Drawings IFB.pdf
PDF 36 MB Posted
- Attached to
- Waterloo Vehicle Maintenance Shop
- Solicitation number
- C485X2118
- Issued by
- Black Hawk County, Iowa
About this file
This document is a comprehensive set of construction drawings issued for the Waterloo Vehicle Maintenance Shop project for the Iowa National Guard, located at 3106 Airport Boulevard in Waterloo, Iowa. The Iowa Army National Guard (IA-ARNG) is undertaking construction of a new 24,810 square-foot, single-story facility with mixed occupancy classifications (Business Group B and Storage Group S-1). The project, identified as IAARNG Project No. 190185 and Contract No. C485X2118, was issued for construction on March 20, 2026. The drawings include general information, life safety code analysis, architectural plans, civil site plans, structural details, mechanical and plumbing systems, electrical and technology layouts, and fire protection systems. The building will be constructed using load-bearing precast concrete exterior walls with a steel roof structure and will accommodate offices, classrooms, latrines, storage areas, mechanical and electrical rooms, and janitorial spaces. The structure reaches a height of 34 feet with proposed area of 24,810 square feet, which complies with allowable limits under Construction Type II-B. The project includes bid alternates for items such as a bridge crane, permeable concrete paving surfaces, high-density storage systems, and photovoltaic arrays.
The construction is governed by the 2015 International Building Code, 2021 International Plumbing Code, 2012 NFPA 101 Life Safety Code, 2020 National Electrical Code, and other applicable standards. The design accommodates 168 occupants with appropriate fire separation, egress paths, and accessibility features in compliance with 2010 ADA standards and Iowa Accessibility Code Chapter 302. The facility requires an automatic sprinkler system, fire alarm system, and fire department connections in accordance with life safety requirements. Utilities include sanitary sewer, storm sewer, water mains with fire hydrants, and underground electrical services. The contractor must comply with City of Waterloo specifications and standards, coordinate staking under licensed surveyor supervision, manage storm water discharge permits from the Iowa Department of Natural Resources, and maintain strict adherence to OSHA codes throughout construction. Laboratory testing, erosion control, and comprehensive as-built documentation of all utilities are contractor responsibilities. The project site spans 7.26 acres on property zoned M-1 (Light Industrial) and is subject to various easements and deed restrictions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Advertisement.pdf | ||
| Specifications IFB.pdf | ||
| Plan Holders List.html | HTML file | |
| Bidding Documents.html | HTML file | |
| Advertisement for Bids.html | HTML file | |
| 1378354-event.pdf | ||
| Advertisement.pdf | ||
| TSB Form.pdf | ||
| Form of Bid.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NO.: DATE:
PROJECT VICINITY
PROJECT LOCATION
IAARNG PROJECT NO.: 190185
IAARNG CONTRACT NO.: C45X2118
ARCHITECT
CONSULTANTS
LIST OF DRAWINGS
/1
/2
:5 :2
A
M
0231514.00
WATERLOO VEHICLE
MAINTENANCE SHOP
IOWA NATIONAL GUARD
3106 AIRPORT BLVD
WATERLOO, IA 50703
03/20/2026
IO
W
A N
A T
IO
N
A L G
U A
R D
ISSUED FOR CONSTRUCTION
W A
T E
R L O
O V
E H
IC
L
E M
A
IN
T E
N A
N C
E S
H O
P
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DRAWING LIST
GENERAL
G0.1 GENERAL INFORMATION
LS1.1 LIFE SAFETY CODE ANALYSIS
LS1.2 FIRST FLOOR LIFE SAFETY
CIVIL
C0.1 CIVIL NOTES AND REFERENCES
C1.1 SITE SURVEY AND REMOVALS
C2.1 OVERAL LAYOUT PLAN
C2.2 LAYOUT PLAN
C3.1 GRADING PLAN
C4.1 UTILITY PLAN – SANITARY SEWER AND WATER
C4.2 UTILITY PLAN – STORM SEWER
C5.1 LANDSCAPE PLAN
C6.1 DETAILS
C6.2 DETAILS
C6.3 DETAILS
C6.4 DETAILS
C6.5 DETAILS
C7.1 SWPPP
C7.2 SWPPP
STRUCTURAL
S0.1 STRUCTURAL NOTES
S1.1 FOUNDATION PLAN - AREA A
S1.2 FOUNDATION PLAN - AREA B
S2.1 ROOF FRAMING PLAN - AREA A
S2.2 ROOF FRAMING PLAN - AREA B
S3.1 STRUCTURAL PLANS
S5.1 STRUCTURAL DETAILS
S5.2 STRUCTURAL DETAILS
S5.3 STRUCTURAL DETAILS
S5.4 STRUCTURAL DETAILS
S5.5 STRUCTURAL DETAILS
FARNSWORTH GROUP, INC.
14225 UNIVERSITY AVENUE, SUITE 110
WAUKEE, IA 50263
P: 515/225.3469 F: 515/225.9649
BISHOP ENGINEERING
3501 104TH STREET
DES MOINES, IA 50322
P: 515/276.0467 F: 515/276.0217
KED BLUESTONE ENGINEERING
5518 NW 88TH STREET
JOHNSTON, IA 50131
P: 515/727.0700 F: 515/727.0777
KPFF ENGINEERING CONSULTANTS
604 LOCUST STREET, SUITE 202
DES MOINES, IA 50309
P: 515/279.3900 F: 515/276.0217
3106 AIRPORT BLVD WATERLOO, IA 50703
3106 AIRPORT BLVD WATERLOO, IA 50703
NATHAN T.
KRESS
21136
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
DAVID B.
BENTZ
17143
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
RICHARD K.
LARSON
16014
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
Robert C. Ridgway, AIA
06/30/2027
GENERAL AND ARCHITECTURAL
SUPERVISION. I AM A DULY LICENSED ARCHITECT UNDER THE
LAWS OF THE STATE OF IOWA.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
David A Bentz, P.E.
12/31/2027
CIVIL
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF IOWA.
ROBERT C.
RIDGWAY
07570
L
IC
E N
S E
D P
R
OFESS IONA
L A
R C
H
IT
E C
* IO W A *
T
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
Nathan T. Kress, P.E.
12/31/2027
STRUCTURAL
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF IOWA.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
Cory Jacobs, P.E.
12/31/2026
PLUMBING, MECHANICAL AND MECHANICAL PIPING
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF IOWA.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
Richard K. Larson, P.E.
12/31/2027
ELECTRICAL AND TECHNOLOGY
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF IOWA.
CORY
JACOBS
23172
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
DRAWING LIST
ARCHITECTURAL
A1.1 OVERALL FLOOR PLAN
A1.2 FLOOR PLAN - AREA A
A1.3 FLOOR PLAN - AREA B
A2.1 OVERALL ROOF PLAN
A2.2 ROOF DETAILS
A3.1 OVERALL EXTERIOR ELEVATIONS
A3.2 INTERIOR AND EXTERIOR DETAILS
A4.1 BUILDING SECTIONS
A5.1 WALL SECTIONS
A5.2 WALL SECTIONS
A5.3 WALL SECTIONS
A5.4 WALL SECTIONS
A5.5 WALL SECTIONS
A5.6 WALL SECTIONS
A6.1 VERTICAL CIRCULATION PLANS, SECTIONS AND
DETAILS
A7.1 PARTITION TYPES
A7.2 DOOR SCHEDULE, ROOM FINISH SCHEDULE,
GLAZING & DOOR ELEVATIONS
A7.3 EXTERIOR DOOR AND WINDOW DETAILS
A7.4 EXTERIOR DOOR, WINDOW AND CANOPY
DETAILS
A7.5 INTERIOR DOOR AND WINDOW DETAILS
A8.1 INTERIOR ELEVATIONS AND ENLARGED PLANS
A8.2 INTERIOR ELEVATIONS
A8.3 INTERIOR ELEVATIONS
A8.4 CASEWORK DETAILS
A9.1 OVERALL CEILING PLAN
FIRE PROTECTION
F0.1 GENERAL INFORMATION
F1.0 FIRE PROTECTION OVERALL FLOOR PLAN
DRAWING LIST
PLUMBING
P0.1 PLUMBING UNDERFLOOR PLAN - AREA A
P0.2 PLUMBING UNDERFLOOR PLAN - AREA B
P1.1 PLUMBING FLOOR PLAN - AREA A
P1.2 PLUMBING FLOOR PLAN - AREA B
P5.1 PLUMBING DETAILS
P5.2 PLUMBING DETAILS
P5.3 PLUMBING DETAILS
P6.1 PLUMBING SCHEDULES
P6.2 PLUMBING SCHEDULES
P6.3 PLUMBING SCHEDULES
MECHANICAL
M0.0 MECHANICAL GENERAL NOTES & SYMBOLS
M1.1 MECHANICAL FLOOR PLAN - AREA A
M1.2 MECHANICAL FLOOR PLAN - AREA B
M2.1 MECHANICAL ROOF PLAN - AREA A
M2.2 MECHANICAL ROOF PLAN - AREA B
M5.1 MECHANICAL DETAILS
M5.2 MECHANICAL DETAILS
M6.1 MECHANICAL SCHEDULES
M6.2 MECHANICAL SCHEDULES
M6.3 MECHANICAL SCHEDULES
M7.1 TEMPERATURE CONTROL ZONE PLAN
M7.2 MECHANICAL CONTROLS DETAILS
M7.3 MECHANICAL CONTROLS DETAILS
M7.4 MECHANICAL CONTROLS DETAILS
M7.5 MECHANICAL CONTROLS DETAILS
M7.6 MECHANICAL CONTROLS DETAILS
M7.7 MECHANICAL CONTROLS DETAILS
M7.8 MECHANICAL CONTROLS DETAILS
M7.9 MECHANICAL CONTROLS DETAILS
M7.10 MECHANICAL CONTROLS DETAILS
M7.11 MECHANICAL CONTROLS DETAILS
DRAWING LIST
MECHANICAL PIPING
MP0.0 MECHANICAL PIPING SITE PLAN
MP0.2 UNDERFLOOR MECHANICAL PIPING PLAN -
AREA B
MP1.1 MECHANICAL PIPING PLAN - AREA A
MP1.2 MECHANICAL PIPING PLAN - AREA B
MP3.1 MECHANICAL PIPING SECTIONS
MP4.1 ENLARGED MECHANICAL PIPING PLAN
MP5.1 MECHANICAL PIPING DETAILS
MP5.2 MECHANICAL PIPING DETAILS
MP6.1 MECHANICAL PIPING SCHEDULES
MP6.2 MECHANICAL PIPING SCHEDULES
ELECTRICAL
E0.0 ELECTRICAL GENERAL NOTES & SYMBOLS
E0.1 ELECTRICAL SITE PLAN
E1.1 LIGHTING FLOOR PLAN - AREA A
E1.2 LIGHTING FLOOR PLAN - AREA B
E2.1 POWER FLOOR PLAN - AREA A
E2.2 POWER FLOOR PLAN - AREA B
E3.1 SYSTEMS FLOOR PLAN - AREA A
E3.2 SYSTEMS FLOOR PLAN - AREA B
E4.1 ELECTRICAL ROOF PLAN - AREA A
E4.2 ELECTRICAL ROOF PLAN - AREA B
E5.1 ELECTRICAL DETAILS
E5.2 ELECTRICAL DETAILS
E5.3 ELECTRICAL DETAILS
E5.4 ELECTRICAL DETAILS
E6.1 ELECTRICAL SCHEDULES
E6.2 ELECTRICAL SCHEDULES
E6.3 ELECTRICAL SCHEDULES
TECHNOLOGY
T1.1 TECHNOLOGY FLOOR PLAN - AREA A
T1.2 TECHNOLOGY FLOOR PLAN - AREA B
T4.1 TECHNOLOGY ENLARGED PLANS
T5.1 TECHNOLOGY DETAILS
T5.2 TECHNOLOGY DETAILS
T6.1 TECHNOLOGY SCHEDULES
NORTH
TRUE
NORTH
TRUE
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
Wade C. Ross, P.E.
12/31/2027
FIRE PROTECTION
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF IOWA.
WADE C.
ROSS
20211
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
EXPOSED
PLUMBING AT
BARRIER
FREE
LAVATORIES
SHALL BE
INSULATED
LEVER OPERATING
CONTROLLED
SOAP DISPENSER
NOTE: SINKS IN COUNTERS TO BE
MOUNTED WITH RIM NO MORE
THAN 2'-10" HIGH AND WITH AT
LEAST 2'-3" KNEE CLEARANCE.
CLEAR
TYPICAL ACCESSIBLE
CLEARANCE AT LAVATORY
TYPICAL ACCESSIBLE
LAVATORY AND MIRROR
1'-3" 1'-3"
M
IN
M A
X
M
A X
M
A X6
A
.F .F
MIN
8"
MIN
11"
M
IN9
M
IN
M
IN
M A
X
17" MIN
TYPICAL URINAL
MOUNTING
CLEAR
15"
CLEAR
15"
"3
M
A X
W H
E R
E A
D A
A C
C E
S S
R E
Q U
IR
E
D
OF DOOR WIDTH WHEN
ON WALL BEYOND
DOOR
COAT RACK / COAT HOOK
T
Y P
M A
X
WALL MOUNTED TACKBOARD
AND MARKERBOARD
WALL MOUNTED LECTURE UNIT
BOARD
4'-0" MAX TO
HIGHEST OPERABLE
POINT - IF FIRE
EXTINGUISHER
OVER 40 LBS
3'-6" MAX HT.
FIRE EXTINGUISHER
CABINET
WALL PROTECTION
BUMPER GUARD
HANDRAIL
OR DOOR FRAME
3" TO CORNERGUARD
CORNER GUARD
DIAPER CHANGING
STATION
M
IN
M A
X
T O
B O
T T
O M
O F
E F
L E
C T
IV
S
U R
F A
C E
M
IR
R
O R
M A
X I
C
A B
IN
T
P
O J E
C
S
M
H A
N
MOP BASIN
MOP SHELF
TYPICAL JANITORS CLOSET
4'-0" MIN
4'-0" MIN
4'-0"x4'-0" STAINLESS
STEEL PANELS,
EACH WALL
1-1/2"
DIAMETER
GRAB BAR
TOILET
TISSUE
DISPENSER
SANITARY
NAPKIN
DISPOSAL
TOILET
FIXTURE
TOILET
FIXTURE
TOILET
TISSUE
DISPENSER
1-1/2"
DIAMETER
GRAB BAR
ACCESSIBLE TOILET 16" - 18"
T S
E A
T
60" MIN.
36" MIN. 6"
T
G R
IP
MAX.
12" 42" MIN.
28"
60" MIN.
TYPICAL TOILET NON-ACCESSIBLE
TOILET
TISSUE
DISPENSER
33"
TOILET
FIXTURE
18"
T S
E A
T
/2
7"-9"
TOILET
FIXTURE
TOILET
TISSUE
DISPENSER
1-1/2"
DIAMETER
GRAB BAR,
EACH SIDE
17" - 19"
T S
E A
T
AMBULATORY TOILET
54" MIN.
24" MIN.
MIN.
12"
M
IN
M
A X
35"-37"
PAPER TOWEL DISPENSER/
WASTE RECEPTACLE
HAND DRYER
NOTES:
1. FIXTURES SHOWN ARE FOR REFERENCE ONLY AND
ARE NOT PROJECT SPECIFIC. SEE PLUMBING
DRAWINGS AND SCHEDULES FOR FIXTURE TYPES.
2. MOUNTING HEIGHTS ARE TO BE COMPLIANT WITH 2010
ADA, ICC/ANSI A117.1-2007 AND THE IOWA
ACCESSIBILITY CODE- CHAPTER 302 PROVIDE ALL
NECESSARY CONCEALED BLOCKING AND
REINFORCEMENT FOR THE SECURE INSTALLATION OF
ALL EQUIPMENT AND ACCESSORIES.
3. EXPOSED PLUMBING BARRIER FREE LAVATORIES MUST
BE INSULATED OR OTHERWISE CONFIGURED TO
ELIMINATE POSSIBLE CONTACT.
4. SEE TOILET ACCESSORY SCHEDULE AND RESTROOM
ELEVATIONS, A8.1
PAPER TOWEL
DISPENSER
2'-0" AT SIDEWALLS
AT COUNTER SINKS
1'-6" AT SIDEWALLS
AT LAVATORY
DRINKING FOUNTAIN
WHEELCHAIR ACCESSIBLE
(CANTILEVERED STYLE)
17" - 19"
8" MIN
9" MIN
MAX
6"2
M
IN
T O
P O
F S
P O
U T
' M
A X
TOWEL BAR
ACCESSIBLE
ROBE/COAT HOOK
ROBE/COAT
HOOK
TOILET ACCESSORIES
6"
SANITARY
NAPKIN
DISPOSAL
CHAIR RAILING
- SEE SPEC.
FINISHED FLOOR
℄6
FINISHED WALL
CHAIR RAIL MOUNTING
HEIGHT
TYPICAL MONITOR
MOUNTING
4'-2"
THE FOLLOWING SYSTEMS ARE A DESIGN/BUILD RESPONSIBILITY OF THE
CONTRACTOR OR PRODUCT MANUFACTURER AND WILL REQUIRE THE DEFERRED
SUBMITTAL OF DESIGN WORK TO THE CITY OF WATERLOO AND IOWA STATE FIRE
MARSHAL'S OFFICE FOR PLAN REVIEW AND PERMITTING:
1. FIRE SPRINKLER SYSTEMS
DEFERRED SUBMITTALS
REFERENCE SECTION 01 2300 ALTERNATE BID ITEMS AND 00 4100 FORM OF BID
WITHIN OF THE PROJECT MANUAL FOR THE SCHEDULE OF BID ALTERNATES TO
BE INCLUDED WITH THE BID PACKAGE
ALTERNATE NO. 1 - BRIDGE CRANE
ALTERNATE NO. 2 - 8" PCC IN LIEU OF GRAVEL FOR DRIVE & PARKING
ALTERNATE NO. 3 - 8" PCC IN LIEU OF GRAVEL @ MAIN BUILDING DRIVE
ALTERNATE NO. 4 - HIGH DENSITY STORAGE SYSTEM
ALTERNATE NO. 5 - PHOTOVOLTAIC ARRAY SIZE
BID ALTERNATES
A. REFER TO GENERAL INFORMATION SHEETS FOR SYMBOLS AND ABBREVIATIONS.
B. DO NOT SCALE DRAWINGS TO DETERMINE DIMENSIONS. IF A REQUIRED
DIMENSION IS NOT INDICATED, CONTACT THE ARCHITECT FOR DETERMINATION.
C. THE CONTRACTOR SHALL NOT CUT STRUCTURAL MEMBERS/ELEMENTS IN A
MANNER RESULTING IN A REDUCTION OF LOAD CARRYING CAPACITY OR
LOAD/DEFLECTION RATIO.
D. PAINT ALL STEEL DOORS, DOOR FRAMES, INTERIOR BORROW LITE FRAMES,
LINTELS AND OTHER EXPOSED METAL ITEMS UNLESS OTHERWISE NOTED OR
SHOWN.
PROJECT GENERAL NOTES
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
ABBREVIATIONS
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
LTTR LONG-TERM THERMAL
RESISTANCE
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PCC PRE-CAST CONCRETE
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS
DEMOLITION KEYNOTE
WINDOW TYPE
TOILET ACCESSORY
WALL TYPE
ROOF PITCH
DOOR NUMBER
TYPICAL KEYNOTE
CEILING/ SOFFIT
HEIGHT
D#.#
MATL
1'-0"
T20 SHOWER ROD & CURTAIN
-1
SLOPE: 1/4"
SLOPE/ROOF SLOPE
WALL SECTION
INTERIOR ELEVATION
COLUMN GRID
ELEVATION
REVISION NOTE
ENLARGED CALLOUT
ROOM DESIGNATION
BREAK LINE
DETAIL #
SHEET #
DETAIL #
SHEET #
A8.1
EXTERIOR ELEVATION
DETAIL #
SHEET #
A8.1
A8.1
A8.1
BUILDING SECTION
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
DETAIL #
SHEET #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
ROOM
NAME
0"
-6" CHANGE IN LEVEL
A. REFER TO LIFE SAFETY PLAN (LS-2) AND PARTITIONS FOR LOCATIONS OF RATED
PARTITIONS, SEPERATION INFORMATION, REFRENCE (A7.1) FOR PARTITION
TYPES. ALL INTERIOR PARTITIONS ARE TYPE P6 UNLESS OTHERWISE NOTED OR
SHOWN.
B. CONTRACTOR TO PROVIDE ALL ADDITIONAL FRAMING NECESSARY FOR ALL
OPENINGS AND SUPPLEMENTAL FRAMING ABOVE PARTITIONS.
C. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR SYSTEM RELATED
PENETRATIONS NOT SHOWN.
D. CONTRACTOR SHALL MAINTAIN THE BUILDING IN A WEATHERPROOF CONDITION
AT ALL TIMES.
E. PROJECTS SHALL REMAIN IN COMPLIANCE WITH ALL ASPECTS OF ALL
GOVERNING CODES AND ORDINANCES DURING THE COURSE OF
CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, EXITING, FIRE ALARM
SYSTEM(S) SMOKE/FIRE DETECTION SYSTEM(S), SPRINKLER SYSTEM(S).
F. TEMPORARY BARRICADES AS PERTAINING TO CONTRACTOR'S ACTIVITIES SHALL
BE INSTALLED TO PREVENT POSSIBLE INJURY TO PERSONS IN AND AROUND
DEMOLITION AND CONSTRUCTION AREAS IN ACCORDANCE WITH OSHA
REQUIREMENTS. COORDINATE WITH OWNER..
G. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR TO PROVIDE COMPLETE
WORKING SYSTEMS FOR ALL NEW ELEMENTS AND TO COORDINATE THEIR
WORK WITH ALL OTHER TRADES.
H. ALL CONTRACTORS SHALL PROVIDE NEW, UNDAMAGED MATERIALS UNLESS
OTHERWISE SPECIFIED.
I. STORE MATERIALS IN SUCH A MANNER AS NOT TO OVERSTRESS, OVERLOAD, OR
OTHERWISE PUT AN UNSAFE LOAD ON ANY STRUCTURE DURING
CONSTRUCTION.
J. INSTALL ALL WORK IN ACCORDANCE WITH CURRENT APPLICABLE CODES,
PUBLISHED STANDARDS, AND ACCEPTABLE CONSTRUCTION STANDARDS.
K. DETAILS ARE GENERALLY TYPICAL AND ARE NOT TO BE CONSTRUED AS LIMITED
TO THOSE AREAS SPECIFICALLY INDICATED. REVIEW ANY QUESTIONS OR
CONFLICTING INFORMATION WITH THE DESIGN PROFESSIONAL PRIOR TO
FABRICATION OR INSTALLATION.
L. CONTRACTOR SHALL VERIFY DIMENSIONS IN FIELD PRIOR TO BEGINNING
CONSTRUCTION.
M. HINGE SIDE OF DOOR JAMBS TO BE LOCATED 4” FROM NEAREST WALL
INTERSECTION UNLESS OTHERWISE NOTED.
GENERAL NOTES
M
IN
15" MAX
CL
M
IN
M A
X
TRANSFER - TYPE
SHOWER COMPARTMENT
18"
3" MAX
C
L E
A R
1-1/2"
DIAMETER
GRAB BAR
L-SHAPED
FOLDING
SHOWER
SEAT
CONTROL WALL BACK WALL SEAT WALL
SHOWER
CONTROL
SHOWER
FAUCET
ENTRANCE
SHOWER CURTAIN
CURTAIN ROD
22"-23"
1 1/2" MAX15"-16"
14"-15"
ALLOWANCES
NOT APPLICABLE
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
IAARNG PROJECT #:
CONTRACT #:
/1
/2
:5 :2
A
M G0.1
GENERAL
INFORMATION
KNG/SH
0231514.00
WATERLOO VEHICLE
MAINTENANCE SHOP
IOWA NATIONAL GUARD
3106 AIRPORT BLVD
WATERLOO, IA 50703
03/20/2026
03/20/2026
ISSUED FOR
CONSTRUCTION
LS
190185
C485X2118
SCALE: 3/8" = 1'-0"
STANDARD MOUNTING HEIGHTS
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
IAARNG PROJECT #:
CONTRACT #:
/1
/2
:5 :2
A
M LS1.1
LIFE SAFETY CODE
ANALYSIS
KNG/SH
KV
0231514.00
WATERLOO VEHICLE
MAINTENANCE SHOP
IOWA NATIONAL GUARD
3106 AIRPORT BLVD
WATERLOO, IA 50703
03/20/2026
03/20/2026
ISSUED FOR
CONSTRUCTION
LS
190185
C485X2118
Iowa Army National Guard – Waterloo Vehicle Maintenance Shop 3106 Airport Blvd, Waterloo, IA 50703 Code Analysis
Project Summary: New building consists of approximately 24,810 sf, single story structure. the building is to be constructed of load bearing Pre-cast concrete exterior walls with a steel roof structure. The buildings usage shall be the regular vehicle maintenance and cleaning. The spaces in the building shall include offices, classroom, latrines, storage, mechanical, electrical, and janitorial spaces.
Applicable Codes (Including State of Iowa Amendments):
2015 International Building Code 2012 International Energy Conservation Code 2024 International Mechanical Code 2015 International Fire Code 2023 National Electrical Code 2012 NFPA 101 Life Safety Code 2021 Uniform Plumbing Code 2010 ADA Standards
IBC 2015
Chapter 3 Use and Occupancy
311.2 Moderate-hazard storage, Group S-1. Storage Group S-1 occupancies are buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following:
Books and paper in rolls or packs Boots and shoes Cardboard and cardboard boxes Motor vehicle repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 307.1(1) (see Section 406.8)
304.1 Business Group B. Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts.
Chapter 4 Special Detailed Requirements Based on Use and Occupancy
Section 406 Motor-Vehicle-Related Occupancies
406.1 General. Motor-vehicle-related occupancies shall comply with Sections 406.1 through 406.8.
406.8 Repair garages. Repair garages shall be constructed in accordance with the International Fire Code and Sections 406.8.1 through 406.8.6. This occupancy shall not include motor fuel-dispensing facilities, as regulated in Section 406.7.
406.8.1 Mixed uses. Mixed uses shall be allowed in the same building as a repair garage subject to the provisions of Section 508.1.
406.8.2 Ventilation. Repair garages shall be mechanically ventilated in accordance with the International Mechanical Code. The ventilation system shall be controlled at the entrance to the garage.
406.8.3 Floor surface. Repair garage floors shall be of concrete or similar noncombustible and nonabsorbent materials.
Exception: Slip-resistant, nonabsorbent, interior floor finishes having a critical radiant flux not more than 0.45 W/cm2, as determined by NFPA 253, shall be permitted.406.8.4 Heating equipment. Heating equipment shall be installed in accordance with the International Mechanical Code.
406.8.4 Heating equipment. Heating equipment shall be installed in accordance with the International Mechanical Code.
[F] 406.8.6 Automatic sprinkler system. A repair garage shall be equipped with an automatic sprinkler system in accordance with Section 903.2.9.1.
Chapter 5 Heights and Areas
504.2 Mixed occupancy. In a building containing mixed occupancies in accordance with Section 508, no individual occupancy shall exceed the height and number of story limits specified in this section for the applicable occupancies.
Areas of Buildings:
(1) B BUSINESS 12,015 SF
(1) S-1 STORAGE 12,795 SF
Total Building Area 24,810 SF
Table 504.3 Allowable Height in Feet Above Grade Plane.
Construction Type II-B for Occupancy Group B, S Sprinklered = 75 feet.
Conclusion: Buildings height is 34' < 75'.
Table 504.4 Allowable Number of Stories Above Grade Plane Construction Type II-B for Occupancy Group.
B Sprinklered = 4 Stories S-1 Sprinklered = 3 Stories
Conclusion: 1 story is acceptable.
Table 506.2 Allowable Area Factor
Group B, S1, Type IIB = 92,000 SF Group S-1, S1, Type IIB = 70,000 SF
(Equation 5-1) Aa = At + (NS × If)
Group B:
Aa = 92,000 + (23,000 x .75) Aa = 109,250 SF
Group S-1 Aa = 70,000 + (17,500 x .75) Aa = 83,125 SF
Conclusion: 24,810 SF < 83,125 SF max allowable area
Section 508 Mixed Use and Occupancy
508.1 General. Each portion of a building shall be individually classified in accordance with Section 302.1. Where a building contains more than one occupancy group, the building or portion thereof shall comply with the applicable provisions of Section 508.2, 508.3 or 508.4, or a combination of these sections.
508.2 Accessory occupancies. Accessory occupancies are those occupancies that are ancillary to the main occupancy of the building or portion thereof. Accessory occupancies shall comply with the provisions of Sections 508.2.1 through 508.2.4.
508.2.1 Occupancy classification. Accessory occupancies shall be individually classified in accordance with Section 302.1. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that space.
508.2.2 Allowable building height. The allowable height and number of stories of the building containing accessory occupancies shall be in accordance with Section 504 for the main occupancy of the building.
508.2.3 Allowable building area. The allowable area of the building shall be based on the applicable provisions of Section 506 for the main occupancy of the building. Aggregate accessory occupancies shall not occupy more than 10 percent of the floor area of the story in which they are located and shall not exceed the tabular values for non-sprinklered buildings in Table 506.2 for each such accessory occupancy.
508.2.4 Separation of occupancies. No separation is required between accessory occupancies and the main occupancy.
Exceptions:
1. Group H-2, H-3, H-4 and H-5 occupancies shall be separated from all other occupancies in accordance with Section 508.4.
508.3 Nonseperated occupancies. Buildings or portions of buildings that comply with the provisions of this section shall be considered as nonseperated occupancies.
508.3.1 Occupancy classification. Nonseperated occupancies shall be individually classified in accordance with Section 302.1. The requirements of this codeshall apply to each portion of the building based on the occupancy classification of that space. In addition, the most restrictive provisions of Chapter 9 that apply to the nonseperated occupancies shall apply to the total nonseperated occupancy area. Where nonseperated occupancies occur in a high-rise building, the most restritive requirments of Section 403 that apply to the nonsepreated occupancies shall apply throughout the high-rise building.
508.4 Separated occupancies. Buildings or portions of buildings that comply with the provisions of this section shall be considered as separated occupancies.
Table 508.4 Required Separation of Occupancies (Hours) B/S-1 = No Seperation (0 Hours) B/H-3 = 1 Hour (Sprinklered) S-1/H-3 = 1 Hour (Sprinklered)
Chapter 6 Types of Construction
602.2 Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code.
Table 601 Fire-Resistance Rating Requirements for Building Elements (Hours)
Building Element Type II B Primary structural frame (see Section 202) 0 Bearing walls
Exterior 0 Interior 0
Nonbearing walls and partitions (see Table 602) Exterior 0
Nonbearing walls and partitions Interior 0
Floor construction and associated 0 secondary members
(See Section 202) Roof construction and associated 0 secondary members
(See Section 202) Conclusion: 0 Hours of fire resistance required for all building elements.
Table 602:
Fire-Resistance Rating Requirements for Exterior Walls Based on Fire Separation Distance
Fire Separation Distance =Type of Construction Occupancy Group: B/S-1
X ≥ 30 All 0/0 Conclusion: Where X ≥30', All Types of Construction have 0 hours of Fire-Resistance for Exterior Walls.
Chapter 7 Fire and Smoke Protection Features
Section 707 Fire Barriers
707.3 Fire-resistance rating. The fire-resistance rating of fire barriers shall comply with this section.
707.3.9 Separated occupancies. Where the provisions of Section 508.4 are applicable, the fire barrier separating mixed occupancies shall have a fire-resistance rating of not less than that indicated in Table 508.4 based on the occupancies being separated.
707.5 Continuity. Fire barriers shall extend from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above and shall be securely attached thereto. Such fire barriers shall be continuous through concealed space, such as the space above a suspended ceiling. Joints and voids at intersections shall comply with Sections 707.8 and
707.6 Openings. Openings in a fire barrier shall be protected in accordance with Section 716.
Openings shall be limited to a maximum aggregate width of 25 percent of the length of the wall, and the maximum area of any single opening shall not exceed 156 square feet (15 m2). Openings in enclosures for exit access stairways and ramps, interior exit stairways and ramps and exit passageways shall also comply with Sections 1019, 1023.4 and 1024.5, respectively.
707.7 Penetrations. Penetrations of fire barriers shall comply with Section 714.
707.9 Voids at intersections. The voids created at the intersection of a fire barrier and a nonfire-resistance-rated roof assembly or a nonfire-resistance-rated exterior wall assembly shall be filled. An approved material or system shall be used to fill the void, and shall be securely installed in or on the intersection for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to retard the passage of fire and hot gases.
Section 714 Penetrations
714.3.1 Through penetrations. Through penetrations of fire-resistance-rated walls shall comply with Section 714.3.1.1 or 714.3.1.2.
Section 716 Opening Protectives
Table 716.5 Opening Fire Protection Assemblies, Ratings and Markings
Type of Assembly Req. Wall Fire Door Vision Panel Fire Glazing Other Fire Barriers 1 3/4 Max Size Tested D-H
Section 717 Ducts and Air Transfer Openings
717.3.1 Damper testing. Dampers shall be listed and labeled in accordance with the standards in this section.
Table 717.3.2.1 Fire Damper Rating
Type of Penetration Minimum Damper Rating Less Than 3-hour fire-resistance-rated assemblies 1.5 3-hour or greater fire-resistance-rated assemblies 3
717.5.2 Fire barriers. Ducts and air transfer openings of fire barriers shall be protected with approved fire dampers installed in accordance with their listing. Ducts and air transfer openings shall not penetrate enclosures for interior exit stairways and ramps and exit passageways, except as permitted by Sections 1023.5 and 1024.6, respectively.
717.5.4.1 Corridors. Duct and air transfer openings that penetrate corridors shall be protected with dampers as follows:
1. A corridor damper shall be provided where corridor ceilings, constructed as required for the corridor walls as permitted in Section 708.4, Exception 3, are penetrated.
2. A ceiling radiation damper shall be provided where the ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly, constructed as permitted in Section 708.4, Exception 2, is penetrated.
3. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor enclosure required to have smoke and draft control doors in accordance with Section 716.5.3.
Chapter 9 Fire Protection Systems
Section 903 Automatic Sprinkler Systems
903.2 Where Required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12.
Conclusion: Since an Occupancy Type B is not specifically listed and the space is not used for automotive repair an Automatic Sprinkler System is not required.
[F] 903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406, as shown:
1. Buildings having two or more stories above grade plane, including basements, with a fire area containing a repair garage exceeding 10,000 square feet (929 m2).
2. Buildings not more than one story above grade plane, with a fire area containing a repair garage exceeding 12,000 square feet (1115 m 2).
3. Buildings with repair garages servicing vehicles parked in basements.
4. A Group S-1 fire area used for the repair of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2).
[F] 903.3 Installation requirements. Automatic sprinkler systems shall be designed and installed in accordance with Sections 903.3.1 through 903.3.8.
[F] 903.3.1 Standards. Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1 unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other chapters of this code, as applicable.
[F] 903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Sections 903.3.1.1.1 and 903.3.1.1.2.
Section 906 Portable Fire Extinguishers
906.1 Where required. Portable fire extinguishers shall be installed in all the following locations:
1. In Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Conclusion: Seven portable fire extinguishers shall be provided for access by occupants due to travel distance.
Section 907 Fire Alarm and Detection Systems
907.2 Where required. New buildings and structures. An approved fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and provide occupant notification in accordance with Section 907.5 unless other requirements are provided by another section of this code.
Conclusion: A new Fire Alarm System shall be provided for the project.
Section 912 Fire Department Connections
[F] 912.1 Installation. Fire department connections shall be installed in accordance with the NFPA standard applicable to the system design and shall comply with Sections 912.2 through 912.6.
[F] 912.2 Location. With respect to hydrants, driveways, buildings and landscaping, fire department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of fire department connections shall be approved by the fire chief.
Chapter 10 Means of Egress
Section 1003 General Means of Egress
1003.2 Ceiling height. The means of egress shall have a ceiling height of not less than 7 feet 6 inches (2286 mm).
1003.4 Floor surface. Walking surfaces of the means of egress shall have a slip-resistant surface and be securely attached.
1003.5 Elevation change. Where changes in elevation of less than 12 inches (305 mm) exist in the means of egress, sloped surfaces shall be used. Where the slope is greater than one unit vertical in 20 units horizontal (5-percent slope), ramps complying with Section 1012 shall be used. Where the difference in elevation is 6 inches (152 mm) or less, the ramp shall be equipped with either handrails or floor finish materials that contrast with adjacent floor finish materials.
Table 1004.1.2 Maximum Floor Area Allowances Per Occupant
Function of Space Occupant Load Factor Accessory Storage Areas, Mechanical Equipment Rooms 300 SF Office Areas (Assume is Business Occupancy) 100 SF Industrial Areas 100 SF Educational (Classroom area) 20 SF(Net) Locker Rooms 50 SF Conclusion: See Sheet LS1.2
1004.1.2 Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.2. For areas without fixed seating, the occupant load shall be not less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table
1004.1.2. Where an intended function is not listed in Table 1004.1.2, the building official shall establish a function based on a listed function that most nearly resembles the intended function.
1004.6 Multiple occupancies. Where a building contains two or more occupancies, the means of egress requirements shall apply to each portion of the building based on the occupancy of that space.
Where two or more occupancies utilize portions of the same means of egress system, those egress components shall meet the more stringent requirements of all occupancies that are served.
Section 1005 Means of Egress Sizing
1005.2 Minimum width based on component. The minimum width, in inches (mm), of any means of egress components shall be not less than that specified for such component, elsewhere in this code.
1005.3 Required capacity based on occupant load. The required capacity, in inches (mm), of the means of egress for any room, area, space or story shall be not less than that determined in accordance with Sections 1005.3.1 and 1005.3.2.
1005.7.1 Doors. Doors, when fully opened, shall not reduce the required width by more than 7 inches (178mm). Doors in any position shall not reduce the required width by more than one-half.
Section 1006 Number of Exits and Exit Access Doorways
1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1.
Table 1006.2.1 Spaces with One Exit or Exit Access Doorway
Occupancy Max Load of Space Common Path of Egress Travel (ft) Sprinklered Type B 49 100ft Type H 3 75 ft Type S 29 100ft
Section 1007 Exit and Exit Access Doorway Configuration
1007.1.1 Two exits or exit access doorways. Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them.
Interlocking or scissor stairways shall be counted as one exit stairway.
Exceptions:
2. Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the separation distance shall be not less than one-third of the length of the maximum overall diagonal dimension of the area served.
Section 1008 Means of Egress Illumination
1008.1 Means of egress illumination. Illumination shall be provided in the means of egress in accordance with Section 1008.2. Under emergency power, means of egress illumination shall comply with Section 1008.3.
1008.2 Illumination required. The means of egress serving a room or space shall be always illuminated that the room or space is occupied.
Section 1009 Accessible Means of Egress
1009.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress.
Where more than one means of egress are required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress.
Conclusion: The building has been provided with a minimum of two accessible means of egress.
Section 1010 Doors, Gates, and Turnstiles
1010.1.1 Size of doors. The required capacity of each door opening shall be sufficient for the occupant load thereof and shall provide a minimum clear width of 32 inches (813 mm). Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees (1.57 rad). Where this section requires a minimum clear width of 32 inches (813 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches (813 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. The height of door openings shall be not less than 80 inches (2032 mm).
1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type.
Exceptions:
1. Private garages, office areas, factory, and storage areas with an occupant load of 10 or less.
1010.1.1.1 Projections into clear width. There shall not be projections into the required clear width lower than 34 inches (864 mm) above the floor or ground. Projections into the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm) above the floor or ground shall not exceed 4 inches (102 mm).
1010.1.4.4 Security grilles. In Groups B and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles.
1010.1.5 Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal (2-percent slope).
Conclusion: Stoops shall be provided at all Exterior door landings.
1010.1.6 Landings at doors. Landings shall have a width not less than the width of the stairway or the door, which-ever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches (1118 mm).
Section 1013 Exit Signs
1013.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Chapter 11 Accessibility
1103.2.2 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individuals with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet in area and located 7 inches or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements.
Conclusion: Able-bodied is required to perform work in the facility. Accessibility is being provided to all areas open to the general public. Minimal accessibility has been provided to other areas.
1FB
1FP
1FW
1FB
F
B
F
B
F
B F
B F
B
F
B
1FB
F
B
1FB 1FB
A. SEE CIVIL DRAWINGS FOR INFORMATION INCLUDING
CONCRETE SIDEWALKS, CONCRETE PADS, AND PARKING
CONFIGURATIONS. CIVIL BACKGROUND DRAWING
INFORMATION IS FOR REFERENCE ONLY.
B. REFER TO ELECTRICAL DRAWINGS FOR FIRE ALARM
NOTIFICATION AND EMERGENCY EGRESS LIGHTING
LOCATIONS.
C. REFER TO PARTITION TYPES FOR FURTHER FIRE
SEPARATION REQUIREMENTS.
D. ALL FIRE RATED ASSEMBLIES SHALL BE INSTALLED IN
STRICT ACCORDANCE WITH TESTED ASSEMBLIES
INDICATED.
E. EXTEND FIRE RATED PARTITIONS, BARRIERS, AND OTHER
SEPARATIONS TO BOTTOM OF ROOF/FLOOR DECK ABOVE
(OR AS DIRECTED BY UL ASSEMBLY) AND TO EXTERIOR
WALL. SEAL JOINT BETWEEN EDGES OF PARTITION WITH
FIRE RATED SEALANT AND/OR INTUMESCENT ASSEMBLY.
F. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES SHALL BE
FIRE-SEALED IN ACCORDANCE WITH APPROVED
MANUFACTURER'S DETAIL FOR LOCATION, TYPE OF
CONSTRUCTION, PENETRATING ITEM AND RATING
REQUIRED.
G. ALL DUCTWORK, DIFFUSERS, GRILLES, LIGHT FIXTURES,
AND ELECTRICAL DEVICES PENETRATING FIRE-RATED OR
SMOKE RESISTANT WALLS, CEILINGS, AND FLOORS SHALL
HAVE THE APPROPRIATE TYPE OF FIRE/SMOKE DAMPER IN
ACCORDANCE WITH THE TYPE OF CONSTRUCTION BEING
PENETRATED AND THE FIRE/SMOKE RATING REQUIRED.
ASSEMBLIES SHALL BE UL-LISTED FOR INSTALLATION IN
THE ASSEMBLY AND SHALL BE INSTALLED SUCH THAT THE
FIRE/SMOKE RATING IS NOT COMPROMISED. REFER TO
MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR
PENETRATIONS THAT MAY NOT BE SHOWN HERE.
H. SMOKE RESISTANT CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF ALL APPLICABLE CODES. AREA SHALL
BE SEPARATED FROM THE REMAINDER OF THE BUILDING
AND BE OF CONSTRUCTION CAPABLE OF RESISTING THE
PASSAGE OF SMOKE. THE PARTITIONS SHALL EXTEND
FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR
ROOF ASSEMBLY ABOVE. DOORS SHALL BE SELF OR
AUTOMATIC CLOSING. DOORS SHALL NOT HAVE AIR
TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN
EXCESS OF CLEARANCE PERMITTED WITH ACCORDANCE
TO NFPA 80.
LIFE SAFETY GENERAL NOTES LIFE SAFETY LEGEND
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS CAPACITY
1 HOUR FIRE BARRIER WALL
CONTROLLED ACCESS - ALWAYS
UNLOCKED IN DIRECTION OF EGRESS
FEC
TRAVEL DISTANCE TO AN EXIT
HAZARDOUS LOCATION
COMMON PATH OF TRAVEL
CAPACITYCLR
EXTERIOR
EXIT
0" 180
FIRE EXTINGUISHER CABINET
CA
1 HOUR FIRE PARTITION WALL
1 HOUR FIRE WALL
FIRE RATINGS
EGRESS
DE DELAYED EGRESS
KB KNOX BOX
OCCUPANCY
ROOM AREA
OCCUPANCY TYPE
OCCUPANCY LOAD USED
OCCUPANCY LOAD FACTOR
ROOM NAME
MISCELLANEOUS
FEB FIRE EXTINGUISHER BRACKET
XX EGRESS PATH TAG
150 SF
XXXX
000 00
Name
131 432
F
E
D
C
B
A
5 6 7 8 9 10 11 12
1881 SF
AS&M
UNHEATED
STORAGE
300 7
109 SF
BUS
INSPECTOR
100 2
VESTIBULE
373 SF
AS&M
ELECT
300 2
535 SF
AS&M
MAINTENANCE/
STORAGE
300 2
67 SF
AS&M
FIRE
RISER
ROOM
300 1
VESTIBULE
565 SF
AS&M
MECH
300 2 159 SF
BUS
PRODUCTION
CONTROLLER
100 2
157 SF
BUS
SUPERVISOR
100 2
138 SF
BUS
IT
SUPPORT
100 2
333 SF
AS&M
BATTERY
300 2
724 SF
CLAS
CLASSROOM
20 37
892 SF
AS&M
SUPPLY
ROOM
300 4
555 SF
AS&M
TOOL
ROOM
300 2
380 SF
AS&M
BULK
POL
300 2
666 SF
ASS-T
BREAK
ROOM
15 46
779 SF
AS&M
BULKY
EQUIPMENT
STORAGE
300 3
461 SF
LOCK
MENS
50 9
373 SF
LOCK
WOMENS
50 8
88 SF
AS&M
COMM
300 1
98 SF
AS&M
LAUNDRY
300 1
86 SF
LIB-S
LIBRARY
100 1
VESTIBULE
CORRIDOR
C O
R R
ID
O
R
290 SF
BUS
LOBBY
100 5
CORRIDOR ALCOVE
2037 SF
WARE
WORK
BAY
500 6
2036 SF
WARE
WORK
BAY
500 6
2028 SF
WARE
WORK
BAY
500 6 2980 SF
WARE
WARM
UP/
WASH
BAY
500 6
82 SF
AS&M
JANITOR
300 1
CAPACITY CLRUSED
EXTERIOR EXIT
33"2206
OCCUPANCY LEGEND
B
H-3 (ACCESSORY
TO BUSINESS)
S-1
ED
B
A
C
CAPACITY CLRUSED
EXTERIOR EXIT
33"2206
CAPACITY CLRUSED
EXTERIOR EXIT
33"2203
CAPACITY CLRUSED
EXTERIOR EXIT
68"45348
CAPACITY CLRUSED
EXTERIOR EXIT
33"22038
F E
B
F E
B
FEC
EWC
F E
B
F E
B
F E
C
F E
B A
R E
A A
A R
E A
B
A R
E A
A
A R
E A
B
CAPACITY CLRUSED
EXTERIOR EXIT
33"22042
CAPACITY CLRUSED
EXTERIOR EXIT
80"5331
CAPACITY CLRUSED
EXTERIOR EXIT
33"22013
CAPACITY CLRUSED
EXTERIOR EXIT
33"2208
CAPACITY CLRUSED
EXTERIOR EXIT
33"2203
TOTAL: 24,805 SQ FT
KB
EWC DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
IAARNG PROJECT #:
CONTRACT #:
/1
/2
:5 :2
A
M LS1.2
FIRST FLOOR LIFE
SAFETY
KNG/SH
KV
0231514.00
WATERLOO VEHICLE
MAINTENANCE SHOP
IOWA NATIONAL GUARD
3106 AIRPORT BLVD
WATERLOO, IA 50703
03/20/2026
03/20/2026
ISSUED FOR
CONSTRUCTION
LS
190185
C485X2118
0 4 8 16
NORTH
PLAN
LAUNDRY ROOM ( < 100 SF) 0 HR
FIRE PUMP ROOM 0 HR
CORRIDORS (CONST TYPE) 0 HR
ROOF CONST/SECONDARY MEMBERS 0 HR
FLOOR CONST/SECONDARY MEMBERS 0 HR
INTERIOR NON-BEARING WALLS 0 HR
EXTERIOR NON-BEARING WALLS 0 HR
INTERIOR BEARING WALLS 0 HR
EXTERIOR BEARING WALLS 0 HR
PRIMARY STRUCTURAL FRAME 0 HR
FIRE RATING
PROPOSED BUILDING HEIGHT: 1 STORIES 30 FEET
ALLOWABLE BUILDING HEIGHT
(CONST TYPE): IIB
3 STORIES 75 FEET
PROJECT TOTAL AREA 24,810 SF
FIRST FLOOR 24,810 SF
TOTAL/FLOOR
PROPOSED AREA (CONST TYPE):
ALLOWABLE AREA (CONST TYPE): 83,125 SF
BUILDING HEIGHT AND AREA
CONSTRUCTION TYPE: IIB
MIXED OCCUPANCY: B & S-1 (NON-SEPARATED)
SPRINKLERED
PROPOSED BUILDING
BUILDING CONSTRUCTION AND OCCUPANCY
2010 ADA STANDARDS
2021 INTERNATIONAL PLUMBING CODE
2012 NFPA 101 LIFE SAFETY CODE
2020 NATIONAL ELECTRIC CODE
2015 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL MECHANICAL CODE
2012 INTERNATIONAL ENERGY CONSERVATION CODE
2015 INTERNATIONAL BUILDING CODE
APPLICABLE CODES
NEW BUILDING CONSISTS OF APPROXIMATELY 24,810 SF, SINGLE
STORY STRUCTURE. THE BUILDING IS PROPOSED TO BE
CONSTRUCTED OF LOAD BEARING PRECAST EXTERIOR WALLS
WITH A STEEL ROOF STRUCTURE. THE BUILDINGS USAGE SHALL
BE THE REGULAR VEHICLE MAINTENANCE AND CLEANING. THE
SPACES IN THE BUILDING SHALL INCLUDE OFFICES,
CLASSROOM, LATRINES, STORAGE, MECHANICAL, ELECTRICAL,
AND JANITORIAL SPACES.
WORK DESCRIPTION
3106 AIRPORT BLVD WATERLOO, IA 50703
WATERLOO FIELD MAINTENANCE SHOP
CODE INFORMATIONOCCUPANCY LOAD TABLE
NUMBER NAME OCCUPANCY AREA
OCCUPANCY
FACTOR
OCCUPANT
LOAD REMARKS
FINISHED FLOOR
100 VESTIBULE B 97 SF 0 SF
101 LOBBY B 290 SF 100 SF 5
101A CORRIDOR B 334 SF 0 SF
101B CORRIDOR B 448 SF 0 SF
101C CORRIDOR B 235 SF 0 SF
102 INSPECTOR B 109 SF 100 SF 2
103 SUPERVISOR B 157 SF 100 SF 2
104 MENS B 461 SF 50 SF 9
105 IT SUPPORT B 138 SF 100 SF 2
106 WOMENS B 373 SF 50 SF 8
107 LAUNDRY B 98 SF 300 SF 1
108 ALCOVE S-1 417 SF 0 SF
109 BULKY EQUIPMENT STORAGE S-1 779 SF 300 SF 3
110 BATTERY H-3 (ACCESSORY TO BUSINESS) 333 SF 300 SF 2
111 WORK BAY S-1 2037 SF 500 SF 6 *NOTE 3,4
112 WORK BAY S-1 2036 SF 500 SF 6 *NOTE 3,4
113 WORK BAY S-1 2028 SF 500 SF 6 *NOTE 3,4
114 WARM UP/ WASH BAY S-1 2980 SF 500 SF 6 *NOTE 3,4
115 BULK POL S-1 380 SF 300 SF 2
116 TOOL ROOM S-1 555 SF 300 SF 2
117 PRODUCTION CONTROLLER B 159 SF 100 SF 2
118 SUPPLY ROOM S-1 892 SF 300 SF 4
119 BREAK ROOM B 666 SF 15 SF 46 *NOTE 1
120 JANITOR B 82 SF 300 SF 1
121 COMM B 88 SF 300 SF 1
122 MAINTENANCE/ STORAGE B 535 SF 300 SF 2
123 MECH B 565 SF 300 SF 2
124 UNHEATED STORAGE S-1 1881 SF 300 SF 7
125 ELECT B 373 SF 300 SF 2
126 VESTIBULE B 54 SF 0 SF
127 CLASSROOM B 724 SF 20 SF 37 *NOTE 2
127A LIBRARY B 86 SF 100 SF 1 *NOTE 2
128 VESTIBULE B 69 SF 0 SF
129 FIRE RISER ROOM B 67 SF 300 SF 1
TOTAL OCCUPANTS: 168
SCALE: 3/32" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
ACTUAL STAFF LOAD WAS UTILIZED TO DETERMINE PLUMBING
FACILITY REQUIRMENTS FOR THIS PROJECT PER STATE
PLUMBING CODE TABLE 403.1. THE GUARD WILL USE ACTUAL
LOAD OF 25 OCCUPANTS. INSTEAD OF THE CALCULATED
LOAD.
PLUMBING REQUIREMENTS
EGRESS DOOR WIDTH .15" x OCC LOAD
EGRESS CORRIDOR WIDTH 44"
DEAD END CORRIDORS 50 FT MAX
EXIT TRAVEL DISTANCE (H-3) 150 FT MAX
EXIT TRAVEL DISTANCE (S-1) 250 FT MAX
EXIT TRAVEL DISTANCE (B) 300 FT MAX
EGRESS
FIRE RATED WALL ASSEMBLIES
CMU - UL U937
PRECAST CONCRETE PANEL
THICKNESS (IN.) OF CONCRETE PANEL FOR FIRE
ENDURANCE OF:
WITH NO AIR SPACE
AGGREGATE 2 HR 3 HR
SAND-LIGHTWEIGHT 2.5 HR 3.6 HR
CARBONATE 2.8 HR 4.0 HR
SILICEOUS 2.9 HR 4.2 HR
ENERGY CODE
SECTION C301
LOCATION: WATERLOO, IOWA
COUNTY: BLACK HAWK
CLIMATE ZONE: 5A
TABLE C402.2 THERMAL ENVELOPE REQUIREMENTS
ROOFS
INSULATION ENTIRELY ABOVE DECK R-25ci
WALLS, ABOVE GRADE
MASS R-11.4ci
WALLS, BELOW GRADE
WALL R-7.5ci
SLAB ON GRADE FLOORS
MASS R-10ci
OPAQUE DOORS
SWINGING U-0.37
ROLL UP OR SLIDING R-4.75
SERVICE SINKS PROVIDED: 1 >= 1 REQUIRED
DRINKING FOUNTAINS PROVIDED: 2 FOUNTAINS >= 2 REQUIRED
FEMAIL SHOWERS PROVIDED: 2 >= N/A REQUIRED
MALE SHOWERS PROVIDED: 2 >= N/A REQUIRED
FEMALE LAVATORIES PROVIDED: 3 >= 2 REQUIRED
FEMALE WATER CLOSETS PROVIDED: 2 >= 2 REQUIRED
MALE LAVATORIES PROVIDED: 3 >= 2 REQUIRED
MALE WATER CLOSETS + URINALS PROVIDED: 2 WC + 3 URINALS >= 2 WC + 2 URINALS REQUIRED
TOTALS 168 4 2 4 4 1 1
84 F 1:25<50+1:50>50 = 2 1:40<80+1:80>80 = 2 -
GUARD REQ.
84 M 1:25<50+1:50>50 = 2 50% OF WC = 2 1:40<80+1:80>80 = 2 -
1 PER 100 1
REQUIRED REQ. MAX. REQUIRED REQUIRED REQUIRED REQUIRED
OCCUPANCY
NO. OF
OCC.
M/F WATER CLOSETS URINALS LAVATORIES SHOWERS
DRINKING
FOUNTAINS
SERVICE
SINKS
PLUMBING FIXTURES PER STATE PLUMBING CODE TABLE #
EGRESS PATH
PATH ID LENGTH
A 76' - 6"
B 84' - 0"
C 71' - 0"
D 72' - 6"
E 69' - 0"
TOTAL PATH LENGTH 373' - 0"
WATERLOO VEHICLE MAINTENANCE SHOP
SITE PLAN
IOWA
ONE CALL
1-800-292-8989 www.iowaonecall.com
Know what's below.
Call before you dig.
ELECTRIC MANHOLE
ELECTRIC METER
ELECTRIC RISER
ELECTRIC VAULT
POWER POLE
TRANSFORMER POLE
LIGHT POLE
ELECTRIC JUNCTION BOX
ELECTRIC PANEL
TRANSFORMER
GROUND LIGHT
GUY WIRE
ELECTRIC HANDHOLE
GAS METER
GAS VALVE
AIR CONDITIONING UNIT
TELEPHONE RISER
TELEPHONE VAULT
TELEPHONE MANHOLE
TRAFFIC SIGNAL MANHOLE
FIBER OPTIC RISER
FIBER OPTIC FAULT
CABLE TV RISER
SIGN
E
EM
E
ELEC
EJ
EP
GM
GV
A/C
T
TEL
T
TS
FO
F/O
TV
CIVIL SHEET INDEX:
C0.1 CIVIL NOTES AND REFERENCES
C1.1 SITE SURVEY AND REMOVALS
C2.1 OVERALL LAYOUT PLAN
C2.2 LAYOUT PLAN
C3.1 GRADING PLAN
C4.1 UTILITY PLAN - SANITARY AND WATER
C4.2 UTILITY PLAN - STORM SEWER
C5.1 LANDSCAPE PLAN
C6.1-C6.5 DETAILS
C7.1-C7.2 SWPPP
SURVEY NOTES:
1. SURVEY WORK WAS COMPLETED BY BISHOP ENGINEERING ON 12/06/2023.
SEE SITE SURVEY PROVIDED AS PART OF THIS SET OF PLANS FOR EXISTING
SITE CONDITIONS AND BOUNDARY INFORMATION.
SOILS REPORT:
1. REFERENCE SOILS REPORT XXXXX, DATED XXXXX PREPARED BY
ALLENDER-BUTZKE ENGINEERS FOR SOILS INFORMATION.
2. SOILS REPORT SHALL GOVERN FOR ANY PREP OR SOILS MITIGATION
REQUIREMENTS UNLESS CALL OUT ON PLANS IS MORE STRINGENT.
GENERAL NOTES:
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS ALONG WITH SUDAS STANDARD SPECIFICATIONS AND ANY AND ALL CITY/COUNTY
SUPPLEMENTAL SPECIFICATIONS. THE CITY OF WATERLOO SUPPLEMENTAL SPECIFICATIONS GOVERN FOR ANY WORK WITHIN THE PUBLIC RIGHT-OF-WAY. THE IA ARNG
MUST BE NOTIFIED BY ALL CONTRACTORS 48 HOURS PRIOR TO COMMENCING WORK.
2. IN EVENT OF A DISCREPANCY BETWEEN THE QUANTITY ESTIMATES AND THE DETAILED PLANS, THE DETAILED PLANS SHALL GOVERN.
3. IN EVENT OF A DISCREPANCY BETWEEN DETAILED PLANS, SPECS, AND SOILS REPORT, CONTRACTOR…
This is the start of the file's text. The full file is on GovTribe.