Drawings Attachment -3- VAV Box Schedule.pdf

PDF 53 KB Posted

Attached to
Project_621-22-133 - Bldg. 200 Wing B2 Renovate VAV Controls Federal contract opportunity
Solicitation number
36C24922B0015
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9

About this file

This document contains a VAV box schedule and specifications for a project to renovate 27 VAV controls and add one new VAV box in Building 200 at a Department of Veterans Affairs medical center. Key details include:

  • The schedule lists 27 existing VAV boxes by room number and provides specifications for each including box size, duct inlet size, minimum and maximum airflow, branch pipe size, reheat valve GPM and Cv. It also includes specifications for a new VAV box to be added in Room B249.

  • The related federal contract opportunity is solicitation number 36C24922B0015 to furnish all labor, materials, equipment and supervision to renovate the existing 26 VAV controls and add the new VAV box in Building 200 wing B, 2nd floor as required by the statement of work, drawings and specifications. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9.

The document provides specifications that will inform contractors' responses to the solicitation for renovating VAV controls at the specified VA medical center location.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VAV Rooms Tstat Location Box Indent. VAV Box Size Duct Inlet Size Min. Inlet S.P.

(In W.C) Max CFM Min CFM Heat CFM

Branch

Pipe Size

(O.D.)

Reheat Valve

GPM

Reheat Valve Cv

1 B202 B202 10 14" 14" 0.6 1590 795 795 1-1/8" 6.0 3.46

2 B201 B201 18 10" 10" 0.5 395 198 198 7/8" 2.0 1.15

3 B203 B203 18 10" 10" 0.5 395 198 198 7/8" 2.0 1.15

4 B204 B204 16 8" 8" 0.4 295 148 148 5/8" 1.0 0.58

5 B205 B205 18 10" 10" 0.5 395 198 198 7/8" 2.0 1.15

6 B207 B207 18 10" 10" 0.5 335 335 168 7/8" 2.0 1.15

7 B206 B206 16 8" 8" 0.4 295 148 148 5/8" 1.0 0.58

8 B208 B208 16 8" 8" 0.4 295 148 148 5/8" 1.0 0.58

9 B209 B209 18 10" 10" 0.5 335 168 168 7/8" 2.0 1.15

10 B211 B211 18 10" 10" 0.5 335 168 168 7/8" 2.0 1.15

11 B210 B210 16 8" 8" 0.4 295 148 148 5/8" 1.0 0.58

12 B212 B212 16 8" 8" 0.4 295 148 148 5/8" 1.0 0.58

13 B213 B213 18 10" 10" 0.5 335 168 168 7/8" 2.0 1.15

14 B214 B214 16 8" 8" 0.4 295 148 148 5/8" 1.0 0.58

15 Corridor Corridor 17 10" 10" 0.4 560 280 280 7/8" 2.0 1.15

16 B216 B216 20 12" 12" 0.5 650 325 325 7/8" 4.0 2.31

17 Nurse's Station Nurse's Station 19 12" 12" 0.4 720 360 360 7/8" 2.0 1.15

18 B254, B256 15 8" 8" 0.4 395 148 148 5/8" 1.0 0.58

19 B221, B223, B251, B253 B223 7 12" 12" 0.5 725 363 363 7/8" 2.0 1.15

20 B218 B218 20 12" 12" 0.5 650 325 325 7/8" 4.0 2.31

21 B220 B220 20 12" 12" 0.5 650 325 325 7/8" 4.0 2.31

22 B222 B222 20 12" 12" 0.5 650 325 325 7/8" 4.0 2.31

23 B233, B235 B233 19 12" 12" 0.4 645 323 323 7/8" 2.0 1.15

24 B225, B228 17 10" 10" 0.4 625 313 313 7/8" 2.0 1.15

25 B226, Corridor, Elevator Lobby B226 19 12" 12" 0.4 660 330 330 7/8" 2.0 1.15

26 B252 B252 6 10" 10" 0.5 405 200 200 7/8" 2.0 1.15

New B249 B249 8" 8" 0.4 300 200 200 7/8" 1.0 0.58

Attachment - 3 -VAV Box Schedule

File details come from the government source that posted it. Updated .