE ALARM

FAS FASCIA

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FIN FLR FINISH FLOOR

FIXT FIXTURE

FLR FLOOR

FP FIRE PROTECTION OR FIREPROOF

FRT FIRE RETARDANT TREATED

FRZ FREEZER

FT FEET OR FOOT

FURN FURNISH OR FURNITURE

GA GAGE OR GYPSUM ASSOCIATION

GAL GALLON

GALV GALVANIC OR GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GEN GENERAL OR GENERATOR

GL GLASS

GLU LAM GLUED LAMINATED WOOD

GT GROUT

GYP GYPSUM

GYP BD GYPSUM BOARD

HB HOSE BIBB

HC HOLLOW CORE

HDWD HARDWOOD

HM HOLLOW METAL

HT HEIGHT

HVAC HEATING, VENTILATING,

AND AIR CONDITIONING

ID IDENTIFICATION

ILLUM ILLUMINATION

INCL INCLUDED

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

JAN JANITOR

J-BOX JUNCTION BOX

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LDR LEADER

LED LIGHT EMITTING DIODE

LT LIGHT

LVD LOUVERED

LVR LOUVER

LVT LUXURY VINYL TILE

LYR LAYER

REINF REINFORCE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RESIL RESILIENT

RET RETURN

REV REVISION

RF RUBBER FLOORING

RM ROOM

RND ROUND

RO ROUGH OPENING

SALV SALVAGE

SBSTR SUBSTRATE

SCHED SCHEDULE

SCHEM SCHEMATIC

SECT SECTION

SEP SEPARATE

SF SQUARE FOOT (FEET)

SLNT SEALANT

SMK SMOKE

SPEC SPECIFICATION

SPKLR SPRINKLER

SPLY SUPPLY

SQ SQUARE

SS STAINLESS STEEL

STD STANDARD

STOR STORAGE

STR STRINGERS

STRUCT STRUCTURAL

SURF SURFACE

SUSP SUSPEND

SVT SOLID VINYL FLOOR TILE

SYS SYSTEM

T&G TONGUE AND GROOVE

TECH TECHNICAL

TEL TELEPHONE

TEMP TEMPERATURE OR TEMPORARY

THK THICKNESS

THRU THROUGH

TMPD TEMPERED

TO TOP OF ___

TRANS TRANSOM

TRTD TREATED

TYP TYPICAL

U HEAT TRANSFER COEFFICIENT

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

UV ULTRAVIOLET

VAC VACUUM

VAR VARIES

VCT VINYL COMPOSITION TILE

VENT VENTILATION

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VOL VOLUME

W/ WITH

W/O WITHOUT

WD WOOD

WSCT WAINSCOT

WSF WELDED SEAM SHEET FLOORING

WT WEIGHT

A. PRIMARY APPLICABLE CODES AND STANDARDS - EXISTING BUILDING / RECONSTRUCTION

THE DEPARTMENT OF VETERANS AFFAIRS HAS ADOPTED THE LATEST EDITION OF THE

FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE

MODERNIZATION, ALTERATION, ADDITION OR IMPROVEMENT OF ITS REAL PROPERTY AND THE

CONSTRUCTION OF NEW STRUCTURE.

a. NFPA 101 LIFE SAFETY CODE, 2021 EDITION

b. NFPA NATIONAL FIRE CODES (WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900)

c. NATIONAL ELECTRIC CODE (NEC)

d. INTERNATIONAL PLUMBING CODE (IPC)

e. ASME BOILER AND PRESSURE VESSEL CODE

f. ASME CODE FOR PRESSURE PIPING

g. ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA

SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)

h. ENERGY POLICY ACT (EPAct)

i. VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL)

j. INTERNATIONAL BUILDING CODE (IBC) - ONLY WHEN SPECIFICALLY REFERENCE IN VA

DESIGN DOCUMENTS

k. OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

l. PHYSICAL SECURITY DESIGN MANUAL (PSDM)

3. RENOVATION TO EXISTING SUITE. REMOVAL OF PARTIAL HEIGHT PARTITION WITHIN

OPEN AREA FOR THE INSTALLATION OF 17 WORKSTATIONS.

NFPA 101 REVIEW

B. CHAPTER 39 EXISTING BUSINESS OCCUPANCIES

1. (39.1.1.1) THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY TO EXISTING BUILDINGS OR

PORTIONS THEREOF USED AS BUSINESS OCCUPANCIES.

C. MEANS OF EGRESS - CHAPTER 39 AND CHAPTER 7

1. THERE IS NO CHANGE TO THE EXISTING SUITE EXITING.

D. FIRE PROTECTION EQUIPMENT - CHAPTER 39 AND CHAPTER 9

1. THE EXISTING SPACE IS FULLY PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM.

2. (39.3.5) EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE EXTINGUISHERS SHALL BE

PROVIDED IN EVERY BUSINESS OCCUPANCY IN ACCORDANCE WITH SECTION 9.9.

A. (9.9) WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE, PORTABLE FIRE

EXTINGUISHERS SHALL BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED IN

ACCORDANCE WITH NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS.

E. INTERIOR FINISHES - CHAPTER 39 AND SECTION 10.2

1. (39.3.3.2.1) INTERIOR WALL AND CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2

SHALL BE CLASS A OR CLASS B IN EXITS AND IN EXIT ACCESS CORRIDORS.

CODE NOTES:

OFFICE

IC-129E

OPEN

WORKSPACE

IC-129R

OFFICE

IC-129Q

OFFICE

IC-129L

MECHANICAL

IB-120

CONFERENCE

IC-129J

CORRIDOR

IC-129K

EQUIP STORAGE

IC-128A

TOILET

IC-129F

TOILET

IC-129G

OFFICE

IC-129H

TRAVEL DISTANCE TO EXIT = 181'-10"16 1

6TRAVEL DISTANCE TO EXIT = 228'-10"

16 70" 350 16 34" 170

FEC

16P

KEY PLAN

PROJECT AREA

EXIT SIGN

LIFESAFETY LEGEND:

1 HOUR RATED FIRE PARTITION

2 HOUR RATED FIRE PARTITION

EXIT ACCESS TRAVEL DISTANCE

FIRE EXTINGUISHER IN CABINETFEC

CUMULATIVE OCCUPANT LOAD00

XX 00" XXX EXIT INFORMATION

MAX. NO. PERSON EXIT ALLOWS

EXIT WIDTH IN INCHES

ACTUAL OCCUPANT LOAD

OCCUPANT LOAD5P5P

1 HOUR SMOKE RATED PARTITION

NOT IN SCOPE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll S p a c e

/2

V

A S a le m R e n o v a te

S h e ll

S p a c e

.r v t

/3

/2

:2

:0

P

M

G002

LIFESAFETY, ABBREVIATIONS &

CODE NOTES

Renovate Shell Space

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TB JC

CONSTRUCTION

DOCUMENTS

Revisions: Date:

1/8" = 1'-0"G002

FIRST FLOOR LIFE SAFETY PLANC4

N

PROJECT

NORTH

A. PATCH AND REPAIR ALL GYPSUM BOARD SURFACES WHERE DEMOLITION

OF ADJOINING OR INTERSECTING PARTITIONS HAS RESULTED IN LESS

THAN A FINISHED CONDITION. PATCHES SHALL BE FLUSH AND SMOOTH.

B. EXISTING ROOMS THAT ARE NOT INDICATED TO BE AFFECTED BY THE

WORK ARE TO BE PROTECTED FROM DAMAGE AND/OR PAINT

DEGRADATION. SHOULD THE GENERAL CONTRACTOR AFFECT THE

CONDITION OR FINISH OF THESE ROOMS, THE SURFACE OR SPACE SHALL

BE RESTORED TO ORIGINAL CONDITION.

C. REFERENCE DRAWING A00X FOR GENERAL DEMOLITION PLANS. VERIFY

ALL DIMENSIONS TO EXISTING ELEMENTS.

D. NOTIFY THE ARCHITECT OF ANY AND ALL DISCREPANCIES BETWEEN

EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS BEFORE

PROCEEDING WITH THAT PORTION OF THE WORK. FAILURE TO NOTIFY

THE ARCHITECT WILL NOT RELIEVE THE CONTRACTOR OF THE

RESPONSIBILITY TO PERFORM THE WORK AS INTENDED BY THE

CONTRACT DOCUMENTS.

E. VERIFY EXISTING DIMENSIONS, CONDITIONS AND CLEARANCES PRIOR TO

THE SUBMISSION OF SHOP DRAWINGS.

GENERAL FLOOR PLAN NOTES:

D6

A101

1 2 3 4

5 6 7 8

CORRIDOR

EQUIP STORAGE

IC-128A

TOILET

IC-129F

TOILET

IC-129G

OFFICE

IC-129H

CONFERENCE

IC-129J

OPEN

WORKSPACE

IC-129R

WORKSTATIONS NIC

CPT 1

121110

14 15 16

CPT 1

VB 1

VB 1

VB 1

VB 1

VB 1

VB 1

VB 1

VB 1

VB 1

KEY PLAN

PROJECT AREA

NEW CONSTRUCTION LEGEND:

EXISTING CONSTRUCTION TO REMAIN

1 HOUR FIRE RESISTANCE RATED FIRE BARRIER

FIRE EXTINGUISHERE

EQ EQ

DIMENSIONAL CENTERLINE

NOT IN SCOPE

NOTE: EXISTING GLASS

PARTITION FRAMING AND

SLIDING DOORS TO REMAIN

OPEN

WORKSPACE

IC-129R

CONFERENCE

IC-129J

OFFICE

IC-129H

TOILET

IC-129G

TOILET

IC-129F

D6

A101

EQUIP STORAGE

IC-128A

TOILET

IC-129F

TOILET

IC-129G

OFFICE

IC-129H

CONFERENCE

IC-129J

7' -1

1/

2" 7'

-9

/2

7' -9

/2

7'

-9

/2

7' -8

/8

PENDANT MTD LIGHT

FIXTURES SUSPENDED

FROM STRUCTURE ABOVE

EXISTING CEILING

STRIP LIGHT

EXISTING CEILING

STRIP LIGHT

A. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS

IN THE FIELD AND COORDINATE ALL REMOVAL ACTIVITIES

WITH NEW CONSTRUCTION. THE CONTRACTOR SHALL

REPORT ALL DISCREPANCIES TO THE OWNER'S

REPRESENTATIVE FOR RESOLUTION PRIOR TO BEGINNING

REMOVALS.

B. PROTECT ALL CONSTRUCTION TO REMAIN FROM DAMAGE

DURING REMOVAL OF ADJACENT CONSTRUCTION.

REPAIR/REPLACE CONSTRUCTION TO REMAIN THAT WAS

DAMAGED DURING DEMOLITION TO MATCH THE QUALITY OF

THE NEW WORK. PROVIDE DUST CONTROL AND CONTAINMENT

MATS, FLOOR AND WALL PROTECTION.

C. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS

WHERE WORK MUST BE ACCOMPLISHED UNDER THIS

CONTRACT. INCIDENTAL WORK MAY ALSO BE NECESSARY IN

AREAS NOT SHOWN ON THE ARCHITECTURAL DRAWINGS DUE

TO CHANGES AFFECTING EXISTING ELECTRICAL, OR OTHER

SYSTEMS. SUCH INCIDENTAL WORK IS ALSO A PART OF THE

CONTRACT. CONTRACTOR SHALL INSPECT THOSE AREAS

AND ASCERTAIN WORK NEEDED AND DO THAT WORK IN

ACCORDANCE WITH THE CONTRACT REQUIREMENTS AND AT

NO ADDITIONAL COST TO THE OWNER.

D. DO NOT DRILL OR CUT EXISTING FLOOR JOISTS, BEAMS,

COLUMNS OR OTHER STRUCTURAL ELEMENTS UNLESS

SPECIFICALLY NOTED. MAKE OPENINGS OF PROPER SIZE FOR

CONDUITS AND PIPING AND OTHER ITEMS PASSING THROUGH

OPENINGS.

E. GC TO SCAN THE SLAB AT EA LOCATION OF PROPOSED

FLOOR/SLAB PENETRATION PRIOR TO CUTTING TO ENSURE

THAT AREA IS CLEAR OF EMBEDDED CONDUITS AND/OR LIVE

CONDUCTORS.

F. REPAIR, PATCH AND FINISH, OR REFINISH AS APPLICABLE, TO

MATCH ADJACENT EXISTING FINISHES DAMAGED OR NEWLY

EXPOSED DURING THE PERFORMANCE OF THE WORK OF THIS

CONTRACT.

G. WHERE CUTTING OF EXISTING SURFACES OR REMOVAL OF

EXISTING FINISHES IS REQUIRED TO PERFORM THE WORK

UNDER THIS CONTRACT, AND A NEW FINISH IS NOT

INDICATED, FILL RESULTING OPENINGS AND PATCH THE

SURFACE AFTER DOING THE WORK, AND FINISH TO MATCH

ADJACENT EXISTING SURFACES.

H. WHERE A NEW CEILING IS NOT SCHEDULED, INSTALL

CONDUITS AND PIPING IN EVERY CASE ABOVE THE CEILING.

REMOVE EXISTING CEILING AS NECESSARY. AFTER

INSTALLATION OF CONCEALED WORK, REINSTALL REMOVED

CEILING AND PATCH AND REFINISH TO MATCH ADJACENT UN-

REMOVED CEILINGS.

I. WORK SHOWN IS NEW UNLESS SPECIFICALLY NOTED OR

OTHERWISE INDICATED AS EXISTING.

J. PROVIDE HEADERS/LINTELS OVER EVERY OPENING IN BOTH

NEW AND EXISTING WALLS AND PARTITIONS.

K. WHERE "MATCH EXISTING" IS INDICATED, NEW

CONSTRUCTION OR FINISHES, AS APPROPRIATE TO THE

NOTE, SHALL MATCH THE EXISTING IN THE PARTICULAR.

GENERAL DEMOLITION NOTES:

L. DEFINITIONS

M1. REMOVE: REMOVE AND LEGALLY DISPOSE OF

ITEMS EXCEPT THOSE INDICATED TO BE REINSTALLED,

SALVAGED, OR EXISTING.

M2. SALVAGE: ITEMS INDICATED TO BE SALVAGED

SHALL REMAIN THE OWNER'S PROPERTY. REMOVE,

CLEAN AND PACK OR CRATE ITEMS TO PROTECT

AGAINST DAMAGE. IDENTIFY CONTENTS OF

CONTAINERS AND DELIVER TO OWNER'S DESIGNATED

STORAGE AREA.

M3. REINSTALL: REMOVE ITEMS INDICATED. CLEAN

SERVICE AND OTHERWISE PREPARE THEM FOR REUSE.

STORE AND PROTECT AGAINST DAMAGE. REINSTALL

ITEMS IN THE SAME LOCATIONS OR IN LOCATIONS

INDICATED.

M4. EXISTING: ORIGINAL ITEM TO REMAIN. PROTECT

CONSTRUCTION INDICATED AS EXISTING AGAINST

DAMAGE AND SOILING DURING SELECTIVE DEMOLITION.

M5. RESTORE: ITEMS INDICATED SHALL BE BROUGHT

BACK TO THEIR ORIGINAL CONDITION. ORIGINAL

CONDITION IS THE CONDITION THAT THE REFERENCED

ITEM WAS IN WHEN THE BUILDING WAS FIRST

CONSTRUCTED.

M6. REPLACE: EXISTING ITEM TO BE REMOVED.

PROVIDE NEW ITEM TO MATCH EXISTING.

M. CONTRACTOR TO ABIDE BY ALL THE ICRA INFECTION

CONTROL REGULATIONS.

N. CONTRACTOR SHALL KEEP THE SITE CLEAN AT ALL

TIMES AND COORDINATE TRASH REMOVAL WITH THE VA.

O. TEMPORARY CONTINUOUS CONSTRUCTION BARRIER

MUST BE IN PLACE PRIOR TO ANY DEMOLITION. G.C. TO

DETERMINE LOCATION FOR TEMPORARY

CONSTRUCTION BARRIER DOOR ACCESS.

CONSTRUCTION BARRIER DOOR(S) MUST BE SELF-

CLOSING. PROVIDE STICKY MATS ON ALL ACCESS

DOORS INTO CONSTRUCTION AREA. ANTE-ROOM

REQUIRED AT CONSTRUCTION ENTRY. PAINT PUBLIC

FACE OF TEMP BARRIER WHITE.

P. PROVIDE NANOMETER PRESSURE MONITORS FOR ALL

CONSTRUCTION BARRIERS.

Q. PROVIDE NEGATIVE PRESSURE AIR HEPA UNITS AND

EXHAUST TO EXTERIOR OF THE BUILDING.

R. CONTRACTOR TO REVIEW & FOLLOW ALL ABATEMENT

REQUIREMENTS PRIOR TO THE START OF GENERAL

DEMOLITION.

S. GC TO COORDINATE WITH VA WHEN MAJOR SHUTDOWNS

ARE TO OCCUR. SHUTDOWNS WILL NEED TO OCCUR

AFTER REGULAR BUSINESS HOURS, OVERNIGHT AND

WEEKENDS AS NEEDED TO MINIMIZE IMPACT TO

PATIENTS AND STAFF.

DEMOLITION LEGEND:

TEMPORARY CONSTRUCTION BARRIER

DEMOLITION SCOPE

EXISTING WALL TO REMAIN

EXISTING DOOR TO REMAIN

DEMOLITION NOTE1

A. NEW PENDANT LIGHT FIXTURES TO BE SUSPENDED OFF THE

EXISTING STRUCTURAL ROOFING TUBE STEEL.

B. REFER TO MEP DRAWINGS FOR ADDITIONAL WORK NOT

SHOWN.

GENERAL RCP NOTES:

NO CEILING

EXIT SIGN

1 HOUR RATED FIRE BARRIER

RCP LEGEND:

PENDANT LIGHTING

PENDANT LIGHT FIXTURES TO

BE MOUNTED TO BEAM ABOVE.

9'-0"

TYPICAL

PENDANT

HEIGHT

DESKS PROVIDED BY VA

INSTALLED BY CONTRACTOR

3/16" = 1'-0"A101

FIRST FLOOR PLANF4

3/16" = 1'-0"A101

FIRST FLOOR DEMOLITION PLANF1

3/16" = 1'-0"A101

FIRST FLOOR RCPF6

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll S p a c e

/2

V

A S a le m R e n o v a te

S h e ll

S p a c e

.r v t

/3

/2

:2

:1

P

M

A101

FIRST FLOOR DEMO , NEW WORK

AND REFLECTED CEILING PLAN

Renovate Shell Space

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TB JC

CONSTRUCTION

DOCUMENTS

Revisions: Date:

1/4" = 1'-0"A101

OPEN WORKSPACE SECTIOND6

N

PROJECT

NORTH

DEMOLITION NOTES

1 EXISTING CARPET TILE TO BE REMOVED IN ITS ENTIRITY.

REMOVE ADHESIVE AND PREPARE FLOORING TO RECEIVE

NEW FINISH

2 DEMOLISH STOREFRONT FRAMING, GLASS, AND OVERHEAD

BRACING TO THE EXTENT SHOWN

FLOOR FINISHES

KEY FINISH MATERIAL MANUF. ITEM NUMBER/COLOR/FINISH SIZE NOTES

CPT 1 CARPET TILE 1 FORBO FLOTEX LINEAR TILE / CIRRUS /t57007 mint 20"x20"

VB 1 6" VINYL BASE JOHNSONITE TRADITIONAL VINYL 1/8"/ TA4 GATEWAY 6"

1PH SINGLE-PHASE

3PH THREE-PHASE

4W FOUR-WIRE

A/E ARCHITECT/ENGINEER

AF AMPERE FRAME OR AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMP AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BLDG BUILDING

C CONDUIT

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CKT CIRCUIT

CLG CEILING

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

COORD COORDINATE

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DISC DISCONNECT

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DS DISCONNECT SWITCH

DWG DRAWING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

ETR EXISTING TO REMAIN

ELECTRICAL ABBREVIATIONS

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FLA FULL LOAD AMPS

FP FIRE PROTECTION

FT FEET OR FOOT

GND GROUND

G OR GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PCB POLYCHLORINATED BIPHENYL

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION

AWG AMERICAN WIRE GAUGE

KCMIL ONE-THOUSAND CIRCULAR MILS

NA NOT APPLICABLE

HD HEAT DETECTOR

NEW (HEAVY, SOLID LINE)

EXISTING TO REMAIN (LIGHT, SOLID LINE)

EXISTING TO BE REMOVED (HEAVY, DASHED LINE)

ABC

PANELBOARD MAIN CIRCUIT BREAKER TYPE, ONE-LINE

### - INDICATES BREAKER RATING

ABC - INDICATES PANEL DESIGNATION

ABC

PANELBOARD MAIN LUG TYPE, ONE-LINE

### - INDICATES BUS RATING

ABC - INDICATES PANEL DESIGNATION

JUNCTION BOX

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DOUBLE DUPLEX (QUADRAPLEX)

ELECTRICAL SYMBOLS - POWER/LIGHTING PLANS

SWITCH (# SUBSCRIPT AS INDICATED BELOW) - SEE PLANS AND SPECIFICATIONS FOR DETAILS

BLANK = SINGLE POLE a= SUBSCRIPT DEFINES FIXTURES THAT ARE CONTROLLED BY SWITCH

D = DIMMER

LV= LOW VOLTAGE - SEE BELOW FOR DETAILS

J

SYMBOL DESCRIPTION DESCRIPTION

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

NAC = BOOSTER PANEL

NAC

DESCRIPTION

TRANSFORMER, PLANT

TRANSFORMER, ONE-LINE

M

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED

LOW VOLTAGE SWITCH - SEE PLANS, SPECIFICATIONS AND WIRING DIAGRAMS FOR DETAILS

LV2Dab

S

S

SUBSCRIPT(S) INDICATE FIXTURES CONTROLLED

'D' INDICATES 0-10V DIMMING

'2' INDICATES NUMBER OF LOW VOLTAGE ZONES

'LV' INDICATES LOW VOLTAGE SWITCH

A

EXIT LIGHT, LED, WALL MOUNTED

EXIT LIGHT, LED, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS

INDICATED; SHADED QUADRANT INDICATES FACE(S) OF LUMINAIRE

LED, RECESSED, PENDANT OR SURFACE CEILING LUMINAIRE

LED, RECESSED, PENDANT OR SURFACE CEILING LIGHTING FIXTURE

SHADING INDICATES FIXTURE CONNECTED TO EMERGENCY CIRCUIT

(TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)

LED FIXTURE, RECESSED, PENDANT OR SURFACE CEILING

FIXTURE TYPE

LOWER CASE LETTER INDICATES CONTROLLING SWITCH

a

CIRCUIT NUMBER

LED, WALL MOUNTED LUMINAIRE

J WALL MOUNTED FURNITURE FEED POWER CONNECTION. '#' REPRESENTS NUMBER OF

WORKSTATIONS POWERED BY FEED.

GROUND BUS BAR, COPPER

SYMBOL SYMBOL

WALL MOUNTED JUNCTION BOXJ LPP LIGHTING POWER PACK RELAY

a

SUBSCRIPT INDICATES CONTROLLING SWITCH AND FIXTURES CONTROLLED (TYPICAL)

LPD LIGHTING POWER PACK RELAY WITH 0-10V DIMMING

LPDE EMERGENCY LIGHTING POWER PACK RELAY - UL924 COMPLIANT AND 0-10V DIMMING

METER, ONE-LINE

ELECTRICAL ONE-LINE

ALARM, SPEAKER/LIGHT, ONE ASSEMBLY. ADJUSTABLE

15CD, 30CD, 75CD UNLESS OTHERWISE NOTED

P(#)

J WALL MOUNTED FURNITURE FEED TELEPHONE/DATA CONNECTION. '#' REPRESENTS NUMBER OF

WORKSTATIONS POWERED BY FEED.

T/D(#)

WORK AREA TCO, COMBINATION TELEPHONE/DATA COMMUNICATION OUTLET - 2

DATA PORT FACE PLATE WITH 2 DATA PORTS - (1) CAT6A CABLE PER PORT.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll

S p a c e /0

V A

M C

S a le m S h e ll

S p a c e

R M

E P

F A

F P

T .r v t

/3

/2

:2 :4

P

M

E-001

ELECTRICAL LEGENDS &

SYMBOLS

RENOVATE SHELL SPACE

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TDB SDL

CONSTRUCTION

DOCUMENTS

SHEET LIST

SHEET NUMBER SHEET NAME

E-001 ELECTRICAL LEGENDS & SYMBOLS

E-002 ELECTRICAL GENERAL NOTES

E-100 FIRST FLOOR PARTIAL OVERALL

ED101 FLOOR PLAN - LIGHTING - DEMOLITION

ED102 FLOOR PLAN - ELECTRICAL EQUIPMENT - DEMOLITION

EL101 FLOOR PLAN - LIGHTING - NEW WORK

EP101 FLOOR PLAN - ELECTRICAL EQUIPMENT - NEW WORK

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL DIAGRAMS

Revisions Date

ELECTRICAL GENERAL NOTES

WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED

APPLICABLE CODES

1. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL CODE (NEC), NFPA 70 - 2023

b. NATIONAL FIRE ALARM CODE, NFPA 72 - 2022

c. LIFE SAFETY CODE, NFPA 101 – 2021

d. EMERGENCY AND STANDBY POWER SYSTEMS, NFPA 110 – 2022

e. HEALTH CARE FACILITIES CODE, NFPA 99 - 2024

2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL SAFETY CODE, ANSI C2

3. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)

4. FACILITY GUIDELINES INSTITUTE (FGI):

a. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIES

5. FEDERAL COMMUNICATION COMMISSION (FCC)

6. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

7. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

9. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

10. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)

11. ILLUMINATION ENGINEERING SOCIETY (IES)

12. ANTI-FRICTION BEARING MANUFACTURERS ASSOCIATION (AFBMA)

13. BUILDING OFFICIALS AND CODE ADMINISTRATORS INTERNATIONAL, INC. (BOCA)

14. INTERNATIONAL CODE COUNCIL (ICC):

a. INTERNATIONAL BUILDING CODE (IBC)

15. UNIFORM BUILDING CODE (UBC)

16. COMBINED ANSI/ASHRAE/IES STANDARD 90.1 – “ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL

BUILDINGS”

17. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION INSTALLATION STANDARDS (NECA)

18. AMERICANS WITH DISABILITIES ACT (ADA)

19. APPLICABLE STATE AND LOCAL CODES, AMENDMENTS, REGULATIONS, AND PRACTICES.

20. APPLICABLE REGULATORY REQUIREMENTS AND ADVISORY PRACTICES OF APPROPRIATE

a. AUTHORITIES HAVING JURISDICTION (AHJs).

21. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE OWNER.

1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP, METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT

ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL DIVISIONS AS A WHOLE.

2. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL ACCEPTANCE. THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME, PHONE NUMBER AND

ADDRESS OF AT LEAST ONE QUALIFIED SERVICE AGENCY.

3. INCLUDE ALL COSTS FOR EXCAVATION, SAW CUTTING, SURFACE RESTORATION, REPAIR OF FINISHES, ETC. THAT IS

REQUIRED IN ORDER TO MEET THE PROJECT REQUIREMENTS.

4. INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR TEMPORARY POWER. ENGINEER OF RECORD SHALL BE PROVIDED WITH ADDITIONAL COMPENSATION FROM THE CONTRACTOR WHERE SIGNED & SEALED DRAWINGS ARE REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF REQUIRED BY THE AHJ FOR THE TEMPORARY POWER.

5. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES, REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH NORTH CAROLINA STATUTES REGARDING MERCURY-CONTAINING DEVICES, AND WITH ALL DEP AND EPA APPLICABLE GUIDELINES AT THE TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN

CERTIFICATION OF ACCEPTED DISPOSAL.

6. ALL BRANCH CIRCUITS SHALL BE FURNISHED WITH A DEDICATED NEUTRAL. SHARED NEUTRALS ARE NOT ALLOWED

UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.

7. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF ELECTRICAL EQUIPMENT.

PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED, UNLESS OTHERWISE NOTED.

8. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF WORK. AVOID INTERFERENCES WITH

THE PROGRESS OF OTHER DIVISIONS/TRADES.

9. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE COMPONENTS

INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED ON PLANS AND VICE VERSA.

10. ROUTING OF CONDUIT IS DIAGRAMMATIC AND NOT INTENDED TO SHOW REQUIRED OFFSETS AND DETAILS.

COORDINATE EXACT ROUTING WITH FIELD CONDITIONS AND OTHER TRADES.

11. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR RELATED INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS PART OF THE WORK. REFER TO ARCHITECTURAL ELEVATIONS

FOR EXACT MOUNTING HEIGHT AND LOCATIONS.

12. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

13. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR

PHASING.

14. ANY TEMPORARY INTERRUPTION ON POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND SCHEDULED IN

ADVANCE.

15. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT.

CONTRACTOR IS RESPONSIBLE FOR ANY LOSSES OR DAMAGE. ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL CONDITION BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

16. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM A/E PRIOR TO BID. CONTRACTOR SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO

RELOCATE OUTLET BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.

17. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO 6' ABOVE EQUIPMENT OR STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL

APPURTENANCES IN ACCORDANCE WITH NEC.

18. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNAGE REQUIRED DURING THE

PROJECT CONSTRUCTION PHASE.

19. THE INFRASTRUCTURE FOR THE ACCESS CONTROL/ CCTV OR SECURITY ELECTRONICS SYSTEM (CONDUITS, ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE ACCESS CONTROL/CCTV OR SECURITY ELECTRONICS SYSTEM CONTRACTOR SHALL PROVIDE AND INSTALL THE WIRE AND CABLE FOR THE SYSTEM AND ALL REQUIRED EQUIPMENT. INSTALLATION OF THE CONDUITS AND ELECTRICAL BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE ACCESS CONTROL/ CCTV SYSTEM CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES, RACEWAY

LOCATIONS, SIZES AND QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.

20. THE INFRASTRUCTURE FOR THE VOICE/DATA TELECOMMUNICATIONS SYSTEM (CONDUITS, ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE TELECOMMUNICATIONS CONTRACTOR SHALL PROVIDE AND INSTALL THE WIRE AND CABLE FOR THE SYSTEM AND ALL REQUIRED EQUIPMENT AND COMPONENTS. INSTALLATION OF THE CONDUITS AND ELECTRICAL BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE TELECOMMUNICATIONS CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES, RACEWAY LOCATIONS, SIZES AND QUANTITY, CONDUIT

STUB-UPS PRIOR TO ROUGH IN.

21. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L.

LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED

WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY.

22. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, TO THE

SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER.

23. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS ACCEPTED BY THE A/E AND OWNER, THE CONTRACTOR SHALL MAKE ALL CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS. WHERE THE CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO

REQUEST COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.

24. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD DOCUMENTS SHALL BE ISSUED TO THE A/E FOR REVIEW AND THEN SUBMITTED TO THE OWNER WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL

FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.

25. OWNER FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH IN REQUIREMENTS FOR OWNER

FURNISHED EQUIPMENT PRIOR TO ROUGH IN.

26. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION, CONDUIT OR WIRING, MAKE

CHANGES IN ACCORDANCE WITH APPLICABLE CODES.

FIRE ALARM SYSTEM NOTES

FA1. ALL FIRE ALARM EQUIPMENT IS TO BE NEW, UL LISTED FOR FIRE SERVICE, AND SHALL BE COMPATIBLE WITH THE SYSTEM

BEING USED. THE EXISTING FIRE ALARM SYSTEM IS SIMPLEX 4100 ES.

FA2. ALL WIRING AND CONDUIT IS TO CONFORM TO NEC ARTICLE 760. WIRING SHALL BE UL LISTED, MINIMUM 300V TYPE FPLP

PLENUM RATED SOLID COPPER OR STANDARD COPPER WITH MAXIMUM 19 STRANDS.

FA3. LOW VOLTAGE CONDUCTORS: PROVIDE CONDUCTORS IN ACCORDANCE WITH NFPA 70 AND NFPA 72, AND AS

RECOMMENDED BY THE FIRE ALARM SYSTEM MANUFACTURER. CONDUCTORS SHALL BE COPPER, MINIMUM NO. 14 AWG, TWISTED SHIELDED PAIR.

FA4. SURVIVABILITY: A 2-HOUR RATED CABLE ASSEMBLY SHALL BE PROVIDED FOR NOTIFICATION APPLIANCE CIRCUITS AND ANY OTHER CIRCUITS NECESSARY FOR THE OPERATION OF THE NOTIFICATION APPLIANCE CIRCUITS FROM THE POINT AT WHICH THEY EXIT THE CONTROL UNIT UNTIL THE POINT THAT THEY ENTER THE NOTIFICATION ZONE THAT THEY SERVE.

FA5. ALL FIRE ALARM POWER CIRCUITS SHALL HAVE A DEDICATED 120V 20A BREAKER THAT SHALL BE RED IN COLOR AND MECHANICALLY PROTECTED (LOCKABLE IN THE "ON" POSITION), MARKED AS "FIRE ALARM CIRCUIT".

FA6. MINIMUM CANDELA RATING OF STROBES IS 15; "##" ADJACENT TO DEVICE INDICATES THE CANDELA RATING. PROVIDE SYNCHRONIZATION OF STROBES IN ALL ADJACENT AREAS WHERE STROBES ARE VISIBLE TO EACH OTHER.

FA7. WHERE A FIRE ALARM RISER IS INDICATED, IT IS DIAGRAMMATIC IN NATURE AND NOT INTENDED TO REPRESENT A COMPLETE WIRING AND DEVICE DISPLAY. ALL WIRING AND DEVICES SHALL BE IN ACCORDANCE WITH SELECTED VENDOR'S POINT-BY-POINT WIRING DIAGRAM. REFER TO FLOOR PLAN FOR DESIGN INTENT AND PROPOSED QUANTITY OF FIRE ALARM

SYSTEM COMPONENTS.

FA8. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE FIRE ALARM SYSTEM BE PROVIDED WITH ALL THE NECESSARY EQUIPMENT, WIRING, CONDUIT, AND CONTROLS, COMPLETELY COORDINATED WITH ALL DISCIPLINES. THE MINIMUM FIRE ALARM DESIGN CRITERIA IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED TO IN ACCORDANCE WITH. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE FIRE ALARM SYSTEM, IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, LOCAL AUTHORITIES AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED AT NO ADDITIONAL COST TO THE OWNER. THE FIRE ALARM CONTRACTOR SHALL CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES

BEFORE PREPARING SHOP DRAWINGS.

FA9. FIRE ALARM CONTRACTOR SHALL BE AWARE OF THE TYPE OF FINISHES, DECOR AND OCCUPANCY. COORDINATION WITH THE STAKEHOLDERS(S) SHALL BE PERFORMED BY THE FIRE ALARM CONTRACTOR FOR PLACEMENT OF FIRE ALARM

DEVICES.

FA10. FIRE ALARM SYSTEM SHALL COMPLY WITH NFPA 70 AND 72 FOR PROPER INSTALLATION PRACTICES.

FA11. FIRE ALARM PATHWAYS IN ALL AREAS SHALL BE IN 3/4" EMT, AND SHALL BE PAINTED RED. ALL FIRE ALARM WIRING SHALL

BE ROUTED THROUGH CONDUIT THAT IS STRICTLY DEDICATED FOR FIRE ALARM. NO OTHER SYSTEMS MAY UTILIZE FIRE

ALARM WIRING CONDUIT OR EMT.

FA12. ALL FIRE ALARM JUNCTION BOX AND PULL BOX COVERS SHALL BE PAINTED RED.

FA13. INCREASE BATTERY CAPACITY OF FIRE ALARM SYSTEMS TO ACCOMMODATE ADDITIONAL LOAD.

FA14. PERFORM RE-ACCEPTANCE TESTING IN ACCORDANCE WITH NFPA 72.

FA15. FIRE ALARM CIRCUITS SHALL NOT HAVE SPLICES. CIRCUITS SHALL BE EXTENDED FROM DEVICE AND APPLIANCE SCREW

TERMINALS.

ELECTRICAL DEMOLITION NOTES

D1. THE FACILITY WILL REMAIN OCCUPIED DURING RENOVATIONS.

D2. DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN DASHED LINE TYPE ARE EXISTING TO BE DEMOLISHED; DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN LIGHT SOLID LINE TYPE ARE EXISTING TO REMAIN, UNLESS OTHERWISE

NOTED.

D3. EXISTING EQUIPMENT, LIGHT FIXTURES, DEVICES SHOWN ARE BASED ON FIELD SURVEYS AND RECORD DRAWINGS PROVIDED BY THE OWNER, AND IS NOT NECESSARILY ALL INCLUSIVE IN EVERY AREA AS FAR AS EXISTING ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND DEVICES. EXISTING CIRCUITING SHOWN IS BASED ON RECORD DRAWINGS AND THE SURVEYED PANEL DIRECTORIES, WHERE THEY WERE AVAILABLE. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE CONDITIONS SHOWN ARE INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT, WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD

CONDITIONS SHALL GOVERN.

D4. WHERE EXISTING DEVICES ARE INDICATED TO REMAIN OR RELOCATED, LOCATED WITHIN THE SCOPE OF THIS PROJECT AND EXISTING CIRCUITING INFORMATION IS UNAVAILABLE, CONTRACTOR IS TO PROVIDE CIRCUIT TRACING TO IDENTIFY PANEL AND CIRCUIT DEVICES ARE CONNECTED TO AND PROVIDE THAT INFORMATION TO A/E PRIOR TO ROUTING CONDUITS AND WIRING FOR NEW DEVICES AND EQUIPMENT WITHIN THE SCOPE OF THIS PROJECT.

D5. PRIOR TO DEMOLITION, FIELD VERIFY CONDUIT AND WIRING WHICH SERVES AREAS OUTSIDE THE SCOPE OF WORK AND

PASSES THROUGH THE AREA OF WORK. MAINTAIN CONTINUITY OF SYSTEMS.

D6. WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR MUST EXTEND EXISTING CIRCUITING WHERE NECESSARY TO

MAINTAIN CONTINUITY OF CIRCUIT.

D7. COORDINATE WITH THE OWNER FOR DISPOSITION OF ELECTRICAL ITEMS TO BE DEMOLISHED. OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS SUCH AS COVERPLATES, RECEPTACLES, LIGHT FIXTURES, PANELBOARDS, TRANSFORMERS, ETC. NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS BEING REMOVED.

D8. COORDINATE EXACT AREAS, WALLS, CEILINGS, ETC. TO BE DEMOLISHED WITH ARCHITECTURAL, STRUCTURAL, PLUMBING

AND MECHANICAL DEMOLITION PLANS.

D9. WHERE EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT ARE INDICATED TO BE DEMOLISHED, REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO NEAREST JUNCTION BOX TO MAINTAIN CIRCUIT CONTINUITY OF DEVICES TO REMAIN AND EQUIPMENT TO REMAIN. WHERE PANELS ARE TO BE REMAIN, TURN BREAKER TO "OFF" POSITION

AND LABEL THE CIRCUIT AS "SPARE" ON THE PANEL DIRECTORY.

D10. ALL AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE PHASING WITH CONSTRUCTION MANAGER AND OWNER PRIOR TO DEMOLITION WHICH MAY RESULT IN INTERRUPTION OF POWER.

D11. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR EXTENT OF AREA REQUIRING DEMOLITION AND ADDITIONAL INFORMATION ON ELECTRICAL DEMOLITION WITHIN THAT AREA. DISCONNECT ELECTRICAL SERVICE TO ALL EQUIPMENT BEING REMOVED. DEMOLITION SHALL BE PHASED AS REQUIRED BY DIVISION 1, OR DIRECTED BY THE OWNER.

D12. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED OR RENOVATED AREA. CAP BOTH ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE CUT. REMOVE ALL ASSOCIATED SUPPORTS. REMOVE

WIRING BACK TO SOURCE OF VOLTAGE.

D13. ELECTRICAL DEVICES WITHIN THE AREA OF WORK., AND NOT NOTED ON THE DEMOLITION DRAWINGS, WHETHER DUE TO CONCEALMENT BY STORAGE SHELVING, CASEWORK, FURNITURE OR FOR OTHER REASONS, ARE TO BE REMOVED AS

REQUIRED, UNLESS SHOWN AS EXISTING TO REMAIN.

D14. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES, UNLESS OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE DONE TO LOGICAL EDGES OF SURFACES AFFECTED AND SHALL MATCH IMMEDIATE ADJACENT AREAS IN CONSTRUCTION, MATERIAL, FIRE RATING, FINISH AND COLOR.

D15. PROVIDE BLANK COVERPLATES WHERE DEVICES ARE BEING REMOVED FROM EXISTING WALLS TO REMAIN. MATCH COLOR

OF NEW ADJACENT DEVICE COVERPLATES.

D16. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN

CLARIFICATIONS FROM ARCHITECT/ENGINEER IF NECESSARY.

D17. COORDINATE SERVICE INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD, AND UTILITY COMPANY, WHERE APPLICABLE, AND DO NOT INTERRUPT POWER WITHOUT WRITTEN PERMISSION. PROVIDE A MINIMUM OF ONE

WEEK'S WRITTEN NOTIFICATION WHEN POWER IS DESIRED TO BE INTERRUPTED.

D18. EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE CONNECTED

TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.

D19. INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS DIAGRAMMATIC IN NATURE.

FIELD VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ALL ELECTRICAL ITEMS SCHEDULED TO BE DEMOLISHED AND

PERFORM THE WORK AS INTENDED AND DEPICTED ON THE DRAWINGS.

D20. UPDATE ALL EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS NECESSARY TO REFLECT FINAL AS-

BUILT CONDITIONS AT THE END OF CONSTRUCTION.

D21. STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED AREA. NOTIFY OWNER

WHEN ITEMS ARE READY TO BE REMOVED.

D22. COORDINATE ANY ALTERATION AND CHANGES TO THE ELECTRICAL SERVICE WITH THE LOCAL UTILITY COMPANY AND THE

OWNER PRIOR TO COMMENCEMENT OF WORK.

D23. SCHEDULE ALL POWER INTERRUPTION WITH OWNER FOR EXACT DATE, TIME AND DURATION. PROVIDE A MINIMUM OF 72 HOURS NOTICE PRIOR TO DISCONNECTING ANY POWER TO ANY PORTION OF THE BUILDING, AND MAKE ARRANGEMENTS TO MAINTAIN POWER TO ALL CRITICAL EQUIPMENT AS NEEDED AND REQUESTED BY THE OWNER PRIOR TO

COMMENCEMENT OF WORK.

D24. PROVIDE ANY NECESSARY REPROGRAMMING OF EXISTING BUILDING FIRE ALARM SYSTEMS TO DISABLE FIRE ALARM DEVICES THAT ARE BEING DISCONNECTED AND REMOVED, AND FOR ANY NEW DEVICES THAT ARE ADDED, AS PART OF

BID PRICE.

D25. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN THE PROJECT AREA. IT IS INTENDED TO PROVIDE A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN SHALL BE BROUGHT TO THE ATTENTION OF THE A/E. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT.

D26. ALL CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER SPACES. ENSURE THAT ALL CONDUITS, NEW OR EXISTING WITHIN THE PROJECT AREA ARE PROPERLY SUPPORTED IN ACCORDANCE WITH THE NEC. ANY EXISTING CONDUIT IS INSTALLED BELOW THE HEIGHT OF THE NEW CEILING SHALL BE RELOCATED TO ABOVE THE NEW CEILING

HEIGHT.

D27. REMOVE ALL ABANDONED WIRING AND CONDUIT THAT IS WITHIN THE PROJECT AREA PRIOR TO THE END OF

CONSTRUCTION.

D28. UPDATE PANELBOARD DIRECTORIES WHICH ARE MODIFIED BY THIS PROJECT.

D29. REPAIR DISTURBED AREAS TO MATCH EXISTING CONDITIONS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll

S p a c e /0

V A

M C

S a le m S h e ll

S p a c e

R M

E P

F A

F P

T .r v t

/3

/2

:2 :4

P

M

E-002

ELECTRICAL GENERAL NOTES RENOVATE SHELL SPACE

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TDB SDL

CONSTRUCTION

DOCUMENTS

OPEN

WORKSPACE

IC-129R

OFFICE

IC-129Q

OFFICE

IC-129L

CORRIDOR

IC-129K

AREA OF WORK

IT ROOM

FIRE

ALARM

CONTROL

PANEL

1LK

1HG

IRM

IB-121

LOUNGE

ID-166

BIO-

HAZARD

IB-115

TOILET

IC-114

STORAGE

IB-114

ID-175

IB-104

ID-152

IB-106

ID-170

ON CALL

IB-123

ELECTRICAL

IB-122 OFFICE

IB-117

STORAGE

IB-109TOILET

123A

IB-111

ID-172

MEN'S

TOILET

IB-124

WOMEN'S

TOILET

IB-125

CLEAN

LINEN

IB-105

MED RM

IB-107

SUPPLY

IB-102

HOUSE

KEEPING

IB-149

OFFICE

IB-101

TOILET

IB-104A

WAITING

ROOM

IC-110

OFFICE

IC-115

HOUSE

KEEPING

IC-105

IC-123

IC-109J

OR-7

IC-145

OFFICE

IC-120

IRM

IC-12

WORK RM

IC-122

OFFICE

IC-118

IC-125A

IC-125A

ANEST.

OFFICE

IC-116

REST RM

IC-106B

ISOLATION

RM

IC-117

ANTE RM

IC-119

OR-8

IC-106

STORAGE

IC-106A

OFFICE

IC-108

OFFICE

IC-109A

OFFICE

IC-109

CORRIDOR

IC-131

OR-1

IC-126

NURSE

STATION

ID-180

PACU

IC-128D

NURSE

STATION

IC-128O

LOUNGE

IB-104B

IB-108

ID-171

IB-113

ID-174

IB-112

ID-173

IB-116A

ID-176

ADMIN

OFFICE

IB-100

MECHANICAL

IB-120

CORRIDOR

ID-153

SUPPLY

IB-118

ISOLATION

RM

IB-116

IC-125

IC-128I

OFFICE

IC-124

CORRIDOR

IC-127

BIO-

HAZARD

IC-111

BREAK RM

IC-113

STORAGE

IC-112

RECOVERY

CI-13A

CORRIDOR

IC-130

CONFERENCE

IC-129J

OFFICE

IC-129H

TOILET

IC-129G

TOILET

IC-129F

EQUIP

STORAGE

IC-128A

OFFICE

IC-129E

ELEVATOR

ELEVATOR

ELEVATOR

Room

CORRIDOR

CHASE-1

0-1

CHASE-2

0-2

HOUSE

KEEPING

IC-101

HOUSE

KEEPING

IC-102

Room

Room

ELEVATOR

ELEVATOR

ELECTRICAL

CLOSET

IC-100

ELEVATOR

Room

LOCKER

IC-107A

OFFICE

CI-16

TOILET

IC-107B

Room

CORRIDOR

NAC

NAC

PROJECT AREA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll

S p a c e /0

V A

M C

S a le m S h e ll

S p a c e

R M

E P

F A

F P

T .r v t

/3

/2

:2 :4

P

M

E-100

FIRST FLOOR PARTIAL OVERALL RENOVATE SHELL SPACE

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TDB SDL

CONSTRUCTION

DOCUMENTS

DRAWING NOTES:

1. NO NEW WORK INDICATED ON THIS SHEET. PARTIAL OVERALL FLOOR PLAN INCLUDED TO SHOW

AREA OF WORK AND EXISTING SYSTEM EQUIPMENT LOCATIONS.

3/32" = 1'-0"

FIRST FLOOR PARTIAL OVERALL

NN

0 8' 16' 24' 32'

3/32" = 1'-0"

N.T.S.

KEY PLAN

J J

WORKSPACE

IC-129R

OFFICE

IC-129Q

OFFICE

IC-129L

CORRIDOR

IC-129K

1LK

1HG

S

EXISTING TO REMAIN NURSE CALL DOME LIGHT

EXISTING TO REMAIN NURSE CALL DOME LIGHT

111111

1 1 1 1 1 1

TRANSFORMER

1LK

EQUIP

STORAGE

IC-128A

TOILET

IC-129F

TOILET

IC-129G

OFFICE

IC-129H

CONFERENCE

IC-129J

MECHANICAL

IB-120

CORRIDOR

IC-127

OFFICE

IC-129E

PROJECT AREA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s /2

V

A S a le m R e n o v a te

S h e ll

S p a c e /0

V A

M C

S a le m S h e ll

S p a c e

R M

E P

F A

F P

T .r v t

/3

/2

:2 :4

P

M

ED101

FLOOR PLAN - LIGHTING -

DEMOLITION

RENOVATE SHELL SPACE

1970 ROANOKE BLVD

SALEM, VA 24153

658-22-104

03 APRIL 2024 TDB SDL

CONSTRUCTION

DOCUMENTS

CODED NOTES:

DRAWING NOTES:

1. CONTRACTOR TO FIELD VERIFY EXACT QUANTITIES AND LOCATIONS OF DEVICES PRIOR TO

DEMOLITION. DEVICE LOCATIONS INDICATED ON THIS PLAN ARE APPROXIMATE.

EXISTING LIGHT FIXTURES ARE TO REMAIN AND BE PROTECTED DURING CONSTRUCTION.

NO WORK IN THIS AREA, UNLESS OTHERWISE NOTED.

1/4" = 1'-0"

FIRST FLOOR PLAN - LIGHTING - DEMOLITION

NN

0 2' 4' 8' 12'

1/4" = 1'-0"

N.T.S.

KEY PLAN

J

WORKSPACE

IC-129R

OFFICE

IC-129Q

OFFICE

IC-129L

CORRIDOR

IC-129K

1LK

1HG

EXISTING WATER COOLER

TRANSFORMER

1LK

CONFERENCE

IC-129J

OFFICE

IC-129H

TOILET

IC-129G

TOILET

IC-129F

EQUIP

STORAGE

IC-128A

OFF…