Drawings 657-23-108JC_Bid Documents 20240308 -61 Sheets r.pdf
PDF 19 MB Posted
- Attached to
- Z2DA--657-23-108JC, FCA - Repair Air Handler AC-1 (VA-25-00052824) John J. Cochran Veterans Hospital
- Solicitation number
- 36C25525R0049
About this file
These are detailed architectural and engineering design drawings for a federal construction project at the John J. Cochran Veterans Hospital in St. Louis, Missouri. The project involves repairing Air Handling Unit AC-1 and associated mechanical systems on the second floor of the main hospital building. Specific scope includes replacing the steam humidifier inside AC-1, fixing duct leakage above room D263, and replacing approximately 70 variable air volume (VAV) boxes, with 68 of those being converted to digital control.
The comprehensive set contains 61 technical drawings spanning multiple disciplines including general, architectural, mechanical, electrical, and plumbing plans. The project is being managed by Romanyk Consulting Corp. for the Department of Veterans Affairs, Network Contracting Office 15, with a project number of 657-23-108JC. The design documents provide detailed specifications for demolition, installation, and renovation work, with specific attention to maintaining hospital operations, infection control protocols, and existing building systems during construction.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1i
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
TRUE NORTH
PLAN NORTHNORTH
NORTH ARROW WITH TRUE
NORTH INDICATION
EGRESS ROUTE ID AND
SECTION LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY & AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
INDEX OF DRAWINGS
DISCIPLINE:
G - GENERAL
S - STRUCTURAL
A - ARCHITECTURE
M - MECHANICAL
E - ELECTRICAL
SHEET TYPE
DESIGNATOR
VICINITY MAP
ANNOTATION DRAWING SYMBOLSGENERAL NOTES
BUILDING NUMBER
A101
A101
SHEET NUMBER
WITHIN SERIES
01 - AE 1 0 1
LEVEL:
2 = LEVEL 02
3 = LEVEL 03
ENRIGHT AVE
DELMAR BLVD
G R
A N
D B
L V
D
N S
PRIN
G A
VE
BELL AVE
WINDSOR
5T
1T 08
## = BUILDING №
PROJECT TEAM
BUILDING SUMMARY
PROJECT INFORMATION
THE PROJECT IN BUILDING 01 (MAIN BUILDING) WILL REPLACE THE HUMIDIFIER FOR AC-1, ALONG WITH ITS ASSOCIATED PIPING.
THIS PROJECT WILL CORRECT DEFICIENCIES IN MECHANICAL SYSTEMS TO PROVIDE BETTER HEALTHCARE EXPERIENCE FOR
VETERANS.
THE PROJECT WILL ALSO REPLACE 70± VAV BOXES DOWNSTREAM FROM AC-1 TO INCLUDE CONVERSION OF 68 BOXES TO DIGITAL CONTROL. ADDITIONALLY, THE PROJECT WILL FIX DUCT LEAKAGE ABOVE ROOM D263. LIFE SAFETY, INFECTION CONTROL, PHASING AND CEILING DESIGN CONSIDERATIONS ADDRESSED BY HVAC WORK IMPACTS.
PROJECT NAME: FCA- REPAIR AIR HANDLER AC-1
PROJECT NUMBER: 657-23-108JC
PROJECT LOCATION: 657 - ST. LOUIS, MO
PROJECT PURPOSE/USE: REPAIR EXISTING AIR HANDLING UNIT AC-1 AND ASSOCIATED MECHANICAL DEFICIENCIES.
SCOPE OF WORK SUMMARY:
LEVEL 02:
LEVEL 03:
OVERALL:
BUILDING AREA:
73,900 GSF
68,800 GSF
142,700 GSF
DRAWING LIST
NORTH
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW
ALL DRAWINGS AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.
2. THE CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS OF THE DRAWINGS AND THE PROJECT MANUAL.
CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THESE DRAWINGS, THE PROJECT MANUAL, AND IMMEDIATELY
NOTIFY THE DESIGN PROFESSIONAL OF ANY INCONSISTENCIES THAT ARE DISCOVERED.
3. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT.
4. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE
REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION.
THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.
5. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE
CONTRACTOR'S EXPENSE.
6. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.
7. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND
WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH
RESPECT TO DELIVERY DATE, QUALITY, OR COST.
8. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S
MEANS AND METHODS OR FOR TEMPORARY STRUCTURES.
9. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL
EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.
10. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA
REGULATIONS DURING CONSTRUCTION.
11. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.
12. IN THE CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK, AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
13. THE GC SHALL BE RESPONSIBLE FOR COORDINATING THE INSTALLATION OF NEW UTILITIES WITH EXISTING ADJACENT
UTILITIES.
14. ANY WORK NOT SHOWN ON THE DRAWINGS, BUT CONSIDERED NECESSARY FOR THE COMPLETION OF THE WORK IN A
PROPER MANNER SHALL BE PROVIDED BY THE GC WITHOUT ADDITIONAL CHARGE.
15. WHERE PRESENT WORK IS DAMAGED IN THE EXECUTION OF THE CONTRACT OR WHERE OPENINGS ARE LEFT DUE TO THE REMOVAL OF PIPES, CONDUITS, CABLE TRAYS, EQUIPMENT OR APPARATUS, REPAIR OR CLOSE UP CORRESPONDING MATERIAL FINISH OF THE ADJOINING WORK WHERE DAMAGE IS NOT REPAIRABLE. NEW ITEMS OR EQUIPMENT SHALL BE
PROVIDED.
16. CONTRACTOR TO COORDINATE WITH THE COR FOR QUESTIONS REGARDING SITE ACCESS OF WORKERS, MATERIAL
DISPOSAL AND HOURS OF OPERATION.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND VERIFYING DIRECTLY WITH THE COR REGARDING ANY OWNER DESIRED CHANGES TO THE NUMBERING SYSTEM AND/OR NAMING CONVENTION, LABELING AND/OR IDENTIFICATION FOR (OR ON) THE ELECTRICAL PANELS, MECHANICAL EQUIPMENT, FIRE ALARM SYSTEMS/PANELS, SIGNAGE, ETC.
LEVEL 02 SCOPE AREA: 34,000 SF
LEVEL 03 SCOPE AREA: 12,000 SF
OVERALL: 36,000 SF
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/2
/2
:2
:2
P
M
RO DC
657-23-108JC
01-GI100
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
PROJECT COVER SHEET 100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
PROJECT NUMBER - 657-23-108JC
FCA-REPAIR AIR HANDLER AC-1
100% CONTRACT DOCUMENTS ■ MARCH 8, 2024
SHEET # SHEET TITLE
01-MH120B LEVEL 02 - ENLARGED PLAN - AREA 1B - HVAC
01-MH120C LEVEL 02 - ENLARGED PLAN - AREA 1C - HVAC
01-MH120D LEVEL 02 - ENLARGED PLAN - AREA 1D - HVAC
01-MH120E LEVEL 02 - ENLARGED PLAN - AREA 1E - HVAC
01-MH130 LEVEL 03 - HVAC PLAN
01-MH300 HVAC DETAILS
01-MH301 VAV BOX EXISTING CONDITION PHOTOS
01-MH302 VAV BOX EXISTING CONDITION PHOTOS
01-MH303 VAV BOX EXISTING CONDITION PHOTOS
01-MH304 VAV BOX EXISTING CONDITION PHOTOS
01-MM330 LEVEL 03 - ENLARGED MECHANICAL ROOM PLANS - MECHANICAL
01-MP120 LEVEL 02 - ENLARGED PLAN - MECHANICAL PIPING
01-MP120A LEVEL 02 - ENLARGED PLAN - AREA 1A - MECHANICAL PIPING
01-MP120B LEVEL 02 - ENLARGED PLAN - AREA 1B - MECHANICAL PIPING
01-MP120C LEVEL 02 - ENLARGED PLAN - AREA 1C - MECHANICAL PIPING
01-MP120D LEVEL 02 - ENLARGED PLAN - AREA 1D - MECHANICAL PIPING
01-MP120E LEVEL 02 - ENLARGED PLAN - AREA 1E - MECHANICAL PIPING
01-MP130 LEVEL 03 - MECHANICAL PIPING PLAN
01-MP300 PIPING DETAILS
01-MP301 PIPING DETAILS
01-MI100 MECHANICAL CONTROLS
01-MI101 MECHANICAL CONTROLS
01-MI102 MECHANICAL CONTROLS
PLUMBING
01-P-100 PLUMBING SYMBOLS, NOTES, ABBREVIATIONS, AND DEMOLITION PLAN
ELECTRICAL
01-E-001 ELECTRICAL LEGEND, SCHEDULES, AND ABBREVIATIONS
01-ED120 LEVEL 02 - POWER DEMOLITION PLAN
01-ED130 LEVEL 03 - POWER DEMOLITION PLAN
01-ED200 ENLARGED ROOM PLANS - POWER DEMOLITION
01-EP120 LEVEL 02 - POWER PLAN
01-EP130 LEVEL 03 - POWER PLAN
01-EP200 ENLARGED ROOM PLANS - POWER
Grand total: 61
SHEET # SHEET TITLE
GENERAL
01-GI100 PROJECT COVER SHEET
01-GI200 BUILDING ACCESS, CODE, AND CONSTRUCTION GENERAL NOTES
01-GI201 ICRA DETAILS
01-GI202 LEVEL 02 - LIFE SAFETY PLAN
01-GI203 LEVEL 03 - LIFE SAFETY PLAN
01-GI204 LEVEL 02 - CONSTRUCTION AREA GUIDELINES
01-GI205 LEVEL 03 - CONSTRUCTION AREA GUIDELINES
ARCHITECTURAL
01-AC101 LEVEL 02 - REFLECTED CEILING PLAN
01-AC102 LEVEL 03 - REFLECTED CEILING PLAN
MECHANICAL
01-MG100 MECHANICAL SYMBOLS, NOTES, AND ABBREVIATIONS
01-MG101 MECHANICAL SCHEDULES
01-MG102 MECHANICAL SCHEDULES
01-MG103 MECHANICAL SCHEDULES
01-MD120 LEVEL 02 - HVAC DEMOLITION PLAN
01-MD120A LEVEL 02 - ENLARGED PLAN - AREA 1A - HVAC DEMOLITION
01-MD120B LEVEL 02 - ENLARGED PLAN - AREA 1B - HVAC DEMOLITION
01-MD120C LEVEL 02 - ENLARGED PLAN - AREA 1C - HVAC DEMOLITION
01-MD120D LEVEL 02 - ENLARGED PLAN - AREA 1D - HVAC DEMOLITION
01-MD120E LEVEL 02 - ENLARGED PLAN - AREA 1E - HVAC DEMOLITION
01-MD130 LEVEL 03 - HVAC DEMOLITION PLAN
01-MD220 LEVEL 02 - MECHANICAL PIPING DEMOLITION PLAN
01-MD220A LEVEL 02 - ENLARGED PLAN - AREA 1A - MECHANICAL PIPING DEMOLITION
01-MD220B LEVEL 02 - ENLARGED PLAN - AREA 1B - MECHANICAL PIPING DEMOLITION
01-MD220C LEVEL 02 - ENLARGED PLAN - AREA 1C - MECHANICAL PIPING DEMOLITION
01-MD220D LEVEL 02 - ENLARGED PLAN - AREA 1D - MECHANICAL PIPING DEMOLITION
01-MD220E LEVEL 02 - ENLARGED PLAN - AREA 1E - MECHANICAL PIPING DEMOLITION
01-MD230 LEVEL 03 - ENLARGED PLAN - MECHANICAL PIPING DEMOLITION
01-MD330 LEVEL 03 - ENLARGED MECHANICAL ROOM PLAN - MECHANICAL DEMOLITION
01-MH120 LEVEL 02 - HVAC PLAN
01-MH120A LEVEL 02 - ENLARGED PLAN - AREA 1A - HVAC
OWNER:
Department of Veterans Affairs - Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth, KS 6604
CONTRACTING OFFICER (CO):
Department of Veterans Affairs - Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth, KS 6604
David Sterrett David.Sterrett@va.gov
913.946.1146 208.816.6619
CONTRACTING OFFICER REP. (COR):
St. Louis VAHCS – John Cochran Division 915 North Grand Blvd.
St. Louis, MO 63106
Walter Staas Walter.Staas@va.gov
314.652.4100 x58723
PROJECT MANAGER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, TX 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
ARCHITECT:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, TX 75093
Rebecca Olson, AIA, ACHA, NCARB, LEED AP rebecca.olson@RomanykConsulting.com
855.424.3838 x302
602.430.1265 cell
MECHANICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, TX 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
ELECTRICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, TX 75093
Yumei Wang, PE, PMP, LEED AP yumei.wang@RomanykConsulting.com
855.424.3838 x311
402.321.3766 cell
Revisions: Date:
CONSTRUCTION GENERAL NOTES
DN
PLAN LEGEND
BUILDING SCHEDULE
1 MAIN HOSPITAL & CLINICAL ADDITION
1A EMERGENCY GENERATOR VAULT
1B EMERGENCY GENERATOR VAULT
EDUCATION, MEDICAL MEDIA,
CHAPEL & RESEARCH
2T METHADONE CLINIC
2T2 OATP CLINIC
3 IRM & RESEARCH
4 NON-VA CARE / AFGE
5T OEF/OIF
6 RESEARCH
6A RESEARCH
7 RESEARCH
7A RESEARCH
8 BOILER PLANT
8A CHILLER PLANT
8B EMERGENCY GENERATOR
10 FLAG POLE
11 GAS METER HOUSE
12 WET SALT STORAGE
14 GARAGE
16 ENGINEERING / TRANSITION CARE TEAM
24 WASTE STORAGE FACILITY
DEC DECON TRAILER
1T MODULAR BUILDING
RESTAURANT VACANT
BLDG.
14 3
DELMAR AVE.
ENRIGHT AVE.
S P
R
IN
G S
T
AMEREN MISSOURI
SUBSTATION
8A 7
8B
7A
6A
BELL AVE.
1A
G R
A N
D B
L V
D
2T
5T
2T2
1T
DEC
1B
CODE SUMMARY
KEYED NOTES
1. PRIOR TO ANY WORK COMMENCEMENT, THE GC IS TO IDENTIFY ALL OVERALL RISKS THE PROJECT WILL CREATE FOR PATIENTS, STAFF, AND CONTRACTORS. THIS DATA IS TO BE UTILIZED BY THE ONSITE VA TEAM
THROUGH COLLABORATIVE CREATION OF A PRE-CONSTRUCTION RISK ASSESSMENT (PCRA).
2. THE PURPOSE OF THE CONSTRUCTION PHASING NOTES AND DRAWINGS IS TO PROVIDE THE GC WITH
GUIDANCE FOR THE CONSTRUCTION SCHEDULE. THE VA IS OPEN TO ALTERNATE PHASING AND
CONSTRUCTION SCHEDULES TO MINIMIZE DISRUPTIONS AND TO MAKE CONSTRUCTION MORE EFFICIENT.
ANY PROPOSALS MUST BE APPROVED BY THE CONTRACTING OFFICERS REPRESENTATIVE (COR) AND AT NO EXTRA COST TO THE GOVERNMENT. GENERAL CONTRACTOR TO COORDINATE WITH VA COR ALL REQUIRED PHASING PLANS TO INCLUDE DURATION OF THE WORK. ALL WORK IN CORRIDORS, AND OTHER AREAS DEEMED CRITICAL BY THE VA COR, TO BE PERFORMED AFTER NORMAL BUSINESS HOURS AND ON WEEKENDS TO MINIMIZE DISRUPTION TO THE FACILITY. GENERAL CONTRACTOR TO COORDINATE WITH THE VA COR ANY REQUIRED INTERIM LIFE SAFETY MEASURES(ILSM) DOCUMENTATION IN ACCORDANCE WITH
FACILITY PROTOCOLS.
3. REGULAR MEDICAL CENTER BUSINESS HOURS ARE 8:00AM - 5:00PM. LABORATORY AREAS FUNCTION 24
HOURS A DAY, 7 DAYS A WEEK.
4. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED CONSTRUCTION, SAFETY, AND ICRA BARRIERS. ANY AND ALL ICRA BARRIERS MAY NEED TO BE CONSTRUCTED OUTSIDE REGULAR MEDICAL CENTER BUSINESS HOURS AT NO EXTRA COST TO THE GOVERNMENT. CONSULT WITH THE COR AND ANY PROPOSALS MUST BE APPROVED BY THE COR. BARRIERS MUST BE COMPLETED AND APPROVED BY COR BEFORE CONSTRUCTION
COMMENCES WITH THE ICRA PERMIT DISPLAYED DURING CONSTRUCTION FOR EACH PHASE.
5. ANY OTHER WORK DONE BEHIND A CONTAINMENT BARRIER MAY BE DONE DURING REGULAR BUSINESS HOURS AND DURING LABORATORY OPERATIONS UNLESS NOTED IN THE PHASING LEGEND. ANY EXCESSIVE NOISE PERCEIVED OUTSIDE THE CONSTRUCTION CONTAINMENT BARRIER ABOVE 85 DECIBELS SHALL BE COORDINATED WITH THE COR. THE COR RESERVES THE RIGHT TO DELAY WORK SHOULD EXCESSIVE NOISE
DISTURB PATIENT CARE PROCEDURES OR LABORATORY PROCEDURES IN PROXIMITY TO THE
CONSTRUCTION CONTAINMENT BARRIER. IF THERE IS ANYTHING THE COR HAS DEEMED EXCESSIVE OR DISRUPTIVE TO PATIENT CARE PROCEDURES, LABORATORY PROCEDURES, OR HOSPITAL OPERATIONS, A PLAN OF ACTION WILL BE IMMEDIATELY PUT IN PLACE TO AVOID DISRUPTIONS TO THE CONSTRUCTION
SCHEDULE.
6. ANY UTILITY SHUTDOWNS WILL REQUIRE 21 CALENDAR DAYS NOTICE AND ANY SHUTDOWNS THAT MAY DISRUPT NORMAL MEDICAL CENTER OPERATIONS MAY NEED TO BE PERFORMED OUTSIDE REGULAR MEDICAL CENTER BUSINESS HOURS AT NO EXTRA COST TO THE GOVERNMENT. MAINTAIN UNINTERRUPTED OPERATION OF THE EXISTING FACILITIES, AND MINIMIZE DISRUPTIONS TO THE MEDICAL CENTER FOR ALL SWITCH-OVER OF UTILITIES. COR RESERVES THE RIGHT TO DETERMINE THE SEVERITY OF THE SHUTDOWN.
7. THE GC SHALL COORDINATE WITH THE COR TO DEVELOP A CRITICAL PATH METHOD (CPM) SCHEDULE, SEQUENCING, COMPLETION DATES FOR RENOVATION AND NEW CONSTRUCTION FOR THE PROJECT. THE
CONSTRUCTION SCHEDULE IS ALLOWED TO SHOW PHASES OVERLAPPING EACH OTHER WITH COR
APPROVAL.
8. THE MEDICAL CENTER MUST REMAIN IN FULL OPERATION DURING CONSTRUCTION WITH MINIMAL INTERRUPTION DUE TO ALL CONSTRUCTION ACTIVITIES FOR THE PROJECT, INCLUDING NOISE, DUST, VIBRATION, ETC., CREATED BY CONSTRUCTION ACTIVITIES RELATED TO THIS PROJECT.
9. THE GC'S SCHEDULES SHOULD INCLUDE BUT IS NOT LIMITED TO THE FOLLOWING:
A. ALL CONSTRUCTION-ACTIVITIES-RELATED ISSUES WHICH MAY AFFECT THE CONTINUAL OPERATIONS OF
THE MEDICAL CENTER,
B. SCHEDULES FOR SHUTTING DOWN EXISTING SYSTEMS OR ACCESS FOR TIE-INS AND/OR REPLACEMENT, C. SCHEDULES FOR AFTER-HOURS CONSTRUCTION ACTIVITIES.
D. BARRIERS AND OTHER PROTECTIVE MEASURES SUCH AS ISOLATING THE HVAC SYSTEM IN AREAS
WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCTS, ETC.
E. IBC (2021) CHAPTER 33 SAFEGUARDS DURING CONSTRUCTION 3302.1 AND 1007.3.5 MAINTAIN REQUIRED
CORRIDOR EGRESS AT TEMPORARY BARRIERS AND PROVIDE SIGNAGE.
F. INVESTIGATE EXISTING FIELD CONDITIONS OF FIRE RESISTANCE PARTITIONS/ASSEMBLIES. IBC (2021)
SECTION 714, PROVIDE UL APPROVED FIRE RESISTANT JOINT SYSTEM PENETRATIONS ABOVE CEILING
LABELED, IBC (2021) SECTION 703.
10. PROVIDE APPROPRIATE BARRIERS AS REQUIRED TO SEPARATE CONSTRUCTION ACTIVITIES FROM PUBLIC AREAS AND AREAS REQUIRING ACCESS DURING CONSTRUCTION. BARRIERS SHOULD BE RELOCATED AS REQUIRED AFTER EACH PORTION OF WORK IS COMPLETED TO ACCOMMODATE ACCESS TO EXISTING
FACILITIES AS CONSTRUCTION PROGRESSES.
11. IF MEDICAL CENTER ACCESS PATHWAYS IDENTIFIED ON THE PHASING PLANS ARE REQUIRED TO BE BLOCKED TEMPORARILY TO ACCOMMODATE CONSTRUCTION, COORDINATE ALTERNATE PATHWAYS WITH THE COR AND PROVIDE TEMPORARY SIGNAGE AND TEMPORARY PROTECTIVE BARRIERS TO CREATE ALTERNATE PATHWAYS AS REQUIRED. REFER TO THE PHASING DIAGRAMS FOR ADDITIONAL NOTES. COORDINATE AND
SCHEDULE ANY DOWNTIME FOR THESE ROUTES WITH THE COR.
12. THE GC SHALL SEEK FINAL APPROVAL OF THE LOCATION OF ANY AND ALL BARRIERS AND CONTRACTOR SITE
ACCESS AND DEBRIS AND MATERIAL HAUL ROUTES WITH THE COR.
13. MAINTAIN ACCESS TO ALL EXISTING BUILDINGS, UTILITIES AND FACILITIES WITHIN THE CONSTRUCTION LIMITS TO ACCESS EQUIPMENT AND TO PROVIDE SERVICE OR MAINTENANCE OF EXISTING FACILITIES AND EQUIPMENT SERVING THE MEDICAL CENTER. ALL ACCESS ROADS ARE SHARED WITH STAFF, PATIENTS, AND
CONTRACTORS.
14. THE GC HAS RESPONSIBILITY IN DETERMINING THE CORRECT PHASING TO MATCH THE REQUIREMENTS OF THE CONSTRUCTION CONTRACT AS WELL AS THE ACTUAL LOCATIONS AND THE METHODS THROUGH WHICH
TO CONSTRUCT THE ICRA-COMPLIANT CONSTRUCTION BARRIERS.
15. THE GC SHALL COORDINATE WITH THE COR TO LOCATE THE SAFETY SIGN AND CONSTRUCTION SIGN.
16. MAINTAIN ALL FIRE BARRIERS AND DUST PARTITIONS AS REQUIRED TO PROVIDE A DUST-FREE AND CLEAN ENVIRONMENT BETWEEN RENOVATED AREAS WITHIN THE HOSPITAL AND AREAS ADJACENT TO RENOVATED
AND NEW CONSTRUCTION.
17. MAINTAIN INSULATED AND WATERTIGHT EXTERIOR ENCLOSURE FOR EXISTING FACILITY AT ALL TIMES.
18. ISOLATE HVAC SYSTEM WHERE WORK IS PERFORMED TO PREVENT CONTAMINATION OF DUCT SYSTEM.
19. ALL PERSONNEL ENTERING RENOVATION AREAS WITHIN OCCUPIED FLOORS OF THE MEDICAL CENTER SHALL WEAR SHOE COVERS, AND THESE MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA.
PROVIDE ADHESIVE WALK-OFF MATS AT ENTRANCES TO THESE WORK AREAS. IF THERE IS AN ANTEROOM, MAT SHOULD BE WITHIN THIS AREA. REPLACE MATS DAILY OR WHEN THEY NO LONGER ARE ABLE TO CONTAIN DUST AND DIRT. WET MOP AND/OR VACUUM WORK AREA WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREAS. CONTAIN CONSTRUCTION WASTE IN TIGHTLY COVERED CONTAINERS BEFORE TRANSPORTING. REMOVE HVAC ISOLATION FROM SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE THE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
THOROUGHLY CLEANED.
20. PHASING PLAN AND ICRA DEFINES THE AREAS OF WORK ON ALL AFFECTED LEVELS. THE VA MAY, BASED ON DYNAMIC UNFORESEEN VARIABLES (PATIENT CENSUS, OTHER PROJECTS, ETC..), REQUIRE THE GENERAL CONTRACTOR TO MODIFY EXTENTS AND AREA SIZE OF ICRA BARRIERS. ANY SUCH MODIFICATION WILL REQUIRE THE SAME REQUISITES PROVISIONS REQUIRING CONTAINMENT AS NOTED ON SHEET 01-GI102.
21. VERIFY ALL LABORATORY EQUIPMENT LOCATIONS WITH VA BEFORE COMMENCING WORK. ALL LABORATORY EQUIPMENT THAT IS STATIONARY WILL NOT BE MOVED. CONTRACTOR WILL BE EXPECTED TO PROVIDE A BARRIER AND WORK AROUND THIS EQUIPMENT. SINCE THE LABORATORY FUNCTIONS 24 HOURS A DAY, 7 DAYS A WEEK, SOME LABORATORY EQUIPMENT WILL NEED TO STAY OPERATIONAL DURING CONSTRUCTION.
SEE PHASING PLAN FOR ADDITIONAL INFORMATION.
22. SOME NON STATIONARY LABORATORY EQUIPMENT (EQUIPMENT SITTING ON A COUNTERTOP OR MOBILE UNITS) MAY BE MOVED. CONTRACTOR TO IDENTIFY AND REQUEST THE MOVEMENT OF THE EQUIPMENT WITHIN THEIR CONSTRUCTION SCHEDULE. ONLY MEDICAL CENTER LABORATORY PERSONNEL WILL BE
ALLOWED TO MOVE EQUIPMENT.
23. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING AND STORAGE OF ALL FURNITURE RELATED TO THE PROJECT, INCLUDING BUT NOT LIMITED TO FURNITURE, NON-LABORATORY EQUIPMENT, SIGNAGE, AND
ARTWORK. SEE SPEC.
24. CERTAIN ROOMS AS LISTED ON THE DRAWINGS MAY HAVE DIFFERENT ALLOWABLE CONSTRUCTION TIMES.
SEE THE DRAWINGS FOR LISTED TIMES.
25. ALL LARGE BULKY CONSTRUCTION MATERIAL OR EQUIPMENT DELIVERIES OR DEBRIS REMOVAL MUST BE COMPLETED BY 8:00AM M-F. FOLLOW ALL ICRA GUIDELINES FOR SAFE HANDLING OF MATERIAL AND CLEAN-
UP OUTSIDE THE CONSTRUCTION CONTAINMENT BARRIER.
26. ANY EXCESSIVE NOISE PERCEIVED OUTSIDE THE CONSTRUCTION CONTAINMENT BARRIER ABOVE 85 DECIBELS SHALL BE COORDINATED WITH COR. THE COR RESERVES THE RIGHT TO DELAY WORK FOR 1-2 HOURS SHOULD EXCESSIVE NOISE DISTURB PATIENT CARE PROCEDURES OR LABORATORY PROCEDURES IN
PROXIMITY TO THE CONSTRUCTION CONTAINMENT BARRIER.
27. ANYTHING THE COR HAS DEEMED EXCESSIVE OR DISRUPTIVE TO PATIENT CARE PROCEDURES OR LABORATORY PROCEDURES. A PLAN OF ACTION WILL BE IMMEDIATELY PUT IN PLACE TO AVOID DISRUPTIONS
TO THE CONSTRUCTION SCHEDULE.
01-GI202
01-GI203
SCOPE OF WORK AREA
NO SCOPE OF WORK AREA
CONTRACTOR ACCESS
PROJECT CODE DATA
DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER
915 N GRAND BLVD.
ST. LOUIS, MO 63106
APPLICABLE CODES
2024 NFPA NATIONAL FIRE PROTECTION ASSOCIATION LIFE SAFETY CODE
NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
2021 IBC INTERNATIONAL BUILDING CODE
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
07/01/2023 VA SEISMIC DESIGN REQUIREMENTS, H-18-8
2023 NEC NATIONAL ELECTRIC CODE
2021 IPC INTERNATIONAL PLUMBING CODE
11/01/2023 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS INCLUDING VA
SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG13-18)
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL
CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON
TECHNICAL INFORMATION LIBRARY (TIL) (www.cfm.va.gov/til/)
OCCUPANCY GROUP
IBC OCCUPANCY CLASSIFICATION GROUP B (AMBULATORY CARE FACILITIES) SECTION 304
NFPA 101 CHAPTER 21 EXISTING AMBULATORY HEALTH CARE OCCUPANCY 6.1.6
IBC OCCUPANT LOAD FACTOR TABLE 1004.5 BUSINESS 150 SF, 50 SF CONCENTRATED BUSINESSES
1004.8 50
NFPA 101 TABLE7.3.1.2 OCCUPANT LOAD FACTOR AMBULATORY HEALTH CARE USE 150 SF
BUILDING CONSTRUCTION CLASSIFICATION
NFPA 101 (BLDG. 01 PROJECT SCOPE) TYPE II (000) CHAPTER 21 EXISTING AMBULATORY HEALTH
CARE OCCUPANCIES TABLE 21.1.6.1
IBC II-B TABLE 601.1 (BLDG. 01 PROJECT SCOPE)
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS PER IBC TABLE 601
II-B
0 HR. PRIMARY STRUCTURAL FRAME
0 HR. BEARING WALLS - EXTERIOR
0 HR. BEARING WALLS - INTERIOR
NON BEARING WALLS & PARTITIONS TABLE 602
0 HR. NON BEARING WALLS & PARTITIONS - INTERIOR
0 HR. FLOOR CONSTRUCTION & SECONDARY MEMBERS SECTION 202
0 HR. ROOF CONSTRUCTION & ASSOCIATED SECONDARY MEMBERS SECTION 202
BUILDING IS PROTECTED THROUGHOUT BY AN AUTOMATIC SPRINKLER SYSTEM
OCCUPANCY SEPARATION NFPA 101 TABLE 6.1.14.4.1(A)
NFPA 101 TABLE A.7.6 COMMON PATH, DEAD-END AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)
50 FT. DEAD END LIMIT EXISTING AMBULATORY HEALTH CARE
100 FT. COMMON PATH OF TRAVEL LIMIT EXISTING AMBULATORY HEALTH CARE
200 FT. TRAVEL DISTANCE LIMIT EXISTING AMBULATORY HEALTH CARE
INTERIOR FINISHES PER IBC TABLE 803.13
CLASS B INTERIOR EXIT STAIRWAYS & RAMPS
CLASS C CORRIDORS & ENCLOSURE FOR EXIT ACCESS STAIRWAYS & RAMPS
CLASS C ROOMS & ENCLOSED SPACES
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/1
/2
:0
:5
P
M
RO DC
657-23-108JC
01-GI200
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
BUILDING ACCESS, CODE, AND CONSTRUCTION
GENERAL NOTES
100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
1" = 40'-0"
LEVEL 02 - OVERALL PLAN
1" = 40'-0"
LEVEL 03 - OVERALL PLAN
1" = 100'-0"
OVERALL SITE PLAN
1. SITE ACCESS FOR CONTRACTOR PERSONNEL AND MATERIAL DELIVERY /
SUPPLIES.
2. DESIGNATED PARKING FOR CONTRACTOR, TO BE DETERMINED.
3. CONTRACTOR STAGING AREA, TO BE DETERMINED.
4. CONTRACTOR ACCESS TO THE BUILDING.
5. CONTRACTOR BUILDING ELEVATOR ACCESS.
6. USE OF TOILETS FOR CONTRACTOR, TO BE DETERMINED.
INFECTION CONTROL GENERAL NOTES
1. ISOLATE EXISTING HVAC SYSTEM IN AREAS WHERE WORK IS TO BE PERFORMED. ALL AIR VENTS MUST BE SEALED OFF NEAR THE CONSTRUCTION AREA AS REQUIRED AFTER COORDINATION WITH COR TO ENSURE NON-INTERFERENCE WITH HVAC AND NEGATIVE
PRESSURE SYSTEMS. DUST TO BE CONTROLLED WITHIN THE WORK SITE FROM FLOOR TO DECK.
2. TRAFFIC CONTROL: DESIGNATED ENTRY AND EXIT PROCEDURES WILL BE DEFINED AND CLEARLY ARTICULATED WITH CONSTRUCTION SIGNAGE TO BE PROVIDED BY THE CONTRACTOR. ALL EGRESS WAYS MUST BE MAINTAINED FREE OF DEBRIS AT ALL TIMES. THEY MUST BE UTILIZED AT SCHEDULED TIMES ONLY AS COORDINATED WITH COR. DUST MATS MUST BE PLACED AT ENTRANCES/EXITS OF WORK AREA AND REPLACED DAILY OR MORE FREQUENTLY IF NECESSARY. DEBRIS WHEN TRANSPORTED THROUGH HOSPITAL AREAS MUST BE COMPLETELY TIGHTLY COVERED TO CONTAIN DUST DURING TRANSPORT. DEBRIS SHALL BE REMOVED IN EVENINGS OR NON-DUTY TIMES IF POSSIBLE.
ALL CART WHEELS MUST BE CLEANED BEFORE LEAVING THE CONSTRUCTION AREA.
3. CLEANING: THE CONSTRUCTION ZONE AND ADJACENT ENTRY AREA SHALL BE MAINTAINED IN A CLEAN AND SANITARY MANNER BY THE CONTRACTOR AND WILL BE HIGH EFFICIENCY PARTICULATE AIR (HEPA) VACUUMED AND WET MOPPED WITH DISINFECTANT DAILY OR MORE FREQUENTLY AS NEEDED TO MINIMIZE DUST GENERATION. CLOTHING SHALL BE FREE OF LOOSE SOIL AND DEBRIS UPON EXITING THE CONSTRUCTION ZONE. PROVIDE PERSONAL PROTECTIVE EQUIPMENT, INCLUDING FACE SHIELDS, GLOVES, AND N95 RESPIRATORS REQUIRED
BY THE SAFETY SPECIFICATION.
4. INFECTION CONTROL CONSTRUCTION PERMIT: CONTRACTOR TO OBTAIN INFECTION CONTROL PERMIT BEFORE CONSTRUCTION BEGINS..
5. STAGING AREAS WILL BE DESIGNATED BY THE COR. CONTRACTOR TO COORDINATE WITH THE COR PRIOR TO CONSTRUCTION.
6. THE CONTRACTOR SHALL COORDINATE WITH RISK ASSESSMENT DOCUMENTATION AND THE COR PRIOR TO IMPLEMENTATION.
7. CONTRACTOR TO PROVIDE PROTECTION ABOVE CEILING WITHIN THE CONTAINMENT AREA, IF EXISTING WALLS AND/OR PARTITIONS DO NOT
EXTEND TO THE STRUCTURE ABOVE.
8. COORDINATE WITH MEP/FP.
9. ICRA PLANS DENOTE TOTAL DEFINED AREAS OF WORK ON ALL AFFECTED LEVELS. THE VA MAY, BASED ON DYNAMIC UNFORESEEN VARIABLES
(PATIENT CENSUS, OTHER PROJECTS, ETC.), REQUIRE THE GENERAL CONTRACTOR TO MODIFY EXTENTS AND AREA SIZES OF ICRA BARRIERS. ANY SUCH MODIFICATION WILL REQUIRE THE SAME REQUISITE PROVISIONS REQUIRING CONTAINMENT (ANTE ROOM, WALK-OFF MATS, ETC.) AIR-PRESSURIZATION CRITERIA, AND IDENTIFICATION AS NOTED ON SHEET GI-103 TO GI-106.
10. CERTAIN ROOMS AS LISTED ON THE DRAWINGS MAY HAVE DIFFERENT ALLOWABLE CONSTRUCTION TIMES. SEE THE DRAWINGS FOR LISTED
TIMES.
11. ALL LARGE BULKY CONSTRUCTION MATERIAL OR EQUIPMENT DELIVERIES OR DEBRIS REMOVAL MUST BE COMPLETED BY 8:00AM M-F. FOLLOW ALL ICRA GUIDELINES FOR SAFE HANDLING OF MATERIAL AND CLEAN-UP OUTSIDE THE CONSTRUCTION CONTAINMENT BARRIER.
12. ANY EXCESSIVE NOISE PERCEIVED OUTSIDE THE CONSTRUCTION CONTAINMENT BARRIER ABOVE 85 DECIBELS SHALL BE COORDINATED WITH COR. THE COR RESERVES THE RIGHT TO DELAY WORK FOR 1-2 HOURS SHOULD EXCESSIVE NOISE DISTURB PATIENT CARE PROCEDURES OR
LABORATORY PROCEDURES IN PROXIMITY TO THE CONSTRUCTION CONTAINMENT BARRIER.
13. ANYTHING THE COR HAS DEEMED EXCESSIVE OR DISRUPTIVE TO PATIENT CARE PROCEDURES OR LABORATORY PROCEDURES. A PLAN OF ACTION WILL BE IMMEDIATELY PUT IN PLACE TO AVOID DISRUPTIONS TO THE CONSTRUCTION SCHEDULE.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
NOT TO SCALE
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/1
/2
:0
:5
P
M
RO DC
657-23-108JC
01-GI201
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
ICRA DETAILS 100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
TYPE B
HIGH RISK
III
Revisions: Date:
VHASTLSTAASW
Text Box ICRA Barrier Additional Notes
ICRA barriers shall not be built during Medical Center business hours 8:00am-4:30pm M-F. Some areas may have additional time restrictions.
ICRA barriers at most rooms shall be Class IV. There must be an ante room.
ICRA barriers at locations that will be active for less than 30 calendar days and have minimal dust generating activity may be allowed to have a plastic zippered door separating the ante room and construction zone. The contractor shall provide a written proposal for VA Infection Prevention personnel to review but must be prepared to provide a more restrictive barrier per ICRA requirements at no cost to the government.
ICRA barriers at some locations may be allowed to be a mobile containment unit or other similar mobile or modular containment system. The contractor shall provide a written proposal for VA Infection Prevention personnel to review but must be prepared to provide a more restrictive barrier per ICRA requirements at no cost to the government.
All gaps in the containment barrier must be taped and sealed. Taping is to be done in a manner as to not be destructive to existing infrastructure or the contractor is responsible for repair. Taping is to be inspected daily and any gaps resealed or retaped to maintain the required negative air pressure. Negative air outlet shall use a piece of hard flat material in the window with a hole in it for the tubing and use a round flange and attach the tubing with a band clamp or similar VA approved method.
Doors into ICRA barriers shall be:
• Metal and wipeable to maintain a dust free clean surface. No wood allowed. ADA compliant threshold, or no threshold.
• Pre-manufactured temporary wall systems are allowed per VA approval.
• Have a door closer. Door must close and latch on its own power while the negative air is operational.
• A door latch and lock compatible with the VA key core.
o CL3357 NZD 626 RH CT6 (LFIC LESS CONST. CORE) (Storeroom function) Lock set for JC Large Format Interchangeable Core.
o A potential supplier - IDN-H Hoffman Inc. 314-692-8391.
VHASTLSTAASW
Image
LIFE SAFETY NOTES
LIFE SAFETY LEGEND
1-A2-A3-A4-A5-A6-A7-A8-A9-A10-A11-A12-A13-A14-A
C-A
D-A
E-A
F-A
G-A
B-A
A.1-A
S-A
R-A
Q-A
P-A
N-A
M-A
CONFERENCE RM.
D215
STORAGE
D214
OFFICE
D213
MICROSCOPE
D216
ANCILLARY TESTING
D263
CHEMICAL STORAGE
D264
OFFICE
D265
STORAGE
D205
VACANT
D206
OFFICE
D204
OFFICE/EXAM
D203
TOILET, FEMALE
D202A
TOILET, MALE
D201A
STAIR 07
S207
STORAGE
C213A
EXAM
C212
TOILET
C213
OFFICE
C211
EXAM
C210
LAB
C207
OFFICE
C206
MOLECULAR DIAG.
C205
OFFICE
C209
EXAM
C204
OFFICE
C203
CLINICAL
C201
ANTE ROOM
D219
ELEC CLOSET
D269A
BULK STORAGE
D269
CORRIDOR
H229
OFFICE
D260 OFFICE
D256
OFFICE
D261
OFFICE
D257
OFFICE
D250
OFFICE
D249
OFFICE
D247
PHARMACY STORAGE
C216
NEUROPATHOLOGY
D207
CORRIDOR
D208
LOCKER, FEMALE
D202
WAITING RM.
C208
EXERCISE LAB
C200
SOILED UTILITY
B203B
OFFICE
C215
MECH.RM.
C215A
OFFICE
C220
CONFERENCE
C217
STORAGE
B203C
BLOOD DRAW
B207A
BLOOD DRAW
B207B
BLOOD DRAW
B207C
BLOOD DRAW
B207
BLOOD DRAW
B207D
COMPUTER RM
C218
OI&T
C218A
OFFICE, SUPER
HEMATOLOGY
D242
OFFICE
D243
OFFICE
D245
BREAK RM.
D244
BREAK RM.
D253
BREAK RM.
D254
OFFICE
D252
HAC
D255
OI&T
C215B
PHARMACY STORAGE
C214
EXG & HOLTER MONITOR
B206
STORAGE
B206B
TOILET
B208
TOILET
B209
WORK AREA
B210
LOUNGE
C219
SUPPLIES
B205A
CONFERENCE RM.
B204B
STORAGE
D238AGAS STORAGE
D238
BLOODBANK
D237
STAIR 6
S206
OFFICE
B211
OFFICE
B212
OFFICE
B213
OFFICE
B214
OFFICE
B215
OFFICE
B216
OFFICE
B216A
STAIR 3
S203
URINE/FECES ANALYSIS
D236
IMMEDIATE RESPONSE
D235
STAT CHEMISTRY
D234PATHOLOGY LAB
D241
HVAC
D239
JANITOR
D240
OI&T
D240A
SECRETARY
D248
HEMO STERILE
D271
STERILIZATION
D270
MICROBIOLOGY
D221
OFFICE
D226
WALK-IN REF
D225
WALK-IN REF
D225A
MECH.RM
D225B
MEDIA PREP
D224
IMMUNOLOGY
D228
MICROBIOLOGY
D223
TRANSFER RM.
D222
TB RM.
D220
ELEC. CLOSET
B217
OI&T
B217A
HAC
B218
HOLTER SCANNER LAB
B205D
OFFICE
B204
TEST RM
B204A
KITCHEN
B202D
OFFICE
B203
STORAGE
C202A
OI&T
B206A
ELEVATOR LOBBY
H223
CORRIDOR
H221
ELEVATOR LOBBY
H222
CORRIDOR
H219
CHUTE
B205C
CORRIDOR
C225
CORRIDOR
H226
CORRIDOR
D246
MAIL HOLDING
D259
CORRIDOR
H231
CORRIDOR
H228
HISTOLOGY LAB
D209
CYTOLOGY LAB
D210CYTOLOGY
D211
DARK RM.
D266
HISTOLOGY LAB
D212
STAIR 09
S209
RSO
B219
DEPUTY RSO
B219A
STAFF WORK.RM
B203A
HAC
B203D
CORR.
H223B
ELEC.
D234A
OFFICE
D267
OFFICE
D268
LOCKER, MALE
D201
M A
T C
H L
IN
E
OFFICE
C202
STAIR 08
S208
CORRIDOR
H217
CONFERENCE
B242
SOILED UTILITY
B243
NUC.MED SUPERVISOR
B229READING
B220
BLOOD DRAW
B210A
1. THE LIFE SAFETY PLANS ARE "DIAGRAMMATIC ONLY". THEIR PURPOSE IS
SOLELY TO REPRESENT THE LIFE SAFETY COMPONENTS FOR THE PROJECT.
THE GENERAL CONTRACTOR SHALL USE THE CONSTRUCTION DOCUMENTS
(NOT THE LIFE SAFETY PLANS) FOR THE IMPLEMENTATION OF THE REQUIRED
LIFE SAFETY COMPONENTS INTO THE PROJECT.
SCOPE OF WORK AREA
NO SCOPE OF WORK AREA
EXIT STAIRWELL / PASSAGEWAY
EXIT
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1 HOUR SMOKE COMPARTMENT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
KEY PLAN
PLAN NORTH
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/1
/2
:0
:5
P
M
RO DC
657-23-108JC
01-GI202
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
LEVEL 02 - LIFE SAFETY PLAN 100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
1" = 10'-0"
LEVEL 02 - LIFE SAFETY PLAN
NOTIFICATION: THIS SHEET TO BE PRINTED IN COLOR
LIFE SAFETY NOTES
LIFE SAFETY LEGEND
1-A2-A3-A4-A5-A6-A7-A8-A9-A10-A11-A12-A13-A14-A
C-A
D-A
E-A
F-A
G-A
B-A
A.1-A
S-A
R-A
Q-A
P-A
N-A
M-A
M A
T C
H L
IN
E
RETAIL STORAGE
C303C
RETAIL STORAGE
C303D
OFFICE
C303A
OFFICE
C303
ELEVATOR LOBBY
H311
STORAGE
C304
OFFICE
B303E
OFFICE
B303F
OFFICE
B303G
CONFERENCE
B303H
STORAGE
C304
CORRIDOR
H312
RETAIL STORE (CANTEEN)
B306
CORRIDOR
H309
DINING RM.
B315
STORAGE
B314A
ELEC
B313A
STAIR 06
S306
STAIR 03
S303
MECH RM.
D302B
MECH. RM
D302C
MECH. RM.
D302A
MECH. RM.
C301
MECH. RM.
D303A
MECH. RM.
D302
STAIR 07
S307
MECH. RM.
C301A
MECH. RM.
C301
ELEV 7
A368
ELEV 8
A369
ELEV 9
A370
STAIR 09
S309
STAIR 08
S308
1. THE LIFE SAFETY PLANS ARE "DIAGRAMMATIC ONLY". THEIR PURPOSE IS
SOLELY TO REPRESENT THE LIFE SAFETY COMPONENTS FOR THE PROJECT.
THE GENERAL CONTRACTOR SHALL USE THE CONSTRUCTION DOCUMENTS
(NOT THE LIFE SAFETY PLANS) FOR THE IMPLEMENTATION OF THE REQUIRED
LIFE SAFETY COMPONENTS INTO THE PROJECT.
SCOPE OF WORK AREA
NO SCOPE OF WORK AREA
EXIT STAIRWELL / PASSAGEWAY
EXIT
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1 HOUR SMOKE COMPARTMENT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
KEY PLAN
PLAN NORTH
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/1
/2
:0
:5
P
M
RO DC
657-23-108JC
01-GI203
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
LEVEL 03 - LIFE SAFETY PLAN 100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
1" = 10'-0"
LEVEL 03 - LIFE SAFETY PLAN
CONSTRUCTION GUIDELINES
KEY NOTES
2-A3-A4-A5-A6-A7-A8-A9-A10-A11-A12-A13-A14-A
C-A
D-A
E-A
F-A
G-A
B-A
A.1-A
S-A
R-A
Q-A
P-A
N-A
M-A
CONFERENCE RM.
D215
STORAGE
D214OFFICE
D213
MICROSCOPE
D216
OFFICE
D267
ANCILLARY TESTING DEPT.
D263
CHEMICAL STORAGE
D264
ANCILLARY TESTING LAB
D265
BREAK ROOM
D205
VACANT
D206
OFFICE
D204
OFFICE/EXAM
D203
TOILET, FEMALE
D202A
LOCKER
D201
STAIR 07
S207
STORAGE
C213A
EXAM
C212
TOILET
C213
OFFICE
C211 EXAM
C210 OFFICE
C207
OFFICE
C206
OFFICE
C205
OFFICE
C209
EXAM
C204
OFFICE
C203
OFFICE
C202
CLINICAL
C201
ANTE ROOM
D219
ELEC CLOSET
D269A
BULK STORAGE
D269
CORRIDOR
H229
OFFICE
D260
OFFICE
D256
OFFICE
D261
OFFICE
D257
OFFICE
D250
OFFICE
D249
OFFICE
D247
PHARMACY CACHE
C216
NEUROPATHOLOGY
D207
CORRIDOR
D208
LOCKER RM. FEMALE
D202
WAITING RM.
C208
EXERCISE LAB
C200
SOILED UTILITY
B203B
OFFICE
C215
MECH.RM.
C215A
OFFICE
C220
CONFERENCE
C217
STORAGE
B203C
BLOOD DRAW
B207A
BLOOD DRAW
B207B
BLOOD DRAW
B207C
BLOOD DRAW
B207
BLOOD DRAW
B207D
COMPUTER RM
C218
OI&T
C218A
OFFICE, SUPER
HEMATOLOGY
D242
OFFICE
D243
OFFICE
D245
BREAK RM.
D244
BREAK RM.
D253
BREAK RM.
D254
OFFICE
D252
HAC
D255
OI & T
C215B
PHARMACY CACHE
C214
EXG & HOLTER MONITOR
B206
STORAGE
B206B
TOILET
B208
STORAGE
B209
WORK AREA
B210
OFFICE
C219
SUPPLIES
B205A
CONFERENCE RM.
B204B
STORAGE
D238AGAS STORAGE
D238
BLOODBANK
D237
STAIR 6
S206
OFFICE
B211
OFFICE
B212
OFFICE
B213
OFFICE
D214
OFFICE
B215
URINE/FECES ANALYSIS
D236
IMMEDIATE RESPONSE
D235
STAT CHEMISTRY
D234
PATHOLOGY LAB
D241
HVAC
D239
HVAC
D240
OIT&T
D240A
SECRETARY
D248
HEMO STERILE
D271
STERILIZATION
D270
MICROBIOLOGY
D221
MICRO SUP. OFFICE
D226
WALK-IN REF
D225
WALK-IN REF
D225A
MECH.RM
D225B
MEDIA PREP
D224
IMMUNOLOGY/ SEROLOGY
D228
MICROBIOLOGY
D223
TRANSFER RM.
D222
TB RM.
D220
STAFF WORK.RM
B203A
KITCHEN
B202D
TEST RM
B204A
OFFICE
B204
HAC
B203D
HOLTER SCANNER LAB
B205D
STRESS LAB
B205B
CORRIDOR
H234
2 2
VAV-1-25 (EX)
VAV-1-26 (EX)
VAV-1-30 (EX)
VAV-1-18 (EX)
VAV-1-23 (EX)
VAV-1-48 (EX)
VAV-1-16 (EX)
VAV-1-17 (EX)
VAV-1-21 (EX)
VAV-1-22 (EX)
VAV-1-20 (EX)
VAV-1-19 (EX)
VAV-1-15 (EX)
VAV-1-12 (EX)
VAV-1-14 (EX)
VAV-1-13 (EX)
VAV-1-47 (EX)
VAV-1-44 (EX)
VAV-1-42 (EX)
VAV-1-41 (EX)
3 3
VAV-1-27 (EX)
VAV-1-74 (EX)
VAV-1-24 (EX)
VAV-1-11 (EX)
VAV-53 (EX)
VAV-47 (EX) VAV-38 (EX)
VAV-46 (EX)
VAV-50 (EX)
VAV-1-10 (EX)
VAV-1-28 (EX)
VAV-1-29 (EX)
VAV-1-32 (EX)
VAV-1-33 (EX)
2 2
VAV-1-35 (EX)
VAV-1-34 (EX)
VAV-1-36 (EX)
VAV-1-45 (EX)
VAV-1-37 (EX)
VAV-1-38 (EX)
VAV-1-31 (EX)
VAV-1-3 (EX)
VAV-1-2 (EX)
VAV-1-1 (EX)
VAV-1-57 (EX)
VAV-1-59 (EX)
VAV-1-58 (EX)
VAV-1-60 (EX)
VAV-1-61 (EX)VAV-1-63 (EX)
VAV-1-64 (EX)
VAV-1-62 (EX)
VAV-74 (EX)
VAV-1-55 (EX)
VAV-1-54 (EX)
VAV-1-4 (EX)
VAV-1-49 (EX)
VAV-1-54 (EX)
VAV-1-66 (EX)
VAV-1-59 (EX)
VAV-1-68 (EX)
VAV-1-67 (EX)
OFFICE
D268
DARK RM
D266
VAV-1-50 (EX)
VAV-1-51 (EX)
VAV-1-52 (EX)
CORR
H223A
BLOOD DRAW
D210A
M A
T C
H L
IN
E
STAIR 3
S203
OFFICE
B216A
OFFICE
B216
Room B223Z
Room B223Y
Room B223X
ELEC. CLOSET
B223U
OI&T
B217A
5 6
5 5
STAIR 08
S208
STAIR 09
S209
PHASE 1. WORK TO BE DONE ON ONE VAV AT A TIME IN THE LAB. STAT WITH
VAV-1-25(EX), VAV-1-26(EX), VAV-1-30(EX). THEN SEQUENCING IS UP TO THE
CONTRACTOR'S APPRVED SCHEDULE. SEE FULL PROPOSED CONSTRUCTION
SCHEDULE ON 01-MG103. (LEGEND NOTES 1, 2, 3, 4)
1. THERE IS A MAXIMUM OF TWO WEEKS TO COMPLETE WORK PER VAV BOX.
2. PERSONNEL IN THE OFFICE WILL RELOCATE DURING CONSTRUCTION.
3. FURNITURE WILL NOT BE MOVED BY THE VA.
4. REFER AND COORDINATE WITH MECHANICAL DOCUMENTS.
5. SEE CONSTRUCTION PHASE IDENTIFICATION MARKER. PHASE 1 SHALL BE
FIRST. PHASES 2-8 SHALL BE DETERMINED BY GC IN CONSULTATION WITH
THE COR.
6. INVESTIGATE EXISTING FIELD CONDITIONS OF FIRE RESISTANCE PARTITIONS
THAT ARE AFFECTED BY WORK SCOPE AND PROVIDE UL APPROVED FIRE-
RESISTANT JOINT SYSTEM PENETRATIONS ABOVE CEILING LABELED, IBC
(2021) SECTION 70 AND SECTION 7.1.1.
7. GC SHALL DETERMINE PROJECT DAILY SCHEDULE AND TIMELINE, AND
COORDINATE WITH COR. TAKE PREVENTATIVE MEASURES SUCH AS
SEALING DOORS IN DAILY PROJECT AREA OR TEMPORARY RELOCATION OF
STAFF AND OR PATIENTS. REFER TO ICRA RISK ASSESSMENT.
REFER TO PHASING NOTES LOCATED ON SHEET 01-GI200
SCOPE OF WORK AREA
NO SCOPE OF WORK AREA
VAV LOCATION. SEE MECHANICAL PLANS.
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1 HOUR SMOKE COMPARTMENT
TEMPORARY ICRA BARRIER WALL / CEILING, DUCTS AND
DIFFUSERS AND/OR USE HEPA CART
CONTRACTOR ACCESS
PHASE 2. CONSTRUCTION CAN ONLY HAPPEN IN ONE ROOM AT A TIME.
(LEGEND NOTES 1, 2, 3, 4)
PHASE 3. CONSTRUCTION CAN ONLY HAPPEN IN NO MORE THAN TWO (2)
ROOMS AT A TIME. (LEGEND NOTES 1, 2, 3, 4)
PHASE 4. MAXIMUM TWO (2) WEEKS CLOSED DOWN FOR CONSTRUCTION.
DUCTWORK AND VAV BOXES TO BE COMPLETED DURING THAT TIME FRAME.
(LEGEND NOTES 1, 2, 3, 4)
PHASE 5. MINIMUM EIGHT (8) WEEKS NOTICE FOR SHUTDOWN. CONSTRUCTION
CAN ONLY HAPPEN IN ONE ROOM AT A TIME. (LEGEND NOTES 1, 2, 3, 4)
PHASE 6. RESTRICTED AREA. PHARMACY WILL PROVIDE AN ESCORT IN THE
CACHE AT ALL TIMES DURING CONSTRUCTION. CONSTRUCTION RESTRICTED
TO NORMAL BUSINESS HOURS. (LEGEND NOTES 1, 2, 3, 4)
PHASE 7. MINIMUM EIGHT (8) WEEKS NOTICE FOR SHUTDOWN. WORK SHALL
START IN ROOM C201 OVER A WEEKEND. ROOM C201 CLINICAL WORK MUST
REMAIN OPEN DURING REGULAR BUSINESS HOURS. WORK TO BE PERFORMED
NIGHTS AND WEEKENDS. OTHER ROOMS IN THIS AREA OF CONSTRUCTION
CAN ONLY HAPPEN IN ONE ROOM AT A TIME. (LEGEND NOTES 1, 2, 3, 4)
PHASE 8. REPLACE TERMINAL UNIT OUTSIDE OF NORMAL BUSINESS HOURS.
ALL CONSTRUCTION EQUIPMENT MUST BE REMOVED BY 06:00 AM. (LEGEND
NOTES 1, 2, 3, 4)
VAV LOCATION. SEE MECHANICAL PLANS.
CONSTRUCTION PHASE IDENTIFICATION MARKER#
PLAN NOTES
PHASE 9. WORK SCOPE CAN BE DONE ANYTIME. PER SCHEDULE.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
KEY PLAN
PLAN NORTH
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/1
/2
:0
:0
P
M
RO DC
657-23-108JC
01-GI204
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
LEVEL 02 - CONSTRUCTION AREA GUIDELINES 100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
1" = 10'-0"
LEVEL 02 - CONSTRUCTION AREA GUIDELINES
1 GENERAL CONTRACTOR TO ERECT SCAFOLDING OVER EXISTING EQUIPMENT,
TO ALLOW EQUIPMENT TO BE IN OPERATION AT ALL TIMES.
2 EXISTING VAV BOX IS NOT PART OF THIS PROJECT'S SCOPE OF WORK AND TO
REMAIN AS IS.
3 EXISTING EQUIPMENT IS NOT PART OF THIS PROJECT'S SCOPE OF WORK AND
TO REMAIN AS IS.
4 SOME NON-STATIONARY LABORATORY EQUIPMENT ON THE COUNTERTOP MAY
BE MOVED. CONTRACTOR TO IDENTIFY AND REQUEST LABORATORY
PERSONNEL ONLY TO MOVE EQUIPMENT. DETERMINE BAARRIER WORK SCOPE
EXTENT ON OR AROUND FIXED LABORATORY CASEWORK AND PROTECTION IN
CONSULTATION OF THE COR.
5 PROVIDE BARRIERS AND OR MOBILE CONTAINMENT AS REQUIRED, ISOLATING
HVAC SYSTEM WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF
DUCTS IN ACCORDANCE WITH THE INFECTION CONTROL RISK ASSESSMENT
(ICRA).
6 MAINTAIN OCCUPIED BUILDING EGRESS DURING PROJECT SCOPE.
CONSTRUCTION GUIDELINES
KEY NOTES
1-A2-A3-A4-A5-A6-A7-A8-A9-A10-A11-A12-A13-A14-A
C-A
D-A
E-A
F-A
G-A
B-A
A.1-A
S-A
R-A
Q-A
P-A
N-A
M-A
+ 6" A.F.F.+ 6" A.F.F.
+ 6" A.F.F.
+ 6" A.F.F.
+ 6" A.F.F.
+ 6" A.F.F. + 6" A.F.F.
+ 6" A.F.F.+ 6" A.F.F.
+ 6" A.F.F.
+ 6" A.F.F.
+ 6" A.F.F.
+ 6" A.F.F.+ 6" A.F.F.
+ 6" A.F.F.
MECH. RM
D302A
RETAIL STORAGE
C303C
RETAIL STORAGE
C303D
OFFICE
C303A
OFFICE
C303
CORRIDOR
H312
RETAIL STORE
B306
VESTIBULE
C303B
MECH RM.
D302B
MECH RM.
D302C
STAIR 08
S308
MECH. RM.
C301A
MECH RM
C301B
STORAGE
C304
MECH RM.
D302
VAV-82 (EX) VAV-83 (EX)
VAV-81 (EX)
M A
T C
H L
IN
E
STAIR 06
S306
STAIR 03
S303
STAIR 07
S307
STAIR 09
S309
PHASE 1. WORK TO BE DONE ON ONE VAV AT A TIME IN THE LAB. STAT WITH
VAV-1-25(EX), VAV-1-26(EX), VAV-1-30(EX). THEN SEQUENCING IS UP TO THE
CONTRACTOR'S APPRVED SCHEDULE. SEE FULL PROPOSED CONSTRUCTION
SCHEDULE ON 01-MG103. (LEGEND NOTES 1, 2, 3, 4)
1. THERE IS A MAXIMUM OF TWO WEEKS TO COMPLETE WORK PER VAV BOX.
2. PERSONNEL IN THE OFFICE WILL RELOCATE DURING CONSTRUCTION.
3. FURNITURE WILL NOT BE MOVED BY THE VA.
4. REFER AND COORDINATE WITH MECHANICAL DOCUMENTS.
5. SEE CONSTRUCTION PHASE IDENTIFICATION MARKER. PHASE 1 SHALL BE
FIRST. PHASES 2-8 SHALL BE DETERMINED BY GC IN CONSULTATION WITH
THE COR.
6. INVESTIGATE EXISTING FIELD CONDITIONS OF FIRE RESISTANCE PARTITIONS
THAT ARE AFFECTED BY WORK SCOPE AND PROVIDE UL APPROVED FIRE-
RESISTANT JOINT SYSTEM PENETRATIONS ABOVE CEILING LABELED, IBC
(2021) SECTION 70 AND SECTION 7.1.1.
7. GC SHALL DETERMINE PROJECT DAILY SCHEDULE AND TIMELINE, AND
COORDINATE WITH COR. TAKE PREVENTATIVE MEASURES SUCH AS
SEALING DOORS IN DAILY PROJECT AREA OR TEMPORARY RELOCATION OF
STAFF AND OR PATIENTS. REFER TO ICRA RISK ASSESSMENT.
REFER TO PHASING NOTES LOCATED ON SHEET 01-GI200
SCOPE OF WORK AREA
NO SCOPE OF WORK AREA
VAV LOCATION. SEE MECHANICAL PLANS.
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
1 HOUR SMOKE COMPARTMENT
TEMPORARY ICRA BARRIER WALL / CEILING, DUCTS AND
DIFFUSERS AND/OR USE HEPA CART
CONTRACTOR ACCESS
PHASE 2. CONSTRUCTION CAN ONLY HAPPEN IN ONE ROOM AT A TIME.
(LEGEND NOTES 1, 2, 3, 4)
PHASE 3. CONSTRUCTION CAN ONLY HAPPEN IN NO MORE THAN TWO (2)
ROOMS AT A TIME. (LEGEND NOTES 1, 2, 3, 4)
PHASE 4. MAXIMUM TWO (2) WEEKS CLOSED DOWN FOR CONSTRUCTION.
DUCTWORK AND VAV BOXES TO BE COMPLETED DURING THAT TIME FRAME.
(LEGEND NOTES 1, 2, 3, 4)
PHASE 5. MINIMUM EIGHT (8) WEEKS NOTICE FOR SHUTDOWN. CONSTRUCTION
CAN ONLY HAPPEN IN ONE ROOM AT A TIME. (LEGEND NOTES 1, 2, 3, 4)
PHASE 6. RESTRICTED AREA. PHARMACY WILL PROVIDE AN ESCORT IN THE
CACHE AT ALL TIMES DURING CONSTRUCTION. CONSTRUCTION RESTRICTED
TO NORMAL BUSINESS HOURS. (LEGEND NOTES 1, 2, 3, 4)
PHASE 7. MINIMUM EIGHT (8) WEEKS NOTICE FOR SHUTDOWN. WORK SHALL
START IN ROOM C201 OVER A WEEKEND. ROOM C201 CLINICAL WORK MUST
REMAIN OPEN DURING REGULAR BUSINESS HOURS. WORK TO BE PERFORMED
NIGHTS AND WEEKENDS. OTHER ROOMS IN THIS AREA OF CONSTRUCTION
CAN ONLY HAPPEN IN ONE ROOM AT A TIME. (LEGEND NOTES 1, 2, 3, 4)
PHASE 8. REPLACE TERMINAL UNIT OUTSIDE OF NORMAL BUSINESS HOURS.
ALL CONSTRUCTION EQUIPMENT MUST BE REMOVED BY 06:00 AM. (LEGEND
NOTES 1, 2, 3, 4)
VAV LOCATION. SEE MECHANICAL PLANS.
CONSTRUCTION PHASE IDENTIFICATION MARKER#
PLAN NOTES
PHASE 9. WORK SCOPE CAN BE DONE ANYTIME. PER SCHEDULE.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
KEY PLAN
PLAN NORTH
B
IM
/V
IS
N
S F
C A
R e p la c e A ir H a n d le r A
C -1
/S F
C A
-R e p la c e
A ir H a n d le r
A C
-1
V
.r v t
/1
/2
:0
:0
P
M
RO DC
657-23-108JC
01-GI205
915 North Grand Blvd, St. Louis, MO 63106
MARCH 8, 2024
LEVEL 03 - CONSTRUCTION AREA GUIDELINES 100% CONTRACT DOCUMENTS FCA-REPAIR AIR HANDLER AC-1
1" = 10'-0"
LEVEL 03 - CONSTRUCTION AREA GUIDELINES
1 GENERAL CONTRACTOR TO ERECT SCAFOLDING OVER EXISTING EQUIPMENT,
TO ALLOW EQUIPMENT TO BE IN OPERATION AT ALL TIMES.
2 EXISTING VAV BOX IS NOT PART OF THIS PROJECT'S SCOPE OF WORK AND TO
REMAIN AS IS.
3 EXISTING EQUIPMENT IS NOT PART OF THIS PROJECT'S SCOPE OF WORK AND
TO REMAIN AS IS.
4 SOME NON-STATIONARY LABORATORY EQUIPMENT ON THE COUNTERTOP MAY
BE MOVED. CONTRACTOR TO IDENTIFY AND REQUEST LABORATORY
PERSONNEL ONLY TO MOVE EQUIPMENT. DETERMINE BAARRIER WORK SCOPE
EXTENT ON OR AROUND FIXED LABORATORY CASEWORK AND PROTECTION IN
CONSULTATION OF THE COR.
5 PROVIDE BARRIERS AND OR MOBILE CONTAINMENT AS REQUIRED, ISOLATING
HVAC SYSTEM WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF
DUCTS IN ACCORDANCE WITH THE INFECTION CONTROL RISK ASSESSMENT
(ICRA).
6 MAINTAIN OCCUPIED BUILDING EGRESS DURING PROJECT SCOPE.
RCP LEGEND
RCP NOTES
PLAN LEGEND
KEY NOTES
1-A2-A3-A4-A5-A6-A7-A8-A9-A10-A11-A12-A13-A14-A
C-A
D-A
E-A
F-A
G-A
B-A
A.1-A
S-A
R-A
Q-A
P-A
N-A
M-A
D241
PATHOLOGY
LAB
D234
STAT
CHEMISTRY
D237
BLOODBANK
D235
IMMEDIATE
RESPONSE
D228
IMMUNOLOGY
D223
MICROBIOLOGY
D241
PATHOLOGY
LAB
D226
OFFICE
D225A
WALK-IN
REF
D225
WALK-IN
REF
D225B
MECH.RM
D224
MEDIA PREP
D222
TRANSFER
RM. D223
MICROBIOLOGY
D220
TB RM.
D219
ANTE ROOM
D221
MICROBIOLOGY
H228
CORRIDOR
D216
MICROSCOPE
D215
CONFERENCE
RM.
D213
OFFICE D214
STORAGE
D270
STERILIZATION
D271
HEMO
STERILE
H229
CORRIDOR
D259
HOLDING
D269
BULK
STORAGE
D269A
ELEC
CLOSET
H231
CORRIDOR
D260
OFFICE
D256
OFFICE
H229
CORRIDOR
D234A
ELEC.
D240
JANITOR
D239
HVAC
D234
STAT
CHEMISTRY
H224
CORR.H226
CORRIDOR
C219
LOUNGE
B210A
BLOOD
DRAW
B210
WORK AREA B209
TOILET
B208
TOILET
B206B
STORAGE
B206
EXG &
HOLTER
MONITOR
H221
CORRIDOR
C218
COMPUTER
RM
C218A
OI&T
B207C
BLOOD
DRAW
B207B
BLOOD
DRAW
B207D
BLOOD
DRAW
B207
BLOOD
DRAW H223
ELEVATOR
LOBBY
H221
CORRIDOR
B205A
SUPPLIES
B204B
CONFERENCE
RM.
B203C
STORAGE
H223B
CORR.
B207A
BLOOD
DRAW
C217
CONFERENCE
C220
OFFICE
H222
ELEVATOR
LOBBY
D254
BREAK RM.
D253
BREAK RM.
D244
BREAK RM.
D246
CORRIDOR
D242
OFFICE,
SUPER
HEMATOLOGY
D243
OFFICE
D252
OFFICE
D245
OFFICE
D250
OFFICE
D261
OFFICE
D257
OFFICE
D249
OFFICE
D248
SECRETARY
D247
OFFICE
D267
OFFICE
D266
DARK RM.
D265
OFFICE
D263
ANCILLARY
TESTING
D264
CHEMICAL
STORAGE
H228
CORRIDOR
D208
CORRIDOR
D206
VACANT
D204
OFFICE
D203
OFFICE/EXAM
H226
CORRIDOR
C216
PHARMACY
STORAGE
H221
CORRIDOR
C215A
MECH.RM.
C215B
OI&T
C214
PHARMACY
STORAGE
C215
OFFICE B203B
SOILED
UTILITY
C200
EXERCISE
LAB
C225
CORRIDOR
C201
CLINICAL
C203
OFFICE
C204
EXAM
C205
MOLECUL…