Drawings.pdf
PDF 16 MB Posted
- Attached to
- Greenhouse Modernization
- Solicitation number
- 1232SA26Q0889
About this file
This document is a 95% submittal of architectural and engineering construction drawings for the renovation of Greenhouse #2 at the USDA Agricultural Research Service facility in University Park, Pennsylvania.
The project scope involves comprehensive renovation of the existing greenhouse structure through demolition of the existing glazing system, glazing supports, concrete walkways, and gravel flooring, followed by replacement with new polycarbonate panels and supports, new concrete slabs sloped toward trench drains in each of the three growth rooms, new mechanical and electrical systems, and control systems with weather station. Four existing heaters must be removed and reinstalled. The greenhouse must be equipped with fully automatic shade cloth and ridge vent systems, new stainless steel sink, and evaporative cooling pads with operable vents. The drawings comprise 34 sheets covering structural demolition and slab-on-grade construction, architectural plans and elevations, plumbing systems with trench drains and domestic water distribution, mechanical systems including unit heaters and exhaust fans with environmental controls, electrical power distribution and lighting systems for general and grow lighting applications, and auxiliary systems. The project location is Building 0491 at 532 Curtin Road, University Park, PA 16802, with A/E Contract #12305B21D0013 and Task #1232SA26F0267. The design is based on an ultimate wind speed of 104 MPH and includes coordination with existing greenhouse columns, stem walls, and equipment pads to remain in place during renovation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFIs.pdf | ||
| Design Analysis - Updated 07282026.pdf | ||
| Site Visit Sign-In Sheets.pdf | ||
| SF30 - Amend 01.pdf | ||
| Drawings - Updated 07282026.pdf | ||
| Specifications - Updated 07082026.pdf | ||
| SF-1442.pdf | ||
| Design Analysis.pdf | ||
| Statement of Work.pdf | ||
| Specifications.pdf | ||
| Wage Determination.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NO SCALEVICINITY MAP
N
PASTURE SYSTEMS & WATERSHED RESEARCH MANAGEMENT UNIT
AGRICULTURAL RESEARCH SERVICE
U.S. DEPARTMENT OF AGRICULTURE
LOCATION MAP NO SCALE
N
UNIVERSITY PARK, PA
USDA
RENOVATE GREENHOUSE #2
BID DESCRIPTION
GREENHOUSE #2 MUST BE RENOVATED BY DEMOLISHING THE EXISTING GLAZING SYSTEM AND SUPPORTS AND ATTACHING THEM TO THE EXISTING STRUCTURE TO REMAIN. THE GREENHOUSE CURRENTLY HAS CONCRETE WALKWAYS AND GRAVEL FLOORING THROUGHOUT THE THREE (3) GROWTH ROOMS, WHICH MUST BE DEMOLISHED AND REPLACED WITH A CONCRETE SLAB SLOPING TOWARDS A NEW TRENCH DRAIN IN THE CENTER OF EACH GROWTH ROOM. THE GREENHOUSE MUST BE RESKINNED WITH NEW POLYCARBONATE PANELS AND SUPPORTS ATTACHING TO THE EXISTING STRUCTURAL SYSTEM. THE MECHANICAL AND ELECTRICAL SYSTEMS THROUGHOUT THE GREENHOUSE MUST BE DEMOLISHED AND REPLACED WITH NEW SYSTEMS WITH THE EXCEPTION OF FOUR (4) HEATERS THAT MUST BE REMOVED AND REINSTALLED. THE GREENHOUSE MUST HAVE A FULLY AUTOMATIC SHADE CLOTH SYSTEM AND AUTOMATIC RIDGE VENTS THROUGHOUT EACH GROWTH ROOM. ONE (1) NEW STAINLESS STEEL SINK MUST BE PROVIDED TO THE GROWTH ROOM DIRECTLY ADJACENT TO THE HEAD HOUSE. THE GREENHOUSE MUST BE EQUIPPED WITH A
NEW CONTROL SYSTEM AND WEATHER STATION.
PROJECT
LOCATION
PROJECT
LOCATION
A/E CONTRACT #: 12305B21D0013
A/E TASK #: 1232SA26F0267
US-BUILDING 0491
532 CURTIN ROAD
UNIVERSITY PARK, PA 16802
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
TITLE SHEET
G-001 1 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
CURTIN
RD
EIS
EN
HOWER
RD
BIGLER RD
GREENHOUSE #2
95% SUBMITTAL
HEADHOUSE
GREENHOUSEGREENHOUSE #2
CONTRACTOR
LAYDOWN SPACE
CONTRACTOR ENTRANCE FROM CURTIN ST
BUILDING
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
SHEET INDEX AND SITE PLAN
G-002 2 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
CONTRACTOR LAYDOWN SITE PLAN
1/16"=1'-0"
G-002
SCALE: 1/16" = 1'-0"
48'8' 16' 32'0
NOTE:
BEFORE COMPLETION OF PROJECT, CONTRACTOR MUST RESTORE SITE, INCLUDING PAVEMENTS, TO ORIGINAL CONDITION.
SHEET LIST
GENERAL
G-001 1 OF 34 TITLE SHEET
G-002 2 OF 34 SHEET INDEX AND SITE PLAN
STRUCTURAL
S-001 3 OF 34 STRUCTURAL GENERAL NOTES, ABBREVIATIONS, AND C&C ZONE DIAGRAM
SD101 4 OF 34 STRUCTURAL DEMOLITION PLAN
S-101 5 OF 34 STRUCTURAL SLAB PLAN
S-300 6 OF 34 SLAB DETAILS
ARCHITECTURAL
AD101 7 OF 34 DEMOLITION PLAN
A-101 8 OF 34 FLOOR PLAN
A-111 9 OF 34 ROOF PLAN
A-201 10 OF 34 EXTERIOR ELEVATIONS
A-301 11 OF 34 SECTION
A-501 12 OF 34 DETAIL
PLUMBING
PD101 13 OF 34 PLUMBING DEMOLITION PLAN
P-101 14 OF 34 GREENHOUSE PLUMBING PLAN
P-102 15 OF 34 GREENHOUSE SANITARY PLAN
P-501 16 OF 34 PLUMBING DETAILS
P-502 17 OF 34 PLUMBING DETAILS
P-601 18 OF 34 PLUMBING SCHEDULES
MECHANICAL
MD101 19 OF 34 MECHANICAL DEMOLITION PLAN
M-101 20 OF 34 GREENHOUSE MECHANICAL PLAN
M-501 21 OF 34 MECHANICAL DETAILS
M-601 22 OF 34 MECHANICAL SCHEDULE
ELECTRICAL
E-001 23 OF 34 ELECTRICAL LEGEND
E-501 24 OF 34 ELECTRICAL DETAILS
E-601 25 OF 34 SINGLE-LINE DIAGRAM
E-701 26 OF 34 PANEL SCHEDULES
ED101 27 OF 34 ELECTRICAL DEMOLITION PLAN
EL101 28 OF 34 GENERAL LIGHTING PLAN
EL102 29 OF 34 GROW LIGHTING PLAN
EL501 30 OF 34 FIXTURE SCHEDULE & DETAILS
EP101 31 OF 34 POWER PLAN
EP102 32 OF 34 MECHANICAL CONNECTIONS PLAN
EP501 33 OF 34 EQUIPMENT SCHEDULE
EY101 34 OF 34 AUXILIARY SYSTEMS PLAN
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\S tru ct\ S-0
.dw g Ju n 2 5,
- 1 1:1
3a m c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
STRUCTURAL GENERAL NOTES,
ABBREVIATIONS AND C&C ZONE DIAGRAM
S-001 3 3406/26/26
BP
STM
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
C & C ZONE DIAGRAM
3/32" = 1'-0"
S-001
TABLE 1
DESIGN WIND PRESSURE COMPONENTS AND CLADDING (C & C)
NOTE: THE DESIGN WIND PRESSURES SHOWN BELOW ARE BASED UPON THE ULTIMATE DESIGN WIND SPEED OF 104 MPH. THE WIND PRESSURES SHOWN ARE TO BE USED WITH THE LOAD AND RESISTANCE FACTOR (LRFD) METHOD. ALLOWABLE STRENGTH DESIGN (ASD) PRESSURES SHOULD BE CALCULATED BASED UPON A NOMINAL
VELOCITY OF 80.6 MPH.
SURFACE PRESSURE (psf) AREA WIND ZONE 10sf 100sf 200sf 500sf
ROOF NEGATIVE ZONE 1 -22.7 -16.0 -16.0 -16.0
ROOF NEGATIVE ZONE 2 -36.1 -18.6 -18.6 -18.6
ROOF NEGATIVE ZONE 3 -42.9 -21.3 -21.3 -21.3
ROOF POSITIVE ALL ZONES 16.0 16.0 16.0 16.0
SURFACE PRESSURE (psf) AREA WIND ZONE 10sf 100sf 200sf 500sf
WALLS NEGATIVE ZONE 4 -17.3 -16.0 -16.0 -16.0
WALLS NEGATIVE ZONE 5 -21.3 -16.5 -16.0 -16.0
WALLS POSITIVE ZONE 4 & 5 16.0 16.0 16.0 16.0
NOTES:
1. DESIGN WIND PRESSURES INDICATED MUST BE USED IN THE DESIGN OF ALL COMPONENTS & CLADDING
ELEMENTS COMPRISING THE BUILDING ENVELOPE.
2. POSITIVE PRESSURES ACT INWARD, TOWARD THE WIND SURFACE. NEGATIVE PRESSURES ACT OUTWARD, AWAY FROM THE WIND SURFACE.
3. LINEAR INTERPOLATION IS PERMITTED FOR INTERMEDIATE EFFECTIVE WIND AREAS.
PLAN
NORTH
DESIGN CRITERIA
CODES AND STANDARDS
A. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE
INSTITUTE (ACI), ACI 318-25.
B. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, ASCE 7-22.
C. INTERNATIONAL BUILDING CODE (IBC), IBC 2024.
D. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC), AISC STEEL CONSTRUCTION
MANUAL, 15TH EDITION.
E. STRUCTURAL COMPONENTS IN THIS PROJECT DESIGNED USING LRFD METHODOLOGY.
F. AISI AMERICAN IRON AND STEEL INSTITUTE.
1.0 MINIMUM DESIGN LOADS AND REQUIREMENTS IN ACCORDANCE WITH IBC 2024
FLOOR LIVE LOAD
ROOF LIVE LOAD (REDUCIBLE)
M&E
WIND DESIGN DATA:
ULTIMATE WIND SPEED
NOMINAL WIND SPEED
RISK CATEGORY
WIND IMPORTANCE FACTOR
WIND EXPOSURE
COMPONENTS AND CLADDING DESIGN PRESSURE
EARTHQUAKE DESIGN DATA:
SEISMIC IMPORTANCE FACTOR
SS
S1
SITE CLASS
SDS
SD1
SEISMIC DESIGN CATEGORY
SEISMIC RESISTING SYSTEM
DESIGN BASE SHEAR
CS
R
DESIGN METHOD
100 PSF
20 PSF
5 PSF
104 MPH
80.6 MPH
I 1.0 B
SEE TABLE 1
1.0
11% 3.8%
D
A
STEEL FRAMES NOT SPECIFICALLY
DETAILED FOR SEISMIC RESISTANCE
0.033W 0.033W
EQUIVALENT LATERAL FORCE
2.0 MATERIALS
CONCRETE (28 DAY STRENGTH)
SLAB ON GRADE / FOUNDATION
(SEE SPECIFICATIONS FOR CONCRETE PROPERTIES)
REINFORCING:
BARS
WELDED WIRE FABRIC
STRUCTURAL STEEL SHAPES, PLATES AND MISCELLANEOUS SHAPES:
3,000 PSI
ASTM A615/A615M
ASTM A185
BOLTS:
BOLTS
ANCHOR RODS:
ANCHOR RODS
GROUT:
GROUT
ASTM F1554. GRADE 36
2 KSI
STRUCTURAL GENERAL NOTES
4.0 FOUNDATION:
4.1 THE EXISTING STRUCTURAL FOUNDATION SYSTEM IS UNKNOWN. FOUNDATION WORK WILL INCLUDE
THE CONSTRUCTION OF A CONCRETE SLAB ON GRADE. THE SLAB ON GRADE WILL BE CONSTRUCTED ATOP STRUCTURAL FILL IN ACCORDANCE WITH THE GEOTECHNICAL REPORT BY U.S. ARMY CORPS
OF ENGINEERS - BALTIMORE DISTRICT IN JUNE 2022.
4.2 ALL AT GRADE SLABS MUST BE CONSTRUCTED ON 12 INCH CAPILLARY WATER BARRIER FORM WITH A
15 MIL VAPOR BARRIER.
4.3 PROTECT PIPES AND CONDUITS RUNNING THROUGH WALLS AND SLABS WITH 1/2 INCH EXPANSION
MATERIAL.
4.4 MAINTAIN SUBGRADE AND FILL MOISTURE CONTENT UNTIL FOUNDATIONS ARE PLACED.
4.5 DO NOT PLACE SLAB AGAINST SUBGRADE CONTAINING FREE WATER, FROST, OR ICE.
4.6 MAINTAIN PROPER SITE DRAINAGE DURING CONSTRUCTION TO ENSURE SURFACE RUNOFF AWAY
FROM STRUCTURES AND TO PREVENT PONDING OF SURFACE RUNOFF NEAR THE STRUCTURES.
4.7 KEEP OPEN EXCAVATIONS AROUND BUILDING DRY. BACKFILL AGAINST GRADE BEAMS AS SOON AS PRACTICAL. PUMP WATER OUT OF OPEN EXCAVATIONS IF FLOODING OCCURS PRIOR TO BACKFILLING.
ASTM A325 BEARING TYPE N
TENSION AND DEVELOPMENT SPLICE LENGTHS - f'c = 3000 psi CONCRETE
BAR
SIZE
DEVELOPMENT LENGTH SPLICE LENGTH STANDARD 90 DEGREE HOOK
TOP BAR
(INCHES)
OTHER BAR
(INCHES)
TOP BAR
(INCHES)
OTHER BAR
(INCHES)
EMBED
(INCHES)
LEG LENGTH
(INCHES)
BEND DIA.
(INCHES)
#3 22 17 28 22 6 6 2.25 #4 29 22 37 29 8 8 3 #5 36 28 47 36 10 10 3.75 #6 43 33 56 43 12 12 4.5 #7 63 48 81 63 14 14 5.25 #8 72 55 93 72 16 16 6
APPLICABLE SHAPE SERIES ASTM DESIGNATION MIN. YIELD STRESS (FY)
(KSI)
W A992 50 M A36 36 S A36 36 C A36 36
MC A36 36
L A36 36
HSS (RECTANGLE) A500 46
HSS (ROUND) A500 42
PIPE A53 35
PLATES A36 36
PLATES A572 50
BARS A572 42
3.0 CAST-IN-PLACE CONCRETE NOTES:
3.1 CONCRETE COVER FOR REINFORCEMENT:
A. CONCRETE DEPOSITED AGAINST AND PERMANENTLY EXPOSED TO
EARTH
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 BARS OR SMALLER
#5 BARS OR LARGER
C. CONCRETE NOT EXPOSED TO WEATHER OR NOT IN CONTACT WITH
GROUND:
SLAB, WALL, AND JOISTS BEAMS
3.2 UNLESS SPECIFICALLY NOTED, SCHEDULED OR DETAILED OTHERWISE
PROVIDE DEVELOPMENT LENGTH FOR REINFORCING IN CONCRETE
COMPONENTS IN ACCORDANCE WITH THE SCHEDULE IN NOTE 3.3
BELOW. THIS SCHEDULE SHALL APPLY TO ALL DEVELOPMENT LENGTHS
NOT OTHERWISE NOTED, DETAILED OR SCHEDULED IN THE DRAWINGS
OR SPECIFICATIONS.
3.3 REINFORCING BAR DEVELOPMENT LENGTHS Ld (f'c = 4000 PSI)
3"
1 1/2" 2" 1"
1 1/2"
NOTES:
1. STRAIGHT DEVELOPMENT LENGTH AND SPLICE LENGTHS ARE BASED ON UNCOATED BARS
ASSUMING CENTER TO CENTER BAR SPACING GREATER THAN 3 BAR DIAMETERS WITHOUT TIES OR STIRRUPS OR 2 BAR DIAMETERS WITH TIES OR STIRRUPS, AND CLEAR COVER OF 1 BAR DIAMETER.
2. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES OF CONCRETE BELOW THE BAR.
3. STANDARD 90 DEGREE HOOK EMBEDMENT LENGTH ARE BASED ON SIDE COVER GREATER THAN
2.5 INCHES AND END COVER GREATER THAN 2 INCHES WITHOUT TIES AROUND HOOKS.
3.4 LAP SPLICE LENGTHS FOR REINFORCING BARS MUST BE THE SAME AS SHOWN IN THE TABLE.
3.5 WHEN TWO BARS OF DIFFERENT SIZES ARE LAPPED, THE SMALLER SIZE GOVERNS THE LAP
LENGTH UNLESS SPECIFICALLY NOTE OTHERWISE.
3.6 WHEN REINFORCING STEEL IS NOTED AS CONTINUOUS REINFORCING IN GRADE BEAMS, WALLS, SLABS AND/OR BEAMS, SPLICE CONTINUOUS REINFORCING STEEL ONLY WHEN UNAVOIDABLE DUE TO STOCK LENGTHS. STAGGER ALL SPLICES A MINIMUM OF 4'-0". ADJACENT BAR SPLICES ARE NOT ACCEPTABLE. LOCATE THE TOP BAR SPLICES WITHIN THE MIDDLE HALF OF THE SPAN AND LOCATE THE BOTTOM BAR SPLICES AT SUPPORTS, OR BETWEEN SUPPORTS AND 1/3 SPAN POINT, UNLESS NOTED OTHERWISE ON PLANS, DETAILS OR SCHEDULES.
3.7 HORIZONTAL JOINTS WILL NOT BE PERMITTED IN CONCRETE CONSTRUCTION EXCEPT AS SHOWN
ON THE DRAWINGS. VERTICAL JOINTS SHALL OCCUR AT LOCATIONS INDICATED.
3.8 AT CONSTRUCTION JOINTS, CONTACT SURFACES MUST BE CLEAN AND FREE OF LATENCIES AND
INTENTIONALLY ROUGHENED TO A FULL AMPLITUDE OF APPROXIMATELY 1/4 INCH
3.9 PROVIDE FULL EMBEDMENT WITH 90-DEGREE HOOKS FOR ALL DOWELS IF NOT OTHERWISE NOTED.
3.10 CHAMFER ALL EXPOSED TO VIEW CORNERS 3/4", U.N.O.
5.0 GENERAL:
5.1 WHERE A SECTION OR DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL ONLY APPLY TO LIKE OR
SIMILAR CONDITIONS.
6.0 POST INSTALLED ADHESIVE ANCHORS:
6.1 POST INSTALLED ADHESIVE ANCHORS MUST BE STAINLESS STEEL AND MUST ONLY BE USED WITH THE
WRITTEN CONSENT OF THE CONTRACTING OFFICER. STRENGTH OF ANCHORS MUST BE BASED UPON THE
REQUIRED STRENGTH OF THE SPECIFIC INSTALLATION AND LOCATION OF ANCHORS.
6.2 INSTALL BOLTS PERPENDICULAR TO THE FACE OF THE CONCRETE. DEVIATION FROM PERPENDICULAR
GREATER THAN 10 DEGREES WILL NOT BE ACCEPTABLE.
6.3 CREATE A TEMPLATE AT EACH BOLT CONNECTION LOCATION PRIOR TO FABRICATING HOLES IN
CONNECTION PLATES. MAKE TEMPLATE BY LOCATING EXISTING REBAR WITH PACHOMETER.
REPOSITION BOLTS A MAXIMUM OF 1-1/2" TO AVOID CONFLICTS WITH EXISTING.
6.4 DRILL HOLES TO DEPTH AND DIAMETER RECOMMENDED BY MANUFACTURER. DO NOT ENLARGE OR
REDIRECT HOLES ALONG THE LENGTH OF THE BOLTS.
6.5 DRILL HOLES IN CONTINUOUS OPERATION. BLOW DUST FROM THE HOLE USING COMPRESSED AIR.
6.6 FILL ABANDONED HOLES WITH EPOXY GROUT.
AFF
AISC
APPROX.
ARCH.
AHU
AWS
BC
bf
BFF
BOT. OR B
BRG
C&C
CJ OR CONST. JT.
CL
C.G.
CLR.
CMU
COL.
COMP.
CONC.
CONT.
CRSI
D
DIA.
db
DCJ
DL.
DO
DWG.
EL.
E.O.S.
EQ.
E.S.
E.W.
EXP.
FD
FIN.
F.F.
GALV.
GR
HSS
IP
IN
JST
JT.
K
KSF
LL
LLH
LLV
MAX.
MECH.
MFR.
MIN.
NO. OR #
O.C.
OF
PL
PSF
PSI
RP
REQ'D
SP
SN
SCH
SJ
STIFF.
T t
TC
T.O.C.
T.O.S.
TYP.
U.N.O.
W/
WWF
W.P.
ABOVE FINISHED FLOOR
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
APPROXIMATE
ARCHITECTURAL
AT
AIR HANDLING UNIT
AMERICAN WELDING SOCIETY
BOTTOM CHORD
FLANGE WIDTH
BELOW FINISHED FLOOR
BOTTOM OR BOTTOM MOST
BEARING
COMPONENT AND CLADDING
CONSTRUCTION JOINT
CENTERLINE
CENTER OF GRAVITY
CLEAR
CONCRETE MASONRY UNIT
COLUMN
COMPOSITE
CONCRETE
CONTINUOUS
CONCRETE REINFORCING STEEL INSTITUTE
DEPTH
DIAMETER
BAR DIAMETER
DOWELED CONTROL JOINT
DEAD LOAD
DITTO
DRAWING
ELEVATION
EDGE OF SLAB
EQUALLY
EACH SIDE
EACH WAY
EXPANSION
FLOOR DRAIN
FINISHED, FINISH
FINISHED FLOOR
GALVANIZED
GALVANIZED STEEL GRATING
HOLLOW STEEL SECTION
POSITIVE MOMENT OF INERTIA
NEGATIVE MOMENT OF INERTIA
JOIST
JOINT
KIP (KILO POUND)
KIPS PER SQUARE FOOT
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
NUMBER
ON CENTER
OUTSIDE FACE
PLATE
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
RADIUS POINT
REQUIRED
POSITIVE SECTION MODULUS
NEGATIVE SECTION MODULUS
SCHEDULE
SAW JOINT
STIFFENER
TRUSS
THICKNESS
TOP CHORD
TOP OF COLUMN
TOP OF STEEL
TYPICAL
UNLESS OTHERWISE NOTED
WITH
WELDED WIRE FABRIC
WORKING POINT
ABBREVIATIONS
9.8% 5.4%
SNOW DESIGN DATA:
GROUND SNOW LOAD (pg) 47 PSF
UNIFORM ROOF DESIGN LOAD 28 PSF
RAIN DESIGN DATA:
15-MINUTE PRECIPITATION INTENSITY 5.83 IN/HR
DESIGN RAIN LOAD 1.5 PSF
STRUCTURAL LEGEND
WALL SECTION MARK
CALLOUT HEAD
KEYNOTE
TAGNORTH ARROWS
FLOOR PLANS, ELEVATIONS, SECTIONS AND DETAIL VIEWS TITLE
DWG. NO. WHERE
SECTION IS DRAWN
SCALE:
ELEVATIONS, DETAILS & CALLOUTS
1/8" = 1'-0"
S100
PLAN
NORTH
S100
DWG. NO. WHERE
SECTION IS DRAWN
AREA COVERED BY
DETAIL
DETAIL NUMBER (TYP.)
S100
SECTION NUMBER
DETAIL IDENTIFIER
SCALE: 3/32" = 1'-0"
16' 8' 0 16' a = 3.6FT
5 5
3 3 2
3 3 2 a a
A A
B B
C C
D D
E E
F F
G G
H H
I I H.7 H.7
G.6 G.6
F.8 F.8
D.7 D.7
1.7
1.7
1.3
1.3
0'-
, F
IE
LD
V
ER
IF
Y
BEGINNING WORK.
31'-10" ±, FIELD VERIFY
SCALE:
STRUCTURAL DEMOLITION PLAN
1/8" = 1'- 0"
SD101
PLAN
NORTH
EXISTING BUILDING
EXISTING HAZARDOUS
MATERIAL STORAGE
GENERAL NOTES
1. CONTRACTOR MUST FIELD VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK.
2. EXISTING FOUNDATION SYSTEM IS UNKNOWN. CONTRACTOR MUST PROTECT EXISTING FOUNDATION.
3. REMOVE ALL EXISTING MATERIAL WITHIN GREENHOUSE WALL REQUIRED TO PROVIDE SLAB ON GRADE
CONSTRUCTION INDICATED ON 4 / S-300.
DEMOLITION LEGEND
DEMOLISH CONCRETE
STEM WALLS TO REMAIN
REMOVE GRAVEL SURFACING
DEMOLITION KEYED NOTES
CONTRACTOR MUST PROTECT EXISTING GREENHOUSE COLUMNS AND THEIR ASSOCIATED 10"X10" PEDESTAL
FOUNDATIONS.
DEMOLISH EXISTING CONCRETE SLAB, WALKWAYS, AND MISC. CONCRETE PADS, APPROXIMATELY 2000 SF.
REMOVE EXISTING GRAVEL SURFACING AS REQUIRED TO PROVIDE SLAB ON GRADE CONSTRUCTION AS
INDICATED ON 4 / S-300.
TYP.
TYP.
EXISTING
HAZARDOUS
MATERIAL
STORAGE
2TYP.
2 TYP.
EXISTING CONCRETE CURB
PROTECT EXISTING EQUIPMENT PAD
EXISTING STEM WALL TO REMAIN, TYP.
EXISTING STEM WALL TO REMAIN, TYP.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
STRUCTURAL DEMOLITION PLAN
SD101
4 3406/26/26
BP
STM
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
DEMOLISH EXISTING SLAB
DEMOLISH EXISTING CONCRETE PAVER
DEMOLISH EXISTING CONCRETE WALKWAY
3TYP.
3 TYP.
1TYP.
A A
B B
C C
D D
E E
F F
G G
H H
I I H.7 H.7
G.6 G.6
F.8 F.8
D.7 D.7
1.7
1.7
1.3
1.3
0'-
, F
IE
LD
V
ER
IF
Y
31'-10" ±, FIELD VERIFY BEGINNING WORK.
8'- 0"
8'- 6"
8'- 0"
8'- 4 1
/2"
'-0
8'- 0"
EXISTING EQUIPMENT PAD
C J
C J
C J
C J
CJ CJ
C J
C J
CJ CJ
C J
C J
C J
C J
C J
C J
CJ CJ
C J
C J
CJ CJ
C J
C J
C J
C J
CJ CJ
C J
C J
C J
C J
C J
CJ CJ
CJ CJ
CJ CJ
CJ
C J
CJ CJ
C J
C J
CJ
C J
C J
CSTR
CSTR
C J
SCALE:
STRUCTURAL FOUNDATION PLAN
1/8" = 1'-0"
S-101
PLAN
NORTH
EXISTING BUILDING
EXISTING HAZARDOUS
MATERIAL STORAGE
GENERAL NOTES
1. CONTRACTOR MUST FIELD VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK.
2. EXISTING SUBGRADE FOUNDATION SYSTEM IS UNKNOWN. CONTRACTOR MUST PROTECT
EXISTING FOUNDATION.
LEGEND
STEM WALLS TO REMAIN
TRENCH DRAIN
EXISTING GREENHOUSE TUBE COLUMN TO REMAIN
EXISTING COLUMN PEDESTAL TO REMAIN
SLOPE
CONTRACTION JOINT
CONSTRUCTION JOINT
S1
S1
S1
TRENCH DRAIN TYP.
EXISTING
HAZARDOUS
MATERIAL
STORAGE
1193.15'
1/8"/FT
1193.15'1193.15'
1193.15'
SLOPE LINES, TYP.
1'-0"
1'-0"
S-300
S-300
S-300
EXISTING CONCRETE CURB
NOTE: TOP OF SLAB ELEVATION
MUST BE 1193.15' AROUND
THE PERIMETER OF EACH
BAY.
EXISTING STEM WALL, TYP.
CSTR
CJ
S-300
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
STRUCTURAL SLAB PLAN
S-101 5 3406/26/26
BP
STM
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
1/8" / FT. 1/8" / FT.
1/8" / FT.1/8" / FT.
1/8" / FT.1/8" / FT.
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
CONCRETE STAIR
S-300
1'-0"
1/4
F T.
M
AX
1/4
F T.
M
AX
1/4
F T.
M
AX
1/4
F T.
M
AX
1/4
F T.
M
AX
1/4
F T.
M
AX
CONSTRUCTION JOINT
CONSTRUCTION JOINT
TOP OF GRATE : 1192.99'
TRENCH INVERT: 1192.47'
TRENCH INVERT: 1192.39'
TOP OF GRATE : 1192.99'
TRENCH INVERT: 1192.47'
TRENCH INVERT: 1192.39'
TOP OF GRATE: 1192.99'
TRENCH INVERT: 1192.47
TRENCH INVERT: 1192.12'
1/8" / FT.
14'-11"
CJ CJ
CJ
(3) #4 CONT. #4 STD. ACI BENT BAR @12" O.C.
6"
1/2" EXPANSION JOINT
1/2"
EXISTING CONCRETE CURB1/2" EXPANSION JOINT
#4 @ 12" O.C., E.W.
#4 TIES @ 12" O.C.#4 CONT.
EXISTING CONCRETE STEM WALL
1/2" EXPANSION JOINT
1'- 0"
SCALE:
SECTION
1 1/2" = 1'-0"
S-300
FILLER MATERIAL
(3) #4 X 4'-0" DIAGONAL
PLACED 2" BELOW T/SLAB
SLAB EDGE
RE-ENTRANT CORNER
(2) #3 X 3'-0" @ MID DEPTH, TYP.
DISCONTINUOUS SLAB-ON-GRADE JOINTS
S1 #4 @ 12" O.C., E.W.
XPS INSULATION
6" CAPILLARY WATER BARRIER
15 MIL. VAPOR BARRIER
SCALE:
CONTRACTION JOINTS SLAB ON GRADE
1 1/2" = 1'-0"
S-300
SCALE:
RE-ENTRANT CORNER AND DISCONTINUOUS JOINTS
1 1/2" = 1'-0"
S-300
SCALE:
SLAB ON GRADE DETAIL (S1)
1 1/2" = 1'-0"
S-300
CONTRACTION JOINT NOTES:
1. MAKE SAW CUT AS SOON AS SLAB IS ABLE TO SUPPORT WEIGHT OF WORKERS AND SAWING EQUIPMENT WITHOUT
DAMAGE TO FINISH SURFACE OF SLAB.
2. ALL JOINTS MUST BE CONTINUOUS. DO NOT OFFSET OR STAGGER JOINTS.
3. CLEAN JOINT PRIOR TO FILLING THE JOINT.
JOINT FILLER MATERIAL NOTES:
1. FILLER MATERIAL USED MUST BE EPOXY RESINS WITH A MINIMUM SHORE "A" FILLER MATERIAL USED MUST BE EPOXY
RESINS WITH A MINIMUM SHORE "A" HARDNESS OF 80 AND MUST CONFORM TO ASTM D2240.
2. WHERE POSSIBLE, FILLER MATERIAL MUST BE APPLIED WHEN BUILDING IS UNDER PERMANENT TEMPERATURE CONTROL.
THIS MUST BE EITHER AT THE END OF CONSTRUCTION OF THE COMPLETE BUILDING SHELL OR A MINIMUM OF 90 DAYS
AFTER SLAB CONSTRUCTION.
3. ALL EXPOSED SLAB JOINTS MUST BE FILLED WITH FILLER MATERIAL.
CONTRACTION JOINTS (CJ)
6"
RE-ENTRANT CORNER DISCONTINUOUS JOINTS
4" 2"
3"
3" 3"
T/
T
T/
1/4" SAW CUT
4"
#4 DOWEL, 16" LONG @ 12" O.C.
GREASE AND PAINT ONE END.
8" OF PENNDOT "2A" AGGREGATE
COMPACTED TO 95% ASTM D1557
SCALE:
SECTION
1 1/2" = 1'-0"
S-300
SLOPESLOPE
1/2" R, TYP.
#4 BAR, 1"
CLEARANCE
1193.15'
SCALE:
SECTION
1 1/2" = 1'-0"
S-300
6 7/8" TYP.
SLOPE
1192'
NOTE: APPLY BROOM FINISH TO WALKING SURFACES OF STAIR AND LANDINGS.
S1
12" (2) #4 CONT.
XPS INSULATION
CONSTRUCTION JOINTS (CSTR)
T/
CONSTRUCTION JOINT NOTES:
1. SLAB REINFORCEMENT MUST BE SUPPORTED BY SOIL SUPPORTED BOLSTERS AT SPACING NOT TO EXCEED 4'-0".
2. BREAK BOND BETWEEN NEW AND PREVIOUSLY PLACED SLAB BY SPRAYING OR PAINTING EXPOSED SIDE WITH FORM OIL.
3. SUBGRADE MUST BE FREE OF STANDING WATER AT THE TIME OF CONCRETE PLACEMENT.
4. CONT. DOWEL PERIMETER ONE SIDE OF CONSTRUCTION JOINT W/ BEARING GREASE..
JOINT SPACING NOTES:
1. PROVIDE CONTRACTION AND/OR CONSTRUCTION JOINTS AT EVERY COLUMN CENTERLINE AND AT A MAXIMUM SPACING
OF 36 TIMES THE SLAB THICKNESS, NOT TO EXCEED 16'-0" O.C. U.N.O
2. MAXIMUM ASPECT RATIO OF JOINT DIMENSIONS MUST NOT EXCEED 1.5.
PREPARE EDGE ON EACH SIDE
OF JOINT W/ 1/8" RADIUS AND
FILL W/ FILLER MATERIAL
SLAB REINF.
22 GA KEY WAY
#4 DOWEL 16" LONG @
12" O.C , GREASE AND
PAINT ONE END.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
SLAB DETAILS
S-300 6 3406/26/26
BP
STM
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
XPS INSULATION
11" 2'-10"
XPS INSULATION
4'-0"
2'-0"
TRENCH DRAIN INSERT, SEE PLUMBING.
1193.15
7'-7"
1'- 7 1
/4"
- 1
'-1
1"
+/- 31'-10"
CHEM.
STORAGE
STORAGE
- 2
5'- 0"
4"
- 2 4'-
9" 4"
- 5
0'- 0"
- 7
'-8
+/- 5'-6"
TYP.
12 TYP.
TYP.
EXISTING DOOR TO REMAIN
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\A rch
\AD
1.d wg
Ju n 2
5,
- 1
1:3 4a m c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
DEMOLITION PLAN
AD101
7 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
DEMOLITION KEYNOTES
1. DEMOLISH GREENHOUSE GLAZING SYSTEM AND PANELS
DOWN TO THE MAIN STRUCTURAL FRAMING MEMBERS (STEM
WALLS, COLUMNS, PURLINS, ETC.). PROTECT STRUCTURAL
MEMBERS TO REMAIN.
2. DEMOLISH EXISTING CONCRETE SLAB. SEE STRUCTURAL.
3. REMOVE GRAVEL BASE THROUGHOUT GREENHOUSE.
4. DEMOLISH DOOR AND FRAME.
5. DEMOLISH COMPOSITE STAIRS AND LANDING.
6. CONTRACTOR MUST TEMPORARILY MOVE CHEMICAL
STORAGE AWAY FROM GREENHOUSE DURING DEMOLITION
AND CONSTRUCTION ON THE EXISTING SLAB. INSTALL
TEMPORARY ELECTRICAL UTILITIES TO KEEP CHEMICAL
STORAGE ACTIVE AND AVAILABLE THROUGHOUT
CONSTRUCTION.
7. EXISTING COLUMNS TO REMAIN. SAW CUT CONCRETE BASE AT
JOINTS AND PROTECT BASE AND COLUMN DURING
DEMOLITION, TYP. -- SEE STRUCTURAL.
8. MECHANICAL HEATERS MUST BE REMOVED AND STORED FOR
REINSTALLATION. -- SEE MECH.
9. EVAPORATIVE COOLING SYSTEM MUST BE DEMOLISHED -- SEE
MECH.
10. MECHANICAL FANS MUST BE DEMOLISHED -- SEE MECH.
11. REMOVE EXISTING SEALANT AND EXPANSION MATERIAL
BETWEEN EXISTING HEADHOUSE AND GREENHOUSE. ADJUST
EXISTING FLASHING AT HEADHOUSE TO CREATE A WATER
TIGHT SYSTEM OVER NEW ROOF PANELS AND WALL GLAZING
SYSTEM. (CONTRACTOR HAS THE OPTION TO REPLACE
FLASHING WITH FLASHING OF SAME MATERIALS.
12. DEMOLISH CONCRETE PAVERS, TYP.
LEGEND
DEMOLISH GRAVEL FLOOR
DEMOLISH CONCRETE FLOOR
DEMOLITION GENERAL NOTES
A. EXISTING GREENHOUSE CONCRETE STEM WALL AND
STRUCTURE ARE TO REMAIN. DEMOLITION SCOPE INCLUDES
GREENHOUSE GLAZING SYSTEM AND SUPPORTS, INTERIOR
SLABS AND GRAVEL, EXTERIOR STAIRS, AND MECHANICAL
AND ELECTRICAL SYSTEMS. SEE MEP FOR ADDITIONAL
INFORMATION.
B. ASSUME ALL PAINT COATINGS CONTAIN SOME LEVEL OF
LEAD. IT IS NOT THE INTENT OF THIS PROJECT TO ABATE ALL
LEAD-BASED PAINT COATINGS. ITEMS WITH PAINT COATINGS
INTACT MAY BE DISPOSED OF AS NORMAL CONSTRUCTION
DEBRIS. LOOSE PAINT COATINGS MUST BE DISPOSED OF AS
LEAD HAZARDOUS WASTE UNLESS TESTED TO DETERMINE
OTHERWISE. PROVIDE OSHA REQUIRED WORKER
PROTECTION IN ACCORDANCE WITH OSHA FOR
DISTURBANCE OF PAINT COATINGS.
SCALE:
DEMOLITION FLOOR PLAN
3/16"=1'-0"
AD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
KEYPLAN
NTS
STORAGE
CHEM.
STORAGE
GROWTH ROOM
GROWTH ROOM
GROWTH ROOM
EXISTING DOOR TO REMAIN
0'-
1'-0"
8'- 0"
14'-11"14'-11"
8'- 6"
8'- 6"
1'-0"14'-11"
8'- 0"
8'- 4 1
/2" 8'-
4 1 /2"
14'-11"
1'-0" 14'-11"14'-11"
8'- 0"
'-0
'-0
31'-10"
6'-0"
1'-
1'-
4'- 0"
12LOCATION OF TEMPORARILY
RELOCATED CHEMICAL STORAGE TO
ALLOW FOR INSTALLATION OF
GREENHOUSE EXTERIOR FACADE.
ONLY MOVE STRUCTURE AS FAR AWAY
FROM GREENHOUSE AS NEEDED FOR
GLAZING INSTALLATION.
A-201
A-201
A-201
A-301
A-301
1/8" / FT.
1/8" / FT.
1/8" / FT.
1/8" / FT.
1/8" / FT.
1/8" / FT.
1/4
F T.
MA
X
1/4
F T.
MA
X
1/4
F T.
MA
X
1/4
F T.
MA
X
1/4
F T.
MA
X
1/4
F T.
MA
X
(B
OT
H
SI
DE
S)
DOOR AND FRAME SCHEDULE
DOOR # TYPE WD HGT THK
SIZE
MAT'L
DOOR
TYPE MAT'L
FRAME FIRE
RATING
LABEL
HDW
SET
NO
REMARKS
A A B
3'-0" 3'-0" 5'-0"
7'-0" 7'-0" 7'-0"
1 3/8" 1 3/8" 1 3/4"
MTL
MTL
MTL
A A B
MTL
MTL
MTL
SLIDING DOOR
SLIDING DOOR
PAIR OF DOORS
DOOR AND FRAME TYPES
A B
AS SCHED.
AS
S
CH
ED
2" AS SCHED. 2"
2"
AS
S
CH
ED
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\A rch
\A-
1.d wg
Ju n 2
6,
- 8
:15 am c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
FLOOR PLAN
A-101 8 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
FLOOR PLAN
3/16"=1'-0"
A-101
KEYNOTES
1. PROVIDE GLAZING SYSTEM WITH 16 MIL. POLYCARBONATE
PANEL AT EXTERIOR FRAMING.
2. PROVIDE GLAZING SYSTEM WITH 8 MIL. POLYCARBONATE
PANEL AT INTERIOR FRAMING.
3. EXHAUST FAN. SEE MECHANICAL.
4. EVAPORATIVE COOLING PAD WITH OPERABLE VENTS. SEE
MECHANICAL.
5. PROVIDE TRENCH DRAIN.
6. INSTALL UNIT HEATERS STORED DURING DEMOLITION. SEE
MECHANICAL / PLUMBING FOR PIPING CONNECTIONS.
7. EXISTING PIPE COLUMNS AND CONCRETE BASE. PROTECT
DURING CONSTRUCTION, TYP.
8. PROVIDE CONCRETE SLAB SLOPED TOWARDS TRENCH
DRAINS. SEE STRUCTURAL.
9. PROVIDE DOOR IN EXISTING OPENING. MODIFY OPENING TO
ACCOMMODATE NEW CONSTRUCTION AND REPAIR EXISTING
SURFACES. SEE DOOR SCHEDULE.
10. PROVIDE CONCRETE STAIR. SEE STRUCTURAL FOR
REINFORCING.
11. EXISTING CONCRETE STEM WALL MUST BE PROTECTED
DURING CONSTRUCTION. PATCH AND REPAIR ANY DAMAGED
AREAS.
12. CHEMICAL STORAGE BUILDING MUST BE TEMPORARILY
MOVED AWAY FROM GREENHOUSE ON EXISTING SLAB DURING
CONSTRUCTION. CONNECT TO TEMPORARY UTILITIES TO
ALLOW FOR FULL USE OF STORAGE DURING ENTIRE
CONSTRUCTION TIMELINE.
13. ALUMINUM RACK SUPPORT SYSTEM FOR VENT OPERATORS.
DESIGN BY GREENHOUSE MANUFACTURER.
14. PROVIDE STAINLESS STEEL SINK -- SEE PLUMBING.
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
ALUMINUM
SLIDING
DOOR
TRACK
GLAZING
PER MANUF.
KEYPLAN
NTS
EXISTING GREENHOUSE
EXISTING HEADHOUSE
EXISTING STORAGE
EXISTING
CHEM.
STORAGE
PROVIDE CONTINUOUS MOTORIZED RIDGE
VENT AT EACH GROWTH ROOM -- MATCH
LOCATION AND SIZE TO EXISTING VENTS.
SEE MECHANICAL / ELECTRICAL
PROVIDE 16 MIL POLYCARBONATE
ROOF AND GLAZING SYSTEM FULL
LENGTH FROM EAVE TO BASE OF
RIDGE VENT, TYP.
PROVIDE EAVE & GABLE TRIM FROM
MANUFACTURER TO FACILITATE
INSTALLATION OF NEW ROOF AND
WALL GLAZING SYSTEM, TYP.
A-201
A-201
A-201
A-301
A-301
0'-
31'-10"
INTERIOR WALL LOCATION
LEGEND
BUILDINGS NOT IN CONTRACT
SCALE:
ROOF PLAN
3/16"=1'-0"
A-111
PLAN
NORTH
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
KEYPLAN
NTS
GREENHOUSE #2
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\A rch
\A-
1.d wg
Ju n 2
5,
- 1
1:3 4a m c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
ROOF PLAN
A-111 9 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
CHEMICAL STORAGE
NOT SHOWN FOR
CLARITY
0'-0"
1'-8"
ROOF EAVE
7'-0"
ROOF RIDGE
15'-4 1/2"
GREENHOUSE F.F.
AT STEMWALL
T.O. STEMWALL
EXISTING HEADHOUSE BEYOND
OPERABLE RIDGE VENT WITH 16 MIL
POLYCARBONATE PANELS
EXISTING STEM WALL --
PATCH AND REPAIR
DAMAGED AREAS
EXHAUST FAN -- SEE MECH.
GLAZING SYSTEM WITH 16 MIL
POLYCARBONATE PANEL AT
EXTERIOR WALL AND ROOF -- TYP. SIDE WALL VENT OPERATOR
AND ALUMINUM RACK SYSTEM.
DESIGN BY GREENHOUSE
MANUFACTURER.
CONCRETE STAIR
SITE LIGHTING MOUNTED TO
GREENHOUSE EXTERIOR -- SEE ELEC.
GREENHOUSE F.F.
AT STEMWALL
0'-0"
T.O. STEMWALL
1'-8"
ROOF EAVE
7'-0"
ROOF RIDGE
15'-4 1/2"
EXHAUST FAN - SEE MECH.GLAZING SYSTEM WITH 16 MIL
POLYCARBONATE PANEL AT
EXTERIOR WALL AND ROOF -- TYP.
STORAGE NOT
SHOWN FOR CLARITY
OPERABLE RIDGE VENT
EXISTING STEM WALL --
PATCH AND REPAIR
DAMAGED AREAS
EX
IS
TI
NG
H
EA
DH
OU
SE
0'-0"
1'-8"
ROOF EAVE
7'-0"
ROOF RIDGE
15'-4 1/2"
GREENHOUSE F.F.
AT STEMWALL
T.O. STEMWALL
GLAZING SYSTEM WITH 16 MIL
POLYCARBONATE PANEL AT
EXTERIOR WALL AND ROOF -- TYP. OPERABLE RIDGE VENT
SIDE WALL VENT OPERATOR
AND ALUMINUM RACK SYSTEM
EXISTING STEM WALL --
PATCH AND REPAIR
DAMAGED AREAS
OPERABLE SIDE WALL VENT
(EVAPORATIVE COOLERS
BEHIND -- SEE MECH)
EX
IS
TI
NG
H
EA
DH
OU
SE
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\A rch
\A-
1.d wg
Ju n 2
5,
- 1
1:3 4a m c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
ELEVATIONS
A-201 10 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
EAST ELEVATION
1/4"=1'-0"
A-201
SCALE:
SOUTH ELEVATION
1/4"=1'-0"
A-201
SCALE:
NORTH ELEVATION
1/4"=1'-0"
A-201
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
EXISTING GREENHOUSE
STRUCTURE TO REMAIN
PROVIDE SHADE SCREENS AT
GROWTH ROOMS
PROVIDE PERLINS WHERE
NEEDED PER MANUF.
REQUIREMENTS
EXISTING GREENHOUSE
CONCRETE STEM WALL TO REMAIN
PROVIDE OPERABLE RIDGE VENT WITH 16 MIL
POLYCARBONATE PANELS WITH GLAZING SYSTEM --
SEE MECHANICAL / ELECTRICAL DRAWINGS
PROVIDE SHADE SCREENS AT GROWTH ROOMS
PROVIDE 16 MIL POLYCARBONATE ROOF GLAZING
SYSTEM
PROVIDE 8 MIL POLYCARBONATE PANELS AND
GLAZING SYSTEM @ INTERIOR WALLS AND
PARTITIONS
EXISTING STRUCTURAL SYSTEM
AND MOUNTING SYSTEM TO
REMAIN
PROVIDE CONCRETE SLAB
INFILL -- SEE STRUCTURAL
PROVIDE TRENCH DRAIN -- SEE
STRUCTURAL AND PLUMBING
EXISTING GREENHOUSE
STRUCTURE TO REMAIN
PROVIDE 16 MIL POLYCARBONATE
PANELS AND GLAZING SYSTEM @
EXTERIOR WALLS
ALUMINUM RACK SYSTEM BY
GREENHOUSE MANUFACTURER.
OPERATOR -- SEE MECH.
CONCRETE POST FOOTING. IF
FOOTING OVERLAPS EXISTING
CONCRETE / ASPHALT
8" STRUCTURAL FILL
3'- 0"
8"
1'-6"
EVAPORATIVE COOLING
SYSTEM -- SEE MECH.
PROVIDE SLIDING INTERIOR
DOOR -- SEE SCHEDULE
EXISTING CONCRETE STEM WALL
TO REMAIN
GREENHOUSE F.F. AT STEM WALL
0'-0"
TOP OF STEM WALL
1'-8"
ROOF EAVE @ STRUCTURE
7'-0"
A-501
FAN AND HOOD -- SEE MECH.
EXISTING STEM WALL
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
SECTION
A-301 11 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
BUILDING SECTION
3/4"=1'-0"
A-301
SCALE: 3/4"=1'-0"
0 1' 2' 4'
VENT SECTION TO MATCH EXISTING VENT DIMENSIONS
16 MIL POLYCARBONATE PANELS AT ROOF
ALUMINUM SHAFT
HANGER AS REQUIRED
8" +/-
3 1/2" +/-
EXISTING STRUCTURE
TO REMAIN
DOUBLE VENT RIDGE
DOUBLE VENT RIDGE MOUNT
5" ALUMINUM PURLIN. EXTEND
AND ANCHOR TO EXISTING TRUSSES
EXISTING STRUCTURE
TO REMAIN
MINIMUM 1-1/2" x 1-1/2" x 1/4" ALUMINUM
PURLIN CLIP. (1) PER SIDE
MINIMUM 3/8" DIA. STAINLESS STEEL BOLT
PROVIDE GLAZING BAR
VENT HEADER BAR
VENT BOTTOM RAIL CAP
VENT BOTTOM RAIL
16 MIL POLYCARBONATE PANEL
OPERATOR SHAFT. SEE MECHANICAL / ELECTRICAL
EAVE TRIM
16 MIL POLYCARBONATE PANEL
AT EXTERIOR WALLS
16 MIL GLAZING BAR
NOTES:
1. GREENHOUSE SUB-FRAMING, GLAZING AND COMPONENTS SHOWN ARE MINIMUM
REQUIREMENTS. CONTRACTOR MUST PROVIDE SHOP DRAWINGS BY
GREENHOUSE MANUFACTURER FOR APPROVAL WHICH MUST INCLUDE ALL
CONSTRUCTION REQUIRED BY MANUFACTURER AND MEETING MIN.
REQUIREMENTS OF CONSTRUCTION DOCUMENTS.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\A rch
\A-
1.d wg
Ju n 2
5,
- 1
1:3 4a m c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
DETAIL
A-501 12 3406/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERTY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MD 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
ROOF AND WALL SECTION DETAIL
6"=1'-0"
A-501
STORAGE
DEMOLISH EXISTING
DOMESTIC COLD WATER
PIPING OVERHEAD (TYP.)
DEMOLISH EXISTING UTILITY SINK
AND APPURTENANCES
DEMOLISH EXISTING
FLOOR DRAIN
DEMOLISH EXISTING
FLOOR DRAIN
DEMOLISH EXISTING
FLOOR DRAIN
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\P D1
.dw g Ju n 2 5,
- 5 :24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
PLUMBING DEMOLITION PLAN
PD101
13 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
DEMOLITION KEYED NOTES
1. DEMOLISH EXISTING DOMESTIC COLD WATER PIPING,
HANGERS, INSULATION, AND ALL APPURTENANCES BACK TO
EXISTING 1" ISOLATION VALVE. CAP PIPING AT THE VALVE
AND RETAIN FOR CONNECTION TO NEW WORK.
2. DEMOLISH EXISTING HOSE BIBB AND ASSOCIATED PIPING.
3. DEMOLISH EXISTING DOMESTIC WATER PIPING SERVING
EXISTING SINK. CAP EXISTING WATER PIPING AT THE
NEAREST ACCESSIBLE LOCATION.
LEGEND
POINT OF DISCONNECTION
SCALE:
PLUMBING DEMOLITION PLAN
3/16"=1'-0"
PD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
KEYPLAN
NTS
GREENHOUSE #2
GENERAL DEMOLITION NOTES
1. DEMOLISH EXISTING UNDERGROUND PIPING, INCLUDING
ASSOCIATED FITTINGS AND APPURTENANCES. COORDINATE
WITH STRUCTURAL DRAWINGS FOR EXISTING CONCRETE
SLAB DEMOLITION.
STORAGE
GROWTH ROOM
GROWTH ROOM
GROWTH ROOM
P-1
HB
HB
HB
HB
FHB
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\P -10
1.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
GREENHOUSE PLUMBING PLAN
P-101 14 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
KEYNOTES
1. CONNECT NEW DOMESTIC COLD WATER SUPPLY PIPING TO
EXISTING 1" ISOLATION VALVE.
2. ROUTE COLD WATER PIPING TO POINT-OF-USE WATER
HEATER (DWH-1). PROVIDE ISOLATION VALVE AND
ACCESSORIES AS REQUIRED BY MANUFACTURER.
3. ROUTE 3/4" DOMESTIC COLD WATER PIPING DOWN TO
COOLING PAD SUMPS SERVING ECP-1.
4. ROUTE 3/4" DOMESTIC COLD WATER PIPING DOWN TO
COOLING PAD SUMPS SERVING ECP-2.
5. ROUTE 3/4" DOMESTIC COLD WATER PIPING DOWN TO
COOLING PAD SUMPS SERVING ECP-3 AND ECP-4.
LEGEND
1" DCW
1" DCW
1" DCW
3/4" DCW
POINT OF CONNECTION
SCALE:
GREENHOUSE PLUMBING PLAN
3/16"=1'-0"
P-101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
KEYPLAN
NTS
GREENHOUSE #2
3/4" DCW
3/4" DCW
3/4" DCW
3/4" DCW
3/4" DCW
3/4" DCW
3/4" DCW
STORAGE
GROWTH ROOM
GROWTH ROOM
GROWTH ROOM
TD-1
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\P -10
2.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
GREENHOUSE SANITARY PLAN
P-102 15 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
KEYNOTES
1. SEE DETAIL P-501-9 FOR SANITARY CONNECTION TO MANHOLE.
2. SEE DETAIL P-502-1 FOR SANITARY CONNECTION TO TRENCH
DRAIN.
LEGEND
2" VTR
FCO
GCO
TD-2
TD-1
4" SS
4" SS
P-1
FCO
4" SS
2" SS
4" SS
SCALE:
GREENHOUSE SANITARY PLAN
3/16"=1'-0"
P-102
PLAN
NORTH
KEYPLAN
NTS
GREENHOUSE #2
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\P -50
1.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
PLUMBING DETAILS
P-501 16 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
20"
8"
-1
/2"
2" WASTE & P-TRAP
20" 31"
82"
20"
SCALE:
WORK SINK DETAIL (P-1)
N.T.S
P-501
31"
ROUTE DRAIN PIPING
UNDERGROUND
EXTERIOR WALL
CENTER PIPE IN SLEEVE
SEAL SLEEVE WITH SEALANT
STANDARD WEIGHT STEEL
PIPE ANCHORED IN PLACE
BACK UP MATERIAL
COAT EXTERIOR
SURFACES WITH
TAR COMPOUND
SCALE:
TYPICAL PIPE SLEEVES THROUGH WALLS
N.T.S
P-501
TO UNISTRUT P2500
SERIES PIPE STRAP
(TYP.)
TO UNISTRUT P3400
SERIES PIPE CLAMPS
(TYP.)
TO UNISTRUT P 1000 12 GA CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO MATCH BASE
MATERIAL AND LOAD REQUIREMENTS
INSULATE AS REQD
CONC. OR MASONRY WALL
TO UNISTRUT P 1000 12 GA CHANNEL
(TYP.)
SECURE W/APPROVED ANCHOR TO MATCH BASE
MATERIAL AND LOAD REQUIREMENTS
INSULATE AS REQD
CONC OR MASONRY WALL
NOTE:
PROVIDE MIN ANCHOR
SUPPORT SPACING EVERY 3'
VERTICALLY
FOR PIPES < 4"Ø
FOR CONDUIT < 2"Ø
SCALE:
PIPING WALL SUPPORT DETAIL
N.T.S
P-501
HOT OR COLD WATER SUPPLY
IF BRANCH IS GREATER THAN 20'-0" LONG,
PROVIDE AN ADDITIONAL WHA IN MIDDLE OF
RUN. EACH SIZED FOR HALF THE FIXTURE
UNITS. IF HORIZONTAL BRANCH IS LESS
THAN 20'-0" LONG, PROVIDE ONE
WHA AT END OF LINE.
FIXTURE (TYP.)
NOTE: INSTALL PER MANUFACTURER'S INSTRUCTIONS.
PROVIDE DIAPHRAGM TYPE WATER HAMMER ARRESTOR AT
ALL QUICK-CLOSING VALVES.
SINGLE/DOUBLE FIXTURE
WHA
SIZE
PIPE
SIZE
FIXTURE UNIT
LOAD
A 1/2" 1-11 B 3/4" 12-32 C 1" 33-60 D 1-1/4" 61-113 E 1-1/2" 114-154 F 2" 154-330
SCALE:
WATER HAMMER ARRESTOR (WHA) SCHEMATIC
N.T.S
P-501
HANGER ROD
GRINNELL FIG. 260
ADJUSTABLE GALV.
CLEVIS OR EQUAL
PIPE
INSULATION - DETERMINE
TYPE AND THICKNESS
FROM SPECS.
16" GA. GALV. PROTECTION
SADDLE 12" LARGE
SPACER- HIGH DENSITY
INSULATION ALONG
BOTTOM SEGMENT OF PIPE
SCALE:
HANGER FOR INSULATED PIPE
N.T.S
P-501
SCALE:
P.O.U. WATER HEATER PIPING SCHEMATIC (DHW-1)
N.T.S
P-501
6"
MIN.
6" MIN.
1" MIN. CLEAR
1"
SCALE:
FLUSH GRADE CLEANOUT
N.T.S
P-501
EXISTING MANHOLE STRUCTURE
CORED HOLE
SEWER LINE
STAINLESS STEEL
PIPE CLAMP
FLEXIBLE
CONNECTOR
EXISTING MANHOLE
INVERT (1184.83')
NON-SHRINK GROUT
(AS REQUIRED)
"BOOT" CONNECTION
SEWER LINE INVERT
(1188.98')
SCALE:
SANITARY CONNECTION TO MANHOLE
N.T.S
P-501
NOTE:
INSTALL 'T&P' VALVE, INSTALL ON THE HOT
WATER OUTLET PIPE BEFORE THE ISOLATING
VALVE
BALL OR STOP
VALVE
WATER HEATER
MOUNT ON WALL
WITH BRACKET
IN-LINE FLOW CONTROL,
AS REQUIRED
THREE WAY ANGLE
STOP VALVE
3/4" CW SUPPLY
FROM WALL
SINK
FINISHED GRADE
BRASS PLUG
1" MIN CLEARANCE BETWEEN
PLUG & COVER
C.I. BOX W/ COVER
PVC PIPE
WYE BRANCH
PLUG
CONCRETE 6" THICK X 1'-0" WIDE
SQUARE CONC. PAD
SCALE:
FLOOR CLEANOUT DETAIL
N.T.S
P-501
14-GAUGE STEEL SINK
BOWL CONSTRUCTION
FINISHED FLOOR
PROVIDE NICKEL BROZE FLOOR PLATE
TO BE COMPATIBLE WITH FLOOR
INSTALLED
LONG SWEEP 1/4 BEND OR
COMBINATION "Y" & 1/8
BEND. (USE REDUCING
TYPE WHERE REQUIRED)
BUILDING DRAIN
SCALE:
EXTERIOR WALL HYDRANT DETAIL (FHB)
N.T.S
P-501
MOUNT AT 18" AFF
UNLESS NOTED OTHERWISE
REFER TO PLANS
FREEZE PROTECTED WALL
HYDRANT PER SCHEDULE
COLD WATER PIPING. REFER TO
PLANS FOR SIZE.
STRAP PIPE TO WALL
90° ELL
VANDAL PROOF LOCKING
ENCLOSURE
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\P -50
2.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
PLUMBING DETAILS
P-502 17 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
SCALE:
TRENCH DRAIN DETAIL (TD-1 & TD-2)
N.T.S
P-502
DRAIN CHANNEL
4" WASTE PIPE
P-TRAP
HUB DRAIN MOUNTED FLUSH
WITH BOTTOM OF DRAIN
REMOVABLE GALVANIZED DUCTILE IRON
SLOTTED (8' SECTIONS) AND INSTALLED PER
MANUFACTURER WRITTEN INSTRUCTION FOR
THIS APPLICATION FINISHED FLOOR/GRADE
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\P -60
1.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
PLUMBING SCHEDULE
P-601 18 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
MARK DESCRIPTION CW HW MIN. WASTE REMARKSVENTMIN. TRAP
PLUMBING FIXTURE SCHEDULE
HB 3/4" -HOSE BIBB - - -
P-1 WORK SINK 1/2" 1/2" 2" 2"2"
PROVIDE ONE PIECE SELF SUPPORTING TYPE 304 STAINLESS STEEL SINGLE COMPARTMENT SINK. PROVIDE GOOSENECK, CENTER SET FAUCET. PROVIDE WITH INTEGRAL 30" DRAIN BOARDS ON EACH SIDE OF BOWL. OVERALL DIMENSIONS 82" X 27". MOUNT AND ANCHOR TO FLOOR ACCORDING TO MANUFACTURES WRITTEN INSTRUCTIONS.
PROVIDE WITH DWH-1 TO SERVE WORK SINK.
FHB 3/4" -
PRIER C-144 NON-FREEZE, ANTI-SIPHON DESIGN WALL-HYDRANT. MOUNT 18" AFF.
FREEZE PROTECTED HOSE BIBB - - -
PRIER C-634 OR EQUAL HEAVY COMMERCIAL FREEZELESS WALL HYDRANT WITH INTEGRAL ASSE 1052 VACUUM BREAKER/DOUBLE BACKFLOW PREVENTER, KEY OPERATION, AND AUTOMATIC DRAINING CAPABILITY. PROVIDE
OPERATINGKEY AND WALL CLAMPING RING. MOUNT 18" AFF.
TD-1
ZURN Z882-Z-GDC-USA OR EQUAL 12" WIDE TRENCH DRAIN WITH GALVANIZED DUCTILE IRON
SLOTTED GRATE, 4" NO-HUB BOTTOM OUTLET. PROVIDE 8'-0" OVERALL LENGTH.
TRENCH DRAIN -TD-2
-FLOOR CLEANOUT - - -FCO
ZURN CO-PV3 OR EQUAL, ADJUSTABLE FLOOR CLEAN OUT, PVC 3" X 4" SOLVENT WELD BODY WITH
BOTTOM OUTLET, CLEAN OUT PLUG, AND LIGHT DUTY NICKEL BRONZE OR STAINLESS STEEL
STRAINER. SEE PLANS FOR SIZING.
GRADE CLEANOUT - - -- - - -GCO
TRENCH DRAIN - - -4"4"
- 4"4"
ZURN Z882-Z-GDC-USA OR EQUAL 12" WIDE TRENCH DRAIN WITH GALVANIZED DUCTILE IRON
SLOTTED GRATE, 4" NO-HUB BOTTOM OUTLET. PROVIDE 32'-0" OVERALL LENGTH.
ZURN CO-PV3-SS OR EQUAL, ADJUSTABLE FINISHED AREA CLEAN OUT WITH PVC BODY, CLEAN
OUT PLUG, AND STAINLESS STEEL ROUND COVER. SEE PLANS FOR SIZING.
MARK
EWT
(°F) REMARKS
DWH-1
NOTES:
1. INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. CONTRACTOR MUST FIELD VERIFY ALL EXISTING DIMENSIONS AND CONNECTION CONDITIONS.
3. ACTIVATION OF INSTANTANEOUS WATER HEATER SHALL BE 0.17 GPM.
SEE NOTES51
WATER HEATER SCHEDULE
TYPE
POINT OF USE
TANKLESS
LWT
(°F)
FUEL TYPE DIMENSIONS
WIDTH
(IN)
HEIGHT
(IN)
11.25 15.5AOSMITH
UPVA-110E
BASIS
OF DESIGN
ELECTRICAL
V PH FREQ.
208 1 60
DEPTH
(IN)
INPUT
(KW)
11 ELECTRIC1.05
GPM AT
TEMPERATURE
RISE
TANK
SIZE
(GAL.)
EFFICIENCY
91%
WEIGHT
(LB)
SERVES
P-1
STORAGE
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\M D1
.dw g Ju n 2 5,
- 5 :24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
MECHANICAL DEMOLITION PLAN
MD101
19 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
DEMOLITION KEYNOTES
1. REMOVE EXISTING UNIT HEATER AND RETAIN FOR
REINSTALLATION. PROTECT EQUIPMENT FROM DAMAGE
DURING CONSTRUCTION.
2. DEMOLISH EXISTING HEATING WATER SUPPLY AND RETURN
PIPING BACK TO EXISTING 2" ISOLATION VALVES. CAP PIPING
AT VALVES AND RETAIN VALVES FOR FUTURE CONNECTIONS.
3. DEMOLISH EXISTING SIDEWALL EXHAUST FAN.
LEGEND
DEMOLISH EXISTING
EVAPORATIVE COOLING PAD
SYSTEM, SUMPS, TANKS AND
ALL APPURTENANCES (TYP.)
DEMOLISH EXISTING
EVAPORATIVE COOLING PAD
AND APPURTENANCES (TYP.)
DEMOLISH EXISTING HEATING
WATER SUPPLY AND RETURN
PIPNG, HANGERS, SUPPORTS,
INSULATION AND ALL
APPURTENANCES (TYP.)
DEMOLISH EXISTING HEATING
WATER SUPPLY AND RETURN
(TYP.)
DEMOLISH EXISTING HEATING
WATER SUPPLY AND RETURN
(TYP.)
POINT OF DISCONNECTION
SCALE:
MECHANICAL DEMOLITION PLAN
3/16"=1'-0"
MD101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
KEYPLAN
NTS
GREENHOUSE #2
DEMOLISH EXISTING
GREENHOUSE CONTROLS
SYSTEM
STORAGE
GROWTH ROOM
GROWTH ROOM
GROWTH ROOM
EF-1
EF-2
EF-3
EF-4
EF-5
EF-6
EF-7
EF-8
ECP-1
ECP-2
ECP-3
ECP-4
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\M -10
1.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
GREENHOUSE MECHANICAL PLAN
M-101 20 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND PROPERY D
5601 SUNNYSIDE AVENUE
RM 3-2102
BELTSVILLE, MS 20705
XXX
XXX
XXX
XXX
XXX
KEYNOTES
1. REINSTALL EXISTING UNIT HEATER AND ASSOCIATED
VALVES, CONTROLS, SUPPORTS AND APPURTENANCES.
RECONNECT TO NEW HEATING WATER PIPING.
2. PROVIDE COOLING PAD SUMP COMPLETE WITH PUMP,
FLOAT CONTROLS, AND PIPING FOR A COMPLETE AND
OPERATIONAL SYSTEM.
3. CONNECT NEW HYDRONIC HEATING WATER SUPPLY AND
RETURN PIPING TO EXISTING 2" ISOLATION VALVES.
4. PROVIDE MICRO-GROW GROW MASTER CONTROLLER
SYSTEM OR APPROVED EQUAL. MASTER CONTROLLER
SYSTEM MUST BE MOUNTED ON APPROXIMATELY 4'-0" X 4'-0"
MARINE-GRADE PLYWOOD BASE AND MUST BE COMPLETE
WITH RELAYS, CONTACTORS, ALL SENSORS, AND
APPURTENANCES FOR A COMPLETE OPERATIONAL SYSTEM.
PROVIDE CONTROL OF ENTIRE GREENHOUSE AND
HEATING/COOLING EQUIPMENT SPECIFIED HEREIN
INCLUDING EXHAUST FANS, EVAPORATIVE COOLERS, &
ROOF/SIDE VENTS. SEE SHEET M601 FOR CONTROLS.
TESTING: CHECK THE COMPUTERIZED CLIMATE
CONTROLLER, ADJUST EQUIPMENT AND COMPUTER FOR
PROPER OPERATION AND DEMONSTRATE OPERATION TO
CONTRACTING OFFICER.
5. PROVIDE DRIVE UNIT AND APPURTENANCES FOR ROOF
VENT FOR AUTOMATIC OPERATION OF VENT SYSTEM.
PROVIDE DRIVE UNIT INCLUDING GEAR MOTOR, ROLLER
BEARING PIPE HANGERS, GALVANIZED PIPE, ARM AND ROD
LINKAGE, OPEN AND CLOSE LIMIT SWITCHES, SCREENS,
THERMOSTAT AND OTHER COMPONENTS AS REQUIRED FOR
A COMPLETE OPERATING SYSTEM WITH EMERGENCY
RELEASE MECHANISM: QUICK DISCONNECT-RELEASE OF
ELECTRIC-MOTOR DRIVE SYSTEM, PERMITTING MANUAL
OPERATION IN THE EVENT OF OPERATING FAILURE.
MOTORIZED VENT MUST BE THE FULL LENGTH OF THE
GREENHOUSE BAY. INTER-COMPONENT WIRING BY THE
CONTRACTOR; 110V POWER WIRING TO COMPONENTS BY
ELECTRICAL. GEAR MOTORS MUST BE
HIGH-STARTING-TORQUE, REVERSIBLE, CONTINUOUS-DUTY,
CLASS A INSULATED, ELECTRIC MOTORS, COMPLYING WITH
NEMA MG 1, WITH THERMAL-OVERLOAD PROTECTION; SIZED
TO OPEN AND OPERATE SIZE AND WEIGHT OF ROOF VENT
WITHOUT EXCEEDING NAMEPLATE RATINGS OR
CONSIDERING SERVICE FACTOR, WITH THE FOLLOWING
SPECIFICATIONS:
··· SERVICE FACTOR: ACCORDING TO NEMA MG 1,
UNLESS OTHERWISE INDICATED.
··· ENCLOSURE: OPEN DRIP PROOF, UNLESS
OTHERWISE INDICATED.
··· MOTORS: SINGLE PHASE, 110V, 60 HZ.
··· LIMIT SWITCHES: ADJUSTABLE SWITCHES,
INTERLOCKED WITH MOTOR CONTROLS AND SET
TO AUTOMATICALLY STOP ROOF VENT AT OPEN
AND CLOSED POSITIONS.
LEGEND
2" HWS
2" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
2" HWS
2" HWR
5 5
5 5
POINT OF CONNECTION
HF-1
HF-2
HF-3
HF-4
HF-5
HF-6
HF-7
HF-8
SCALE:
GREENHOUSE MECHANICAL PLAN
3/16"=1'-0"
M-101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
KEYPLAN
NTS
GREENHOUSE #2
BALANCING VALVE
SET TO 5.2 GPM
BALANCING VALVE
SET TO 5.2 GPM
BALANCING VALVE
SET TO 5.2 GPM
BALANCING VALVE
SET TO 6.5 GPM
NORTH
48"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
J:\ jo bs \18
US
DA
Re no va te Gr ee nh ou se
#2
- U niv ers ity Pa rk
PA
\07 W ork ing
Fo lde r\M ec h\M -50
1.d wg
Ju n 2
5,
- 5
:24 pm c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
RENOVATE GREENHOUSE #2
US-BUILDING 0491
532 CURTIN RD.
UNIVERSITY PARK, PA 16802
MECHANICAL DETAILS
M-501 21 3306/26/26
BP
BEB
JGM USDA ARS ACQUISITION
AND…