DRAWINGS OR 2.pdf
PDF 2 MB Posted
- Attached to
- FAYETTEVILLE | Z2DA | CON | 564-23-502 | UPGRADE ELECTRICAL POWER OR 1-4 | AMENDMENT 0001
- Solicitation number
- 36C25623R0104
About this file
This is an amendment to a federal solicitation seeking proposals to upgrade the electrical power in operating rooms 1 through 4 at the Veterans Affairs Medical Center in Fayetteville, Arkansas. The amendment provides additional time for offerors to submit proposals, extending the response deadline from April 3rd to April 17th, 2023. The work includes replacing existing isolation panels and adding new panels to meet current electrical codes. The solicitation is designated for small businesses under the Veterans First Contracting Program set-aside. The Department of Veterans Affairs is the contracting agency.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C O
LL
EG
E
AV
E
E. HUNTSVILLE
ROAD
CAMPUS MAP
PROJECT DESCRIPTION AND GENERAL
REQUIREMENTS
LOCATION MAP
LIST OF DRAWINGS
FAYETTEVILLE, AR
ARKANSAS
FAYETTEVILLE,
AR
1100 N. COLLEGE AVE.
FAYETTEVILLE, AR
PROJECT
LOCATION
UPGRADE ELECTRICAL POWER IN OR-2 (B-1)
PROJECT 564-23-501 VHSO FAYETTEVILLE, AR 72703
VETERANS HEALTH ADMINISTRATION
GENERAL
1 of 10 GI001 COVER SHEET 2 of 10 GI002 GENERAL NOTES, ABBREVIATIONS, AND STANDARD SYMBOLS 3 of 10 GC101 ENLARGED ICRA FLOOR PLAN - THIRD FLOOR
ARCHITECTURAL
4 of 10 AE100 OVERALL FLOOR PLAN - THIRD FLOOR 5 of 10 AE101 ENLARGED FLOOR PLAN - THIRD FLOOR
ELECTRICAL
6 of 10 E001 ELECTRICAL LEGEND 7 of 10 E103 OVERALL ELECTRICAL PLAN - THIRD FLOOR 8 of 10 E200 ENLARGED ELECTRICAL PLANS 9 of 10 E300 ELECTRICAL SCHEDULES AND RISER 10 of 10 E301 PANEL SCHEDULES
ETERANS EALTH ARE YSTEMV H C S
OF THE ZARKSO
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
03/31/2023
GI001
COVER SHEET
OR #2 - 564-23-501
1100 NORTH COLLEGE AVENUE
FAYETTEVILLE, AR
THE CONTRACTOR MUST FURNISH ALL MANAGEMENT, SUPERVISION, LABOR, MATERIAL, EQUIPMENT, TOOLS, SUPPLIES, CONSUMABLES, PARTS, AND RELATED SERVICES, REQUIRED FOR THE UPGRADE OF THE ELECTRICAL SYSTEM IN ORS 2.
REMOVE EXISTING ISOLATED POWER SYSTEM PANEL IPU-3. PANEL MUST BE OFFERED TO COR FOR VA USE AS SPARE. IF COR DOES NOT WANT PANEL, THEN IT IS THE RESPONSIBILITY OF CONTRACTOR TO PROPERLY DISPOSE OF PANEL OFF SITE. FURNISH AND INSTALL NEW 120-VOLT ISOLATED POWER SYSTEM PANEL IPU, SQUARE D, OR APPROVED EQUAL, WITH INTEGRAL LINE ISOLATION MONITOR IN EXISTING LOCATION INCLUDING: 1. SMIB - ISOLATED POWER PANEL INTERIOR BOLT-ON W/LIM, 2. SXMK05BASC - ISOLATED POWER PANEL TRANSFORMER/ BREAKER,
3. ST6826R- ISOLATED POWER PANEL TRIM STANDARD, 4. SB662408F - ISOLATED PANEL BACKBOX 8" DEEP, 5. 5 KVA TRANSFORMER WITH 16 QOB220 BREAKERS. CONTRACTOR MUST ENLARGE EXISTING OPENING IN WALL TO ACCEPT FLUSH MOUNTED NEW PANEL AND REPAIR FINISHED AS NEEDED. CONTRACTOR MUST RECONNECT PANEL TO EXISTING FEEDER AND RECEPTACLES. CONTRACTOR MUST FURNISH
CERTIFICATION CERTIFICATE.
FURNISH AND INSTALL NEW 120-VOLT ISOLATED POWER SYSTEM PANEL IPU-10, SQUARE D, OR APPROVED EQUAL, WITH INTEGRAL LINE ISOLATION MONITOR IN EXISTING LOCATION INCLUDING: 1. SMIB - ISOLATED POWER PANEL INTERIOR BOLT-ON W/LIM, 2. SXMK05BASC - ISOLATED POWER PANEL TRANSFORMER/ BREAKER, 3. ST6826R - ISOLATED POWER PANEL TRIM STANDARD, 4. SB662408F - ISOLATED PANEL BACKBOX 8" DEEP, 5. 5 KVA TRANSFORMER WITH 16 QOB220 BREAKERS. FURNISH, INSTALL, AND CONNECT PANEL FEEDER TO ISOLATION PANEL WITH NEW 30-AMP 2 POLE SQUARE D QOB BREAKER FROM PANEL 13S, ROOM E302. FEEDER MUST BE MINIMUM SIZE #10 COPPER WITH #10 GROUND IN ¾" EMT. CONTRACTOR MUST CUT OPENING IN WALL TO FLUSH MOUNT NEW PANEL AND REPAIR FINISHES AS REQUIRED.
FURNISH, INSTALL, AND CONNECT POWER PANEL WITH FOUR RED DUPLEX HOSPITAL GRADE RECEPTACLES, FOUR GROUNDING CONNECTIONS, AND #304 STAINLESS STEEL WITH A #4 BRUSHED FINISH FRONT TRIM, SQUARE D MODEL SGPPMF4DR4 AND SB120804, OR APPROVED EQUAL, IN LOCATION AS SHOWN ON DRAWING 3. MUST USE COPPER CONDUCTORS WITH XHHW INSULATION AND A DIALECTIC CONSTANT LESS THAN 3.5 AND INSTALLED AS REQUIRED BY THE LATEST NEC CODE FOR THE RECEPTACLE FEEDERS. CONTRACTOR MUST
FURNISH CERTIFICATION CERTIFICATE.
FURNISH AND INSTALL NEW 208-VOLT ISOLATED POWER SYSTEM PANEL IPU-9, SQUARE D, OR APPROVED EQUAL, WITH INTEGRAL LINE ISOLATION MONITOR IN LOCATION SHOWN ON DRAWING 3 INCLUDING: 1. SMIB - ISOLATED POWER PANEL INTERIOR BOLT-ON W/LIM, 2.
SXMK07BBSC - ISOLATED POWER PANEL TRANSFORMER I BREAKER, 3. ST6826R - ISOLATED POWER PANEL TRIM STANDARD, 4. SB662408F - ISOLATED PANEL BACKBOX 8" DEEP, 5. 7.5 KVA TRANSFORMER WITH 8 QOB220 AND 8 QOB230 BREAKERS. FURNISH, INSTALL, AND CONNECT PANEL FEEDER TO ISOLATION PANEL WITH NEW 60-AMP 2 POLE SQUARE D QOB BREAKER FROM PANEL 13SE ROOM E302. FEEDER MUST BE MINIMUM SIZE #6 COPPER WITH #10 GROUND IN 1" EMT. CONTRACTOR MUST CUT OPENING IN WALL TO FLUSH MOUNT NEW PANEL AND REPAIR FINISHES AS REQUIRED. FURNISH, INSTALL, AND CONNECT TWO 30- AMP TWIST LOCK 3 PRONG NEMA L6-30R FLUSH MOUNTED RECEPTACLES EACH ON THEIR DEDICATED BREAKER WITH STAINLESS STEEL COVER PLATES IN LOCATIONS AS SHOWN ON DRAWING 3. MUST USE COPPER CONDUCTORS WITH XHHW INSULATION AND A DIALECTIC CONSTANT LESS THAN 3.5 AND INSTALLED AS REQUIRED BY THE LATEST NEC CODE
FOR THE RECEPTACLE FEEDERS. CONTRACTOR MUST FURNISH CERTIFICATION CERTIFICATE.
A. DEMOLISH EXISTING WALL IN AREAS LOCATED ON PLANS TO FACILITATE INSTALLATION WALL BUMP OUTS TO FACILITATE
INSTALLATION OF NEW IPU PANELS AT LOCATIONS INDICATED ON PLANS.
B.INSTALL AND FINISH WALL BUMP OUTS AT LOCATIONS INDICATED ON PLANS TO FACILITATE IPU PANEL INSTALLATION.
1. INSTALL 2 X 6” METAL STUDS AND GYPSUM WALL AS INDICATED ON PLANS.
2. INSTALL SOLID SURFACE PANELS TO MATCH EXISTING MATERIAL DIMENSIONS AND FINISH. INSTALL IN ACCORDANCE WITH
MANUFACTURERS INSTALLATION INSTRUCTIONS.
3. SALVAGE EXISTING SHEET VINYL FLOORING, MODIFY TO FIT NEW BUMP OUTS, AND FINISH TO MATCH EXISTING BASE PROFILE
AND SEAMLESS CONSTRUCTION.
a) IF EXISTING FLOORING IS NOT ABLE TO BE SALVAGED; MATCHING NEW FLOORING MUST BE PROVIDED, INSTALLED, AND JOINED WITH EXISTING FLOORING A MINIMUM OF 12” AWAY FROM BASE AND FINISHED TO MATCH EXISTING BASE PROFILE AND SEAMLESS CONSTRUCTION. INSTALL IN ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS.
4. FINISH GYPSUM WALLS TO MATCH EXISTING WALL FINISH, TEXTURE, AND COLOR.
NO DATE REVISION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text e85
AutoCAD SHX Text
AutoCAD SHX Text Garage
AutoCAD SHX Text Main Hospital 1
AutoCAD SHX Text
AutoCAD SHX Text Arkansas Veterans Home
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WOODSLEY AVE.
AutoCAD SHX Text
NORTH COLLEGE AVE.
AutoCAD SHX Text
WEST NORTH ST.
AutoCAD SHX Text Parking
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
NW
AutoCAD SHX Text
SW
AutoCAD SHX Text
NE
AutoCAD SHX Text
SE
AutoCAD SHX Text S
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
NW
AutoCAD SHX Text
SW
AutoCAD SHX Text
NE
AutoCAD SHX Text
SE
AutoCAD SHX Text S
AutoCAD SHX Text W
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BUS
AutoCAD SHX Text
BUS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LITTLE ROCK
AutoCAD SHX Text
DUMAS
AutoCAD SHX Text
PINE BLUFF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
NW
AutoCAD SHX Text
SW
AutoCAD SHX Text
NE
AutoCAD SHX Text
SE
AutoCAD SHX Text S
AutoCAD SHX Text W
SHIPPING
REF:1A123
ROOM NAME
ROOM NUMBER
REFERENCE ROOM NUMBER:
INDICATES ROOM TO REFERENCE
FOR TYPICAL MEDICAL EQUIPMENT
LAYOUT, GENERAL ANNOTATION
AND DIMENSIONS UON.
INTERIOR ELEVATION
REFERENCE
SPOT ELEVATION
CENTERLINE
EL: +10'-0"
PARTITION TYPE TAGXXXXX
BREAK, STRAIGHT (SEE SECTION
INDICATORS, BUILDING, WITH
BREAK STANDARDS)
DETAIL INDICATOR
DETAIL INDICATOR
DETAIL INDICATOR FOR
SMALL CONDITIONS
DRAWING BLOCK
TITLE, TYPICAL
ELEVATION INDICATOR, EXTERIORA-201
A4
A2 A-202
A
BC
D
A-201 A4
A-512 D2
A-512 D2
A-512 D2
COLUMN GRID
A4 A-201
BUILDING SECTION
INDICATOR
MARK STUD SIZE OVERALL THK. "R" RATING FIRE TEST STC RATING
REFER TO PARTITION TAG AND
PARTITION NOTES FOR REQD.
INSULATION
ONE LAYER OF 5 8" GWB EACH SIDE
ON METAL STUDS
HOLD BOTTOM OF GWB 12" OFF FINISH FLOOR.
NO EXCEPTIONS.
REFER TO WALL DETAIL SHEET AND PARTITION NOTES
FOR HEAD DETAILS
PARTITION TAGS ARE READ LEFT TO RIGHT:
THE FIRST CHARACTER INDICATES WHICH PARTITION / BARRIER TYPE TO REFERENCE FOR
CONSTRUCTION.
THE SECOND CHARACTER INDICATES A REFERENCE TO THE STRUCTURAL CORE THICKNESS
(STUD OR CMU).
THE THIRD CHARACTER INDICATES:
"A" - ACOUSTICAL PARTITION
"R" - FIRE RATED
"S" - SMOKE RESISTANT PARTITION (UNRATED)
"T" - FIRE RATED / ACOUSTICAL BARRIER
"V" - FIRE RATED / SMOKE BARRIER
"W" - ACOUSTICAL / SMOKE RESISTANT PARTITION
"Z" - FIRE RATED / SMOKE / ACOUSTICAL BARRIER
EXAMPLE:
A TAG OF C3T INDICATES A 4-7 8" 1 HOUR RATED BARRIER WITH ACOUSTICAL INSULATION.
PLAN
SILL
PARTITION TYPE - C
PARTITION TAG NOTES:
C1
C2
C3
C4
C6
C8
1 5/8"
2 1/2"
3 5/8"
6"
8"
2 7/8"
3 3/4"
4 7/8"
5 1/4"
7 1/4"
9 1/4"
4"
1 HR
1 HR
1 HR
1 HR
U419 47
U419 47
U419 47
U419 47
GENERAL PROJECT NOTES
GENERAL FLOOR PLAN NOTES
1. REFER TO GENERAL REQUIREMENTS OF THE PROJECT SPECIFICATIONS FOR REQUIREMENTS RELATED TO WORK RESTRICTIONS, NOISE CONTROL, SECURITY, LIFE SAFETY, INFECTION CONTROL RISK ASSESSMENT.
2. REFER TO TITLE SHEET FOR COORDINATION DRAWING REQUIREMENTS.
3. THE EXISTING CONDITIONS AND DEMOLITION WORK INDICATED IS INTENDED TO SHOW THE GENERAL
SCOPE OF THE WORK. THE CONTRACTOR IS TO STUDY THE COMPLETE SET OF DOCUMENTS AND
PERFORM ANY AND ALL DEMOLITION AND NEW CONSTRUCTION REQUIRED TO COMPLETE THE WORK SHOWN. VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS AND REPORT ANY DISCREPANCIES IN
CONDITIONS TO THE COR BEFORE BEGINNING OR CONTINUING WORK.
4. AT PROJECT COMPLETION, THE GENERAL CONTRACTOR SHALL PROVIDE TO THE COR AN “AS BUILT DRAWINGS” FOR THE WORK. REFER TO GENERAL REQUIREMENTS SECTION OF THE SPECIFICATIONS.
5. VERIFY AND ASCERTAIN THE LOCATION, DEPTH, DIRECTION, SIZE OF ANY AND ALL EXISTING UTILITIES IN THE GENERAL VICINITY OF THE WORK AREA. IT SHALL BE THE GENERAL CONTRACTOR’S RESPONSIBILITY TO REPAIR ANY UTILITY DISRUPTED, BROKEN, OR OTHERWISE RENDERED NON FUNCTIONAL DUE TO THE WORK PERFORMED AT NO ADDITIONAL COST TO THE VETERANS AFFAIRS DURING THIS COURSE OF WORK. THE GENERAL CONTRACTOR SHALL IDENTIFY ANY NON-FUNCTIONING UTILITY/SYSTEM, PRIOR TO THE START OF WORK TO THE COR. IDENTIFICATION OF SUCH AFTER THE START OF WORK SHALL BE DEEMED AS DISTURBED/DAMAGED BY THE GENERAL CONTRACTOR AND SHALL BE REPAIRED AT THE
EXPENSE OF THE GENERAL CONTRACTOR.
6. THE GENERAL CONTRACTOR SHALL PROPERLY SUPPORT ANY UTILITY ENCOUNTERED IN THE COURSE OF
THIS WORK.
7. THE GENERAL CONTRACTOR SHALL PROVIDE STORAGE FOR MATERIALS. MATERIALS SHALL NOT BE
STORED IN DEPARTMENT OF VETERANS AFFAIRS BUILDINGS, UNLESS AGREED TO BY VA.
8. COORDINATE MATERIAL STAGING AREAS WITH THE COR.
9' THE CONTRACTOR SHALL NOT LEAVE THE WORK AREA UNATTENDED FOR ANY REASON, UNLESS SAFETY
PARTITIONS, SAFETY FENCING ARE INSTALLED AND SECURED.
10. THE GENERAL CONTRACTOR IS ADVISED THAT ANY RIGGING SHALL BE PERFORMED BY PROFESSIONAL
RIGGERS AT THE EXPENSE OF THE GENERAL CONTRACTOR.
11. CONTRACTOR SHALL HAVE REPRESENTATIVE ON SITE AT ALL TIMES DURING CONSTRUCTION ACTIVITIES.
12. REFER TO SPECIFICATIONS FOR GENERAL REQUIREMENTS OF THE CONTRACT.
13. INFECTION CONTROL, SAFETY AND PHASING: VERIFY REQUIREMENTS RELATED TO INFECTION CONTROL, DUST MITIGATION, SAFETY AND RISK ASSESSMENT. CONTRACTOR TO DEVELOP AND PUBLISH WORK PLAN ADDRESSING INFECTION CONTROL, SAFETY, AND PHASING FOR APPROVAL BY COR PRIOR TO BEGINNING THEIR WORK. PLAN TO INCLUDE MEANS AND METHODS OF DEBRIS STAGING AND REMOVAL, BOTH INTERNALLY AND EXTERNALLY. INFECTION CONTROL PLAN TO INCLUDE TEMPORARY DUST AND DEBRIS
BARRIERS AND VESTIBULES AROUND PROJECT WORK AREAS. TEMPORARY BARRIERS ARE NOT TO
RESTRICT REQUIRED MEANS OF EGRESS PATHS AND WIDTHS.
14. CONTRACTOR SHALL PROVIDE EGRESS SIGNAGE AS REQUIRED BY THE VA COR.
15. ALL PENETRATIONS THROUGH RATED FLOOR/CEILING ASSEMBLIES AND THROUGH FIRE RATED WALL AND
SMOKE BARRIER ASSEMBLIES - THOSE CREATED BY REMOVAL OF DEMOLISHED ITEMS UNDER THIS CONTRACT AND THOSE DISCOVERED DURING CONSTRUCTION UNDER THIS CONTRACT AS A RESULT OF PREVIOUS WORK AND THOSE CREATED BY NEW WORK UNDER THIS CONTRACT - MUST BE SEALED AS PART OF THIS CONTRACT. ALL RATED SEPARATIONS MUST MEET CURRENT CODE REQUIREMENTS.
16. PROTECT EXISTING HORIZONTAL AND VERTICAL FIREPROOFING AND FIRE STOPPING DURING PROJECT.
ONCE DEMOLITION IS COMPLETE, CONTRACTOR SHALL REPAIR ALL DAMAGED FIREPROOFING AND RESTORE MISSING FIREPROOFING, WHETHER A RESULT OF DEMOLITION OPERATIONS OR NOT, TO MEET REQUIRED RATING(S). SEE SHEET GI003 FOR APPLICABLE UL DESIGNS FOR BASIS OF DESIGN.
1. PARTITION TYPES AS NOTED BY THE SYMBOL CONTINUE BETWEEN ROOM/SPACE
CORNERS OR ANY INTERSECTING PARTITION.
2. DIFFERING PARTITION TYPES SHALL ALIGN SO THAT WALL PLANES CONTINUE
UNBROKEN WITHIN/ACROSS ROOMS AND/OR SPACES.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS NOTED AS “CLR", "CLEAR” OR “MIN".
DIMENSIONS NOTED AS “HOLD” ARE CRITICAL TO COORDINATE OTHER WORK (E.G.
CEILING GRIDS, LIGHTING, FINISHES).
4. CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO INITIATING CONSTRUCTION
AND REPORT DISCREPANCIES TO COR PRIOR TO COMMENCING WORK.
5. CONTRACTOR SHALL PROVIDE ALL BLOCKING REQUIRED TO ANCHOR ALL WALL AND
CLG MOUNTED ITEMS, INCLUDING BUT NOT LIMITED TO EQUIPMENT BLOCKING
REQUIREMENT SCHEDULE ON SHEET QH601.
6. FIRE STOPPING SYSTEMS – REFER TO SPEC SECTION 07 84 00 FOR INFO REGARDING
PENETRATIONS OF ALL RATED ASSEMBLIES (BOTH SINGLE AND DOUBLE MEMBRANE
PENETRATIONS) INCLUDING BUT NOT LIMITED TO PENETRATIONS FOR DUCTWORK,
CONDUIT, PIPING AND SUPPORT FOR WALL MOUNTED EQUIPMENT, CABINETS AND
COUNTERTOPS.
GENERAL DEMOLITION NOTES
1. THE EXISTING CONDITIONS AND DEMOLITION WORK INDICATED IS INTENDED TO SHOW THE GENERAL
SCOPE OF THE WORK. THE CONTRACTOR IS TO STUDY THE COMPLETE SET OF DOCUMENTS AND
PERFORM ANY AND ALL DEMOLITION AND NEW CONSTRUCTION REQUIRED TO COMPLETE THE WORK SHOWN. VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS AND REPORT ANY DISCREPENCIES IN
CONDITIONS TO THE COR BEFORE BEGINNING OR CONTINUING WORK.
2. ALL DEMOLITION WORK SHALL BE PERFORMED WITH "DUE CARE AND DILIGENCE" SO AS TO PREVENT THE
ARBITRARY DESTRUCTION OR INTERRUPTION OF CONCEALED UTILITIES WHICH COULD NOT BE
PREDETERMINED UNTIL DEMOLITION WAS STARTED. ALL SUCH DISCOVERIES OF UTILITIES DURING THE DEMOLITION PROCESS WHICH ARE IN A LOCATION DIFFERENT FROM FLOOR TO FLOOR, ETC., OR ARE
UNIDENTIFIED SHALL BE REPORTED TO THE COR BEFORE REMOVAL FOR FINAL DISPOSITION.
3. REMOVE ALL CONSTRUCTION DESIGNATED TO BE REMOVED AND CLEAR TO RECEIVE NEW WORK AS
HEREIN INDICATED.
4. REMOVE PORTIONS OF EXISTING CONSTRUCTION AS DRAWN AND PATCH TO MATCH ADJACENT
CONSTRUCTION.
5. WHEREVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE REQUIRED TO BE REMOVED, SUCH REMOVAL SHALL INCLUDE ALL ANCHORS, HANGARS, BRACING, FOUNDATION, ETC. AFTER REMOVAL, AFFECTED CONSTRUCTION AND SURFACES, SUCH AS FLOORS, WALLS, BASES, AND CEILINGS, SHALL BE FINISHED TO
MATCH ADJACENT SURFACES UNLESS OTHERWISE NOTED.
6. NEW WORK AS A RESULT OF PATCHING SHALL ALIGN WITH AND MATCH EXISTING WORK EXCEPT WHERE
OTHERWISE DIMENSIONED OR DETAILED.
7. ANY EXISTING CONDITIONS WHICH ARE INCONSISTENT WITH CONTRACT DRAWINGS RELEVANT TO THIS
CONTRACT SHALL BE REPORTED TO THE COR.
8. WHERE DEMOLITION OR RELATED WORK LEAVES FLOOR SURFACES WITH IMPERFECTIONS OR NOT LEVEL
TO TOLERANCES SPECIFIED FOR NEW WORK, PROVIDE SELF-LEVELING UNDERLAYMENT.
9. WHERE DEMOLITION WORK UNCOVERS OR LEAVES OPENINGS IN PARTITIONS OR INCOMPLETE
PARTITIONS, EXTEND, RESTORE, AND/OR CLOSE OPENING IN PARTITION AS INDICATED AND/OR AS REQUIRED TO MAINTAIN FIRE RATINGS. MATCH EXISTING CONSTRUCTION, U.N.O., WITHIN THE LIMITS AND TOLERANCES FOR MATERIALS AS SPECIFIED OR RECOMMENDED BY THE MANUFACTURER. REFINISH
SURFACES TO ALIGN FLUSH WITH EXISTING.
10. WHERE DEMOLITION WORK OR RELOCATION OF EXISTING ITEMS LEAVES UNFINISHED SURFACES AND/OR SUBSTRATES, CUT AND PATCH AS REQUIRED TO RESTORE SUBSTRATE AND/OR FINISH MATERIAL EVEN
AND FLUSH WITH ADJOINING SURFACES. TEXTURE AND REFINISH TO MATCH EXISTING U.N.O.
11. CONTRACTOR SHALL DISPOSE OF ALL ITEMS PER SPECIFICATIONS. OWNER RESERVES THE RIGHT TO SELECT SPECIFIC ITEMS FOR SALVAGE. THESE ITEMS SHALL BE IDENTIFIED DURING A PRE-CONSTRUCTION
WALK-THROUGH.
12. WALK-OFF MATS, THE CONSTRUCTION BARRIER, AND IN PHASE I, NEGATIVE PRESSURE BY HEPA
FILTRATION SHALL BE IN PLACE PRIOR TO START DEMOLITION.
13. ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO MATCH ADJACENT FINISH. PREPARE SURFACES TO RECEIVE NEW
FINISH(S).
14. DISTURBANCE OF EXISTING MATERIALS ARE THE RESPONSIBILITY OF THE CONTRACTOR WITH REFERENCE TO PROPER LEGAL DISPOSAL, LEGAL ABATEMENT, PATCHING AND FINISHING. ALL DISTURBED AREAS AND
MATERIALS SHALL MATCH EXISTING CONDITIONS.
15. COORDINATE WITH M/E/P DRAWINGS FOR ADDITIONAL DEMOLITION IN FLOORS, WALLS AND ROOFS & RELATED ITEMS AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION OR UTILITIES ON THESE FLOORS
OR RELATED ADJACENT FLOORS. PATCH/REPAIR BY EACH RESPECTIVE DISCIPLINE.
COORDINATE DEMOLITION WITH OTHER DISCIPLINES. HOLES/PENETRATIONS IN RATED WALLS CREATED WHEN DEMOLITION OCCURS ARE TO BE FILLED TO MATCH THE EXISTING RATED CONDITION OR BETTER.
16. WHERE TILE FLOORING OR TERRAZO FLOOR AND BASE ARE REMOVED, PROVIDE FLOOR LEVELING AS REQUIRED TO CREATE A LEVEL FLOOR SURFACE WITH THE FLOORS THAT ARE TO REMAIN. PREPARE NEW
SURFACE TO RECEIVE NEW FINISHES.
17. WHERE EXISTING WALL IS REMOVED, PROVIDE FLOOR LEVELING AS REQUIRED TO CREATE A LEVEL FLOOR SURFACE WITH THE FLOOR LEVELS AT EACH SIDE OF THE DEMO-ED WALL LOCATION. PREPARE
NEW SURFACE TO RECEIVE NEW FINISHES.
18. DURING DEMOLITION AND CONSTRUCTION PHASES, MAINTAIN ALL REQUIRED EXISTING WALL RATINGS AT WALLS TO REMAIN. AS ARE INDICATED ON DRAWINGS. REMOVE ALL MISC. FASTENING ANCHORS, CLIPS, CONDUIT, PIPING AND RELATED ITEMS THAT ARE NOT IN USE.
19. COORDINATE THE EXACT PHASING OF THE DEMOLITION FOR SPECIFIC STRUCTURAL MEMBERS WITH
DRAWINGS.
INTERIOR PARTITION NOTES
1. REFER TO PLANS FOR LOCATION OF PARTITION TYPES. C6 IS THE TYPICAL PARTITION
TYPE UNLESS OTHERWISE NOTED.
2. ERECT PARTITIONS IN ORDER OF RATING PRIORITY BEGINNING WITH HIGHEST FIRE
RATED PARTITION. CONSTRUCTION OF HIGHER RATED PARTITIONS SHALL BE
CONTINUOUS PAST/THROUGH LOWER RATED INTERSECTING PARTITION.
3. ALL STUD GAUGES AND LIMITING HEIGHTS IN GYPSUM BOARD REFERENCE
SPECIFICATIONS.
4. ANY MODIFICATIONS TO EXISTING PARTITIONS AND/OR SURFACES TO FINISHED TO MATCH EXISTING
CONSTRUCTION, QUALITY, DIMENSIONS, AND APPLICABLE VA STANDARD SPECIFICATIONS.
5. THE FOLLOWING LIST OF ROOMS (IF USED) SHALL HAVE THEIR PERIMETER
PARTITIONS INSULATED USING THERMAL INSULATION:
- ALL ELECTRICAL / MECHANICAL ROOMS
- A/V EQUIPMENT / LIGHTING ROOMS
- STAIRWAYS
6. THE FOLLOWING LIST OF ROOMS (IF USED) SHALL HAVE THEIR PERIMETER
PARTITIONS INSULATED WITH SOUND ATTENUATION BATTS:
- OFFICES AND OFFICE SUITES
- STAFF WORK AREAS, LOUNGES, AND LOCKER ROOMS
- WALLS CONTAINING WASTE OR DRAIN LINES
7. ALL PARTITIONS SHALL EXTEND FULL HEIGHT TO UNDERSIDE OF DECK /
INTERSTITIAL ABOVE OR HAVE THEIR TOPS BRACED PER PARTITION BRACING
DETAILS.
8. ALL RATED PARTITIONS TO EXTEND FROM TOP OF SLAB TO UNDERSIDE OF
STRUCTURE. SEAL ENTIRE PERIMETER WITH FIRESTOP SEALANT UON.
9. ALL INTERIOR ROOF AND OVERFLOW DRAIN LEADERS TO BE WRAPPED
CONTINUOUSLY WITH SOUND ATTENUATION INSULATION.
10. INSTALL FRAMING AND GWB TO OFFSET AROUND STRUCTURAL MEMBERS OR OTHER
OBSTRUCTIONS TO MAINTAIN FIRE RESISTIVE RATINGS.
11. WHERE GWB EXTENDS TO THE UNDERSIDE OF STRUCTURE, STOP GWB 1/2” BELOW
LINE OF STRUCTURE AND SEAL AS REQUIRED.
12. NON-RATED PARTITIONS SHALL HAVE ENTIRE PERIMETER SEALED WITH
ACOUSTICAL SEALANT, UON.
13. REFER TO MECHANICAL DRAWINGS FOR DETAILS ON PIPE PENETRATIONS THROUGH
ACOUSTICAL PARTITIONS AS WELL AS RATED PARTITIONS.
14. INSTALL METAL STUD BLOCKING IN PARTITIONS AT ALL WALL MOUNTED EQUIPMENT,
WHETHER CC, VC OR VV.
15. ALL PARTITIONS SCHEDULED TO RECEIVE TILE, IN BATHING ROOMS AND/OR
LOCATED ADJACENT TO OR BEHIND PLUMBING FIXTURES SHALL BE CONSTRUCTED
OF TILE BACKER BOARD (SEE SPECIFICATIONS).
16. FOR MOLD PREVENTION, DO NOT INSTALL GWB IN DIRECT CONTACT WITH THE
FLOOR. ALL GWB SHALL BE SHIMMED ½” OFF THE FLOOR WITH NON-POROUS SHIMS.
PLASTIC NON-POROUS HORSESHOE SHIMS ARE RECOMMENDED. GWB SHIMS ARE
NOT ACCEPTABLE.
17. CABLES PENETRATING RATED PARTITIONS (WITH OR WITHOUT SLEEVES) SHALL BE
SECURED ON BOTH SIDES OF THE PARTITION. METHOD OF SECURING THE CABLES
SHALL BE SLEEVED TO PRECLUDE ANY MOVEMENT OF THE CABLE DISTURBING THE
INTEGRITY OF THE PENETRATION FIRE - STOPPING ASSEMBLY. SEE
SPECIFICATIONS.
18. REFER TO DRAWINGS FOR TYPICAL WALL FRAMING FOR FIRE DAMPERS IN RATED
WALLS. COORDINATE EXACT FRAMING REQUIREMENTS WITH FIRE DAMPER
MANUFACTURER. COORDINATE ALL PARTITION CONSTRUCTION WITH MECHANICAL
PRIME CONTRACTOR PRIOR TO COMMENCING PARTITION CONSTRUCTION. GENERAL
CONTRACTOR SHALL OBTAIN FROM THE MECHANICAL CONTRACTOR THE PROPER
INSTALLATION INSTRUCTIONS FOR ALL FIRE AND SMOKE DAMPERS AND SHALL
PROVIDE THE REQUIRED METAL FRAMING, DRYWALL, ETC., ACCORDING TO THESE
INSTRUCTIONS. INSTALLATION INSTRUCTIONS TO BE SUBMITTED TO THE COR FOR
REVIEW.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING FIRE AND SMOKE SEALED
PENETRATIONS IN ACCORDANCE WITH TESTED AND APPROVED PENETRATION
SEALING SYSTEM FOR THE PARTITION CONSTRUCTION / FIRE RATING AND THE
PENETRATING ELEMENTS.
20. PARTITION TYPES AS NOTED BY THE SYMBOL CONTINUE BETWEEN ROOM/SPACE
CORNERS OR ANY INTERSECTING PARTITION.
21. DIFFERING PARTITION TYPES SHALL ALIGN SO THAT WALL PLANES CONTINUE
UNBROKEN WITHIN/ACROSS ROOMS AND/OR SPACES.
NOTE:
THE RATING (FIRE) AND UL ASSEMBLY DESIGNATION ONLY
APPLIES WHEN THE PARTITION SUFFIX "R, T, V, & S" IS
ADDED TO THE WALL TAG(S) OTHERWISE THE PARTITION
TYPE IS A NON-RATED WALL AND / OR SOME OTHER
DISTINCTION NOTED UNDER PARTITION TAG NOTES.
IF NOTED ON TAG
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
XXX
Author Checker 230080F
OR #2 - 564-23-501
1100 NORTH COLLEGE AVENUE
FAYETTEVILLE, AR
VETERANS
HEALTHCARE
SYSTEM
OF THE
OZARKS
GI002
NOTES, PARTITION TYPES,
AND STANDARD SYMBOLS
AutoCAD SHX Text
DRAWING BLOCK TITLE
AutoCAD SHX Text 1 1/2" = 1'-0"
AutoCAD SHX Text C4
AutoCAD SHX Text 1 1/2'
AutoCAD SHX Text 1/2'
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1/4" = 1'-0"
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
STANDARD SYMBOLS
AutoCAD SHX Text D4
AutoCAD SHX Text
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 6"
AutoCAD SHX Text 3"
AutoCAD SHX Text 1" = 1'-0"
AutoCAD SHX Text
PARTITION TYPES
D1
EXISTING
CORRIDOR
C319
337B
337D
341A
337C
323C
323D
305A
C304
S301
C302
S302
L04
M3-1
350349E302
T300C309
C308
C306
C307
C300
C320
355-01
353-01
332328
323E
337A
360-01
L06
L05
STERILE CORE
STERILE PREP
CORRIDOR
ELEVATOR
LOBBY
GENERAL
STORAGE
CLEAN
EQPT
CLEAN
LINEN
CLEAN
UTILITY/
SCOPES
SOILED
UTILITY
MED
ROOM
EQPT
STORAGE
HVAC
MED RM
WAITING
SURGICAL
DUMBWAITER
ROOF
DRESSING
STERILIZER
MINOR OR
OR SUPERVISER
TOILET
OPERATING RM
TOILET
CYSTO
STERILIZER
OPERATING RM
OFFICE, ICU
CONSULT
TOILET
RECOVERY
CORRIDOR
HAC
CORRIDOR
STAIR
CORRIDOR
CORRIDOR
STAIR
ELEVATOR
MECH
TOILET
CHAPEL
CONTROL
EDUCATION
OFFICE
ITS
BREAK RM
SOILED UTILMED GASELECTRICAL
TELECOMCORRIDOR
HAC
FEMALE
TOILET
CORRIDOR
HAC
CORRIDOR
LOBBY
SURGERY WAITING
SERVICEELEVATOR
SERVICEELEVATOR
ELEVATOR
TOILET
MALE
OPERATING
ROOM #2
OPERATING
ROOM #1
OPERATING ROOM #3
OPERATING ROOM #4
1/8" = 1'-0"
1 ENLARGED ICRA OR FLOOR PLAN
DATE:
DRAWN BY: C. STAGGS
CHECKED BY: T. STRAHAN
PROJ. NO: 564-23-501
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
03/31/2023
Au to de sk
D oc s:
//F ay et te vi lle V
A O
R Is ol at io n
Pa ne ls /F ay et te vi lle V
A O
R Is ol at io n
Pa ne ls _E
_R
.rv t
3/
/2
:4 7:
A
M
GC101
ENLARGED ICRA FLOOR
PLAN - THIRD FLOOR
OR #2 - 564-23-501
1100 NORTH COLLEGE AVENUE
FAYETTEVILLE, AR
VETERANS
HEALTHCARE SYSTEM
OF THE OZARKS
NO DATE REVISION
KEY NOTES
01.01
01.04 TEMPORARY BARRIER SYSTEM PROVIDED BY G.C. BASIS OF DESIGN: STARC SYSTEMS http://starcsystems.com/ OR APPROVED EQUAL.
XX GENERAL SHEET NOTES
A. ALL WORK IS CLASS IV, UNLESS OTHERWISE NOTED.
B. WORK WITHIN OR #2 TEMPORARY BARRIERS CAN OCCUR DURING NORMAL HOURS.
C. WORK OUTSIDE OF OR #2 TEMPORARY BARRIERS TO OCCUR AFTER OR DEPARTMENT'S NORMAL HOURS AND REQUIRES ADDITIONAL CLEANING MEASURES BY VA's EMS
DEPARTMENT. COORDINATE WITH COR.
D. ANY WORK CREATING EXCESSIVE DISTURBANCE SHALL OCCUR AFTER OR DEPARTMENT'S NORMAL HOURS. OR DEPARMENT LEAD RESERVES THE RIGHT TO STOP WORK
THAT MAY INTERFERE WITH SURGERY.
E. OR EMERGENCY PROCEDURES MAY OCCUR OUTSIDE OF NORMAL OR HOURS. CONTRACTOR MUST SUBMIT WRITTEN REQUEST A MIN. OF 14 DAYS AHEAD OF WORK
OUTSIDE OF CLASS IV ICRA BARRIERS FOR OR TO GO INTO DIVERT STATUS WHERE EMERGENCY PROCEDURES WOULD BE ROUTED TO OTHER LOCATIONS. IF OR IS NOT IN DIVERT STATUS; PRIORITY MUST BE GIVEN TO OR EMERGENCY PROCEDURE AND CONTRACTOR MUST ADJUST WORK SCHEDULE TO ACCOMMODATE OR
REQUIREMENTS.
F. CONTRACTOR WILL BE RESPONSIBLE FOR LOCATING AND IDENTIFYING ALL UTILITIES THAT MAY PRESENT INTERFERENCE OR CONFLICTS IN PROJECT AREA. ICRA SYMBOL LEGEND
CLASS IV
DEMO EXISTING WALL TO ACCOMMODATE NEW IPU PANEL. NEW WALL PARTITION TO MATCH EXISTING CONSTRUCTION AND FINISHINGS.
PARTITION GRAPHICS
EXISTING PARTITION TO REMAIN
NEW PARTITION
TEMPORARY PARTITION
01.05 TEMPORARILY SEAL DOOR OFF WITH VISQUEEN OR APPROVED EQUAL PER VA SPECIFICATIONS.
TEMPORARY DOOR SEAL
IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS DEPENDING UPON THE AREA
CLASS DESIGNATION
TYPE OF CONSTRUCTION / PROJECT ACTIVITY TABLE
GROUP 1-LOW RISK
PATIENT RISK GROUP TABLE
GROUP 3-HIGH RISK GROUP 4-HIGHEST RISK
INFECTION CONTROL MATRIX-CLASS OF PRECAUTIONS: CONSTRUCTION PROJECT BY PATIENT RISK
PATIENT RISK GROUP TYPE A
I I I I
NOTE: INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION
ACTIVITY AND RISK LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE
NECESSARY.LOW RISK GROUP 1
MEDIUM RISK GROUP 2
HIGH RISK GROUP 3
HIGHEST RISK GROUP 4
1.
2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION.
1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS I.
2.
3. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.
4. SEAL UNUSED DOORS WITH DUCT TAPE.
5. BLOCK OFF AND SEAL AIR VENTS.
6. PLACE ADHESIVE WALK-OFF MATS AT ENTRANCE AN EXIT OF WORK AREA.
REPLACE USED MATS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
7.
1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS II.
2.
3.
4.
5.
6.
7. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERS.
1.
2.
3.
4.
1.
2.
3.
DURING CONSTRUCTION PROJECT UPON COMPLETION OF PROJECT
CLASS I
CLASS II
CLASS III
INCLUDES BUT IS NOT LIMITED TO:
TYPE A
INCLUDES BUT IS NOT LIMITED TO:
● INSTALLATION OF TELEPHONE AND COMPUTER CABLING
● ACCESS TO CHASE SPACES
TYPE B
INCLUDES BUT IS NOT LIMITED TO:
● MAJOR, UNCONTROLLED SANDING OF WALLS FOR PAINTING OR WALL COVERING
● REMOVAL OF FLOOR COVERINGS
● NEW WALL CONSTRUCTION
● MAJOR DUCT WORK OR MAJOR ELECTRICAL/CABLE SYSTEM WORK ABOVE CEILINGS
TYPE C
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
INCLUDES BUT IS NOT LIMITED TO:
● ACTIVITIES THAT REQUIRE CONSECUTIVE WORK SHIFTS
● NEW CONSTRUCTION
TYPE D
ICRA GENERAL NOTES
● ENDOCARDIOGROPHY
● PRIMARY CARE
● MENTAL HYGIENE
● PHYSICAL THERAPY
● RESPIRATORY THERAPY
● NUCLEAR MEDICINE
● MRI/CT SCAN
● URGENT CARE
● SURGICAL INPATIENT
● MEDICAL INPATIENT
● PSYCHIATRY INPATIENT
● CLINICAL LABS
● PHARMACY
● VCS (CAFETERIA)
TYPE B
II
II
II
III
TYPE C
II
II
III
IV
III
IV
IV
IV
A. PROVIDE CONTAINMENT AS REQUIRED (BY HOSPITAL) INFECTION CONTROL REPRESENTATIVE FOR WORK OUTSIDE MAJOR AREA.
B. PROVIDE CONTAINMENT AT THE FLOOR BELOW FOR ANY WORK IN THE CEILING PLENUM.
C. PROVIDE TEMPORARY DOOR WITH GASKETING TO PREVENT THE MOVEMENT OF DUST.
D. PROVIDE TEMPORARY EMERGENCY EXIT FROM CONSTRUCTION ZONE; HOWEVER, ALL GENERAL CONSTRUCTION TRAFFIC SHOULD BE THROUGH VESTIBULE.
E. CONTRACTOR TO PROTECT ALL FINISHES INCLUDING (BUT NOT LIMITED TO) FLOORING, CEILING, WALL SURFACES, DOORS, AND DOOR FRAMES DURING THE MOVEMENT OF MATERIALS
TO / FROM LIMIT OF WORK. COORDINATE WITH COR AND SPECIFICATIONS FOR PROCEDURES/REQUIREMENTS.
CLASS IV
DURING CONSTRUCTION PROJECT UPON COMPLETION OF PROJECT
INSPECTION AND NON-INVASIVE ACTIVITIES
REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE IN 50 SQUARE
FEET
PAINTING (BUT NOT SANDING), WALL COVERING
ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES THAT DO NOT
GENERATE DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER
THAN FOR VISUAL INSPECTION
SMALL SCALE, SHORT DURATION ACTIVITIES THAT CREATE MINIMAL DUST
CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED
WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR
REMOVAL OF ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES
REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE CEILING
SYSTEM
OFFICE AREAS
(NON-CLINICAL)
ULTRASOUND
ENDOSCOPY
AMBULATORY SUGERY
PREP
NUTRITION & FOOD SERVICE
(CAFETERIA)
ALL OPERATING ROOMS INCLUDING LABOR AND DELIVERY
ANESTHESIA AND PUMP AREAS
ONCOLOGY CLINIC
SPD/STERILE PROCESSING
RADIATION ONCOLOGY
ALL INTENSIVE CARE UNITS
EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS.
PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE.
WIPE WORK SURFACES WITH
DISINFECTANT.
CONTAIN CONSTRUCTION WASTE
BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK WAS BEING
PERFORMED.
COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM
NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD BEFORE CONSTRUCTION BEGINS.
REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS OR IMPLEMENT
CONTROL CUBE METHOD.
MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-EQUIPPED AIR FILTRATION
UNITS.
CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
REMOVE BARRIER MATERIALS CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH
CONSTRUCTION.
WET MOP AND/OR VACUUM WORK
AREA WITH HEPA FILTERED
VACUUM BEFORE LEAVING WORK
AREAS.
MINOR DUCT WORK OR MINOR ELECTRICAL/CABLE WORK ABOVE CEILINGS
SANDING OF WALLS FOR WALL COVERING WHERE DUST CAN BE CONTROLLED
NON PATIENT CARE ROOMS
PROSTHETICS
BUILDING 3
BUILDING 4 ADMIN
ENGINEERING SHOPS
LAUNDRY ● RADIOLOGY/IMAGING
NUCLEAR MEDICINE
ALL OUTPATIENT/DENTAL CLINICS
WOMEN'S HEALTH
● RADIOLOGY/SPECIAL
PROCEDURE
PHARMACY ADMIXTURE●
ICU/PACU●
NEGATIVE PRESSURE ISOLATION ROOMS/AREAS
(INCLUDING BRONCHOSCOPY AREA)
VACUUM WORK WITH HEPA-FILTERED
VACUUMS. WET MOP WITH DISINFECTANT
DEPENDING ON THE PROJECT LOCATION AND THE
ICRA, PROTECTIVE CLOTHING SHOULD BE WORN
AND REMOVED EACH TIME THE WORKER LEAVES
THE WORKSITE TO CONTROL DUST THROUGHOUT
THE MEDICAL CENTER. OTHERWISE, AND
ANTEROOM MUST BE CONSTRUCTED AND
CLOTHING WILL BE VACUUMED USING A
HEPA-FILTERED VACUUM BEFORE ENTERING THE
"CLEAN" SPACE.
1. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT
SYSTEM AS REQUIRED ON A PER PROJECT BASIS.
2. TAKE NECESSARY ACTIONS TO ENSURE HVAC SYSTEM CANNOT CROSS CONTAMINATE OTHER AREAS OF THE HOSPITAL.
3. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK AREA OR
IMPLEMENT CONTROL CUBE METHOD BEFORE CONSTRUCTION BEGINS.
4. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS AS REQUIRED ON
A PER PROJECT BASIS.
5. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR APPROPRIATE PROTECTIVE CLOTHING AS REQUIRED BY
THE AREA.
7. PLACE TACKY MATS AT ENTRANCE AND EXIT OF WORK AREAS AND REPLACE WITH NEW MATS DAILY OR AS NECESSARY. IT
IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE CONTAMINATION IS KEPT AT AN ABSOLUTE MINIMUM OUTSIDE THE
WORK AREA.
8. PROVIDE APPROPRIATE CLEAN UP DAILY; WET MOP WITH DISINFECTANT AS REQUIRED.
9. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
10. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
1. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE VA'S IH/SAFETY OFFICER, INFECTION CONTROL
COORDINATOR, & ENGINEERING SERVICE AND THOROUGHLY CLEANED BY THE
VA'S ENVIRONMENTAL MANAGEMENT SERVICE.
2. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION.
3. WET MOP AREA AND/OR VACUUM WORK AREA WITH FILTERED VACUUMS.
4. PROTECTIVE CLOTHING SHOULD BE WORN AND REMOVED EACH TIME THE
WORKER LEAVES THE WORK SITE TO CONTROL DUST THROUGHOUT THE
MEDICAL CENTER. OTHERWISE AN ANTEROOM MUST BE CONSTRUCTED AND
CLOTHING WILL BE VACUUMED USING A HEPA-FILTERED VACUUM BEFORE
ENTERING THE "CLEAN SPACE".
1. CLEANUP AND DISPOSAL AS APPROPRIATE.
2. TRAFFIC: DECREASE PATIENTS' EXPOSURES.
3. WATER: SCHEDULE INTERRUPTIONS DURING LOW ACTIVITY.
01.06 MAINTAIN ACCESS TO FIRE DEPARTMENT VALVE.
GC101
01.02 SALVAGE EXISTING FLOORING FROM EXISTING PARTITION. REUSE AND REATTACH TO NEW PARTITION TO MATCH EXISTING.
AutoCAD SHX Text
TEMPORARY WALL
AutoCAD SHX Text 01.04
AutoCAD SHX Text
TEMPORARY WALL
AutoCAD SHX Text
TEMPORARY DOOR SEAL
AutoCAD SHX Text 01.04
AutoCAD SHX Text 01.05
AutoCAD SHX Text
CLASS IV
AutoCAD SHX Text 01.02
AutoCAD SHX Text 01.01
AutoCAD SHX Text 01.06
AutoCAD SHX Text
GROUP 2-MEDIUM RISK
TYPE D
C319
337B
337D
341A
337C
373A
374A
384384A
385A
386A
387388
370A
387A
323B
323C
323D
324322
305A
C304
C303
S301
303 302
C301
C302
S302
L04
M3-1
350349E302
T300C309
C308
C306
C307
C310
3B330 3B331
3B332
3B333
3B334
3B335 3B3363B337
3B338A3B339
3B342
3B338
3B340
3B341
3B341A
3B343
3B344A3B344
3B345A
3B345
3B346
3B347 3B348
3B348A3B347A
3B330
3B330
S303
363362
C312
C300
301 C
301 A 301 B
308A
306A
313A 314
C320
355-01
353-01
303A
14131211
4 3 2 1
323E
323A
337A
360-01
E300
L06
L05
STERILE CORE
STERILE PREP
CORRIDOR
ELEVATOR
LOBBY
GENERAL
STORAGE
CLEAN
EQPT
CLEAN
LINEN
TOILET
CLEAN
UTILITY/
SCOPES
EXAM RM
EXAM RM
EXAM RM
EXAM RMEXAM RMEXAM RMRECOVERY
RECOVERY
RECOVERY
RECOVERY
EXAM RMEXAM RMEXAM RM
EXAM RM EXAM RM EXAM RM EXAM RM
SOILED
UTILITY
MED
ROOM
EQPT
STORAGE
EQPT
STORAGE
HVAC
MED RM
WAITING
SURGICAL
DUMBWAITER
BELOW
ROOF ROOF
ROOF
BELOW
ROOF
ROOF BELOW
1008-21
DRESSING
STERILIZER
MINOR OR
OR SUPERVISER
TOILET
OPERATING RM
TOILET
CYSTO
STERILIZER
OPERATING RM
MEDICATION
STEP-DN
RM-6
TOILET
STEP-DN
RM-5
TOILET
NURSES
STATION
ELECT/IT
CLOSET
SOILED
UTILITY
CLEAN
LINEN
ISOLATION
STEP-DOWN-4TOILET
STEP-
DOWN-3
TOILET
STEP-
DOWN-2
STEP-
DOWN-1EQUIPMENT
STAFF
TOILET
NOURISHMENT
AISLE
TOILET
AISLE
OFFICE, ICU
CONSULT
TOILET
NURSES
ICU-7
RECOVERYICU-6
ICU-5
ICU-4
ICU-3
ICU-2
ICU-1
CORRIDOR
HAC
ENDOSCOPY
CORRIDOR
STAIR
ENDOSCOPY ENDOSCOPY
CORRIDOR
CORRIDOR
STAIR
ELEVATOR
MECH
TOILET
CHAPEL
CONTROL
EDUCATION
OFFICE
ITS
BREAK RM
SOILED UTILMED GASELECTRICAL
TELECOMCORRIDOR
HAC
FEMALE
TOILET
CORRIDOR
HAC
CORRIDOR
CORRIDOR
HOUSEKEEP
DATA/TELE
CLEAN LINEN
WAITING
SOILED LINEN CONFERENCE RMTOILET
MEDSBREAK RM
NURSE STA
OFFICE
OFFICE
PATIENT
TOILET
LINEN
TOILETPATIENT
TOILET
PATIENT
KITCHEN
PATIENT
PATIENT
TOILETTOILET
CORRIDOR
CORRIDOR
OFFICE/ IC
STAIR
ATTIC
OFFICE/ ANEST
ICU WAITINGLOUNGE
LOCKER RM
TOILET
TOILET
CORRIDOR
CORRIDOR
LOBBY
CHAPLIN SERVICES
STORAGE
CONSULT
OFFICE
SURGERY WAITING
UNDER
SUITENURSE MGR
CLEAN SUPPLY
TOILET
CLEAN LINEN
NURSE STA
TOILET
RECOVERY
RECOVERY
TOILET
BREAK RM
LOCKES
NURSES STORAGE
CLEAN LINEN
ELECTRICAL
SERVICEELEVATOR
SERVICEELEVATOR
ELEVATOR
TOILET
TOILET
MALE
OPERATING
ROOM #2
OPERATING
ROOM #1
OPERATING ROOM #3
OPERATING ROOM #4
AE101
AE101
3/32" = 1'-0"AE100
1 OVERALL THIRD FLOOR PLAN
DATE:
DRAWN BY: C. STAGGS
CHECKED BY: T. STRAHAN
PROJ. NO: 564-23-501
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
03/31/2023
Au to de sk
D oc s:
//F ay et te vi lle V
A O
R Is ol at io n
Pa ne ls /F ay et te vi lle V
A O
R Is ol at io n
Pa ne ls _E
_R
.rv t
3/
/2
:4 7:
A
M
AE100
OVERALL FLOOR
PLAN - THIRD FLOOR
OR #2 - 564-23-501
1100 NORTH COLLEGE AVENUE
FAYETTEVILLE, AR
VETERANS
HEALTHCARE SYSTEM
OF THE OZARKS
NO DATE REVISION
PARTITION GRAPHICS
EXISTING PARTITION TO REMAIN
NEW PARTITION
TEMPORARY PARTITION
TEMPORARY DOOR SEAL
337B 337D
341A
STERILE PREP
STERILIZER
MINOR OR
TOILET
CYSTO
CORRIDOR
OPERATING
ROOM #2
OPERATING
ROOM #1
EXISTING
CORRIDOR
C319
337B
337D
341A
337C
323C
323D
305A
C304
S301
C302
S302
L04
M3-1
350349E302
T300C309
C308
C306
C307
C300
C320
355-01
353-01
332328
323E
337A
360-01
L06
L05
STERILE CORE
STERILE PREP
CORRIDOR
ELEVATOR
LOBBY
GENERAL
STORAGE
CLEAN
EQPT
CLEAN
LINEN
CLEAN
UTILITY/
SCOPES
SOILED
UTILITY
MED
ROOM
EQPT
STORAGE
HVAC
MED RM
WAITING
SURGICAL
DUMBWAITER
ROOF
DRESSING
STERILIZER
MINOR OR
OR SUPERVISER
TOILET
OPERATING RM
TOILET
CYSTO
STERILIZER
OPERATING RM
OFFICE, ICU
CONSULT
TOILET
RECOVERY
CORRIDOR
HAC
CORRIDOR
STAIR
CORRIDOR
CORRIDOR
STAIR
ELEVATOR
MECH
TOILET
CHAPEL
CONTROL
EDUCATION
OFFICE
ITS
BREAK RM
SOILED UTILMED GASELECTRICAL
TELECOMCORRIDOR
HAC
FEMALE
TOILET
CORRIDOR
HAC
CORRIDOR
LOBBY
SURGERY WAITING
SERVICEELEVATOR
SERVICEELEVATOR
ELEVATOR
TOILET
MALE
OPERATING
ROOM #2
OPERATING
ROOM #1
OPERATING ROOM #3
OPERATING ROOM #4
1/8" = 1'-0"AE101
1 ENLARGED OR FLOOR PLAN
DATE:
DRAWN BY: C. STAGGS
CHECKED BY: T. STRAHAN
PROJ. NO: 564-23-501
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
03/31/2023
Au to de sk
D oc s:
//F ay et te vi lle V
A O
R Is ol at io n
Pa ne ls /F ay et te vi lle V
A O
R Is ol at io n
Pa ne ls _E
_R
.rv t
3/
/2
:4 7:
A
M
AE101
ENLARGED FLOOR
PLAN - THIRD FLOOR
OR #2 - 564-23-501
1100 NORTH COLLEGE AVENUE
FAYETTEVILLE, AR
VETERANS
HEALTHCARE SYSTEM
OF THE OZARKS
NO DATE REVISION
1/4" = 1'-0"AE101
2 ENLARGED OR#2 FLOOR PLAN
KEY NOTES
01.01
01.02
01.03
DEMO EXTERIOR PORTION OF EXISTING WALL TO ACCOMMODATE NEW IPU PANEL. NEW WALL PARTITION TO MATCH EXISTING
CONSTRUCTION AND FINISHINGS.
XX
SALVAGE EXISTING FLOORING FROM EXISTING PARTITION. REUSE AND REATTACH TO NEW PARTITION TO MATCH EXISTING.
EXTENTS OF WALL PARTITION TO AVOID CONFLICT WITH EXISTING MED GAS LINES AND VALVE BOX.
GENERAL SHEET NOTES
PARTITION GRAPHICS
EXISTING PARTITION TO REMAIN
NEW PARTITION
TEMPORARY PARTITION
TEMPORARY DOOR SEAL
A. WORK WITHIN OR #2 TEMPORARY BARRIERS CAN OCCUR DURING NORMAL HOURS.
B. WORK OUTSIDE OF OR #2 TEMPORARY BARRIERS TO OCCUR AFTER OR DEPARTMENT'S NORMAL HOURS AND REQUIRES ADDITIONAL CLEANING MEASURES BY VA's EMS
DEPARTMENT. COORDINATE WITH COR.
C. ANY WORK CREATING EXCESSIVE DISTURBANCE SHALL OCCUR AFTER OR DEPARTMENT'S NORMAL HOURS. OR DEPARMENT LEAD RESERVES THE RIGHT TO STOP WORK
THAT MAY INTERFERE WITH SURGERY.
D. OR EMERGENCY PROCEDURES MAY OCCUR OUTSIDE OF NORMAL OR HOURS. CONTRACTOR MUST SUBMIT WRITTEN REQUEST A MIN. OF 14 DAYS AHEAD OF WORK
OUTSIDE OF CLASS IV ICRA BARRIERS FOR OR TO GO INTO DIVERT STATUS WHERE EMERGENCY PROCEDURES WOULD BE ROUTED TO OTHER LOCATIONS. IF OR IS NOT IN DIVERT STATUS; PRIORITY MUST BE GIVEN TO OR EMERGENCY PROCEDURE AND CONTRACTOR MUST ADJUST WORK SCHEDULE TO ACCOMMODATE OR
REQUIREMENTS.
E. CONTRACTOR WILL BE RESPONSIBLE FOR LOCATING AND IDENTIFYING ALL UTILITIES THAT MAY PRESENT INTERFERENCE OR CONFLICTS IN PROJECT AREA.
AutoCAD SHX Text
PROJECT LIMITS
AutoCAD SHX Text 01.03
AutoCAD SHX Text 01.02
AutoCAD SHX Text 01.01
AutoCAD SHX Text
PROJECT LIMITS
AutoCAD SHX Text
PROJECT LIMITS (SEE GENERAL SHEET NOTE B)
AutoCAD SHX Text
COORDINATE WITH COR TO ESTABLISH ACCESS.
AutoCAD SHX Text 01.03
AutoCAD SHX Text 01.02
01.01
DUPLEX RECEPTACLE (NEMA 5-20R); MOUNTED
8" ABOVE COUNTERTOP.
QUADRUPLEX RECEPTACLE (TWO NEMA 5-20R)
SPECIAL RECEPTACLE: VERIFY NEMA TYPE WITH MANUFACTURER
GFI DUPLEX RECEPTACLE (NEMA 5-20R), SELF-TEST TYPE
GFI DUPLEX RECEPTACLE (NEMA 5-20R), SELF-TEST TYPE;
MOUNTED 8" ABOVE COUNTERTOP.
ABBREVIATIONS
AC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
CB CIRCUIT BREAKER
E EXISTING
EC ELECTRICAL CONTRACTOR
EP EXPLOSION PROOF
GFI GROUND FAULT CIRCUIT INTERRUPTER
GR GROUND
HP HORSE POWER
SWITCH MOUNTED AT +48"; SINGLE POLE UON.
LOWER CASE LETTER, WHEN PRESENT, INDICATES FIXTURES CONTROLLED.
* ABBREVIATIONS FOR SWITCH
2 DOUBLE POLE SWITCH
3 3-WAY SWITCH
4 4-WAY SWITCH
D DIMMER SWITCH (SHALL BE COMPATABLE WITH FIXTURE BEING DIMMED)
F FAN SWITCH: DUAL OPERATION WITH DIMMER
K KEYED SWITCH
M MOTOR RATED SWITCH
OS DUAL TECHNOLOGY OCCUPANCY SENSOR
V VOLUME CONTROL SWITCH
OSD OCCUPANCY SENSOR/DIMMER COMBO
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH SPARE
DRY CONTACTS.
FLOOR BOX WITH DATA: LEGRAND WIREMOLD SERIES RFB4E-OG OR RFB6E-
OG WITH EVOLUTION COVER. ROUTE (2)1" FOR DATA FROM FLOOR BOX TO
NEAREST ACCESSIBLE CEILING SPACE. ON FLOOR LEVELS WITH ACCESSIBLE
SPACE BELOW, USE POKE-THRU STYLE FLOOR BOXES: LEGRAND 6AT SERIES.
SEE ARCHITECTURAL PLANS FOR LOCATION UON.
DIRECT EQUIPMENT CONNECTION: VERIFY CONNECTION DETAILS WITH
MANUFACTURER
J
EQUIPMENT DISCONNECT: INTERIOR DISCONNECTS SHALL BE NEMA 1 TYPE.
EXTERIOR DISCONNECTS SHALL BE NEMA 3R TYPE. SIZE AS INDICATED IN THE
PLANS AND PER NAMEPLATE RATING.
DUPLEX RECEPTACLE (NEMA 5-20R)
PHONE/DATA: PROVIDE 4"X4", 30-1/4 CUBIC INCH OUTLET BOX AT 8" ABOVE
COUNTER (UON) WITH (2) 3/4" CONDUITS (WITH PULL STRINGS) ROUTED TO
ACCESSIBLE CEILING SPACE. PROVIDE SINGLE GANG MUD RING WITH BLANK
COVER. PROVIDE PLASTIC BUSHINGS ON EXPOSED CONDUIT ENDS. WIRING BY
OTHERS.
PHONE/DATA: PROVIDE 4"X4", 30-1/4 CUBIC INCH OUTLET BOX AT +18" (UON)
WITH (2) 3/4" CONDUITS (WITH PULL STRINGS) ROUTED TO ACCESSIBLE CEILING
SPACE. PROVIDE SINGLE GANG MUD RING WITH BLANK COVER. PROVIDE
PLASTIC BUSHINGS ON EXPOSED CONDUIT ENDS. WIRING BY OTHERS.
IG ISOLATED GROUND
MCC MOTOR CONTROL CENTER
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOC.
NIC NOT IN CONTRACT
NL NIGHT LIGHT
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
WP WEATHERPROOF
WR WEATHER RESISTANT
SWITCHES
RECEPTACLES
SINGLE RECEPTACLE (NEMA 5-20R)
SPLIT WIRED DUPLEX RECEPTACLE (NEMA 5-20R)
PANELS AND MISC.
FLOOR BOX: HUBBEL 3SFBSS WITH 3SFBC COVER. EC SHALL ROUTE A 1"C FOR
FLOOR BOX TO NEAREST ACCESSIBLE CEILING SPACE. ON FLOOR LEVELS
WITH ACCESSIBLE SPACE BELOW, USE POKE-THRU STYLE FLOOR BOXES:
HUBBELL PT2X2 SERIES. SEE ARCHITECTURAL PLANS FOR LOCATION UON.
LIGHT OR POWER PANEL
TV
4x4 JUNCTION BOX.
S CEILING MOUNTED SPEAKER
TELEVISION: PROVIDE 4X4 JUNCTION BOX WITH (2) 3/4" CONDUITS (WITH PULL
STRINGS) ROUTED TO ACCESSIBLE CEILING SPACE. PROVIDE SINGLE GANG MUD
RING WITH BLANK COVER. CONFIRM HEIGHTS WITH ARCHITECT PRIOR TO
ROUGH-IN.
CR CARD READER: REFER TO SYSTEM PLANS AND SPECIFICATIONS. AT EACH
DOOR WITH A CARD READER PROVIDE ALL ELECTRICAL CONNECTIONS FOR
DOOR HARDWARE SYSTEMS AS REQUIRED TO MAKE A COMPLETE
OPERATIONAL SYSTEM. WHERE REQUIRED, BACK TO BACK 2"X4" BOXES ARE
ALLOWED FOR CARD READER AND PUSH TO EXIT SWITCH. PROVIDE POWER
TO THE LOCK SYSTEM IN THE I.T. ROOM WHERE NEEDED BY CONTRACTOR
INSTALLING SYSTEM.
CEILING MOUNTED RECEPTACLE(NEMA 5-20R)
(ALL RECEPTACLE TYPES) WITH USB CHARGING PORTSU
PHONE/DATA: PROVIDE 4"X4", 30-1/4 CUBIC INCH OUTLET BOX IN CEILING.
PROVIDE SINGLE GANG MUD RING WITH BLANK COVER. WIRING BY OTHERS.
TELEVISION: PROVIDE THREE INDIVIDUAL DEVICE BOXES WITH 1/2" CONDUIT FOR
POWER AND 1" CONDUIT (WITH PULL STRINGS) FOR A/V AND DATA ROUTED TO
ACCESSIBLE CEILING SPACE. PROVIDE CONNECTIONS FOR POWER, DATA, COAX,
AND HDMI. MOUNT AT +72" AFF UNO. CONFRIM HEIGHTS WITH ARCHITECT PRIOR
TO ROUGH-IN.
SECURITY CAMERA: DOUBLE GANG BOX AND 3/4"C TO ABOVE CEILING.
F FURNITURE FEED FLOOR BOX: LEGRAND WIREMOLD EVOLUTION
POKE THRU WITH FF COVER ASSEMBLY.
OS
TV
U T H
N
IC
C E
R
T
AS -
A
A N
HP
ENGINEERING,
INC.
#1653
E E
OF
R
A R
K
S
E
A
ENG I
T
I F
HP ENGINEERING
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
5504 W PINNACLE POINT DR
Suite 200
ROGERS, AR 72758
TEL 479-899-6370
CLIENT:
XXX
PROJECT NUMBER:
COMPLETION
A u to d e sk D o cs
/F a ye tt e vi lle
V A
O R
I so la tio n P a n e ls
/F a ye tt e vi lle
V A
O R
E
R
.r vt
/3
/2
:1 :5
A
M
E001
CPB
CPB
230080F
ELECTRICAL LEGEND
OR #2 - 564-23-501
1100 NORTH COLLEGE AVENUE
FAYETTEVILLE, AR
VETERANS
HEALTHCARE SYSTEM
OF THE OZARKS
230080F
100%
INDEX OF ELECTRICAL DRAWINGS
E001 ELECTRICAL LEGEND
E103 OVERALL ELECTRICAL PLAN - THIRD FLOOR
E200 ENLARGED ELECTRICAL PLANS
E301 PANEL SCHEDULES
GENERAL ELECTRICAL NOTES
1 DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF THE
WORK. REVIEW ALL GENERAL NOTES, SPECIFICATIONS AND PLANS FOR ADDITIONAL
REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE
CONSTRUCTION DOCUMENTS.
2 SPECIAL ATTENTION SHALL BE GIVEN TO ALL RACEWAYS WITHIN FINISHED AREAS
WITHOUT CEILINGS AND EXPOSED TO STRUCTURE. IN GENERAL, ALL RACEWAYS SHALL
BE CONCEALED WITHIN WALLS, ABOVE STRUCTURE FINISH, OR BELOW FLOOR SLABS
WHEN SPECIFIED. WHERE EXPOSED CONDITIONS ARE NECESSARY OR UNAVOIDABLE DUE
TO OTHER CONDITIONS, THE BID SHALL INCLUDE ANY REASONABLE MEANS TO MINIMIZE
THE AMOUNT OF SURFACE MOUNTED EQUIPMENT. PRIOR TO ROUGH-IN, COORDINATE
ALL EXPOSED RACEWAY AND BOX CONDITIONS WITH ARCHITECT PRIOR TO
CONSTRUCTION OF WALLS, ROOF DECK, OR FLOOR SLABS. ATTACHMENT TO ROOF DECK
OR JOIST WEBBINGS IS NOT ALLOWED, MAINTAIN A MINIMUM SPACING OF 1-1/2” FROM
CONDUIT TO ROOF DECK. IN AREAS WHERE EXPOSED RACEWAYS ARE REQUIRED,
INSTALL SYSTEMS SQUARE AND TIGHT TO STRUCTURE AND PAINT TO MATCH THE
STRUCTURE PER ARCHITECT AND/OR OWNER SPECIFICATIONS. FAILURE TO PROPERLY
COORDINATE THE ROUTING OF EXPOSED RACEWAYS MAY RESULT IN RELOCATION OF
SUCH RACEWAYS AT NO ADDITIONAL COST TO THE OWNER.
3 OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE-RESISTANT-RATED
WALLS, PARTITIONS, FLOORS OR CEILINGS SHALL BE FIRESTOPPED USING APPROVED
METHODS TO MAINTAIN THE FIRE RESISTANCE RATING. PROVIDE PENETRATION FIRE
STOPPING WITH RATINGS DETERMINED PER ASTM E 814 OR UL 1479. FIRE STOPPING
SHALL NOT BE LESS THAN FIRE RESISTANCE RATING OF CONSTRUCTED PENETRATIONS.
4 INSTALL EQUIPMENT IN A MANNER TO REMAIN ACCESSIBLE WITH REASONABLE MEANS BY
THE OWNER FOLLOWING COMPLETION OF WORK. SPECIAL ATTENTION AND ADDITIONAL
COORDINATION IS EXPECTED IN AREAS OF THE BUILDING WHERE THE CEILING AND
STRUCTURE HEIGHTS HAVE SIGNIFICANT DIFFERENT ELEVATIONS. EQUIPMENT
REQUIRING POSSIBLE FUTURE ACCESS SHALL BE INSTALLED SUCH THAT IT MAY BE
SAFELY ACCESSED FROM A STANDARD STEP LADDER OR PERSONNEL LIFT SUITABLE FOR
THE LOCATION AND CEILING HEIGHT, WITHOUT REMOVING OR DAMAGING THE CEILING
GRID STRUCTURE.
5 FIELD VERIFY LOCATIONS OF EXISTING ELECTRICAL EQUIPMENT, INCLUDING POWER
POLES, TELEPHONE PEDESTALS, OVERHEAD AND UNDERGROUND FEEDERS, METERS,
PANELS, DEVICES, ETC. PROVIDE FOR COORDINATION WITH EXISTING EQUIPMENT.
6 ROOM NAMES/NUMBERS SHOWN IN PANELBOARD SCHEDULES ARE PER ARCHITECTURAL
FLOOR PLANS. CONTRACTOR SHALL PROVIDE FINALIZED PANELBOARD SCHEDULES AT
COMPLETION OF PROJECT WITH OWNER PROVIDED ROOM NAMES/NUMBERS.
7 CONDUCTORS FOR BRANCH CIRCUITS AS DEFINED IN ARTICLE 100, SHALL BE SIZED TO
PREVENT A VOLTAGE DROP EXCEEDING 3% AT THE FARTHEST LOAD, AND WHERE THE
MAXIMUM TOTAL VOLTAGE DROP ON BOTH FEEDERS AND BRANCH CIRCUITS TO THE
FARTHEST LOAD DOES NOT EXCEED 5%.
8 ALL WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH THE NATIONAL
ELECTRICAL CODE, STATE LAWS, ALL AUTHORITIES HAVING JUISDICTION, AND ALL OTHER
REGULATIONS GOVERNING WORK OF THIS NATURE.
9 THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIAL, AND LABOR TO SATISFY A
COMPLETE AND WORKING SYSTEM WHETHER SPECIFIED OR IMPLIED.
10 CONTRACTOR TO CONFIRM EXACT LOCATION OF EXISTING AND NEW EQUIPMENT.
11 THE CONTRACTOR SHALL FURNISH AND INSTALL ALL GROUNDING SYSTEMS (AS
REQUIRED) IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.
12 ALL ELECTRIC MATERIALS AND EQUIPMENT FOR THE PROJECT SHALL BE NEW AND U.L.
OR EQUALLY LISTED.
13 SUBMIT TO THE OWNER CERTIFICATES OF INSPECTIONS IN DUPLICATE FROM AN
APPROVED INSPECTION AGENCY UPON COMPLETION.
14 THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICATIONS AND PAY ANY AND ALL
FEES AS REQUIRED,
15 THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND QUALIFIED PERSONNEL OR
FIRM TO PERFORM ALL REQUIRED TESTS.
16 NO EQUIPMENT SHALL BE ENERGIZED UNTIL ALL TEST AND ADJUSTMENTS HAVE BEEN
MADE. THREE COPIES OF ALL TEST RESULTS SHALL BE DELIVERED TO THE OWNER
17 JUNCTION BOXES LOCATED ABOVE GRID CEILINGS SHALL BE LOCATED NO GREATER
THAN 4-FEET ABOVE THE CEILING IN A LOCATION ACCESSIBLE VIA A LADDER FROM THE
ROOM BELOW.
18 ALL WIRING DEVICE COVERPLATES SHALL INDICATE PANELBOARD AND CIRCUIT SERVING
THE DEVICE. UTILIZE CLEAR VINYL (BLACK LETTERING) IDENTIFICATION LABLES
MANUFACTURED BY 3M COMPANY (OR APPROVED EQUIVALENT).
19 SEISMIC PROTECTION FOR SEISMIC CONCERNS OF ALL BUILDING SYSTEMS INCLUDING
BUT NOT LIMITED TO MECHANICAL, PLUMBING, AND ELECTRICAL MUST MEET MINIMUM
REQUIREMENTS OF ALL APPLICABLE CODES FOR BUILDINGS’ CLASSIFIED SEISMIC USE
GROUP AND SEISMIC DESIGN CATEGORY. ANY REQUIREMENTS FOR SEISMIC
PROTECTION MEASURES TO BE APPLIED SHALL BE INSTALLED IN STRICT ACCORDANCE
WITH ALL APPLICABLE LOCAL, STATE, AND/OR FEDERAL CODES AND WITH
MANUFACTURER’S REQUIREMENTS, THE MOST STRINGENT SHALL APPLY.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE TYPE AND LOCATION
OF SEISMIC RESTRAINTS REQUIRED FOR THE VARIOUS SYSTEM’S ELEMENTS CONTAINED
IN THE CONSTRUCTION DOCUMENTS BASED ON THE RELATED SEISMIC CODE CRITERIA,
THE SIZE AND WEIGHT OF THE SUPPORTED ELEMENT AND THE DISTANCE FROM
STRUCTURE THAT THE ELEMENT WILL BE INSTALLED. IF REQUIRED BY LOCAL, STATE,
FEDERAL CODES AND/OR OTHER AUTHORITY HAVING JURISDICTION (AHJ) THE
CONTRACTOR SHALL SUBMIT DESCRIPTIVE CATALOG DATA OF SEISMIC RESTRAINTS,
SHOP DRAWINGS SHOWING THE TYPES, LOCATIONS AND INSTALLATION DETAILS OF
SEISMIC RESTRAINTS AND CALCULATIONS SHOWING THAT THE SEISMIC RESTRAINTS
MEET THE SEISMIC REQUIREMENTS TO THE LOCAL AHJ FOR REVIEW AND APPROVAL.
CALCULATIONS SHALL BE SIGNED AND SEALED BY A REGISTERED PROFESSIONAL
ENGINEER, LICENSED IN THE STATE OF THE PROJECT LOCATION AND EMPLOYED BY THE
MANUFACTURER OF THE SEISMIC RESTRAINT PRODUCTS. CALCULATIONS SHALL INCLUDE
DEAD LOADS, STATIC SEISMIC LOADS AND CAPACITY OF MATERIALS UTILIZED FOR
CONNECTIONS TO EQUIPMENT AND STRUCTURE.
20 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLETING ALL ELECTRICAL
SYSTEM TESTING THAT IS REQUIRED IN THE LOCALLY ADOPTED EDITION OF NFPA 99:
STANDARD FOR HEALTHCARE FACILITIES. THE ELECTRICAL CONTRACTOR SHALL
PROVIDE ALL EQUIPMENT TO PERFORM THE VOLTAGE AND IMPEDANCE TESTS REQUIRED
IN NFPA 99. PROVIDE COMPLETE RESULT DOCUMENTATION TO THE ELECTRICAL
ENGINEER, LOCAL AND STATE AUTHORITY UPON COMPLETION OF THE TESTS.
21 DESIGNATED SPARE CIRCUIT BREAKERS SHALL BE PLACED IN THE OFF POSITION
22 PROVIDE SPECIAL PROTECTION AGAINST ELECTRICAL SHOCK IN WET PROCEDURE
LOCATIONS AS REQUIRED IN NEC ARTICLE 517.
EXISTING ELECTRICAL AND DEMOLITION NOTES
1 PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED WITH THE
EXISTING CONDITIONS OF THE FACILITY AND RELATED SITE. REVIEW THE GENERAL NOTES
AND ALL OTHER TRADE DRAWINGS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE
CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT,
ENGINEER OR OWNER, AS SPECIFIED, OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO
SUBMITTING BID.
2 ANY EXISTING CONDITIONS REFLECTED WERE TAKEN…
This is the start of the file's text. The full file is on GovTribe.