Design Analysis - Updated 07282026.pdf

PDF 6 MB Posted

Attached to
Greenhouse Modernization
Solicitation number
1232SA26Q0889
Issued by

About this file

This is a Design Analysis document for the renovation of Greenhouse #2 at the USDA Pasture Systems & Watershed Management Research Unit in University Park, Pennsylvania. The project is a 100% design submittal prepared by The Johnson-McAdams Firm, P.A. under Contract No. 12305B21D0013, Task Order No. 1232SA26F0267, dated July 28, 2026.

The project involves complete demolition and reconstruction of Greenhouse #2, a 3,200 square-foot facility divided into three bays (two growth rooms and one entrance bay). The design includes retention of the existing steel frame and stem wall foundation, with new construction consisting of a slab-on-grade with 8 inches of structural fill, XPS insulation, and interior trench drains. The greenhouse will feature new aluminum glazing framing with translucent polycarbonate glazing, operable ridge vents with automated controls, automatic shade cloths for each room, and a new evaporative cooling system with four 23-foot cooling pads and interior sumps. Mechanical systems include reinstallation of existing unit heaters, new exhaust fans, replacement plumbing with stainless-steel work sinks and hose bibbs, and domestic water replacement to existing isolation valves. The electrical design specifies modifications to existing panels GDP2-A and GDP2-B, new LED lighting with grow light fixtures, wireless access points, and a greenhouse controller. The design conforms to 2024 International Building Code, ACI 318-25, ASCE 7-22, ASHRAE standards, and UFC specifications. Key design considerations address facility requests for interior trench drains, LED lighting for adjustability, automatic controls for heating and ventilation with freeze prevention, and evaporative cooling systems resistant to mold formation.

View the file

Other files

File Type Posted
RFIs.pdf PDF
Site Visit Sign-In Sheets.pdf PDF
Specifications - Updated 07082026.pdf PDF
SF30 - Amend 01.pdf PDF
Drawings - Updated 07282026.pdf PDF
Statement of Work.pdf PDF
Drawings.pdf PDF
Specifications.pdf PDF
Wage Determination.pdf PDF
SF-1442.pdf PDF
Design Analysis.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN ANALYSIS

RENOVATE GREENHOUSE #2

100% Design Submittal

Includes:

Basis of Design Project Reports Basis of Design Cut Sheets Calculations

Pasture Systems & Watershed Management Research Unit US-Building 0491 532 Curtin Rd.

University Park, PA

Prepared For:

U.S. Department Of Agriculture USDA ARS Acquisition and Property D 5601 Sunnyside Avenue

RM3-2102

Beltsville, MD 20705

Contract No.

12305B21D0013

Task Order No.

1232SA26F0267

Prepared By:

The Johnson-McAdams Firm, P.A.

Greenwood, Mississippi

July 28, 2026

Design Analysis – 100% Design Submittal Renovate Greenhouse #2 USDA PSWMRU, University Park, PA

DESIGN ANALYSIS

TABLE OF CONTENTS

Basis of Design Architectural Design Structural Design Mechanical Design Electrical Design Attachments Project Reports

Site Visit Meeting Report Basis of Design Cut Sheets Mechanical Plumbing Calculations

Mechanical

PART 1 - BASIS OF DESIGN

USDA PSWMRU, University Park, PA

Renovate Greenhouse #2

Greenhouse 2 will be demolished down to the steel structure and slab to allow for full reconstruction of all greenhouse systems. Currently, the greenhouse is accompanied by a newly renovated headhouse and main building with an adjacent greenhouse to be replaced with a new lab in a future project. The greenhouse is approximately 3200 sqft, divided into 3 bays (2 growth rooms with one entrance bay).

USDA PSWMRU, University Park, PA

Architectural Design

Applicable Codes and Standards

• International Building Code (IBC) - 2018

• Unified Facilities Criteria, “DoD Building Code, UFC 1-200-01 with Change 3

• Unified Facilities Criteria, “Architecture”, UFC 1-300-01 with Change 4

Architecture Design Overview

EXISTING CONDITIONS:

Greenhouse 2 is a pre-engineered frame construction with standard greenhouse glazing panels and aluminum frames with a concrete stem wall and interior columns and support mounting throughout the growth rooms. The floors are a mixture of concrete walkways with gravel sections for drainage throughout 2 of the 3 bays.

DEMOLITION:

The greenhouse is to be demolished down to the main structural frame and stem wall.

All aluminum frames and glazing panels must be demolished in their entirety. The concrete walkways and gravel flooring are to be demolished in their entirety. Any attachment to the existing headhouse must be removed carefully to not cause any damage to the headhouse.

NEW WORK:

Greenhouse 2 is to be replaced with a similar layout of the current greenhouse, attaching a new aluminum glazing system to the existing structure. The greenhouse will be separated into three growth chambers with a similar layout to the existing greenhouse divided by interior partitions and sliding doors. The roof will have an operable ridge vent with controls linked into the mechanical/electrical system for each room to have control of its vents. Each growth room will have automatic shade clothes programmed into the mechanical system.

USDA PSWMRU, University Park, PA

Structural Design

• IBC 2024 International Building Code

• ACI 318-25 Building Code Requirements for Reinforced Concrete, American Concrete Institute

• IEBC 2024 International Existing Building Code

• ASCE 7-22 Minimum Desing Loads for Buildings and Other Structures

Structural Design Overview

EXISTING CONDITIONS:

The existing greenhouse consists of a tube steel structure supporting greenhouse glazing. The structural foundation system is for the existing structure is unknown. During the site investigation it was note that the interior tube columns are supported by 10”x10” concrete pedestals. The support for the pedestals in unknown. The exterior walls and interior walls of the greenhouse bear on a concrete stem wall. The existing floor system consists of concrete walkways and equipment support pads and gravel. The existing greenhouse layout consists of three bays divided by interior glazing panels supported by stem walls.

The existing greenhouse steel framing structure and foundation are to remain and be protected during construction.

DEMOLITION:

The structural demolition consists of demolishing the existing slabs, equipment pads and walkways. The demolition will also excavate and remove the interior fill of the greenhouse to accommodate the new construction.

NEW WORK:

The new work will consist of providing a slab on grade sloped to new trench drains. The slab on grade will be supported by 8” of structural fill as directed by the Geotechnical Report performed by the US Army Corps of Engineers – Baltimore District in June of 2022. Constructing the slab on the structural fill material will remove the concerns of frost heave of the slab. An expansion joint will be provided between the existing headhouse masonry wall and new slab as well as between the existing stem walls and the concrete slab. A layer of XPS insulation will be provided beneath the slab to mitigate heat loss through the slab.

USDA PSWMRU, University Park, PA

Mechanical Design

• International Plumbing Code

• International Mechanical Code

• UFC 3-420-01

• UFC 3-410-01

• ASHRAE 90.1

• ASHREA 62.1

Mechanical Design Overview

The existing hydronic unit heaters and associated appurtenances shall be removed and reinstalled to provide a complete and fully functional greenhouse heating system.

Existing heating water piping shall be demolished and reinstalled to match the existing configuration, with reconnection at the existing 2-inch heating water supply and return isolation valves.

The existing greenhouse ventilation and evaporative cooling system shall be replaced to provide the airflow and cooling required to maintain greenhouse environmental conditions. The system shall consist of new exhaust fans installed in the existing locations with a new evaporative cooling system consisting of four 23-foot-long by 36-inch-tall evaporative cooling pads mounted along the interior wall of the greenhouse. Cooling pad sumps shall be located inside of the greenhouse to improve accessibility for operation and maintenance while providing protection from freezing outside conditions. The replacement cooling system shall provide the cooling necessary to maintain greenhouse environmental conditions.

The domestic water system within the greenhouse shall be replaced up to the existing 1-inch isolation valve. The plumbing system shall include a new stainless-steel work sink with dual drainboards, the relocation of the 4 existing hose bibbs to the interior side of the greenhouse exterior wall, and one new exterior hose bibb to provide water within and outside of the greenhouse. Four additional hose bibbs will be located near the evaporative cooling pad sumps to supply make up water to the cooling systems. Upon completion of the project, Greenhouse #2 shall be provided with fully functional mechanical and plumbing systems capable of supporting normal greenhouse operations while maintaining greenhouse environmental conditions.

USDA PSWMRU, University Park, PA

Electrical Design

Applicable Codes and Standards

UFC 1-200-01 DoD Building Code UFC 3-501-01 Electrical Engineering UFC 3-520-01 Interior Electrical Systems UFC 3-530-01 Interior and Exterior Lighting and Controls UFGS Unified Facilities Guide Specifications 2023 NFPA 70 National Electrical Codes 2022 NFPA 72 National Fire Alarms and Signaling Code 2021 NFPA 101 Life Safety Code IESNA Handbook Lighting Handbook Reference 10th Edition

ASHRAE/IESNA 90.1-2007

ARS Manual

Energy Standard for Buildings Agricultural Research Service Facilities Design Guide

ELECTRICAL SYSTEM

The electrical systems shall consist of a distribution system, a power system, and a lighting system.

Distribution System

The existing electrical service at the greenhouses consists of a 2 section panelboard located directly outside the greenhouse #2 labeled GDP2-A and GDP2-B fed from the main distribution switchboard in the headhouse basement electrical room. Panels GDP2-A and GDP2-B shall be existing to remain and breakers modified to accommodate new mechanical equipment and all other greenhouse electrical requirements.

There is also an existing panel labeled EVPD located inside the greenhouse that may be used for additional greenhouse requirements.

All existing circuitry located inside the greenhouse shall be demolished back to the source. All existing electrical devices shall be removed and installed new as indicated on the drawings.

The existing Chemical Storage shop that is connected to the greenhouse shall remain in service throughout the duration of the project. The contractor shall protect the existing conduit, disconnects, and associated load center. The Chemical Storage shop is fed from panel GDP2-B circuit 68,70.

Power System Receptacles shall be furnished and installed where noted on the drawings as required to adequately serve each space.

USDA PSWMRU, University Park, PA

All receptacles in the greenhouse shall be mounted in a weatherproof while-in-use box and be of the GFCI type. All boxes shall be cast metal weatherproof boxes.

All circuitry in the new greenhouse shall be IMC or Galvanized Rigid Steel.

Exposed, exterior circuitry above grade shall be galvanized rigid steel.

All conductors in wet locations shall have XHHW insulation. Conductors in dry locations shall be THHN/THWN copper. Solid conductors shall be used for #10 and #12 AWG, and stranded conductors shall be used for larger sizes.

Each greenhouse shall be provided with a greenhouse controller provided by the mechanical contractor and installed by the electrical contractor. Coordinate the exact requirements with the greenhouse controller manufacturer for a fully functioning system.

Lighting System

Interior Lighting:

• The illumination levels of the interior lighting system will be consistent with the current standards as defined by the Illuminating Engineering Society of North America (IESNA) Lighting Handbook current codes and UFC 3-530-01.

• Lighting fixtures shall be LED.

• Greenhouse fixtures shall be 4’ linear fixtures offering broad and dual spectrum options.

• Exit signs shall be furnished with NiCad batteries.

• Emergency lighting in the greenhouse and vestibule shall be accomplished by providing NiCad battery packs.

• All fixtures mounted in the Greenhouses shall be aluminum or non-metallic construction.

• All Grow Light fixtures and associated ceiling-mounted receptacles shall be secured to tubular mounting structures.

• Grow Light fixtures in the greenhouse shall be suspended from an existing overhead tubular structure.

Lighting controls:

• Greenhouse lighting controls shall be routed through existing Tork time clock contactors.

• General greenhouse lighting shall have local manual controls via toggle switches.

• All lighting controls shall comply with UFC 3-530-01.

LIGHTNING PROTECTION SYSTEM

The existing counterpoise shall be protected throughout the duration of the project.

TELECOMMUNICATION SYSTEM

The contractor shall install ceiling mounted wireless access points (WAP) in the greenhouse. All required CAT6A cable shall be installed from the existing cable secured to the ceiling in the existing lab building.

SPECIAL SYSTEMS

The contractor shall protect the existing speaker/strobe located inside greenhouse and mounted to exterior wall of headhouse building. Protect device and circuitry throughout the duration of the project.

PART 2 - ATTACHMENTS

Project Reports

Site Visit Meeting Report

Basis of Design Cut Sheets

Plumbing

Project Reports

SITE VISIT REPORT

Renovate Greenhouse #2 – University Park, PA June 8, 2026

USDA Pasture Systems & Watershed Management Research Unit

Renovate Greenhouse #2 University Park, PA

Site Visit Date: June 4, 2026

Attendees:

Brandon Burton, Evan Heller, Steven Marshall, Alex Fann, Scott Spear, Kathy Soder, Sarah Goslee

General:

The project includes demolition of the existing Greenhouse #2 façade, mechanical, plumbing, and electrical systems. It is anticipated that all existing concrete knee walls and structure of the greenhouse are in good condition and will remain. The new construction will include new Greenhouse framing attached to the existing structure, translucent polycarbonate glazing, evaporative cooling system, RO water, domestic water, automatic shade cloth in each room, new control system (Micro-Grow) and weather station.

Site Visit Notes:

The team toured the site and made the following notes and observations:

1. Interior trench drains are a high priority to the facility.

2. The drawings provided by USACE added a 4th bay into the greenhouse. The facility indicated that either keeping the 3 current bays or adding the 4th would be acceptable.

3. The facility requested interior and exterior hose bibbs on the exterior walls (currently on interior walls).

4. The evapocool system sump would be preferred to be moved inside the greenhouse.

5. The facility requested stainless steel sink(s) for the greenhouse. (1 sink on each end if possible)

6. The two (2) chemical storage buildings adjacent to the greenhouse will need temporary power during construction.

7. Remove existing site lighting and provide new lighting attached to the exterior of the greenhouse if possible.

8. LED lighting for adjustability was requested.

9. Automatic shade cloths with controls for each bay were requested.

10. Automatic ridge vents for each bay were requested.

11. The facility requested heater controls with auto freeze prevention.

12. The facility requested the evaporative cooling system be specified to be less susceptible to molding.

13. Unit heaters in each bay are new, so remove and retain for reinstallation.

Site Survey:

After discussion with facility members, the team gathered information and measurements about the existing greenhouse and compared them with the drawings provided.

Site Photos:

Greenhouse #2 South Entrance Existing space between GH and Chemical Storage

Greenhouse to Headhouse connection Existing slab / gravel base and structural tube steel

New mechanical heaters to be reinstalled Existing ventilation fans

END of REPORT

Basis of Design Cut Sheets

JobName:AER-24-03-0625CutSheet
Tag:MK-1
Quantity:1
PrintedDate:June18,2026
Model:AER-24-03-0625
SidewallDirectDriveExhaustFan
StandardConstructionFeatures:Galvanizedsteelpanelwithfabricatedgalvanizedsteeldriveframe
(optionalwallhousingorwallcollar).Propeller,fabricatedsteel(02)orcastaluminum(03).Directdriven
motorintheairstream.
Certifications/specialrequirements:SelectedwithVFD
FanConfiguration
Drivetype Direct

Performance Requested Volume (CFM) 6,900

ActualVolume(CFM) 6,900
TotalExternalSP(in.wg) 0.49
Operatingfrequency(Hz) 49
FanRPM 1,425
OperatingPower(bhp) 1.3

Startup Power (bhp) 2.5

FEI 1.26

FEPInputPower(kw) 1.21
AirStreamTemp(F) 80
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.071
Elevation(ft) 1151
StaticEfficiency(%) 41

Outlet Velocity (ft/min) 2,129

Motor Size (hp) 3

V/C/P 208/60/3 NEC FLA (Amps) 10.6

MinCircuitAmpacity(MCA) 13.2
MaxOverloadProduction(MOP) 20
MotorSpeed(RPM) 1750
MotorEfficiency(%) 87.8
Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,425 FRPM

Don
oto

pe rat

ei
ns

ha de d a re a

System

Volume (CFM) x 1000 0 1 2 3 4 5 6 7 8 9 10

St at ic P re ss ur e (in

. w g)

0.4

0.8

1.2

1.6

Br ak e Ho rs ep ow er (B

HP

0.4

0.8

1.2

1.6

ExternalSP 0.1in.wg
BackdraftDamper 0.09in.wg
WallHousing 0.14in.wg
Weatherhood 0.16in.wg
TotalExternalSP 0.49in.wg

Static Pressure Calculations

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 80 86 89 86 81 78 74 68 88 76 25

GreenheckFanCorporationcertifiesthatthemodelshownherein
islicensedtobeartheAMCASeal.Theratingsshownarebasedon
testsandproceduresperformedinaccordancewithAMCA
Publication211andAMCAPublication311andcomplywiththe
requirementsoftheAMCACertifiedRatingsProgram.TheAMCA
certifiedratingssealappliestosoundandairperformanceandFEI
ratingsonly.PerformancecertifiedisforinstallationtypeA:Free
inlet,freeoutlet.FEIcalculationisbasedontheselectedMotor
Size,MotorSpeed,andMotorEfficiencystated(seecorresponding
parameters).Powerratingdoesnotincludetransmission
losses.Performanceratingsdonotincludetheeffectsof
appurtenances.TheAMCAlicensedairand/orsoundperformance
datahasbeenmodifiedforinstallation,appurtenances,etc.not
includedinthecertifieddata.Themodifiedperformanceisnot
AMCAlicensedbutisprovidedtoaidinselectionandapplications
oftheproduct.Thesoundratingsshownareloudnessvaluesin
hemisphericalsonesat1.5m(5ft)inahemisphericalfreefield
calculatedperANSI/AMCAStandard301.TheA-weightedsound
ratingsshownhavebeencalculatedperAMCAInternational
Standard301.ValuesshownareforInstallationTypeA:freeinlet
hemisphericalsonelevels.dBAlevelsarenotlicensedbyAMCA
International.TheAMCACertifiedRatingsSealappliestoLwiAand
inletsoneratingsonly.
FLA-basedontables150or148ofNationalElectricCode2002.Actual
motorFLAmayvary,forsizingthermaloverload,consultfactory.
MCAandMOPvaluesshownonlyaccountforthemotor,notaccessories
(damperactuator,fieldsuppliedVFD,etc.).

Page 1 of 2 Version 3.14.0, June 2026

JobName:AER-24-03-0625CutSheet
Tag:MK-1
Quantity:1
PrintedDate:June18,2026

Dimensions and Weights Label Value Description

- 24.125 ImpellerDiameter(in)
- 220 Weightw/oaccessories(lbs)
A 38 OverallHeight(in)
B 38 OverallWidth(in)
C 38 OverallLength(in)
D 31 WTHDLength(in)
- 33.5 WallOpeningWidth(in)
- 33.5 WallOpeningHeight(in)
*Alldimensionsareininches.
Page2of2 Version3.14.0,June2026

VK12

VK12

Product Description

Reduce heat stress and improve air quality with Schaefer’s uniquely designed circulation fans. Unrivaled in the market, these fans are engineered to produce greater air movement and superior cooling no matter the application. You don’t hear them. You don’t see them. You only feel them!

Also known as Horizontal Air Flow (HAF) fans, these fans move air in a coherent horizontal pattern creating a gentle ‘racetrack’ air flow pattern needed in greenhouses to maximize heat distribution and humidity control by mixing the air, from ceiling to floor.

Features

Deep guard design for unmatched performance, low noise levels and safety without sacrificing airflow

Matched high quality motors and blades for maximum efficiency

Powder coated steel guards for increased durability and corrosion resistance

Hot dipped galvanized guards on VK12-GA and VK20-GA models for even greater rust protection

Powder coated steel mounting bracket and power cord included

Wide variety of mounting options available for flexible and easy installation

Variable speed controls available

Misting kits available for even greater cooling

Two year warranty

Made in the USA

Specifications

Air Velocity (@

10')

TBD

Blade Color Metallic

Brand Schaefer

Cfm (free Air) 1470

Drive Direct

Mount Included VS12FMT

Phase 1

Speeds 1

Vfd Compatible No

Cfm/watt (free 14

Mount Type

Included

Ceiling

Nameplate

Amps

1.3/.65

Number Of

Wings

Bess Lab

Performance

Test #

12370

Power (hp) 1/10

Product Net

Weight (lbs)

Switch Not included

Product

Shipping

Dimensions (in)

15 x 15 x 17

Speed Control

Compatible?

Yes

Able To Ship

Small Parcel

Yes

Cfm Range (free

Air)

1001 - 2500

Cord Length

(feet)

Fixed Or

Portable

Fixed https://schaeferventilation.com/ https://schaeferventilation.com/ https://schaeferventilation.com/wp-content/uploads/2026/06/VK12-200.png

Air)

Cord Included -

Not Wired

Diameter

(inches)

Frequency (hz) 60

Guard Color White

Voltage 115/230

Maximum Rpm 1725

Air Velocity (@ 5

Times Diameter)

Blade Material Aluminum

Cfm Calculation

Standard

ANSI/AMCA

Standard

230-99

Pallet Quantity 45

Product Color White

Guard Material Powder

Coated Steel

Oscillating No

Country Of

Origin

US

Guard Spacing

(inches)

1/2 - 1 UL507

Housing Color White

Cfm/watt

(@0.10")

TBD

Cfm/watt

(@0.05")

TBD

KOOL-CEL OSBG/CSBG

Open Stainless Steel Top with Bell Joint Gutter Closed Stainless Steel Top with Bell Joint Gutter

ACME EVAPORATIVE COOLING SYSTEM FOR 6-INCH PADS

Acme’s OSEG or CSEG provides a rugged stainless steel top and a water tight extruded gutter for evaporative cooling pads. The gutter has UV protection for use in full sunlight.

APPLICATION

BENEFITS

UV PROTECTED GUTTER

ALL METAL PARTS ARE STAINLESS STEEL

WATER TIGHT GUTTER SERVES AS STORAGE TANK

PREFORMED GUTTER - READY TO INSTALL

STRINGER OR FLOOR GUTTER MOUNT

THE OSBG HAS 10 FEET TO 120 FEET AVAILABLE IN 5 FEET INCREMENTS

THE CSEG HAS 10 FEET TO 120 FEET IS AVAILABLE IN 1 FOOT INCREMENTS

NO IN-GROUND TANK REQUIRED

USES STANDARD PVC CEMENT

HEAVY DUTY STAINLESS STEEL GUTTER MOUNTING BRACKETS

OPEN TOP FOR EASY MAINTENANCE OR CLOSED TOP FOR PROTECTION FROM DEBRIS

PADS ARE CONTINUOUS THROUGH SPLIT SYSTEM

SEALS TO BUILDING WITHOUT ADDITIONAL FLASHING OR FURRING STRIPS

The Acme OSBG or CSBG evaporative cooling system offers the optimum in installation ease and upkeep. The gutter’s UV protection and the stainless steel top offers many years of trouble free operation. Just glue the sections together and snap in the pad tray. The gutter may be either mounted on the wall stringer or set on the cement pad. Wall mount uses heavy stainless steel brackets.

ACME offers two unique top systems with the extruded gutter. The special open top design allows for easy monitoring of water flow while the closed top offers superior protection from debris.

The sump pump (70S and smaller) is located in an extension of the gutter located at one end or in the center. Recirculated water is supplied from a submerged pump through an in-line filter and water flow control. A sediment trap is included to reduce trash in the recirculating water. In addition a bleed-off tube allows for continual refreshment of the recirculated water. Fresh water is supplied by way of a Topaz water valve. A plumbing completer kit is included in the In-Line tank.

NEW Bell Joint Gutter makes installation

33% faster and saves on system cost.

US GLOBAL RESOURCES

85 YEARS OF SERVICE TO A GROWING WORLD

TOLL-FREE: +1 (888) 334-1440 | +1 (830) 755-4768

EMAIL: USGR@USGR.COM | WWW.USGR.COM

DESCRIPTION

FEATURES

Made in the U.S.A

NEW

LOWER

COST!

RUGGED LONG LIFE

EASY TO INSTALL

EASY TO MAINTAIN

6” HIGH-EFFICIENCY KOOL-CEL® PADS

LIVESTOCK AND GREENHOUSE COOLING

Est. 1940

US GLOBAL RESOURCES

85 YEARS OF SERVICE TO A GROWING WORLD

TOLL-FREE: +1 (888) 334-1440 | +1 (830) 755-4768

EMAIL: USGR@USGR.COM | WWW.USGR.COM

Est. 1940

The tank offers space for the pump and float valve and has a stainless steel top designed for easy access to both.

Approximately 30” length space is needed for the pump tank kit. It can be mounted at either end or in the center of the system. The kit includes all plumbing parts necessary to complete the system.

To mount the tank in the center of the system you need the optional wrap around kit shown below:

TANK

PAD

Water Inlet Float Valves are used for the automatic replacement of the water evaporated off from the Kool-Cel® system.

Topaz float valves are commonly used for flows up to 50 gal/min at 50 PSI and are designed with a small pilot valve, which in turn operates the main float valve.

IN-LINE TANK

WATER INLET VALVES

PUMPS

Many other tank mounting options are available.

The optional wrap around kit allows the tank to be mounted in front of the system rather than inline and does not include the tank.

Pump Features:

• Corrosion-resistant construction

• Stainless steel motor casing, motor shaft, and fasteners

• Upper and lower heavy duty ball bearing construction

• Motor is permanently lubricated for extended service life and is powered for continuous duty

• Built-in thermal overload protection with automatic reset

• Maximum liquid temperature: 104°F (40°C)

20S Pump:

• 1/3 HP, 115 V (2.9 amps)

• Maximum capacity: 36 GPM

• Maximum head: 20 ft

• Power cord length: 10 feet

70S Specifications:

• 3/4 HP, 115 V (7.1 amps) or 230 V (3.5 amps)

• Maximum capacity: 57 GPM

• Maximum head: 34 feet TDH

• Power cord length: 20 feet

B225C January 2025

PADS

ASK FOR THEM BY NAME

KOOL-CEL® evaporative cooling media is manufactured according to Acme’s rigid standards.

HIGH QUALITY MEANS A LONGER-LASTING PAD

• Greenhouse Space Cooling

• Agriculture Hog, Poultry, Egg Houses, Dairy

Agriculture / Horticulture Specifications

4” Pads 6” Pads 2” Fogger Pads

Model No.

D x W x H

(in.)

Shipping

Wt. (lbs.)

Model No.

D x W x H

(in.)

Shipping

Wt. (lbs.)

Model No.

D x W x H

(in.)

Shipping

Wt. (lbs.)

KU4-24 4 x 12 x 24 1.81 CU6-24 6 x 12 x 24 2.70 FPU2-12-48 2 x 12 x 48 1.81

KU4-36 4 x 12 x 36 2.70 CU6-36 6 x 12 x 36 4.05 FPU2-12-60 2 x 12 x 60 2.24

KU4-48 4 x 12 x 48 3.59 CU6-48 6 x 12 x 48 5.40 FPU2-12-72 2 x 12 x 72 2.70

KU4-60 4 x 12 x 60 4.51 CU6-60 6 x 12 x 60 6.75 FPU2-24-48 2 x 24 x 48 3.59

KU4-72 4 x 12 x 72 5.40 CU6-72 6 x 12 x 72 8.10 FPU2-24-60 2 x 24 x 60 4.48

CU6-60 6 x 24 x 60 13.5 FPU2-24-72 2 x 24 x 72 5.40

CU6-72 6 x 24 x 72 16.2

All sizes available either uncoated, coated 1 side, or coated 2 sides.

Specify when ordering.

US G L O B A L R E S O U R C E S

86 YEARS OF SERVICE TO A GROWING WORLD

TOLL-FREE: +1 (888) 334-1440 | +1 (830) 755-4768

EMAIL: USGR@USGR.COM | WWW.USGR.COM

STATIC PRESSURE VS FACE VELOCITY

0.18

0.16

0.14

0.12

0.1 4 in PAD

0.08 6 in PAD

0.06

0.04

0.02

200 300 400 500 600

FT PER

MINUTE

EFFICIENCY VS FACE VELOCITY

6 in PAD

4 in PAD

200 300 400 500 600

FT PER

MINUTE

IN

C

H W

G

P

ER

C

EN

T

KOOL-CEL® Pads are the best choice for evaporative cooling systems because:

Strongest, heaviest pad available.

Made with the heaviest (90 lb.), highest quality virgin kraft paper High percentage of resin content Out-performs the competition in tests:

High tensile strength, psi High dry crush strength, psi High wet crush strength, psi

Produced using the most advanced curing process.

• Cure is consistent and completely established at all contact points throughout the pad

• Pad Cure is designed to give the longest usable life

Available in custom sizes and flute angles Pads for agriculture/horticulture applications Acme Engineering ships custom orders promptly

Advanced resin technology Improves strength, longevity, absorption and cooling efficiency

Edge coating available Available with or without edge coating

Unique coral color Distinguishes KOOL-CEL® from all others

KOOL-CEL® is a registered trademark of Acme Engineering & Manufacturing Corporation

US G L O B A L R E S O U R C E S

86 YEARS OF SERVICE TO A GROWING WORLD

TOLL-FREE: +1 (888) 334-1440 | +1 (830) 755-4768

EMAIL: USGR@USGR.COM | WWW.USGR.COM

SPECIFICATION SHEET

TAG ________

Zurn Industries, LLC | Specification Drainage Operation 1801 Pittsburgh Avenue, Erie, PA 16502, Ph. 855.663.9876

In Canada | Zurn Industries Limited 7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, Ph. 877.892.5216 www.zurn.com

Design and Dimensional Data (inches and [ mm ]) are Subject to Manufacturing Tolerances and Change Without Notice

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov ADVERTENCIA: Cáncer y daño reproductivo - www.P65Warnings.ca.gov AVERTISSEMENT: Cancer et effets néfastes sur la reproduction - www.P65Warnings.ca.gov

CO

3 [76] X 4 [102] ADJUSTABLE FINISHED AREA CLEANOUT

ENGINEERING SPECIFICATION:

Zurn CO adjustable floor cleanout, PVC 3 [76] x 4 [102] solvent weld body with bottom outlet, cleanout plug, and square or round light duty strainer in nickel bronze or stainless steel.

SUFFIXES

-CMCarpet Marker
-VPVandal Proof
Rev.B
Date:05/09/25
C.N. No.146859

Prod. | Dwg. No. CO

Dimensions in Inches [mm] Approx.

Wt. Lbs

[kg] Strainer TypeProduct

Number A B

PVC Body Pipe Size Strainer Size CO-PV3 3-4 [76-102] 5-3/16 [132] 5 [2] Nickel Bronze Round

CO-PV3-R6 3-4 [76-102] 6 [152] 6 [3] Nickel Bronze Round

CO-PV3-ST 3-4 [76-102] 5-3/16 [132] 5 [2] Nickel Bronze Square

CO-PV3-S6 3-4 [76-102] 6 [152] 6 [3] Nickel Bronze Square

CO-PV3-SS 3-4 [76-102] 5-3/16 [132] 5 [2] Stainless Steel Round

CO-PV3-R6-SS 3-4 [76-102] 6 [152] 6 [3] Stainless Steel Round

CO-PV3-ST-SS 3-4 [76-102] 5-3/16 [132] 5 [2] Stainless Steel Square

CO-PV3-S6-SS 3-4 [76-102] 6 [152] 6 [3] Stainless Steel Square

CO-PV3-DI 3-4 [76-102] 5-3/16 [132] 5 [2] Ductile Iron Round

C-634 Heavy Commercial Wall Hydrant

With Integral P-004 Vacuum Breaker

•Anti-Siphon
•Freezeless
•Commercial / Industrial
•Double Backflow Check Valve

C-634-U

PRIER C-634 provides a year round source of water to areas that are subject to freezing temperatures. The hydrant valve is connected to the supply piping in the heated portion of the structure, eliminating the possibility of freezing. To assure freeze protection, the hydrant will drain even with the hose attached and under pressure.

The integral vacuum breaker/backflow preventer provides protection against cross-connection with the potable water system, utilizing 2 check valves to prevent back pressure and a vacuum breaker to vent in the case of siphonage. This commercial wall hydrant is key oper-ated, code approved, and flows up to 16 GPM. A removable operating key is provided to prevent unauthorized usage of the hydrant. No special installation tools are required.

ORDERINGFEATURES

4515 E. 139th Street Grandview, MO 64030 | (800) 362-9055 | PRIER.com

BX1

BX2

BX3

RB1

• Field testable as required by ASSE 1052, pressure rated to 125 PSI, temperature to 140°

• Satin nickel plated body rmaintains an attractive finish

• Multiple vent holes ensure proper draining and reduce problems associated with insect nesting

• Patented PRIER “triple seal” positive shutoff system offers triple redundancy to assure shutoff

• High flow rate, 16 gallons per minute at 25 PSI differential

•Same key operates box lock and hydrant
•Tested to 250,000 cycles; designed to last the life of

the plumbing system

• Heavy pattern cast brass hydrant for use with or without brass box or aluminum box

• Heavy duty brass piping, significantly stronger than copper, with threaded and sealed joints

• Simple, solderless design and solid non-ferrous operating rod for long wear life

• Design enables valve to be easily secured to any type of inner wall, utilizing the provided clamping ring

• Integral 3/8”-16 mounting lugs on box provide easy and secure installation.

• Round Box (RB1) installs through 6” hole or 6”

Schedule 40 PVC sleeve

• Patented PRIER quick opening and modulating design requires less force and fewer turns to operate

• Gasket prevents water and air intrusion into the building

C-634BX1

BX1- Satin Nickel Plated BX2- Rough Brass BX3- Aluminum RB1- Round Box (Satin Nickel Plated)

Box Finish

N- 1” MPT x ¾” FPT P- 1” Male SWT x ¾” Female SWT V- ¾” Copper-Press Fitting Ready

4- ¾” Garden Hose 6- 1” Hose

C-634N10 Length 04- 4" Insertion 06- 6" Insertion 08- 8" Insertion 10- 10" Insertion 12- 12" Insertion 14- 14" Insertion 16- 16" Insertion 18- 18" Insertion 20- 20" Insertion 22- 22" Insertion 24- 24" Insertion XX- Special Size

InletHose Thread Outlet

Wall Hydrant Only

Optional Hydrant Box

Included with C-634 hydrant boxes

C-634 Gasket

C-634-U

ROUGH-IN DIMENSIONS

SPECS

4515 E. 139th Street Grandview, MO 64030 | (800) 362-9055 | PRIER.com

C-634 REPLACEMENT PARTS AND STEMS

ID Part No. Description ID Part No. Description 1 See Below Stem Assembly, Contains: 5, 6, 10, 11, 13 5 336-0001 O-Ring Worm Sleeve

P-231-0604 Stem for 4” C-634 Hydrant, 4 11/16” OAL 6 336-6001 O-Ring Worm Drive

P-231-0606 Stem for 6 “ C-634 Hydrant, 6 11/16” OAL 7 337-6001 Check Spider-Vacuum Breaker

P-231-0608 Stem for 8” C-634 Hydrant, 8 11/16” OAL 8 346-6001 Diaphragm-Vacuum Breaker

P-231-0610 Stem for 10” C-634 Hydrant, 10 11/16” OAL 9 C-108KT-808 Loose Key on Lanyard

P-231-0612 Stem for 12” C-634 Hydrant, 12 11/16” OAL 10 C-634KT-802 Stopper Kit, Includes Stopper and Pin, Contains: 5, 10

P-231-0614 Stem for 14” C-634 Hydrant, 14 11/16” OAL 11 324-0004 Pin Only

P-231-0616 Stem for 16” C-634 Hydrant, 16 11/16” OAL 12 C-634KT-806 Vacuum Breaker Assembly

P-231-0618 Stem for 18” C-634 Hydrant, 18 11/16” OAL 13 C-634KT-808 Worm Sleeve with O-Ring, Pin and Tool

P-231-0620 Stem for 20” C-634 Hydrant, 20 11/16” OAL 14 C-634KT-809 Worm Drive Assembly with O-Ring

P-231-0622 Stem for 22” C-634 Hydrant, 22 11/16” OAL 15 C-634WCR Wall Clamping Ring

P-231-0624 Stem for 24” C-634 Hydrant, 24 11/16” OAL 16 399-0001 Secondary Check for ASSE 1052

2 300-6003 Valve Stem Cap (NP Brass) 17 346-0004 C-634 Gasket

3 300-6004 3/4” Hose Piece (NP Brass) C-634KT-807 C-634 Overhaul Kit, Contains: 9, 10, 11, 12, 13, 14

310-6009 1” Hose Piece for C-636 (NP Brass)

**For the old style C-634 Series wall hydrant stems, see C-634 Series retired style spec sheet at PRIER.com.

7 8 3 16

1513 14

10 11

2.125” (57 mm)

0.75” (19 mm) Hydrant Length*2”

(51 mm)

0.25” (6 mm)

6.50” (165 mm)

6.0” (152 mm)

5.75” rough-in

5.5” rough-in

Diameter 6.94” (6 15/16”)

4.5” (114.3mm)

2.125”

5.94” (fits 6” hole)

Furnish and install Model C-634 Heavy Commercial Wall Hydrant manufactured by PRIER Products, Inc. Hydrant shall be surface mount and installed through 1 3/8” round opening. Hydrant shall have automatic draining capabilities with integral vacuum breaker/double backflow preventor. Hydrant shall flow 16 gallons per minute minimum at 25 PSI Differential and be at full flow in 2 handle rotations. Hydrant shaft shall be brass with connections.

Hydrant shall have 3/4” or 1” (choose one) hose connection with freezeless water flow and self-draining functions, one piece valve plunger, satin nickel finish, brass operating rod with positive triple seal shutoff mechanism. Hydrant shall be approved under ASSE 1052 standard. Operating key & wall clamping ring to be furnished with each hydrant. Hydrant insertion length to be x inches. (Length minimum of 4” to choice length in 2” increments.)

Optional: Furnish and install flush-mount hydrant box for each valve. Hydrant box shall be manufactured of solid cast brass or aluminum with a rough brass, satin nickel plated brass or aluminum (choose one) finish. Box shape may be round or square and round box only comes with satin nickel finish.

Box may be installed separately and hydrant be insertable and removable from front of the box. Access to the hydrant box shall be provided by the same operating key as the valve. A gasket shall be installed between the box and hydrant to prevent water intrusion into the structure.

4.5” (114 mm)

2.25” (55 mm)

2.50” (63 mm)

1.125” (28 mm)

Zurn Industries, LLC | Specification Drainage Operation 1801 Pittsburgh Avenue, Erie, PA 16502, Ph. 855.663.9876

In Canada | Zurn Industries Limited 7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, Ph. 877.892.5216 www.zurn.com

Design and Dimensional Data (inches and [ mm ]) are Subject to Manufacturing Tolerances and Change Without Notice

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov ADVERTENCIA: Cáncer y daño reproductivo - www.P65Warnings.ca.gov AVERTISSEMENT: Cancer et effets néfastes sur la reproduction - www.P65Warnings.ca.gov

CO

3 [76] X 4 [102] ADJUSTABLE FINISHED AREA CLEANOUT

ENGINEERING SPECIFICATION:

Zurn CO adjustable floor cleanout, PVC 3 [76] x 4 [102] solvent weld body with bottom outlet, cleanout plug, and square or round light duty strainer in nickel bronze or stainless steel.

SUFFIXES

-CMCarpet Marker
-VPVandal Proof
Rev.B
Date:05/09/25
C.N. No.146859

Prod. | Dwg. No. CO

Dimensions in Inches [mm] Approx.

Wt. Lbs

[kg] Strainer TypeProduct

Number A B

PVC Body Pipe Size Strainer Size CO-PV3 3-4 [76-102] 5-3/16 [132] 5 [2] Nickel Bronze Round

CO-PV3-R6 3-4 [76-102] 6 [152] 6 [3] Nickel Bronze Round

CO-PV3-ST 3-4 [76-102] 5-3/16 [132] 5 [2] Nickel Bronze Square

CO-PV3-S6 3-4 [76-102] 6 [152] 6 [3] Nickel Bronze Square

CO-PV3-SS 3-4 [76-102] 5-3/16 [132] 5 [2] Stainless Steel Round

CO-PV3-R6-SS 3-4 [76-102] 6 [152] 6 [3] Stainless Steel Round

CO-PV3-ST-SS 3-4 [76-102] 5-3/16 [132] 5 [2] Stainless Steel Square

CO-PV3-S6-SS 3-4 [76-102] 6 [152] 6 [3] Stainless Steel Square

CO-PV3-DI 3-4 [76-102] 5-3/16 [132] 5 [2] Ductile Iron Round

POU ELECTRIC TANKLESS WATER HEATERS

COMMERCIAL/RESIDENTIAL

© July 2024 A. O. Smith Corporation. All rights reserved.

www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015

ABESS00124

EASY INSTALLATION

• Compact size perfect for point-of-use applications close to fixtures

• Mounts easily to the wall

• No venting required

• ½” NPT water connection

• No T&P valve required (check local codes)

WIDE ARRAY OF MODELS AND MODES

OF OPERATION

• 1.75kW – 3.5kW, 120V

• 3.5kW – 11kW, 240V (208V)

• 4kW – 11kW, 277V

• Single Phase, 50/60 Hz

• Two mode options, easy switching

• Lavatory mode, default 105°F; temp range 80°F – 149°F

• Emergency Eye Wash mode, 85°F

ONBOARD SELF-DIAGNOSTICS &

TROUBLESHOOTING

• Onboard self-diagnostics to monitor performance and protect the unit

• Bright LED display for status updates and making system selections and adjustments

• Error codes for troubleshooting and faster resolution

HIGHLY EFFICIENT & RELIABLE

THERMOSTATIC DESIGN

• On-demand water heater capable of supplying endless hot water when appropriately sized

• Ultra-low activation of 0.17 GPM min.

• Energy efficiency 0.91 UEF or higher

• Dry-Fire protection to prevent premature element failures

• Secondary temperature regulation to limit hot water output appropriate for use with hand or eye washing applications

• Scale detection (Patent Pending) and easy maintenance for extended service life of the heater

CONSTRUCTION

• Housing – Bayblend® FR3010 plastic, dark gray

• Chamber Material – Entec Nylon, glass-filled

• Sheathed copper elements for longer life

WARRANTY

• 5-Year limited warranty on chambers

• 1-Year limited warranty on all parts

• For complete information, consult the written warranty or go to hotwater.com

POINT-OF-USE ELECTRIC TANKLESS

ABESS00124

POU ELECTRIC TANKLESS WATER HEATERS

COMMERCIAL/RESIDENTIAL

Copper conductors only. All wiring/conductors must be rated for 90°C or greater.

+ This model may be connected to a 208 VAC supply with reduced power output. Connection to 208 VAC may require different breaker and/or wire size than shown in the table.

NOTICE: Incoming line voltage variations may result in nuisance breaker trips. Contact Technical Support if there are multiple breaker trips when the recommended breaker size is in use.

Model Number Total Input Wattage (kW) Voltage (V) Total Current

Draw (Amps)

Recommended U.S.

Circuit Breaker Size

(Amps) Conductor Size (AWG) Activation GPM

UPVA-18K 1.75 120 14.58 15 14 0.17

UPVA-24K 2.40 120 20.00 20 12 0.17

UPVA-30K 3.00 120 25.00 25 10 0.17

UPVA-35K 3.50 120 29.17 30 10 0.17

UPVA-35E 3.50 240+ 14.58 15 14 0.17

UPVA-45E 4.50 240+ 18.75 20 12 0.17

UPVA-55E 5.50 240+ 22.92 25 10 0.17

UPVA-70E 7.00 240+ 29.17 30 10 0.17

UPVA-90E 9.00 240+ 37.50 40 8 0.17

UPVA-110E 11.00 240+ 45.83 50 8 0.17

UPVA-40Y 4.00 277 14.44 15 14 0.17

UPVA-55Y 5.00 277 19.86 20 12 0.17

UPVA-80Y 8.00 277 28.88 30 10 0.17

UPVA-110Y 11.00 277 39.71 40 8 0.17

Volts kW

GPM AT TEMPERATURE RISE

25°F 30°F 35°F 40°F 45°F 50°F 55°F 60°F 65°F 70°F 75°F 80°F 85°F

120V

1.75kW 0.47 0.39 0.33 0.29 0.26 0.23 0.21 0.20 0.18 0.17 - - - 2.4kW 0.64 0.54 0.46 0.40 0.36 0.32 0.29 0.27 0.25 0.23 0.21 0.20 0.19 3kW 0.80 0.67 0.57 0.50 0.45 0.40 0.36 0.33 0.31 0.29 0.27 0.25 0.24

3.5kW 0.94 0.78 0.67 0.59 0.52 0.47 0.43 0.39 0.36 0.33 0.31 0.29 0.28

240V (208V)

3.5kW 0.94 0.78 0.67 0.59 0.52 0.47 0.43 0.39 0.36 0.33 0.31 0.29 0.28 4.5kW 1.20 1.00 0.86 0.75 0.67 0.60 0.55 0.50 0.46 0.43 0.40 0.38 0.35 5.5kW 1.47 1.23 1.05 0.92 0.82 0.74 0.67 0.61 0.57 0.53 0.49 0.46 0.43 7kW 1.87 1.56 1.34 1.17 1.04 0.94 0.85 0.78 0.72 0.67 0.62 0.59 0.55 9kW 2.41 2.01 1.72 1.50 1.34 1.20 1.09 1.00 0.93 0.86 0.80 0.75 0.71 11kW 2.94 2.45 2.10 1.84 1.63 1.47 1.34 1.23 1.13 1.05 0.98 0.92 0.87

277V

4kW 1.07 0.89 0.76 0.67 0.59 0.54 0.49 0.45 0.41 0.38 0.36 0.33 0.31 5.5kW 1.47 1.23 1.05 0.92 0.82 0.74 0.67 0.61 0.57 0.53 0.49 0.46 0.43 8kW 2.14 1.78 1.53 1.34 1.19 1.07 0.97 0.89 0.82 0.76 0.71 0.67 0.63 11kW 2.94 2.45 2.10 1.84 1.63 1.47 1.34 1.23 1.13 1.05 0.98 0.92 0.87

PRODUCT SPECIFICATIONS

Cold water inlet temperatures raised to 105°F setpoint.

ABESS00124

POU ELECTRIC TANKLESS WATER HEATERS

COMMERCIAL/RESIDENTIAL

Models

DIMENSIONS – SHIPPING

Width Height Depth Weight

1.75kW - 5.5kW 11.25 15.5 8 6.0 7.0kW - 11kW 11.25 15.5 8 8.0

DIMENSIONS

Front View Side View

Top View

°F

°C

ENTER

7.65” (19.43 cm)

11.25” (28.58 cm)

12.22” (31.04 cm)

1.03” (2.62 cm)

12.22” (31.04 cm)

4.77” (12.12 cm)

1.24” (3.15 cm)

2.29” (5.82 cm)

7.65” (19.43 cm)

5.11” (12.98 cm)

2.29” (5.82 cm)

2.29” (5.82 cm)

2.45” (6.22 cm)

2.45” (6.22 cm)

2.20” (5.59 cm)

5.11” (12.98 cm)

POU ELECTRIC TANKLESS WATER HEATERS

© July 2024 A. O. Smith Corporation. All rights reserved.

www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015

ABESS00124

For technical information, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.

INSTALLATION

°F

°C

ENTER

12” (30.5 cm)

12”+ (30.5 cm +)

8” (20.3 cm)

8” (20.3 cm)

Drain Pan

Wall Wall or adjacent object

Front Clearance:

15” + (38.1 cm +)

Drain Pan

12”+ (30.5 cm +)

Floor

ORIENTATION & CLEARANCE

•All models must be oriented with the inlet and outlet facing upward.
•Top clearance – a minimum of 12 inches (30.5 cm) to provide access for plumbing

connections.

• Side clearance – a minimum of 8 inches (20.3 cm) to remove the screws and protective cover and to provide access for electrical wires to enter through the side of the unit.

• Bottom clearance – a minimum of 12 inches (30.5 cm) for access to and maintenance of heating elements. Do not store any items beneath the water heater.

• Front clearance – a minimum of 8 inches (20.3 cm). In the absence of a door or removable access panel in front of the heater, allow a minimum of 15 inches (38.1

cm) for cover removal and ease of service.

Hot Cold

°F

°C

ENTER

Side View

MINIMUM CLEARANCES

Front View

EG20.32 Rev. 09/24

Catalog Specification Sheet N o.

EG20.32

Spec-M aster

® FN

Series Coved Corner One-Com partm ent Sinks Item No.:

Project No.:

S.I.S. No.:

Spec-Master® FN Series Coved Corner One-Compartment Sinks

Specification Sheet

MODELS:

FN2016-1-*

FN2018-1-*

FN2020-1-*

FN2424-1-*

FN2820-1-*

Short Form Specifications Eagle Spec-Master® One-Compartment Sinks, model ________________. Unit constructed of 14 gauge 300 series, 18-8 stainless steel throughout. Sink bowls coved with a full 5⁄8˝ radius, and shall have a 14˝ water level. Drainboards, when required, shall be “V” creased for positive drainage. 91⁄2˝ high backsplash with 1˝ upturn and tile edge. Legs to be 15⁄8˝ O.D., stainless steel, with stainless steel gussets, stainless steel crossbracing and adjustable stainless steel bullet feet.

one-compartment FN sink

Top:

• Drainboards, backsplash and rolled rims are 14 gauge

300 series stainless steel.

• Drainboards, when provided, are integrally welded.

• All rolled edges are highlighted for enhanced appearance.

• 91⁄2˝ high backsplash with 1˝ upturn and tile edge.

• 11⁄8˝ (29mm) faucet holes punched on 8˝ (203mm) centers.

Base:

• Legs: 15⁄8˝ (41mm)-diameter stainless steel tubing with stainless steel gussets and fully adjustable stainless steel bullet feet.

• Crossbracing: Adjustable, 11⁄4˝ (32mm)-diameter stainless steel;

running left-to-right and front-to-back.

• Leg locations fall directly under sink bowl*, pro vid ing increased stability and maximum weight support.

• Leg gussets welded to a die-cut heavy-gauge stainless steel reinforcing corner plate.

• Legs are crossbraced on all sides for increased stability.

Sink Bowl:

• 14 gauge 300 series stainless steel.

• 14˝ (356mm) water level, 17˝ (432mm) flood level.

• Sink compartment coved on a full 5⁄8˝ (41mm) radius and constructed using state-of-the-art seamless welding techniques.

• Basket-type waste drain fits sink bowl’s 31⁄2˝ (89mm) opening and features 11⁄2˝ (38mm) outlet.

* On sinks with drainboard(s) 30˝ or longer, legs are located underneath the outer end of drainboard(s).

Options / Accessories Lever drain Lever drain with overflow Twist handle drains Overflow hole

Sink kits Faucets Polyboard sink covers Stainless steel sink covers

* See chart on back for complete model numbers.

Assembly:

• Entire assembly is fuse-welded and planished, provid ing a one-piece seamless sink unit.

• Welded areas are high-speed belt blended to match adjacent surfaces with continuity of satin finish.

• All outside corners of assembly are bullnosed to provide safe, clean edges.

• Water supply is 1⁄2˝ (13mm) NPS for hot and cold lines.

Certifications / Approvals

For custom configuration or fabrication needs, contact our SpecFAB® Division.

Phone: 302-653-3000 • Fax: 302-653-2065 • e-mail: quotes@eaglegrp.com

Eagle Foodservice Equipment, Eagle MHC, and SpecFAB® are divisions of Eagle Group. ©2024 by the Eagle Group

Spec sheets available for viewing, printing or downloading from our online literature library at our websites

EAGLE GROUP

100 Industrial Boulevard, Clayton, DE 19938-8903 USA Phone: 302-653-3000 • 800-441-8440 • Fax: 302-653-2065 www.eaglegrp.com www.eaglemhc.com

EAGLE GROUP

100 Industrial Boulevard, Clayton, DE 19938-8903 USA Phone: 302-653-3000 or 800-441-8440 • Fax: 302-653-2065 www.eaglegrp.com • www.eaglemhc.com

Spec sheets available for viewing, printing or downloading from our online literature library at our websites Although every attempt has been made to ensure the accuracy of the information provided, we cannot be held responsible for typographical or printing errors. Information and specifications are subject to change without notice. Please confirm at time of order.

Rev. 09/24

Printed in U.S.A.

©2024 by Eagle Group

BOWL DIMENSIONS DRAINBOARD OVERALL DIMENSIONS

width length length width length weight model # in. mm in. mm quantity in. mm in. mm in. mm lbs. kg

FN2016-1-14/3 20˝ 508 16˝ 406 0 - 27˝ 686 21˝ 533 55 24.9

FN2016-1-18R or L-14/3 20˝ 508 16˝ 406 1 18˝ 457 27˝ 686 371⁄2˝ 953 68 30.9

FN2016-1-18-14/3 20˝ 508 16˝ 406 2 18˝ 457 27˝ 686 54˝ 1372 93 37.6

FN2016-1-24R or L-14/3 20˝ 508 16˝ 406 1 24˝ 610 27˝ 686 431⁄2˝ 1105 80 33.1

FN2016-1-24-14/3 20˝ 508 16˝ 406 2 24˝ 610 27˝ 686 66˝ 1676 113 51.3

FN2016-1-30R or L-14/3 20˝ 508 16˝ 406 1 30˝ 762 27˝ 686 491⁄2˝ 1257 113 51.3

FN2016-1-30-14/3 20˝ 508 16˝ 406 2 30˝ 762 27˝ 686 78˝ 1981 209 94.8

FN2016-1-36R or L-14/3 20˝ 508 16˝ 406 1 36˝ 914 27˝ 686 551⁄2˝ 1410 156 70.8

FN2016-1-36-14/3 20˝ 508 16˝ 406 2 36˝ 914 27˝ 686 90˝ 2286 212 96.2

FN2018-1-14/3 20˝ 508 18˝ 457 0 - 27˝ 686 23˝ 584 58 26.3

FN2018-1-18R or L-14/3 20˝ 508 18˝ 457 1 18˝ 457 27˝ 686 391⁄2˝ 1003 76 34.4

FN2018-1-18-14/3 20˝ 508 18˝ 457 2 18˝ 457 27˝ 686 56˝ 1422 96 43.5

FN2018-1-24R or L-14/3 20˝ 508 18˝ 457 1 24˝ 610 27˝ 686 451⁄2˝ 1156 81 36.7

FN2018-1-24-14/3 20˝ 508 18˝ 457 2 24˝ 610 27˝ 686 68˝ 1727 161 73.0

FN2018-1-30R or L-14/3 20˝ 508 18˝ 457 1 30˝ 762 27˝ 686 511⁄2˝ 1308 156 70.8

FN2018-1-30-14/3 20˝ 508 18˝ 457 2 30˝ 762 27˝ 686 80˝ 2032 118 53.5

FN2018-1-36R or L-14/3 20˝ 508 18˝ 457 1 36˝ 914 27˝ 686 571⁄2˝ 1464 163 74.0

FN2018-1-36-14/3 20˝ 508 18˝ 457 2 36˝ 914 27˝ 686 92˝ 2337 215 97.5

FN2020-1-14/3 20˝ 508 20˝ 508 0 - 27˝ 686 25˝ 635 60 27.2

FN2020-1-18R or L-14/3 20˝ 508 20˝ 508 1 18˝ 610 27˝ 686 411⁄2˝ 1054 138 62.6

FN2020-1-18-14/3 20˝ 508 20˝ 508 2 18˝ 457 27˝ 686 58˝ 1473 167 75.8

FN2020-1-24R or L-14/3 20˝ 508 20˝ 508 1 24˝ 457 27˝ 686 471⁄2˝ 1207 144 65.3

FN2020-1-24-14/3 20˝ 508 20˝ 508 2 24˝ 610 27˝ 686 70˝ 1778 184 83.5

FN2020-1-30R or L-14/3 20˝ 508 20˝ 508 1 30˝ 762 27˝ 686 531⁄2˝ 1359 157 71.2

FN2020-1-30-14/3 20˝ 508 20˝ 508 2 30˝ 762 27˝ 686 82˝ 2083 168 76.2

FN2020-1-36R or L-14/3 20˝ 508 20˝ 508 1 36˝ 914 27˝ 686 591⁄2˝ 1511 179 81.2

FN2020-1-36-14/3 20˝ 508 20˝ 508 2 36˝ 914 27˝ 686 94˝ 2388 219 99.3

FN2424-1-14/3 24˝ 610 24˝ 610 0 - 31˝ 787 29˝ 737 122 55.3

FN2424-1-18R or L-14/3 24˝ 610 24˝ 610 1 18˝ 457 31˝ 787 451⁄2˝ 1156 145 65.8

FN2424-1-18-14/3 24˝ 610 24˝ 610 2 18˝ 457 31˝ 787 62˝ 1575 182 82.6

FN2424-1-24R or L-14/3 24˝ 610 24˝ 610 1 24˝ 610 31˝ 787 511⁄2˝ 1308 151 68.5

FN2424-1-24-14/3 24˝ 610 24˝ 610 2 24˝ 610 31˝ 787 74˝ 1880 182 82.6

FN2424-1-30R or L-14/3 24˝ 610 24˝ 610 1 30˝ 762 31˝ 787 571⁄2˝ 1461 165 74.8

FN2424-1-30-14/3 24˝ 610 24˝ 610 2 30˝ 762 31˝ 787 86˝ 2184 176 79.8

FN2424-1-36R or L-14/3 24˝ 610 24˝ 610 1 36˝ 914 31˝ 787 631⁄2˝ 1613 187 84.8

FN2424-1-36-14/3 24˝ 610 24˝ 610 2 36˝ 914 31˝ 787 98˝ 2489 220 99.8

FN2820-1-14/3 28˝ 711 20˝ 508 0 - 35˝ 889 25˝ 635 79 35.8

FN2820-1-18R or L-14/3 28˝ 711 20˝ 508 1 18˝ 457 35˝ 889 411⁄2˝ 1054 101 45.8

FN2820-1-18-14/3 28˝ 711 20˝ 508 2 18˝ 457 35˝ 889 58˝ 1473 117 53.1

FN2820-1-24R or L-14/3 28˝ 711 20˝ 508 1 24˝ 610 35˝ 889 471⁄2˝ 1207 114 51.7

FN2820-1-24-14/3 28˝ 711 20˝ 508 2 24˝ 610 35˝ 889 70˝ 1778 166 75.3

FN2820-1-30R or L-14/3 28˝ 711 20˝ 508 1 30˝ 762 35˝ 889 531⁄2˝ 1359 182 82.6

FN2820-1-30-14/3 28˝ 711 20˝ 508 2 30˝ 762 35˝ 889 82˝ 2083 191 86.6

FN2820-1-36R or L-14/3 28˝ 711 20˝ 508 1 36˝ 914 35˝ 889 591⁄2˝ 1511 189 85.7

FN2820-1-36-14/3 28˝ 711 20˝ 508 2 36˝ 914 35˝ 889 94˝ 2388 226 102.5

Ca ta lo g

Sp ec ifi ca tio n

Sh ee t N o.

EG

.3

Sp ec

-M as te r®

F N

S er ie s

Co ve d Co rn er

O ne

-C om pa rt m en t S in ks Item No.:

Project No.:

S.I.S. No.:

Spec-Master® FN Series Coved Corner One-Compartment Sinks bowl bowl width length Dimension A

in. mm in. mm 20˝ 508 16˝ 406 14˝ 356 20˝ 508 18˝ 457 14˝ 356 20˝ 508 20˝ 508 14˝ 356 24˝ 610 24˝ 610 16˝ 406 28˝ 711 20˝ 508 18˝ 457

Drain location for rough-in

Alex Fann Highlight

Zurn Industries, LLC | Specification Drainage Operation 1801 Pittsburgh Avenue, Erie, PA 16502, Ph. 855.663.9876

In Canada | Zurn Industries Limited 7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, Ph. 877.892.5216 www.zurn.com

Design and Dimensional Data (inches and [ mm ]) are Subject to Manufacturing Tolerances and Change Without Notice

Z882

Rev.KPage 1 of 2
Date:10/28/25
C.N. No.146986
Patentzurn.com/patents

Prod. | Dwg. No. Z882

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov ADVERTENCIA: Cáncer y daño reproductivo - www.P65Warnings.ca.gov AVERTISSEMENT: Cancer et effets néfastes sur la reproduction - www.P65Warnings.ca.gov

* Regularly furnished unless otherwise specified.

12” WIDE REVEAL TRENCH DRAIN SYSTEM WITH STEEL

FRAME

PREFIX OPTIONS (Check/specify appropriate options) -Z Eight-foot High Density Polyethylene (HDPE) Channel, Heavy-Duty Frame with Anchor Studs.*

SUFFIX OPTIONS (Check/specify appropriate options)

Outlet Adapters (Add/Each)

-E1Closed End Cap
-E44 [102] No Hub End Outlet
-E66 [152] No-Hub End Outlet
-E88 [203] No-Hub End Outlet
-U44 [102] No Hub Bottom Outlet
-U66 [152] No Hub Bottom Outlet
-U88 [203] No Hub Bottom Outlet

ENGINEERING SPECIFICATION:…